No Mu Req; As Min As Actural Design Design¿ No. Of


(k-in) (in2) (in2) Bearing Bearing Actural bar
strength strength (check) (nos.)
(ksi) (ksi)
1. 25.59 0.29 0.16 0.167 4.05 OK 2-12mm
use2#4bars
(As=0.39in2)
2. 5.72 0.14 0.06 0.09 3 OK 1-12mm
use1#4bars
(As=0.2in2)
3. 207.4 0.91 0.71 0.43 7.14 OK 3-16mm
use3#5bars
(As=0.91in2)
4. 334.4 1.11 1 0.61 7.68 OK 4-16mm
use6#4bars
(As=1.18in2)
5. 283.7 1.01 0.89 0.56 7.32 OK 4-16mm
use6#4bars
(As=1.18in2)
6. 408.5 1.24 1.15 0.69 8 OK 4-16mm
use4#5bars
(As=1.23in2)
7. 189.4 0.82 0.66 0.45 6.6 OK 3-16mm
use2#6bars
(As=0.88in2)
8. 278.9 1 0.88 0.55 7.3 OK 4-16mm
6 use6#4bars
(As=1.18in2)
10. 508.4 1.39 1.36 0.78 8.6 OK 5-16mm
use7#4bars
(As=1.37in2)
12. 801.9 1.8 1.88 1 9.8 OK 6-16mm
use6#5bars
(As=1.84in2)
13. 388.6 1.21 1.12 0.66 8 OK 4-16mm
use2#7bars
(As=1.2in2)
14. 348.7 1.15 1.03 0.64 7.8 OK 4-16mm
use6#4bars
(As=1.18in2)

15. 897.1 1.93 2.04 1.07 10.2 OK 7-16mm


use7#5bars
(As=2.15in2)
16. 849.6 1.86 1.96 1.04 10 OK 7-16mm
use2#9bars
(As=2in2)

(Continued)
(Continued)
38

17. 385.3 1.21 1.11 0.66 8 OK 4-16mm


use2#7bars
(As=1.2in2)
18. 241.9 0.95 0.79 0.497 7.14 OK 3-16mm
use5#4bars
(As=0.98in2)
19. 645.3 1.61 1.61 0.88 9.3 OK 6-16mm
use4#6bars
(As=1.77in2)
20. 577.2 1.5 1.5 0.84 9 OK 5-16mm
use8#4bars
(As=1.57in2)
21. 280.7 1 0.88 0.55 7.3 OK 4-16mm
use6#4bars
(As=1.18in2)
23. 39.5 0.36 0.22 0.2 4.5 OK 2-12mm
use234bars
(As=0.39in2)
24. 34.4 0.33 0.2 0.2 4.3 Ok 2-12mm
use2#4Bars
(As=0.39in2)

Isolated Size LxB


Footing (ft2)
F1 1.7x1.7
F2 2.3x2.3
F3 2.4x2.4
F4 2.5x2.5
F5 3.7x3.7
F6 4x4
F7 4.1x4.1
F8 4.3x4.3
F9 4.4x4.4
F10 4.5x4.5
F11 4.8x4.8
F12 5x5
F13 5.2x5.2
F14 5.5x5.5
F15 5.6x5.6
F16 5.7x5.7
39

Figure:4.2. Foundation Plan of Isolated Footing for two and half Storeyed Building