Sei sulla pagina 1di 4

Checking Sub Girder For = 325.

00 ton test pile


Total Kentledge Load = 399.50 ton
Total Loading Area Sub Girder = 10.00 x 9.59 = 95.90 m2

399.50
UDL on sub girder = = 4.17 tonnes/m2
95.90

UDL of DL from Kentledge on each Girder = 4.17 tonnes/m2 x 1.07 = 4.44 t/m
= 44.41 kN/m

Assume Self Weight of Girder = 2.00 kN/m

Total UDL on each girder = 44.41 kN/m + 2.00 kN/m


= 46.41 kN/m

Design Of Sub Girder

2
Mx = 46.41 x 5.00 / 2.00 Shear Force, Fv = 232 kN
= 580.09 kNm

46.41 kN/m

4.64 kN

^ 5
580.09 x 10.00
Z = ^ 2 = 3,515.71 CM3
165.00 x 10.00

Section Properties

A = 201.80 cm2
Ixx = 115703.00 cm4
rxx = 1.69 cm
Zxx = 3,955.60 cm3
Z = 3,520.00 cm3
D = 585 mm T = 20 BD² bd³
Sx = -
d = 545 mm t = 15 6 6D
B = 300 mm d/t = 36.333
b = 285 mm b/T = 7.5 = 3967.26 cm3

Trial Section Using Steel Grade S275, with T<= 16mm,

Mx
Sx = = 2,189.03 cm3
Sx = = 2,189.03 cm3
PY

Class Section T=20mm < 40mm, Py = 265 N/mm2 ;

€ = 275 = ### Table 11


265

Limiting b/T = 9€ = 9; Actual b/T = 7.5

In the results, the flange is class 1 Class 1 Plastic

Limiting d/t = 80€ = 80; Actual d/t = 36.33 Clause 4.4.5

Therefore there is no need to check shear buckling

Check For Shear Capacity


Clause 4.2.3
Pv = 0.6 Py Av

= 1395.23 kN > Fv OK

Therefore shear capacity is adequate

Check For Moment Capacity


Clause 4.2.5.2
0.6 Pv = 837.14 kN > Fv OK

The Shear is low; For low shear, Class 1 Plastic

Mc = Py Sx
= 1051.32 kNm > Mx OK

Check For Deflection


Clause 3.1.3
dmax = WL3
8EZ
3
46.30 x 10 ^ 3 x 5000
= = 2.98 mm OK
8.00 x 2.10 x 10 ^ 5x 115703 x 10 ^ 4

l 5000.00
Allowable Deflection = = = 25 mm
200.00 200.00

Therefore section is adequate with respect to deflection.

Main Girder Beam Support for 325 ton Test Pile

Section Properties

232.0 464.1 464.1 464.1 464.1 464.1

1066 1066 1066 1066 533


Fv = 2,552.41 kN

Mx = 464.07 x 0.53 + 464.07 x 1.6 + 464.07 x 2.67 + 464.07 x 3.73


+ 56.5 x 10 x 4.797
= 6,670.25 kNm

6,670.25 x 10 ^ 5 = 667,024,874.45
Z = = 40,425.75 CM3
165.00 x 10 ^ 2 16,500.00

Section properties
A = 606.00 cm2
Zxx = 17761.00 cm3
rxx = 1.48 cm
Ixx = 799262.00 cm4

D = 900 mm T = 28 BD² bd³


Sx = -
d = 844 mm t = 32 6 6D
B = 600 mm d/t = 26.38
b = 26 mm b/T = 10.71 = 78105.28 cm3

Trial Section Using Steel Grade S275, with T<= 40mm,

Mx
Sx = = 25170.75 cm3
PY

Class Section T=20mm < 40mm, Py = 265 N/mm2 ;

€ = 275 = ### Table 11


265

Limiting b/T = 15€ =15; Actual b/T = 10.71

In the results, the flange is class 3 Class 3 Semi Compact

Limiting d/t = 80€ = 80; Actual d/t = 26.38 Clause 4.4.5

Therefore there is no need to check shear buckling

Check For Shear Capacity


Clause 4.2.3
Pv = 0.6 Py Av

= 4579.20 kN > Fv OK

Therefore shear capacity is adequate

Check For Moment Capacity


Clause 4.2.5.2
0.6 Pv = 2747.52 kN > Fv OK

The Shear is low; For low shear, Class 1 Plastic

Mc = Py Sx
= 20697.90 kNm > Mx OK

Check For Deflection


Clause 3.1.3

3
dmax = Pa 3b
x 1 +
3EZ 2a

3 3
232.04 x 4,670 x 10
P1 = = 4.69 mm
3.00 x 2.10 x 10 ^ 5x 799,262.00 x 10 ^ 4

3 3
464.07 x 3,600 x 10 3x 1.066
P2 = + 1 +
3.00 x 2.10 x 10 ^ 6x 799,262.00 x 10 ^ 4 2x 3.6

= 1.87 mm
3 3
464.07 x 2,525 x 10 3x 2.132
P3 = + 1 +
3.00 x 2.10 x 10 ^ 5x 799,262.00 x 10 ^ 4 2x 2.525

= 3.75 mm

3 3
P4 = 464.07 x 1,455 x 10 + 1 + 3x 3
3.00 x 2.10 x 10 ^ 5x 799,262.00 x 10 ^ 4 2x 1

= 0.94 mm

3 3
P5 = 464.07 x 433 x 10 + 1 + 3x 4
3.00 x 2.10 x 10 ^ 5x 799,262.00 x 10 ^ 4 2x 4

= 2.5 mm

Total Defelection 13.75 mm OK

= l = 4797.00 = 27 mm
Allowable Deflection
250.00 180.00

Therefore section is adequate with respect to deflection.