Sei sulla pagina 1di 4

Isolating amplifier KFD2 - SR2 - Ex1.

5.7.1
System components
Function
The isolating amplifier transmits digital signals from the explosion risk area. The input is de-
signed for connecting a sensor according to NAMUR (DIN 19234). The output is switched
off in case of a wire break in the input circuit.
Switch S3 must be set to position 1.
The direction of action can be set with switch S1.

A1 82688-0 Circuit diagram of the isolating amplifier KFD2 - SR2 - Ex1.W

1 Isolating amplifier
2 Mains
3 Relay output

Technical data

Mains VDC 20...30


Safety-technical maximum VDC 40
voltage
Ripple <-10
Nominal current mA 20...23
EMC acc. to NAMUR NE 21
Electrical isolation safe acc. to DIN EN 50 020 and DIN VDE 0106
Part 101

OBJ_DOKU-1927-001.fm 1 © 0399
5.7.1
System components

Direction of action

Cutout front panel Input Output

Relay pulled up

Relay dropped out

82690-0

Relay pulled up

Relay dropped out

82691-0

OBJ_DOKU-1927-001.fm 2 © 0399
5.7.1
System components
Dimensioned drawing

A2 82689-0 Front view, dimensioned drawing, isolating amplifier KFD2 - SR2 - Ex1.W

1 LED signal output (yellow)


2 LED LB (red)
3 LED mains (green)
4 Switch S1 (direction of action)
5 Switch S2 (no function)
6 Switch S3 (LB detection)

OBJ_DOKU-1927-001.fm 3 © 0399