Sei sulla pagina 1di 32

User Manual

TM70
EEPROM Programmer v: 12.3.0

www.danfoss.com
User Manual
TM70 EEPROM Programmer

Revision history Table of revisions

Date Changed Rev

August 2019 Rebranded to Danfoss. 0101

2 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Contents

Introduction
General Information........................................................................................................................................................................ 4
Software Installation........................................................................................................................................................................4
Driver Installation............................................................................................................................................................................. 7
Re-installation/Update of the Software....................................................................................................................................9
Software Removal..........................................................................................................................................................................10
Complete Installation................................................................................................................................................................... 12
Main Window EeproTM70.......................................................................................................................................................... 13
About Programmer Dialogue Box........................................................................................................................................... 17
Operation Key Functions
Read EEPROM.................................................................................................................................................................................. 18
Program EEPROM...........................................................................................................................................................................19
Open File........................................................................................................................................................................................... 20
Save File.............................................................................................................................................................................................21
Edit display label............................................................................................................................................................................ 22
Import Table.....................................................................................................................................................................................22
Displaying Other IDs..................................................................................................................................................................... 23
Modifying Masks............................................................................................................................................................................ 24
PWM and Voltage Analogue Outputs Setup........................................................................................................................25
Exit....................................................................................................................................................................................................... 26
TM60/RAD Programmer.............................................................................................................................................................. 26
read data from EEPROM (L)................................................................................................................................................... 26
exit (F)........................................................................................................................................................................................... 26
Configurable Parameters
Transmitter Disconnection time due to inactivity............................................................................................................. 27
Radio Parameters Configuration.............................................................................................................................................. 27
CANopen Parameters Setup...................................................................................................................................................... 28
Tele-alignment Activation.......................................................................................................................................................... 28
Information Parameters (Non-configurable)
.EEP.XML Files.................................................................................................................................................................................. 29
AP70 Module Hardware Description
Connectors, Selector Switch, LED signalling........................................................................................................................30
Cables and Accessories................................................................................................................................................................ 31

© Danfoss | August 2019 BC314244826802en-000101 | 3


User Manual
TM70 EEPROM Programmer

Introduction

General Information
The TM70 programming kit (the programmer x 64.msi plus hardware AP70) allows to install, manage and
modify operating data of the Danfoss Radio Remote Control configuration (Transmitter and Receiver) in
the EEPROM modules.
A computer using Windows OS version is required, as well as AP70 EEPROM recorder module; the
corresponding cables are also supplied with the kit. Hardware interface is through a USB port. It is not
necessary to use an external power supply, as the AP70 module is powered via the USB port from the
computer.
Recommended steps to install the TM70 application:
• Install the program, the drivers and the software
• Verify the right assignment of the communication port by operating system (OS)
• Verify the right communication between the application software and the hardware AP70.

Software Installation
Use the following recommended steps to install the recorder software for the first time:
1. Copy the file EeproTM70-V12.2-Danfoss.msi on your computer using Windows Explorer.
2. Double click on the EeproTM70-V12.2-Danfoss.msi file to start the installation process.

3. Click the Next button and select I Agree the License Terms and Conditions for the Programmer
software, and click the Next button again.

4 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Introduction

4. Choose the destination with the Browse option and the name of the folder in which the program will
be installed.
By default the folder will be C:\Program Files(x86) > EEPRO TM70.
5. Select who can use the program in a computer and click Next button.

The default is Everyone.

© Danfoss | August 2019 BC314244826802en-000101 | 5


User Manual
TM70 EEPROM Programmer

Introduction

6. Click the Next button in the Confirm Installation screen.

Once the installation is finished, the used file can be erased. The installation software will guide you
through the setup wizard in order to have both drivers and software installed.

6 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Introduction

Driver Installation
Use the following steps to install the driver:
1. In the setup window click Next.

If the driver had been installed previously, the following screens will not appear.
2. Accept the exposed terms and conditions by clicking I Accept... option and continue the installation
clicking Next.

3. Choose the destination with the Browse option and the name of the folder in which the program will
be installed.

© Danfoss | August 2019 BC314244826802en-000101 | 7


User Manual
TM70 EEPROM Programmer

Introduction

By default the folder will be C:\Program Files(x86) > Texas Instruments. After click on the Install
button, the driver setup is complete.
4. By clicking Finish button the TM70 installation will continue.

5. Click the Close button once the software has been installed in the appeared screen.

8 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Introduction

Re-installation/Update of the Software


The software allows to repair or to uninstall the current version.
Available options (clicking in the right option box):
• Repair: to update the program with the latest version.
• Remove: to remove the current program from the computer.

Repair option updates the software files

A Warning message will pop up to remind you the Driver software is correct, click continue.

Once the software has been installed the above screen will appear, you can press Close button.

© Danfoss | August 2019 BC314244826802en-000101 | 9


User Manual
TM70 EEPROM Programmer

Introduction

Software Removal
How to remove the software application using the TM80 Eeprom programmer installation software.
This software installs several common files to other applications running under windows operating
system which will remain installed after a software removing process.

It is highly recommended not to remove these files, as requested, because they can be used by other
software applications different from the EEPROM recorder software.
1. Select the Remove TM80 Eeprom programmer option and press Finish

Removing the software

While the program is uninstalling, message may appear about uninstalling the Driver as well.

10 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Introduction

C Caution
If there is any message asking you to remove shared files, it is highly recommended not to delete any
of them, since this may mean that other programs may not operate correctly. Always select No.
2. Once the Driver has been uninstalled, press Finish.

C Caution

If you continue to use the TM70 Eeprom programmer, please do not uninstall the driver, otherwise
the EEPROM programmer will not work.
3. Press Close button.

The programmer is successfully uninstalled.

© Danfoss | August 2019 BC314244826802en-000101 | 11


User Manual
TM70 EEPROM Programmer

Introduction

Complete Installation
The installed software can be found in the application’s root directory or folder: EeproTM70 > eepro
TM70.exe; as well as the readme.txt file, containing several explanations about the application.
After finishing the program setup process the default folder architecture becomes as follows:

AuxBin there are several files that are used by the program.

DATOS is the default address for .eep files corresponding to TM60 systems (MS DOS version) it is
recommended to place them there to avoid possible errors typing the paths in MS DOS.

Lng The folder contains the character strings to support several languages stored in the file
“default.lng” which is always loaded when running the software.

12 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Introduction

Main Window EeproTM70


1. Double Click on the icon which appears on the desktop to execute the TM70 program:
EeproTM70 programmer icon

At the first use of the EEPROM Programmer the window to enter the License number will pop up that
has been assigned upon the signing of the License agreement.
2. Insert the string of characters (paste or type) and click Apply.
License registration

© Danfoss | August 2019 BC314244826802en-000101 | 13


User Manual
TM70 EEPROM Programmer

Introduction

The main window for the program will appear. For the first time it may appear in Spanish or English.
English language window

3. Optional: To change the language to Spanish click Language Sel., the window will pop up, select
from the options Espanol and click OK, the programmer will switch to English Language.

14 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Introduction

Spanish language window

The programmer will change into Spanish Language.


4. Optional: To change the language back to English, click Sel Idioma, the window will pop up, select
from the options English and click OK.

© Danfoss | August 2019 BC314244826802en-000101 | 15


User Manual
TM70 EEPROM Programmer

Introduction

5. Connect on one USB connector the AP70 Hardware supplied, then click on Port Sel., in order to select
the right port.

A port where TUSB3410 Device will appear, select it and Click OK.

16 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Introduction

About Programmer Dialogue Box


Clicking the right mouse button in the program window the following options are available:

Click in “About programmer…” option and the following dialogue box appears:

If you do require to enter a new License number on an existing EEPROM programmer, by clicking Insert
new License number, you will be allowed to insert the new License number that may have been
assigned.

© Danfoss | August 2019 BC314244826802en-000101 | 17


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Read EEPROM
Selecting this option, the content of the Eeprom inserted into the AP70 module can be read.
Depending of the EEPROM type connected to the AP70 module the program will detect and perform the
task. On the main Window press Read EEPROM. After the reading has taken place, the following
messages can appear:

There is an EP70 EEPROM and the content has been read correctly.
If any of the messages below appear, it means: There is no EEPROM connected on the socket, the
EEPROM chip is erased or Data is corrupted.

READ NOK will appear.

By clicking Read EEPROM button the information in the EEPROM file, inserted in the TM70 EEPROM
recorder, is read.
The information which has been read is shown in the corresponding boxes and resides in memory. If it
does not exist any previously loaded EEPROM, confirmation will not be requested, but if there is already
one EEPROM information in memory, yes. This is because, in this operation, the current content in the
recorder is lost if it was not saved previously.

18 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Program EEPROM
By Clicking on the Program EEPROM button, the EEPROM file that is stored on the programmer will be
programmed on the EEPROM chip inserted on the EEPROM programmer socket.
The following messages can appear:

This means that there is no data available on the programmer.

This means the EEPROM file has been burnt on the EEPROM chip correctly.

This means there has been some failure when burning the EEPROM chip and it has not been burnt.

© Danfoss | August 2019 BC314244826802en-000101 | 19


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Open File
When you click on the button, a warning will pop up as follows:

When loading a new file from the computer data stored on the EEPROM programmer is lost. If you want
to have that Data stored on a file, you will need to save it first. If this is not the case, click Yes.
A window will appear where you can browse to select the file to be loaded (accessing the directory where
it is saved).

It is recommended to always save EEPROM files in the same directory and using the equipment serial
number as a name to make it easier to find them in the future.

Select the right EEPROM file you do require, and click open. Once you have completed the operation, you
will see whether it has been successful or not.

20 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Save File
By clicking on Save file, you can save what is currently on the screen in an EEPROM file.
By clicking on this button, a dialogue box appears allowing to browse and to select the directory where
the file is going to be saved (entering its name).
It is advisable to save always EEPROM files in the same directory using the equipment serial number as a
reference name to make it easier to find it in the future.
If any changes have been performed it is advisory to save the file with a revision of it such that the
original file can be retrieved.

Once the operation has been completed, the software will advert whether it has been successfully
performed or not.

© Danfoss | August 2019 BC314244826802en-000101 | 21


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Edit display label

By clicking this button the program allows to open the screen in which text can be edited in the display
(for configurations with display):

The “Char List” contains several characters which can be used for writing the text to be shown in the
display (2lines x 12 characters max.). Two lines of text can be written, filling in the two boxes for this
purpose. This Text will appear at the time of starting the system. Its purpose is to identify the machine
that is to be used with the transmitter.

Import Table
The Import Table button allows using the windows explorer tool, to select another EEPROM that it was
previously recorded and to load the assigned inputs/outputs that it had been configured (relay table).
The imported table must have the same type of receiver in order that this option is going to be able to be
performed. Only Relay configuration is changed. If the system does have analogue outputs, these will not
be changed.

If the receiver of the EEPROM serial number which Relay configuration want to be imported is different
model than the original one, it will not allow you to import the table configuration.

22 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Displaying Other IDs


By clicking on this button, all the programmed ID’s either in the transmitter, either in the receiver are
shown (Multi ID equipment; Tandem equipment; First Come First Served equipment, etc.) , as well as the
Range Limiter option IDs.

C Caution
This ID table can not be changed, but it does inform you if the system does have additional transmitters
and/or receivers.

© Danfoss | August 2019 BC314244826802en-000101 | 23


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Modifying Masks
This button allows to adapt the masks of the hand held transmitters in order to be able to configure
"push buttons" where before there were "selectors" and vice-versa.

After Clicking “Modify Mask” the hand held transmitter Layout will appear as it was manufactured. On this
example there was a selector switch on Position 10. We click on Positions 7 and 8 to add a selector switch.

After clicking Apply, a window will pop up explaining the Hardware modifications needed to place a
selector switch instead of the existing push button.
When replacing a Push button with a Selector Switch you need to remove the bridge as shown on the
window on the respective positions. This modification will be on the active table that is selected.

24 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Operation Key Functions

PWM and Voltage Analogue Outputs Setup

Selecting the “Analogue outputs” option from the main Menu, the software allows to modify the
following parameters for each analogue output.

On the Tab Configurable output, you can select each proportional output of the system:

Configurable output parameters – range and allowed values:

ACCELERATION 0.0s, 0.1s, 0.2s, 0.3s, 0.4s, 0.5s, 0.6s, 0.8s, 1.0s, 1.2s, 1.5s, 1.7s, 2.0s, 2.5s, 3.5s, 5.0s
RAMP Time in seconds of each ramp. Minimum, maximum and pre-defined values

DECELERATION 0.0s, 0.1s, 0.2s, 0.3s, 0.4s, 0.5s, 0.6s, 0.8s, 1.0s, 1.2s, 1.5s, 1.7s, 2.0s, 2.5s, 3.5s, 5.0s
RAMP Time in seconds of each ramp. Minimum, maximum and pre-defined values

PWM Available range: 30Hz to 300Hz; Steps = 10 Hz.


FREQUENCY Different PWM value configuration available for each analogue output

OUTPUT MODES MOMENTARY or LATCHING configuration mode available

Output values can be determined in % respect to the initial value and maximum value per semi axis,
being Min- and Min+ The initial output value per semi axis (Negative and Positive) and Max- and Max+
the maximum output value per semi axis.
Selecting the Curve Tab, you can select among linear curve and three different exponential curves, the
curve is displayed on the central diagram.
Once all the values have been selected, you can Export the analogue configuration to an external file,
such that it can be reused on another system by importing the configuration. This possibility is good for
prototyping until the final analogue configuration is fine tuned.
Once all the analogue output parameters are configured press “Ok” to update them or press “Cancel” to
leave without updating the modified values.

© Danfoss | August 2019 BC314244826802en-000101 | 25


User Manual
TM70 EEPROM Programmer

Operation Key Functions

Exit
By clicking on the Exit button to leave the program, the programmer will be switched off.

TM60/RAD Programmer
This option will execute the TM60/RAD compatible programmer, window without loading any EEPROM
information.

Press the corresponding character to execute the selected option. As these systems have been
discontinued, the only use at present on this programmer is to Read EEPROM files from old Systems that
may require upgrading to TM70 systems.

read data from EEPROM (L)


Pressing “L” option the software allows to load the content of the physical EEPROM into the AP70
memory displaying the EEPROM parameters. On serial number it will be displayed and it may help to
quote the right new system.

exit (F)

Pressing “F” option the software exits the running program.

26 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Configurable Parameters

It is possible to modify some of the values of the EEPROM using the TM70 EEPROM recorder program as
shown below:

Transmitter Disconnection time due to inactivity


In this box, it is possible to configure the disconnecting time of the equipment due to inactivity checking.
A value in seconds must be entered in the dialogue box shown below:

• By clicking on the Infinite box option, the transmitter will not disconnect due to inactivity (the
default value for infinite is shown, which is 6553.5 seconds).
• By clicking again on the Infinite box, the standard value of 240 seconds is configured again, and this
time can be modified up to a maximum of 6553.5 seconds.

Radio Parameters Configuration

By clicking on the Radio—> , a new window will pop up in order to


modify the radio parameters:

Depending on the system configuration, you are able to select the band width in which the system will
work:
• Transceiver 1 bands from 860 to 930 MHz
• Transceiver 2 bands from 430 to 450 MHz
Primarily the Base channel in which the system will transmit can be changed. The Work channel should
be kept to the system value, as it is used for Tandem and Multiple Transmitter systems.

© Danfoss | August 2019 BC314244826802en-000101 | 27


User Manual
TM70 EEPROM Programmer

Configurable Parameters

When we are working with Multiple transmitter systems, the Base channel should be the same for all of
them and the Work channel should be different. Each channel is separated 25 kHz from the previous one,
and after selecting the Base channel, the corresponding frequency will show up on the Frequency Box. It
is recommended to change these values together with the channel frequency list.
The maximum value of the Base Channel depends on the frequency range selected in the EEPROM file
which has been loaded or read before. The Max Value is shown on the Max. Box.
The Initial Scanning on Transmitter option allows the user to enable or to disable this function.
Enabling this feature the transmitter is able to start in the first free working channel in the selected range
by EEPROM.

For example:
The programming a base channel value of 7 and a working channel value of 1, the radio remote system
will start up on channel 8 (base channel number + working channel number).

CANopen Parameters Setup


This option allows to modify the “Node ID” (Device address in the CAN bus network) and the
“Baudrate” (data transfer speed) of the device.

Allowed “NodeID” values from 1 to 127 (decimal value).


Allowed “Baudrate” values from 10 kb/sg to 1Mb/sg. Default value = 250 kb/sg
Within the Protocol dropdown menu

Tele-alignment Activation
Tele-aligment (Teleteaching) option can be enabled (by clicking on) or disabled (by clicking off) in the
following check box.

28 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

Information Parameters (Non-configurable)

There are some dialogue boxes (fields) that cannot be modified; but they show practical information.

Serial Number
It displays the equipment serial number.

Transmitter & Receiver ID Codes


It displays the assigned IDs and the number of IDs assigned to each equipment. The range Limiter code
can be changed for a particular system provided there is Range Limiter:

.EEP.XML Files
These files contain all the information about the configurable parameters of the TMX0 range systems.
These files have a double extension:

• .eep because these files are recorded into the TM70 EEPROMs format.
• .xml because data is recorded in this format (xml compatible format -> they cannot be easily
modified using a text editor).

The content of this files can be displayed using any “xml” format viewer (e.g. Internet Explorer, etc…)
but the content cannot be modified. The only tool which allows to modify the EEPROM parameters
is the EEPROM programmer and the System Configurator.
It has also stored a date and identification number, in order to keep its traceability.

© Danfoss | August 2019 BC314244826802en-000101 | 29


User Manual
TM70 EEPROM Programmer

AP70 Module Hardware Description

The AP70 hardware is prepared to setup TM60 / RAD / RMJ / TM70 and TM80 EEPROM parameters.

Connectors, Selector Switch, LED signalling

3 4 5 6 1 2
1. TM60 EEPROM socket
2. TM80/TM70/RAD/RMJ EEPROM socket
3. HARD OK +5v
4. HARD OK +3v
5. TX ON
6. RX ON

1. DC 10-35 V external power supply


2. USB serial port
3. RS–232 serial port

30 | © Danfoss | August 2019 BC314244826802en-000101


User Manual
TM70 EEPROM Programmer

AP70 Module Hardware Description

Cables and Accessories


USB cable

© Danfoss | August 2019 BC314244826802en-000101 | 31


Products we offer: Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and
electric components. We specialize in providing state-of-the-art technology and solutions that
• DCV directional control
excel in the harsh operating conditions of the mobile off-highway market as well as the
valves
marine sector. Building on our extensive applications expertise, we work closely with you to
• Electric converters
ensure exceptional performance for a broad range of applications. We help you and other
• Electric machines customers around the world speed up system development, reduce costs and bring vehicles
• Electric motors and vessels to market faster.
• Hydrostatic motors Danfoss Power Solutions – your strongest partner in mobile hydraulics and mobile
electrification.
• Hydrostatic pumps
• Orbital motors Go to www.danfoss.com for further product information.

• PLUS+1® controllers We offer you expert worldwide support for ensuring the best possible solutions for
outstanding performance. And with an extensive network of Global Service Partners, we also
• PLUS+1® displays
provide you with comprehensive global service for all of our components.
• PLUS+1® joysticks and
pedals
• PLUS+1® operator
interfaces
• PLUS+1® sensors
• PLUS+1® software
• PLUS+1® software services,
support and training
• Position controls and
sensors
• PVG proportional valves
• Steering components and
systems
• Telematics

Hydro-Gear
www.hydro-gear.com Local address:
Daikin-Sauer-Danfoss
www.daikin-sauer-danfoss.com

Danfoss
Power Solutions Trading
Danfoss Danfoss Danfoss (Shanghai) Co., Ltd.
Power Solutions (US) Company Power Solutions GmbH & Co. OHG Power Solutions ApS Building #22, No. 1000 Jin Hai Rd
2800 East 13th Street Krokamp 35 Nordborgvej 81 Jin Qiao, Pudong New District
Ames, IA 50010, USA D-24539 Neumünster, Germany DK-6430 Nordborg, Denmark Shanghai, China 201206
Phone: +1 515 239 6000 Phone: +49 4321 871 0 Phone: +45 7488 2222 Phone: +86 21 3418 5200

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

© Danfoss | August 2019 BC314244826802en-000101

Potrebbero piacerti anche