Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
GB
RES-403
Operating
Instructions
Important features
• Microprocessor technology
• Automatic zero calibration (AUTOCAL)
• Automatic optimization (AUTOTUNE)
• Automatic configuration of the secondary voltage and current ranges
(AUTORANGE, as of October 2005)
• Automatic phase angle compensation (AUTOCOMP, as of October 2005)
• Automatic frequency adjustment
• Large current and voltage range
• Set point selection with potentiometer
• 0…10VDC analog output for ACTUAL temperature
• Activated with contact or 24VDC signal
• Alarm function with fault diagnosis
• Heatsealing band alloy and temperature range selectable
19.11.07
Page 2 RES-403
Safety and warning notes
RES-403 Page 3
Application
operating safety. They are not included in the scope of 1.7 Standards / CE marking
supply of the standard control system and are
described in a separate document. The controller described here complies with the
following standards, provisions and directives:
2 Application
This RESISTRON temperature controller is an integral The controller is most commonly used for impulse-
part of the "Series 400", the outstanding feature of heatsealing PE films in:
which is its microprocessor technology. All RESI-
• Vertical and horizontal f/f/s machines
STRON temperature controllers are used to control the
temperature of heating elements (heatsealing bands, • Pouch, filling and sealing machines
beaded bands, cutting wires, heatsealing blades, • Film wrapping machines
solder elements etc.), as required in a variety of heat-
sealing processes. • Pouch-making machines
• Group packaging machines
• etc.
Page 4 RES-403
Principle of operation
3 Principle of operation
The resistance of the heatsealing band, which is tem- to the required dynamic range despite the exceptionally
perature-sensitive, is monitored 50x per second (60x at compact dimensions of the controller.
60Hz) by measuring the current and voltage. The tem-
perature calculated with the help of these measure- PLEASE NOTE!
ments is displayed and compared with the set point.
The primary voltage of the impulse transformer is adju- RESISTRON temperature controllers play a significant
sted by phase-angle control, if the measured values role in enhancing the performance of modern
deviate from the set point. The resulting change in the machines. However, the full benefit can only be
current through the heatsealing band leads to a change obtained from the advanced technology offered by this
in the band temperature and thus also its resistance. control system if all the system components, in other
This change is measured and evaluated by the RESI- words the heatsealing band, the impulse transformer,
STRON temperature controller. the wiring, the timing signals and the controller itself,
The control loop is closed: ACTUAL temperature = SET are compatible and interrelated.
temperature. Even minute thermal loads on the heat-
sealing band are detected and can be corrected quickly
and precisely.
We will be pleased to
A highly high response thermo-electric control loop is contribute our many
formed which is highly accurate because purely elec- years of experience
trical variables are measured at a high sampling rate. A towards optimizing your
high secondary current can be controlled because heatsealing system.
power is controlled on the primary side of the trans-
former. This allows optimum adaptation to the load and
RESISTRON controller
IR UR Actual value
Current
transformer R=f(T)
Indicators
U2 and
sec. Start
U1 controls
_
prim. or
+ Set point bus interface
Impulse transformer
LINE
RES-403 Page 5
Description of the controller
Page 6 RES-403
Accessories and modifications
Line filter
Essential in order to ensure CE conformity.
Optimized for the RESISTRON temperature controller.
Impulse transformer
Designed according to VDE 0570/EN 61558 with a one section bobbin.
Optimized for impulse operation with RESISTRON temperature controllers.
Specified according to the heatsealing application (ª ROPEX Application Report).
Booster
External switching amplifier, necessary for high primary currents (continuous
current > 5A, pulsed current > 25A).
RES-403 Page 7
Accessories and modifications
Actual value
Set+ ∆ϑ upper
Set
Set+ ∆ϑ lower
Time
Signal
„Temp. OK“
Conductive
Not conduct.
Time
Page 8 RES-403
Technical data
6 Technical data
Type of construction Housing for installation in the electrical cabinet
Snaps onto a standard top hat rail (DIN TS35 rail, 35 mm) acc. to DIN EN 50022
Dimensions: 90 x 75mm; height: 135mm (incl. terminals)
Five different ranges can be set on the controller with a rotary coding switch:
Temperature coefficient 1100ppm, 0…300°C (e.g. Alloy-A20), default
Temperature coefficient 780ppm, 0…300°C (e.g. Alloy L)
Temperature coefficient 1100ppm, 0…500°C (e.g. Alloy-A20)
Temperature coefficient 780ppm, 0…500°C (e.g. Alloy L)
Temperature coefficient 3500ppm, 0…300°C (e.g. NOREX)
The settings for a temperature coefficient of 780ppm are only available on control-
lers manufactured as of October 2003.
Set point selection With an external PD-3 or PD-5 precision potentiometer (R = 2kΩ)
Terminals 16+17 0…2kΩ, equivalent to 0…300°C or 0…500°C
RES-403 Page 9
Technical data
Ambient +5…+45°C
temperature
End holders to mechanical fix the controller must be fitted at both ends for moun-
ting on a vertical top hat rail.
Weight Approx. 0.7kg (incl. connector plug-in parts)
Page 10 RES-403
Dimensions
7 Dimensions
135.0
113.0
75.0 90.0
8 Installation
ª See also section 1 "Safety and warning notes" on controller in the range from 47Hz…63Hz.
page 3. 3. Install the RESISTRON temperature controller in
the electrical cabinet on a standard top hat rail (DIN
Installation and startup may only be per- TS35 rail, according to DIN EN 50022). If several
!formed by technically trained, skilled per- controllers are installed on one top hat rail, the
sons who are familiar with the associated risks and minimum clearance specified in section 6 "Technical
warranty provisions. data" on page 9 must be allowed between them.
4. Wire the system in accordance with the instructions
in section 8.3 "Power supply" on page 13,
8.1 Installation procedure section 8.6 "Wiring diagram (Standard)" on page 15
and the ROPEX Application Report. The information
Proceed as follows to install the RESISTRON tempera-
provided in section 8.2 "Installation steps" on
ture controller RES-403:
page 12 must also be heeded additionally.
1. Switch off the line voltage and verify that the circuit
is de-energized. Check the tightness of all the system connec-
2. The supply voltage specified on the nameplate of ! tions, including the terminals for the impulse
the RESISTRON temperature controller must be transformer windings.
identical to the line voltage that is present in the
plant or machine. The line frequency is automati- 5. Make sure that the wiring conforms to the relevant
cally detected by the RESISTRON temperature national and international installation regulations.
RES-403 Page 11
Installation
Page 12 RES-403
Installation
LINE Line
L1 (L1)
N (L2) 115VAC, 230VAC, 400VAC
GND/ 50/60Hz
Earth
Circuit breaker
Double-pole, C characteristic
ON K1
(ª ROPEX Application Report)
Short-circuit protection only.
I> I> ! RESISTRON temperature controller not protected.
OFF
3
Ka Relay Ka
For "HEAT ON - OFF" function (all-pole) or
"EMERGENCY STOP".
Line filter
LINE The filter type and size must be determined according to
FILTER the load, the transformer and the machine wiring
(ª ROPEX Application Report).
Short wires Do not run the filter supply wires (line side) parallel
3 ! to the filter output wires (load side).
UR ROPEX
temperature RESISTRON temperature controller belonging to the
IR controller 4xx Series.
Relay Kb
Kb Load break (all-pole), e.g. in combination with the alarm
output of the temperature controller.
When using a series resistor RV-....-1 the relay Kb
! shall be installed.
U1 3
Impulse Transformer
PRIM.
Designed according to VDE 0570/EN 61558 (isolating
transformer with reinforced insulation). Connect core to
ground.
Use transformers with a one section bobbin. The
2
U2 ! power, duty cycle and voltage values must be deter-
SEC.
mined individually according to the application (ª ROPEX
1
Application Report and "Accessories" leaflet for impulse
2
transformers).
Wiring
The wire cross-sections depend on the application
(ª ROPEX Application Report).
Guide values:
Primary circuit: min. 1.5mm², max. 2.5mm²
R Secondary circuit: min. 4.0mm², max. 25mm²
c These wires must always be twisted (>20/m)
d These wires must be twisted (>20/m) if several control
loops are laid together ("crosstalk").
e Twisting (>20/m) is recommended to improve EMC.
RES-403 Page 13
Installation
8.4 Line filter installed and wired correctly, they guarantee com-
pliance with the EMC limit values.
To comply with EMC directives – corresponding to You can find the exact specification of the line filter in
EN 50081-1 and EN 50082-2 – RESISTRON control the ROPEX Application Report calculated for your par-
loops must be operated with line filters. ticular heatsealing application.
These filters damp the reaction of the phase-angle con- For more technical information: ª "Line filter" docu-
trol on the line and protect the controller against line mentation.
disturbances.
It is permissible to supply several RESI-
The use of a suitable line filter is part of the ! STRON control loops with a single line filter,
! standards conformity and a prerequisite of providing the total current does not exceed the
the CE mark. maximum current of the filter.
ROPEX line filters are specially optimized for use in The wiring instructions contained in section 8.3 "Power
RESISTRON control loops. Providing that they are supply" on page 13 must be observed.
Large cross-section
wire to ground
max. 1m
PE
LINE ROPEX
temperature
controller
8.5 Current transformer PEX-W3 of the control system. The current transformer may only
be operated if it is connected to the temperature con-
The PEX-W3 current transformer supplied with the troller correctly (ª section 8.3 "Power supply" on
RESISTRON temperature controller is an integral part page 13).
24 75 14
23 28
terminal
wires
60
12
39
26
14
terminal
block
Page 14 RES-403
Installation
AUTOCAL
8
with 24VDC signal
6
ALARM
OUTPUT
max. 50V/0,2A 5
Contact closed or 3
opened by ALARM
START (HEAT) (see configuration) 4
12
with 24VDC signal U1
prim.
GND 13 Impuls
transformer
Ground
U2
for 24VDC signals. sec.
Must be grounded
externally to prevent
electrostatic
charging! 7 Heat-
UR R sealing
0V 9 band
18 (Internal ground) twisted
No external
START (HEAT) grounding allowed!
with contact 10
IR
15 up to 11
_
production Current transformer
ATR date PEX-W2/-W3
°C September 2005
+
ANALOG 14 0V
OUTPUT (Internal ground)
+0...10VDC No external
Cable shielded grounding allowed!
cw
16
2K 0V
(Internnal ground)
17
SET POINT No external
POTENTIOMETER grounding allowed!
PD-3 or PD-5
RES-403 Page 15
Installation
GND 13 Impuls
transformer
Ground
U2
for 24VDC signals. sec.
Must be grounded
externally to prevent
electrostatic
charging! 7 Heat-
UR R sealing
0V 9 band
18 (Internal ground) twisted
No external
START (HEAT) grounding allowed!
with contact 10
IR
15 up to 11
_
production Current transformer
ATR date PEX-W2/-W3
°C September 2005
+
ANALOG 14 0V
OUTPUT (Internal ground)
+0...10VDC No external
Cable shielded grounding allowed!
cw
16
2K 0V
(Internnal ground)
17
SET POINT No external
POTENTIOMETER grounding allowed!
PD-3 or PD-5
Page 16 RES-403
Installation
19 20
BOOSTER
Additional terminals
in housing cover
for MOD 26 (Booster connection)
+24VDC +24VDC
RES- 403
1
ALARM
HEAT
2
+ OUTPUT
AUTOCAL
Imax. 50mA
3
4
GND GND
Additional terminals
in housing cover
for MOD 40 (”Temp. reached” signal)
or MOD 46 (”Temp. OK” signal)
MOD 40 cannot be used in combination with MOD 46 cannot be used in combination with
! MOD 26 (booster connection) manufactured ! MOD 40.
prior to September 2005.
RES-403 Page 17
Installation
LEDs
Terminals
Button for
AUTOCAL function
Wiring diagramm
Nameplate
8.11 Controller configuration range from 30A to 500A. If the voltage and/or the
current is outside the permissible range, a detailed
The controller must be switched off in order error message appears on the controller (ª see
! to configure the coding switches and plug-in section 9.12 "Error messages" on page 31).
jumpers.
Configuration with coding switches
8.11.1 Configuration of the DIP switches (up to September 2005)
for secondary voltage and current
Set the DIP switches for matching the secondary
Automatic configuration (AUTORANGE) voltage U2 and the secondary current I2 to the correct
(as of October 2005) position for your application.
The secondary voltage and current ranges are You can find the exact configuration of the
automatically configured by the automatic calibration ! DIP switches in the ROPEX Application
function (AUTOCAL). The voltage is configured in the Report calculated for your particular application.
range from 0.4VAC to 120VAC and the current in the
Page 18 RES-403
Installation
OFF
1-10
Factory settings
ON 1 2 3 4 5
SWITCH
U2 ( V )
ON
3
U2 DIP switch I2 DIP switch
12345
4
1 2 3 4 5
1...10V ON OFF OFF 30...100A OFF OFF
OFF
ON
2x
2 34
2 34
0 = Factory settings
6
The settings for a temperature coefficient of If the switch is set to "9" (as of October 2005), more
! 780ppm (switch position 1 and 5) are only temperature ranges and alloys can be selected by
available on controllers manufactured as of means of the ROPEX visualization software (ª see
October 2003. section 9.10 "Diagnostic interface/visualization soft-
ware (as of October 2005)" on page 30).
RES-403 Page 19
Installation
789
1
2 34
(factory setting)
6
5
If the plug-jumper is not inserted - or if it is rature coefficient TCR. Too low a TCR leads to oscilla-
! incorrectly inserted - an error message tion or uncontrolled heating.
appears when the controller is switched on When heatsealing bands with a higher TCR are used,
(ª
ª section 9.12 "Error messages" on page 31). the controller must be calibrated for this.
The first time the heatsealing band is heated to appro-
If the "Alarm output opened by alarm/PC CONFIGURA- ximately 200…250°C, the standard alloy undergoes a
TION" position is selected (as of October 2005), the once-only resistance change (burn-in effect). The cold
behavior of the alarm output can be configured in more resistance of the heatsealing band is reduced by appro-
detail by means of the ROPEX visualization software ximately 2…3%. However, this at first glance slight
(ª see section 9.10 "Diagnostic interface/visualization resistance change results in a zero point error of
software (as of October 2005)" on page 30). 20…30°C. The zero point must therefore be corrected
after a few heating cycles, i.e. the AUTOCAL function
must be repeated.
8.12 Replacing and "burning in" the The burn-in effect described here does not occur if the
heatsealing band heatsealing band has already been thermally pret-
reated by the manufacturer.
8.12.1 "Burning in" the heatsealing band
An overheated or burned-out heatsealing
The heatsealing band is a key component in the control ! band must no longer be used because the
loop, since it is both a heating element and a sensor. TCR has been altered irreversibly.
The geometry of the heatsealing band is too complex to
be discussed at length here. We shall therefore only One very important design feature is the copper or
refer to a few of the most important physical and elec- silver-plating of the heatsealing band ends. Cold ends
trical properties: allow the temperature to be controlled accurately and
The measuring principle applied for this system neces- increase the life of the teflon coating and the heat-
sitates a heatsealing band alloy with a suitable tempe- sealing band.
Page 20 RES-403
Installation
All power supply leads must be disconnected from the As of SW-Revision 106:
RESISTRON temperature controller in order to replace ! If the red "ALARM" LED lights up for 0.3s in
the heatsealing band. addition to the yellow "AUTOCAL" LED when the
voltage is switched on, the configuration of this
The heatsealing band must be replaced in controller has been changed in the visualization
! accordance with the instructions provided by
software (ª ª section 9.10 "Diagnostic interface/
the manufacturer.
visualization software (as of October 2005)" on
page 30). In order to avoid malfunctions, please
Each time the heatsealing band is replaced, the zero
check the controller configuration before
point must be calibrated with the AUTOCAL function
continuing the startup procedure.
while the band is still cold, in order to compensate pro-
duction-related resistance tolerances. The burn-in pro-
7. One of the following states then appears:
cedure described above should be performed for all
new heatsealing bands.
"ALARM" "OUTPUT"
ACTION
LED LED
8.13 Startup procedure OFF Short pulses Go to 7
every 1.2s
Please also refer to section 1 "Safety and warning
notes" on page 3 and section 2 "Application" on BLINKS fast OFF Go to 7
page 4. (4Hz)
RES-403 Page 21
Installation
actual value output: on page 20) and repeat the AUTOCAL function.
The controller is functioning correctly if the tempera-
ture (which corresponds to the signal change at the
analog output) has a harmonious motion, in other The controller is now
words it must not jump abruptly, fluctuate or deviate ready
temporarily in the wrong direction. This kind of beha-
vior would indicate that the UR measuring wires
have been wired incorrectly. 8.13.2 Restart after replacing the heat-
If an error message is displayed, please proceed as sealing band
described in section 9.12 "Error messages" on To replace the heatsealing band, proceed as described
page 31. in section 8.12 "Replacing and "burning in" the heat-
9. Burn in the heatsealing band (ª section 8.12 sealing band" on page 20.
"Replacing and "burning in" the heatsealing band"
Always use a heatsealing band with the cor-
! rect alloy, dimensions and copper-plating in
order to avoid malfunctions and overheating.
Page 22 RES-403
Controller functions
9 Controller functions
See also section 8.6 "Wiring diagram (Standard)" on
page 15.
ALARM
HEAT Yellow LED, lit during heating phase.
2
OUTPUT
AUTOCAL
3
RES- 403
Temperature
controller Button for manual activation of AUTOCAL
function (zero calibration). Do not press
ROPEX
Tel:+49(0)7142-7776-0
unless heatsealing band is cold.
Made in Germany
AUTOCAL
Button for manual activation of AUTOCAL
function (zero calibration). Do not press
1
OUTPUT
HEAT
of AUTOCAL process.
4
ALARM
Green LED, indicates pulses in measure-
ment mode. In control mode, luminous
! intensity is proportional to heating current.
12 13 14 15 16 17 18
5 6 7 8 9 10 11
ROPEX
INDUSTRIE - ELEKTRONIK
.
RES-403 Page 23
Controller functions
In addition to the functions shown in the diagram by the LEDs. These states are described in detail in the
above, various controller operating states are indicated table below:
RESET active,
AUTOCAL START and AUTOCAL AUTOCAL requested, but
AUTOCAL executing
(yellow) functions are locked function disabled
(as of October 2005)
OUTPUT
In control mode the luminous intensity is proportional to the heating current.
(green)
Page 24 RES-403
Controller functions
9.3 Temperature indication (actual The relationship between the change in the output
value output) voltage and the ACTUAL temperature is linear.
Temperature T
which is proportional to the real ACTUAL temperature, 300
at terminals 14+15. 270
240
RES-403 210
180
Actual value max. 5mA
R=33Ohm
150
output 14
0...10VDC 120
0V 15 90
60
20°C
1 2 3 4 5 6 7 8 9 10
0...10VDC 0.66V Voltage U VDC
+ "ZERO"
500
meter
e.g. ATR-3 450
400
350
300
250
Voltage values:
0VDC Æ 0°C 200
10VDC Æ 300°C or 500°C 150
(depending on the controller 100
configuration)
20°C
1 2 3 4 5 6 7 89 10
0.4V Voltage U VDC
"ZERO"
RES-403 Page 25
Controller functions
Page 26 RES-403
Controller functions
You should always wait for the heatsealing • By means of a 24VDC signal at terminals 12+13
! band and the bar to cool down (to ambient
temperature) before activating the AUTOCAL 24VDC
function. START RES- 403
(HEAT)
12
Reasons for disabled AUTOCAL function: max. 6mA
1. The AUTOCAL function cannot be activated until
10 seconds after the controller is switched on. If you
attempt to activate it sooner, it will not function.
GND
2. The AUTOCAL function is not activated if the heat- 13
sealing band is cooling down at a rate of more than
0.1K/sec. If the control signal is activated, the
function is activated automatically providing the
cooling rate has fallen below the above mentioned
value. HIGH: 12VDC
3. If the "START" signal (24VDC) is active, the
AUTOCAL function is not executed ("HEAT" LED
START
lit).
(HEAT)
4. AUTOCAL cannot be activated if error codes
101…103, 201…203, 801 or 9xx (up to September LOW: 2VDC
2005: error codes 1…3, 5…7) occur at start-up.
AUTOCAL cannot be activated with error codes
or
201…203, 801 or 9xx (up to September 2005: error
codes 5…7). If the controller has operated correctly, • By means of a control contact at terminals 15+18
at least one time, after start-up (ª section 9.12
"Error messages" on page 31). max.
5mA RES- 403
If the AUTOCAL function is disabled and if 18
! you attempt to activate it then the
START
"AUTOCAL" LED blinks. (HEAT)
with
contact
9.5 "START" signal (HEAT) 15 0V
When the "START" signal is activated, the controller-
internal set/actual comparison is enabled and the heat-
sealing band is heated up to the SET temperature. It
remains at this temperature until the signal is deacti- The "START" signal is disabled as long as the
vated. !AUTOCAL function is executing
The "HEAT" LED on the front panel of the RES-403 is ("AUTOCAL" LED lit, "HEAT" LED blinks).
lit continuously for the duration of the heating phase.
The "START" signal can be activated in two ways: The terminals 15+18 are not potenial-free and
! might have the potential of the secondary
voltage of the impulse transformer. For the termi-
nals of the control contact touch voltage protection
must be installed. External grounding is not
allowed. If this warning is ignored, the controller
will be damaged by frame currents.
RES-403 Page 27
Controller functions
Function
9.6 Measuring impulse duration AUTOCOMP
(as of October 2005)
AUTOCAL
The length of the measuring impulses generated by the 0
controller can be set with the parameter. It may be t
necessary to set a measuring impulse that is longer "AUTOCAL"
than the default 1.7ms for certain applications LED
(ª ROPEX Application Report). lit
Page 28 RES-403
Controller functions
Set+ ∆ϑ lower
OFF
t
„OUTPUT“
LED
lit
OFF Time
t Alarm
307
The "OUTPUT" LED blinks repeatedly when the
"AUTOCOMP" function is executed and the actual If the temperature diagnosis is not activated by the time
value output (terminals 17+14) is set to 0…3°C the "START" signal is deactivated (i.e. if the ACTUAL
(i.e.approx. 0VDC). temperature does not exceed the upper or lower
tolerance band limit), the corresponding error code
The "AUTOCOMP" function must be (309, 310) is indicated and the alarm relay is switched.
! activated in the ROPEX visualization An additional delay time (0…9.9s) can be set in the
software (ª section 9.10 "Diagnostic interface/ ROPEX visualization software. The first time the lower
visualization software (as of October 2005)" on tolerance band limit is exceeded, the temperature dia-
page 30) (default setting: AUTOCOMP off). gnosis is not activated until the parameterized delay
time has elapsed. The temperature diagnosis function
can thus be explicitly deactivated, e.g. if the tempera-
9.8 Temperature diagnosis ture drops temporarily owing to the closure of the
(as of October 2005) sealing jaws.
An additional temperature diagnosis can be activated in The values that can be set in the ROPEX
the ROPEX visualization software (ª section 9.10 ! visualization software for the upper and
"Diagnostic interface/visualization software (as of lower tolerance band and the delay time are iden-
October 2005)" on page 30). The RES-403 checks tical to those for the "Temperature OK" signal
whether the ACTUAL temperature is within a settable (MOD 46).
tolerance band ("OK" window) on either side of the SET
RES-403 Page 29
Controller functions
states.
• CLOSED in operating state A.3)
Page 30 RES-403
Controller functions
If the alarm relay is configured opposite to the factory fined operating state. This must be taken into
setting (ª section 8.11.3 "Configuration of the alarm account when they are evaluated by the higher-
relay" on page 20), these states are reversed. level controller (e.g. a PLC) in order to avoid false
alarms.
C.) Error code output via the 0…10VDC analog
output (terminals 14+15):
9.12 Error messages
Since a temperature indication is no longer necessary
if a fault occurs, the analog output is used to display The table below shows how the analog voltage values
error messages in the event of an alarm. correspond with the faults that have occurred. It also
13 voltage levels (up to September 2005: 12 voltage describes the fault and the required corrective action.
levels) are offered for this purpose in the 0…10VDC The error messages are listed in two separate tables for
range, each of which is assigned an error code controllers "up to September 2005" and "as of October
(ª section 9.12 "Error messages" on page 31). 2005". The block diagram in section 9.13 "Fault areas
If a state that requires AUTOCAL occurs – or if the con- and causes" on page 36 permits each fault to be
troller configuration is not correct – (error codes cleared quickly and efficiently.
104…106, 111…114, 211, 302, 303; up to September 13 voltage levels for fault diagnostics appear at the
2005: error codes 8…12), the signal at the analog actual value output of all controllers manufactured as of
output jumps back and forth at 1Hz between the October 2005. The error messages are differentiated
voltage value which corresponds to this error and the even more finely in the controller. The error codes
end of the scale (10VDC, i.e. 300°C or 500°C). If the described below can be displayed with the ROPEX
"START" signal is activated in one of these states, the visualization software (ª section 9.10 "Diagnostic
voltage value does not change any more. interface/visualization software (as of October 2005)"
Selective fault detection and indication can thus be on page 30) to facilitate troubleshooting.
implemented simply and inexpensively using the
analog input of a PLC with a corresponding error mes- If the actual value output is evaluated in order
sage (ª section 9.12 "Error messages" on page 31). ! to identify an error message - in the higher-
level controller, for instance - the tolerance window
An alarm can only be reset by switching the must be adjusted to prevent it from being incor-
! controller off and then on again. rectly interpreted. Please note the tolerances of the
actual value output (ª ª section 6 "Technical data"
Invalid error messages may appear when the on page 9).
! controller is switched off owing to the unde-
RES-403 Page 31
Part 1 of 3: Error messages as of October 2005
Page 32
Act. value Temp. Temp. STATUS Action Action if machine
Error ALARM
output; 300°C 500°C of alarm relay Cause if machine started already operating,
code LED
Voltage [V] [°C] [°C] (factory set.) for first time HS band not chang.
3 (103) 2.00 60 100 UR and IR signals missing Fault area d Fault area dk
(107) Temperature step, down Fault area fgh Fault area fgh
(108) Temperature step, up (loose contact) (loose contact)
RES-403
(310)
contin- Closed
(201) uously
Frequency fluctuation, Check
5 (202) 3.33 100 166 Check power supply
inadmissible line frequency power supply
(203)
Heatup time too long
6 (304) 4.00 120 200 Run RESET Run RESET
(ª section 9.9)
NOTE: The specified error messages are initially output as warnings (actual value output jumps back and forth between two values;
alarm LED blinks; alarm relay is open). When the "START" signal is activated, the warning changes to a fault
(actual value output no longer jumps back and forth, see bold italic values; alarm LED lit continuously; alarm relay is closed.
Controller functions
IR signals incorrect,
(104) incorrect specification of
impulse-transformer
Run AUTOCAL,
UR signals incorrect,
Check specification
(105) incorrect specification of
Warning: of transformer,
impulse-transformer
Warning: Open Fault area ij
Blinks UR and/or IR signals
¯5.33« ¯160« ¯266« fast incorrect, Fault area fgh
RES-403
8 (106) (4Hz) Fault:
ª 10 ® ª300® ª500® incorrect specification of (loose contact)
Closed impulse-transformer
Fault: (voltage value
Lit at actual Temperature too low,
contin- value output AUTOCAL wasn’t per-
(302)
uously then no longer formed, loose contact, Run AUTOCAL
changes) ambient temp. fluctuates and/or
temperature too high, fault area fgh
AUTOCAL wasn’t per- (loose contact)
(303)
formed, loose contact,
ambient temp. fluctuates
¯6.00« ¯180« ¯300«
9 (211) Data error Run AUTOCAL ---
ª 10 ® ª300® ª500®
Page 33
Part 3 of 3: Error messages as of October 2005
Page 34
NOTE: The specified error messages are initially output as warnings (actual value output jumps back and forth between two values;
alarm LED blinks; alarm relay is open). When the "START" signal is activated, the warning changes to a fault
(actual value output no longer jumps back and forth, see bold italic values; alarm LED lit continuously; alarm relay is closed).
RES-403
Lit at actual Ext. calibration
(115) contin- value output temperature too high,
¯8.66« ¯260« ¯433«
13 uously then no longer calibration not possible
ª 10 ® ª300® ª500®
changes)
Ext. calibration
(116) temperature fluctuates
calibration not possible
Controller functions
Error messages up to September 2005
Error Act. value Temp. Temp. ALARM STATUS Action Action if machine
output ; 300°C 500°C of alarm relay Cause if machine started already operating,
code LED
Voltage [V] [°C] [°C] (factory set.) for first time HS-band not chang.
Controller functions
Internal fault,
7 4.66 140 233 Replace controller Replace controller
controller defective
RES-403
¯5.33« ¯160« ¯266« UR and/or IR signal
8 Run AUTOCAL Fault areas fgh
ª 10 ® ª300® ª500® Blinks incorrect
fast Open,
¯6.00« ¯180« ¯300« (4Hz)
9 does not close Data error Run AUTOCAL ---
ª 10 ® ª300® ª500®
until "START"
¯6.66« ¯200« ¯333« signal IR signal incorrect, Fault area j,
10 ---
ª 10 ® ª300® ª500® (voltage value calibration not possible check configuration
Blinks at analog
¯7.33« ¯220« ¯365« output then UR signal incorrect, Fault area i,
11 slowly ---
ª 10 ® ª300® ª500® no longer calibration not possible check configuration
(1Hz)
changes)
¯8.00« ¯240« ¯400« UR and IR signals incorrect, Fault areas ij,
12 ---
ª 10 ® ª300® ª500® calibration not possible check configuration
Page 35
Controller functions
5 1 2 2 9
6 3
Temperature
4 controller
HARDWARE
9
123 45
8 I2 8
UR
8
1 U2 7
IR
7
Page 36 RES-403
Factory settings
Turns through PEX-W2/-W3 - Check number of turns (two or more turns required for
current transformer incorrect currents < 30A)
10 Factory settings
The RESISTRON temperature controller RES-403 is
configured in the factory as follows:
2 34
8 300°C
6
9
5
8 300°C
6
9
5
RES-403 Page 37
Maintenance
[X]
[X]
[X]
11 Maintenance
The controller requires no special maintenance. the impulse transformer – is recommended. Dust depo-
Regular inspection and/or tightening of the terminals – sits on the controller can be removed with dry com-
including the terminals for the winding connections on pressed air.
Page 38 RES-403
How to order
12 How to order
Contr. RES - 403 / . . . VAC
115: Power supply 115VAC, Art. No. 740301
230: Power supply 230VAC, Art. No. 740302
400: Power supply 400VAC, Art. No. 740303
Scope of supply: Controller includes connector plug-in
parts (without current transformer)
Please indicate the article numbers of the controller and the required modifications
(optional) in all orders,
e.g. RES-403/400VAC + MOD 26
(controller for 400VAC power supply with booster connection)
Art. No. 740303 + 800026 must be ordered
Impulse transformer
See ROPEX Application Report
for design and ordering information
Potentiometer PD- .
3: For 300°C range, Art. No. 881103
5: For 500°C range, Art. No. 881105
Scope of supply: Potentiometer with digital dial
RES-403 Page 39
How to order
Booster B- . . . 400
075: Max. pulse load 75A, 400VAC, Art. No. 885301
100: Max. pulse load 100A, 400VAC, Art. No. 885304
Page 40 RES-403
Index
13 Index
A Impulse transformer 7, 13, 39
Accessories 6 Installation 10, 11
Actual value output 25 Installation procedure 11
Alarm output 30 Installation regulations 11
Alarm relay 10, 20
Alloy 19, 22 L
Ambient temperature 10 Line filter 7, 13, 14, 39
Analog temperature meter 6 Line frequency 6, 9
Application 4 Line voltage 9
Application Report 11, 14, 18
AUTOCAL 6, 21, 26
M
AUTOCOMP 28
Maintenance 38
Automatic phase angle compensation 28
Measuring impulse duration 28
Automatic zero calibration 6, 21, 26
Modifications 7, 16, 17, 39
AUTOTUNE 6
MODs 7, 16, 17, 39
B O
Booster 7, 16, 40
Overheating of heatsealing band 6
Burning in the heatsealing band 20, 22
C P
PEX-W2/-W3 3
Circuit breaker 13
PEX-W3 14, 39
CI-USB-1 7, 30, 39
Phase angle compensation 28
Communication interface 7, 30, 39
Potentiometer 6, 24, 39
Controller configuration 18
Power dissipation 10
Controls 23
Power supply 13, 39
Current transformer 14, 39
Principle of operation 5
D
R
Degree of protection 10
Replacing the heatsealing band 21, 22
Diagnostic interface 30
Digital temperature meter 6
Dimensions 11 S
DIP switches 18 Secondary current I2 18
Secondary voltage U2 18
Set point potentiometer 6, 24
E
Set point selection 9, 24
Error messages 31
Signal „Temperatur erreicht“ 8
External switching amplifier 7, 16
"START" signal 21, 27
Startup 18
F System diagnostics 30
Factory settings 37 System monitoring 30
Fault areas 36
Fault diagnosis 6
T
TCR 3, 20
H Technical data 9
HEAT 21, 27 Temperature coefficient 3, 20
Heatsealing band type 9 Temperature control 4
Heatup timeout 30 Temperature diagnosis 29
How to order 39 Temperature indication 25
Temperature indicator 25
I Temperature meter 6, 39
Impulse heatsealing method 4 Temperature OK signal 17
RES-403 Page 41
Index
Temperature range 9, 19 V
Temperature reached signal 8, 17 View of the controller 18
Temperature setting 24 Visualization software 30
Transformer 3, 7, 13, 39
Type of construction 9
W
Wiring 11, 13
Wiring diagram 15, 16
Page 42 RES-403