Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
SYSTEM PROTECTION
RELAYING
ENERGIZE YOUR EXPERTISE
AREVA T&D
Basic Protection Philosophy
SO THAT :
X Damage to the faulted equipment is limited;
X Disruption of supplies to adjacent unfaulted
equipment is minimised.
SUMMARY :
Protection must :
X Detect faults and abnormal operating conditions;
X Isolate the faulted equipment.
So as to :
X Limit damage caused by fault energy;
X Limit effect on rest of system.
Underground Cables
Diggers
Overloading
Oil Leakage
Ageing
Overhead Lines
Lightning
Kites
Trees
Moisture
Salt
Birds
Broken Conductors
Machines
Mechanical Damage
Unbalanced Load
a
b
Ø/Ø/E
c
e
a
Ø/Ø b
c
a a
3Ø b b
c 3Ø/E c
a a'
CROSS b b'
COUNTRY c c'
FAULT
e e
a
OPEN
b
CIRCUIT
+ Ø/E c
FAULT
BETWEEN
ADJACENT
PARALLEL
LINES
a
CHANGING
FAULT IN
CABLE
b c
X Fuses
For : LV Systems, Distribution Feeders and
Transformers, VTs, Auxiliary Supplies
X Differential
For : Feeders, Busbars, Transformers, Generators,
etc.
High Impedance
Restricted E/F
Biased (or low-impedance)
Pilot Wire
Digital
X Distance
For : Distribution Feeders and Transmission
and Sub-Transmission Circuits
Also used as Back-up Protection for
Transformers and Generators
X Phase Comparison
For : Transmission Lines
X Directional Comparison
For : Transmission Lines
X Miscellaneous
Under and Over Voltage
Under and Over Frequency
Special Relays for Generators,
Transformers, Motors, etc.
X Control Relays
Auto-Reclose, Tap Change Control, etc.
51
Trip Coil
IF
X AC series trip
common for electromechanical O/C relays
IF '
+
Sensitive
51 Trip
Coil
-
IF
IF
IF '
51
DC SHUNT
BATTERY TRIP COIL
Protected
Circuit
Protected
Circuit
Relay
ZS PT.
IR ZL
Normal
VS VR ZLOAD
Load
VR
Impedance measured ZR = = Z L + Z LOAD
ΙR
ZL
ZS IR ZF
VS VR ZLOAD Fault
jX ZL Impedance Seen At
Measuring Location
For Line Faults
TRIP STABLE
jIX
IF zF
IZ
V2 V1
VF V3
IR
Trip TRIP STABLE
Spring
3 x internal pipe
Conservator
diameter (minimum)
5 x internal pipe
diameter (minimum)
Oil conservator
3 minimum
Transformer
Less damage
Less pre-heating of circuit breaker contacts (reduced
maintenance?)
Less chance of transient fault becoming permanent
LOAD
SOURCE
LOAD
LOAD
F1 LOAD F2
F3
X Speed
Fast operation :
Minimises damage and danger
Very fast operation :
Minimises system instability
Discrimination and security can be costly to
achieve as it generally involves additional
signaling / communications equipment.
TRANSF- BUSBAR
BUSBAR ORMER ZONE
ZONE ZONE
FEEDER
ZONE
GENERATION ZONE
BUSBAR
ZONE FEEDER
ZONE
X Overlap of Protections
No blind spots
Where possible use overlapping CTs
BBP BBP
‘1’ ‘2’
H J
‘Z’
G LP LP K L
‘H’ ‘J’
LP LP
‘K’ ‘L’
X Dependability / Reliability
Protection must operate when required to
Failure to operate can be extremely damaging
and disruptive
Faults are rare. Protection must operate even
after years of inactivity
Improved by use of: Back-up protection and
duplicate protection
X Security / Stability
Protection must not operate when not required to,
e.g. due to : Load switching
Faults on other parts of the system
Recoverable power swings
X Phase Discrimination
Correct indication of phases involved in the fault
Important for single phase tripping and auto-
reclosing applications
DISTRIBUTION SYSTEMS
Outline
¾ What technologies have been employed
¾ What are the key elements of modern protective
relays
¾ Design Considerations
¾ Impact on the Design of protection and control
systems
4 National Control
WAN
3 Area Control
LAN
2 Substation
LAN
1 Bay
Field Bus
Optical
0 transducers Field
CT & VT
Interconnection Bus
User Interface
Signal Processing Communications (HMI)
Interconnection Bus
User Interface
Signal Processing Communications (HMI)
V
Sample ADC
1011011...
+Vref
Vref
Vout
V Vref
in
-Vref
Multiplexer
+10V xn = 5 x 4096
5V
(10 + 10)
0
= 1024
-10V
5V 1024 0100 0000 0000
-5V -1024 1100 0000 0000
Sign bit
10110111...
Sampling element
Apparent Signal
Actual Signal
Sample Points
Ip
Φsat
Average flux
Is
¾ Use of alternative
technologies to measure
voltage and current
¾ Improved linearity
¾ Interface unit to convert to
sampled data
¾ Fixed sample rate
¾ Interface is via digital link
Electrical - RS485
Fibre - Ethernet
¾ Example shows non-
conventional CT
Interconnection Bus
User Interface
Signal Processing Communications (HMI)
8-bit
data
Verify
Interconnection Bus
User Interface
Signal Processing Communications (HMI)
¾ Wetting currents
¾ Burden
¾ Isolation
¾ How many ?
¾ How fast ?
¾ Thermal dissipation
¾ Safety
¾ Operation for different voltage levels
External Trigger
+ +5V
Input state
(Block Operation ?)
Station
battery
0V
Strobe
Mono-stable
-- 0V
Opto isolation
Interconnection Bus
User Interface
Signal Processing Communications (HMI)
Fixed function
LEDs Alarm viewer
Menu browser
Programmable
LEDs
Battery
back-up Download/
Monitor port
Local
communications
MiCOM_29
Interconnection Bus
User Interface
Signal Processing Communications (HMI)
Standards z Modbus
z DNP3.0
Protocols
z IEC60870-5-103
Media z UCA2
z IEC61850
RS485/Fibre/Ethernet
Interconnection Bus
User Interface
Signal Processing Communications (HMI)
Software
¾ Microprocessors:
Microcontroller
Digital Signal Processor
¾ Memory
RAM
FLASH EPROM
NV RAM
¾ Real-time Clock
¾ User Interface
¾ Communication Interfaces
z Software
– Acquisition
Application – Filters
Software – Algorithms
– Scheme logic
Operating Communications
– Communications
Platform – Event logging
BIOS – Recording
– HMI
Hardware – RTOS
¾ Changes to Legislation
Environmental (WEEE Directive)
Safety issues (Company liability)
¾ Algorithm simulation
¾ Module testing
¾ Integration testing
¾ Environmental testing
¾ Automated testing
¾ System simulation tests
RTDS shown
¾ Complex functionality
requires extensive testing
¾ Software modifications
require regression tests
¾ Global Products
Language issues
Local practices
¾ Customer changes
Privatisation
Loss of skills
¾ Environmental Issues
¾ Technology
Component obsolescence
¾ Competition
Bay Monitoring
& Control
Programmability
& Customisation
Comprehensive
Protection
Instrumentation
Self Diagnostics
& Commissioning
Tools Fault
Analysis Tools
Communications
MiCOM40-43
Relay
Optos contacts
Gate
Logic
&
Protection
Elements 1
&
Control Timers
Fixed LEDs
scheme
logic User programmable scheme
logic
MiCOM_47
Protection Programmable
Function Logic Local
Indications
Control
Control Function
System
Inputs
Indications
Scheme Subsystem
WEB access
SCADA Interface
DNP3 & IEC 60870-5-101
Hubs
HV FEEDER
Fast Ethernet
BAY
Hubs UCA2-IEC 61850 Hubs
HV FEEDER
BAY Hubs
I/Os
I/Os
COMMON BAY MV FEEDER
BAYS
TRANSFORMER
Cubicle/Switchboard
EXISTING
BAY integration MV FEEDER
BAYS
55 > Relay design tutorial - Feb 2005 55
55
Protection Scheme using Numeric Products
V I
V = Vsinwt = V ∠0°
θ
I = I ∠-θ° = Isin(wt-θ)
j = 1 ∠90°
90° 90°
j2 = 1 ∠180° 1
= -1
90° 90°
j3 = 1 ∠270°
= -j
1 3
a = 1∠120° = - + j
2 2
120°
120° 1
120°
1 3
a = 1∠240° = − − j
2
2 2
7 > Fault Analysis – January 2004 7
a = 1 ∠120 °
Balanced 3Ø voltages :-
VC = aVA
a2 + a + 1 = 0 VA
VB = a2VA
GENERATOR TRANSFORMER
LINE ‘X’ LINE ‘Y’
LOADS
3Ø FAULT
Eb IbF
Ec IcF
ZLOAD
IaF
Ec Eb
IbF
i
TIME
11kV 11kV
XG=0.2pu 11kV
j0.05 j0.1
20MVA
XG=0.2pu
20MVA
IF
⇒ IF
2 Winding Transformers
ZM ZM Æ Infinity ∴ Represented by
an Open Circuit
N1 ZT1 = ZP + ZS = Positive
Sequence Impedance
P1 ZT1 = ZP + ZS S1
ZP and ZS
both expressed
on same voltage
N1 base.
Xd"
M 1.0
Small Motors
Motor load <35kW neglect
Motor load >35kW SCM = 4 x sum of FLCM
Large Motors
SCM ≈ motor full load amps
Xd"
Definition
11 kV 11/132 kV 132/33 kV
20 MVA 50 MVA 50 MVA
O/H LINE FEEDER
(kVb )2
Base Impedance = Zb = in Ohms
MVAb
MVAb
Base Current = Ιb = in kA
3 . kVb
MVA a
Per Unit MVA = MVAp.u. =
MVAb
KVa
Per Unit Voltage = kVp.u. =
KVb
Za MVAb
Per Unit Impedance = Zp.u. = = Za .
Zb (kVb )2
Ιa
Per Unit Current = Ιp.u. =
Ιb
X1 R2 X2
R1
N : 1
Ideal
Transformer
X If ZT = 5%
with Secondary S/C
5% V (RATED) produces I (RATED) in Secondary.
∴ V (RATED) produces 100 x I (RATED)
5
= 20 x I (RATED)
X If Source Impedance ZS = 0
Fault current = 20 x I (RATED)
Fault Power = 20 x kVA (RATED)
1 2
MVA
kVb / kV1 kVb / kV2
Incorrect selection
of kVb 11.8kV 132kV 11kV
Z p.u.1 Z p.u. 2 Za
Zp.u.1 =
Zb1
Za Z
Zp.u.2 = = Zp.u.1 x b1
Zb2 Zb2
Zb1 Zb2
MVAb1 (kVb1)2 MVAb2
= Zp.u.1 x x
MVAb2 MVAb1 (kVb2 )2
kVb1 kVb2 MVAb2 (kVb1)2
= Zp.u.1 x x
MVAb1 (kVb2 )2
Actual Z = Za
= 0.75p.u.
1.432p.u.
V 1p.u. IF = 1 = 0.698p.u.
1.432
LINE TO GROUND
LINE TO LINE
Causes :
1) Insulation Breakdown
2) Lightning Discharges and other Overvoltages
3) Mechanical Damage
Causes :
1) Broken Conductor
2) Operation of Fuses
3) Maloperation of Single Phase Circuit Breakers
Analysed using :-
X Symmetrical Components
X Equivalent Sequence Networks of Power
System
X Connection of Sequence Networks
appropriate to Type of Fault
120° 240°
VA0
VB0
VC0
Zero Sequence
VA1 VB
VA2 VA0VB0
+ VC0
+ VC2
VC1
VB1 VB2
VA0
VA
VA2
VA1
VC
VC0
VC1
VC2 VB
VB1 VB0
VB2
46 > Fault Analysis – January 2004 46
Converting from Phase Values to
Sequence Components
VA1 = 1/3 {VA + a VB + a2VC}
VA2 = 1/3 {VA + a2VB + a VC}
VA0 = 1/3 {VA + VB + VC}
VA
VB
3VA0
VC
VA0
IA
IB
IC
IRESIDUAL = IA + IB + IC
= 3I0
E/F
VC
VA = 1 ∠0°
VB = 1.5 ∠-90°
VA
VC = 0.5 ∠120°
VB
51 > Fault Analysis – January 2004 51
Solution
VC1 = aVA1
VA1 = 0.965∠15º
15º
VB1 = a2VA1
53 > Fault Analysis – January 2004 53
VA2 = 0.211∠150° VC2 = a2VA2 -55º
150º
VA0 = 0.434∠-55º
VB0 = -
VC0 = -
VB2 = aVA2
Zero Sequence
Voltages
Negative Sequence
Voltages
VC2
VC1 VC0
VC
VA2
VC2
VA2 VA1
VA0
VA
VB2 V0
VB1
VB2
VB0 VB
Solution
IA = IA1 + IA2 + IA0 = 0
P Q
ZT0
a a
P Q
b b
N0
'b' 'b'
N0
P S
P0 ZT0 S0
a a
b b
N0
P S
P0 ZT0
a a S0
b b
N0
P S
P0 ZT0
a a S0
b b
N0
P S
P0 ZT0
a a S0
b b
N0
E1
N1 Z1 F1
E
E1 ZT1 ZL1
N1 ZG1 I1 F1
V1
(N1)
N2 Z2 F2
R
System Single Line
Diagram
E
V2
N IA0
IB0
IC0
3ΙA0
Generator Transformer
Line F
N
RT
R
System Single Line Diagram
E
3R 3RT V0
E0 (N0)
Zero Sequence Network
F1
POSITIVE
SEQUENCE
NETWORK
N1
I2
F2
NEGATIVE
SEQUENCE V2
NETWORK
N2
I0
F0
ZERO
SEQUENCE V0
NETWORK
N0
This is possible if :-
1) Any 3 phase quantities are known (provided they are not all
voltages or all currents)
or 2) 2 are known and 2 others are known to have a specific
relationship.
From the relationship between sequence V’s and I’s, the manner in
which the isolation sequence networks are connected can be
determined.
IA IB IC
VA VB VC
IA IB IC
At fault point :-
VA = 0
VA VB VC VB = ?
VC = ?
IA = ?
IB = 0
IC = 0
To comply with (1) & (2) the sequence networks must be connected in series :-
I1 F1
+ve
Seq
N/W V1
N1 I2
-ve F2
Seq V2
N/W
I0
N2
Zero F0
Seq V0
N/W
N0
79 > Fault Analysis – January 2004 79
Example : Phase to Earth Fault
SOURCE LINE F
A-G
132 kV ZL1 = 10Ω FAULT
2000 MVA ZL0 = 35Ω IF
ZS1 = 8.7Ω
ZS0 = 8.7Ω
8.7 10 I1 F1
N1
8.7 10 I2 F2
N2
8.7 35 I0 F0
N0
I1 F1
POSITIVE
SEQUENCE
NETWORK V1
N1
I2 F2
NEGATIVE
SEQUENCE V2 3ZF
NETWORK
N2
I0 F0
ZERO
SEQUENCE V0
NETWORK
N0
I1 I2 I0
F1 F2 F0
+ve -ve Zero
Seq V1 Seq V2 Seq V0
N/W N/W N/W
N1 N2 N0
132000
√3 8.7 I1
10 F1
N1
8.7 10 I2 F2
N2
ZF
I1 I2
+ve F1 -ve F2
Seq V1 Seq V2
N/W N/W
N1 N2
I0
Zero F0
Seq V0
N/W
N0
I1 I2 I0
+ve F1 -ve F2 Zero F0
Seq V1 Seq V2 Seq
N/W N/W V0
N/W
N1 N2 N0
3ZF
I1 I2 I0
+ve F1 -ve F2 Zero F0
Seq V1 Seq V2 Seq V0
N/W N/W N/W
N1 N2 N0
E XT
Xg
3Ø
Xg XT
E E
ΙF = ≡
Xg + XT Z1
Z1
E IF
1Ø Xg XT
E Z1
Xg2 XT2
3E
ΙF =
Z2 = Z1 IF 2Z1 + Z0
Xg0 XT0
Z0
E 3E 3E
3∅FAULTLEVEL = = =
Z1 3Z1 2Z1 + Z1
3E
1∅FAULTLEVEL =
2Z1 + Z0
∴ IF Z0 < Z1
EA
IF
System Earthing
z Fault current IF
z Damage caused
z Steady state overvoltages
z Transient overvoltages
z Insulation requirements
z Quantities available to detect faults
z Type of Protection
Earthing Method
IF High Low
Overvoltages in Low High
Sound Phases
Damage High Low
Cost of Insulation Low High
Low Voltage Systems For Safety
Medium Voltage Systems To limit current
cost of insulation
acceptable
High Voltage & To limit cost
EHV Systems of insulation
Methods of Earthing In Common Use
Solid
Lowest System Z0
IF High
- Damage
- Easy E/F Protn.
No Arcing Grounds IF >> ICHARGE
Lowest Overvoltages
System Earthing
Reactance
Lower IF
Higher Transient Overvoltages
Cheaper than resistance at high
volts
Overvoltages during E/Fs
0.8 Î 1 x VØ/Ø
Not often used except as tuned
reactor
System Earthing
Petersen Coil
XE ≈ ∑ XCHARGING
Arcing faults self extinguishing
- Good for transient faults
XE needs changing if XC alters
Overvoltages during E/Fs Î VØ/Ø
Insulation important
Tuned Restricts use of auto-transformers
Discriminative E/F protection
difficult
System Earthing
Resistance
Reduced IF
Reduced transient overvoltages
Not self extinguishing but E/F
easier to detect
System Earthing
Unearthed
Insulated
IF Capacitive
Can be self extinguishing if IF
small
Overvoltages during E/Fs = VØ/Ø
Arcing faults likely - high transient
overvoltages
Insulation important
System Earthing
Î 660 V Solid - Safety
Insulated - Special cases where continuity
of supply required
> 33 kV Solid
Overvoltages more important (insulation)
IF ~ 10 Î 15 A
IF ~ 200 Î 300 A
Low Voltage System Earthing
Safety :-
z Sensitive protection by :-
ZF
ZP
ZF = Fault impedance VP
ZE
ZP = Human body impedance
ZE = Environmental impedance
VP = Case / earth potential
Earth Fault Hazard
RCD for High ZF
Unearthed
Appliance
Fuses for
High IF
IF
ZF
ZE = Environmental impedance
Without protective earth : -
VP = Case / earth potential
ZP
VH = E∅/N .
ZP + ZF + ZE
Unearthed L.V. Winding
Normal
V Conditions
H.V. L.V.
Breakdown Between HV and LV Windings
A2
1730V a2
254V
N n
c2 b2
C2 B2
A2
95V
a2
xH x xL
1730V 254V
n
1009V
850V c2 b2 755V
C2 B2
6000
5000
Resistance - Ohms
4000
2000
15-30 minutes Cramp-like contraction of arms. Difficulty in breathing. Rise in blood pressure.
Limit of tolerability.
30-50 seconds Heart irregularities. Rise in blood pressure. Powerful cramp-effect. to minutes
Unconsciousness. Ventricular fibrillation if long shock at upper limit of range.
Threshold
of
10,000 Fibrillation
Threshold
of
Threshold Let Go
of
Perception
Time 1,000
(mS)
IEC Security
Curve
100 Let Go
Hold On
10
0.1 1.0 10 100 1000
Current (mA)
Earthing Impedance Affects Touch & Step Potentials
E
!
Touch RF
Step RE True IF
VH VH Earth
Surface
RG
Don’t forget
communications
cables etc.
entering S/S !
IF
IF
RG ' RG
VH = E True Earth
RE + RF + RG ' d
RG' = f(Distance)
Displacement of Neutral from Earth
during an Earth Fault
Z IF
Va
N
Vc Vb Z
ZE
Va
G G
ZE
VGN = ΙF ZE = VaN . N
ZE + Z
Vc Vb
Methods of Neutral Earthing (1)
Aspect Solid Resistance Resistance & High value Low value Tuned Insulated
reactance reactor reactor reactor
Normal Suitable for Suitable for Suitable for phase Suitable for Suitable for If used for Suitable for line
insulation phase voltage phase voltage voltage line voltage for phase voltage operation with voltage for long
continuously continuously continuously long periods continuously one line earthed
for long periods
insulation must
be suitable for
line voltage
Over voltages:
(a) Initiated by Not excessive Not excessive Not excessive provi- Can be very high Not excessive Not excessive if Arcing ground
faults, ding all three phases e.g. neutral no mutual coup- can give very
switching, etc are made or broken inversion ling between zero high voltages
simultaneously & positive seq-
uence networks
(b) Travelling Negative In general, “ Full reflection at Full reflection at Full reflection at Full reflection
waves reflection negative neutral neutral neutral at neutral
reflection at
neutral
Protection:
(a) Automatic No difficulty No difficulty No difficulty, normal Extremely diffi- No difficulty By using special Extremely
segregation normal methods normal methods methods can be cult if more than normal methods technique can be difficult
of faulty zone can be used can be used used one zone can be used done satisfac-
involved torily
(b) Travelling Diverters rated In general, In general, diverters Diverters rated In general, Diverter rated Diverters rated
waves for phase volts diverters rated rated for line volts for line volts are diverters rated for for line volts are for line volts
are suitable for line voltage are essential essential line volts are essential are essential
are essential essential
Methods of Neutral Earthing (2)
Aspect Solid Resistance Resistance & High value Low value Tuned Insulated
reactance reactor reactor reactor
Earth-fault
Current
(a) Value Highest value High value High value Negligible High value Negligible Capacitive if
small may be
self exting-
uished
(b) Duration Few seconds Few seconds Few seconds Long time Few seconds Few seconds or In general long
continuous, time
depending on
method of
application
(c) Effect on Electromagnetic Electromagnetic Electromagnetic Electrostatic Electromagnetic If used for Electrostatic
communica- interference interference interference interference interference may running contin- interference
tion circuits may necessi- depending on depending on necessitate current uously with one
tate current degree of degree of limitation limitation line earthed
limitation limitation requires partic-
ular consideration
Harmonic No limitation Partial limitations Partial limitation of Limits all Appreciably limits Appreciably limits -
currents in of harmonic of harmonic harmonic currents harmonic all harmonic all harmonic
neutral currents currents currents currents currents
General remarks Maximum In general use In general use where Confined mainly Cheaper than Best continuity Some applica-
disturbance to a source neutral is to protection of resistor at very of supply. Can tions on short
system not available generator on high voltages be a danger to feeders, in
generator trans- personnel general to be
former unit avoided
Application of Non-Directional Overcurrent
and Earthfault Protection
Non-Directional Overcurrent and Earth
Fault Protection
Overcurrent Protection
Purpose of Protection
F1 F2
F3
z Simple
z Can provide very fast fault clearance
z <10ms for large current
z Limit fault energy
Arcing Time
Pre Arc Time
Prospective Fault Current
Total t
Operating
Time
Overcurrent Protection
Fuses - disadvantages
z Problematic co-ordination
Fuse A Fuse B
51
Trip Coil
IF
z AC series trip
z common for electromechanical O/C relays
Overcurrent Protection
Direct Acting AC Trip
IF'
+
Sensitive
51 Trip
Coil
-
IF
51
DC SHUNT
BATTERY TRIP COIL
z Operating Speed
z Instantaneous
z Time delayed
z Discrimination
z Current setting
z Time setting
z Current and time
z Cost
z Generally cheapest form of protection relay
Overcurrent Protection
Instantaneous Relays
B A
50 50
IF2 IF1
TIME
TOP
IS Applied Current
(Relay Current Setting)
Overcurrent Protection
Definite (Independent) Time Relays
51 51
0.9 sec 0.5 sec
TIME
IS Applied Current
(Relay Current Setting)
M CG G
A B C
INST INST No
Ph+
t t In Hz
Vx V
I > Is I > Is
I>1
I>2
Time
I>3
I>4
Current
E D C B A
10
E
Operating time (s)
1 D
C
0.1
0.01
Current (A) FLB FLC FLD
Overcurrent Protection
IEC Characteristics
1000
100
z SI t = 0.14
z EI t = 80 1
(I2 -1) VI
z LTI t = 120 EI
0.1
(I - 1) 1 10 100
Current (Multiples of Is)
Overcurrent Protection
Operating Time Setting - Terms Used
Multiplier
z Therefore characteristics can be 1
z Current grading
z ensure that if upstream relay has started
downstream relay has also started
R1 R2 IF1
R1 R2
z Traditional
z breaker op time - 0.1
z relay overshoot - 0.05
z allow. For errors - 0.15
z safety margin - 0.1
z Total 0.4s
z Calculate using formula
Overcurrent Protection
Grading Margin - between relays
z Formula
z t’ = (2Er + Ect) t/100 + tcb + to + ts
z Er = relay timing error
z Ect = CT measurement error
z t = op time of downstream relay
z tcb = CB interupting time
z to = relay overshoot time
z ts = safety margin
z Op time of Downstream Relay t = 0.5s
z 0.375s margin for EM relay, oil CB
z 0.24s margin for static relay, vacuum CB
Overcurrent Protection
Grading Margin - relay with fuse
Tf
Tr
I FMAX
or
z Tf = 2Tr + 0.33s
Overcurrent Protection
Time Multiplier Setting
100
200/5 100/5
I
FMAX
= 1400 Amp
B A
Is = 5 Amp Is = 5 Amp; TMS = 0.05, SI
200/5 100/5
I
FMAX
= 1400 Amp
B A
Is = 5 Amp Is = 5 Amp; TMS = 0.05, SI
I FMAX
= 1400 Amp
B A
Is = 5 Amp Is = 5 Amp; TMS = 0.05, SI
11kV
MCGG 4 CB 4
350MVA
2 x 1.5MVA
11kV/433V
5.1%
CTZ61 3 ACB CTZ61 3 (Open)
2
ACB
1 MCCB
1 Relay 1
2 Relay 2 27MVA
3 Relay 3
4 Relay 4 Fuse F K
F Fuse
Load 20MVA
ZA2118B
Overcurrent Protection
LV Protection Co-ordination
1000S
100S
TX damage
Fuse
MCCB (cold)
10S
Very
1.0S inverse
Relay 3
Relay 4
0.1S Relay 2
0.01S
0. 1kA 10kA 1000kA
ZA2119
Overcurrent Protection
LV Protection Co-ordination
11kV
KCGG 142 4 CB 4
350MVA
2 x 1.5MVA
11kV/433V
5.1%
KCEG 142 3 ACB 3 (Open)
2
ACB
1 MCCB
1 Relay 1
2 Relay 2 27MVA
3 Relay 3
4 Relay 4 Fuse F K
F Fuse
Load 20MVA
ZA2120C
Overcurrent Protection
LV Protection Co-ordination
1000S
Long time
inverse
100S
TX damage
Fuse
10S
MCCB (cold)
1.0S
Relay 3
0.1S Relay 2
Relay 4
0.01S
0. 1kA 10kA 1000kA
ZA2121
Overcurrent Protection
Blocked OC Schemes
Graded
protection
R3
R2
Block t >
Blocked
IF2 protection
R1 I > Start
IF1
M (Transient backfeed ?)
ZA2135
Delta / Star Transformers
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns Ratio
z A phase-phase fault on one = √3 :1
side of transformer
produces 2-1-1 distribution
on other side
z Use an overcurrent element
in each phase (cover the 2x Iline
phase)
Idelta 0.866 If3∅
z 2∅ & EF relays can be used
provided fault current > 4x
setting
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns Ratio
= √3 :1
z Istar = E∅-∅/2Xt = √3 E∅-n/2Xt
Ø/Ø
51 51
HV LV
HV2 HV1 LV
z Set HV inst 130% IfLV
z Stable for inrush
HV2
HV1 z No operation for LV fault
TIME
LV
z Fast operation for HV
fault
z Reduces op times
required of upstream
CURRENT
IF(LV) IF(HV) relays
1.3IF(LV)
Earthfault Protection
Overcurrent Protection
Earth Fault Protection
E/F OC OC OC E/F OC OC
E/F OC OC OC E/F OC OC OC
z Solid earth
z Resistance earth
z 30% Ifull load
adequate z setting w.r.t earth fault
level
z special considerations
for impedance earthing
- directional?
Overcurrent Protection
Sensitive Earth Fault Relays
A
B
C
z Settings down to
0.2% possible
E/F
z Isolated/high
impedance earth networks
z For low settings cannot use residual connection, use
dedicated CT
z Advisable to use core balance CT
z CT ratio related to earth fault current not line current
z Relays tuned to system frequency to reject 3rd
harmonic
Overcurrent Protection
Core Balance CT Connections
NO OPERATION OPERATION
51 67 67 67
Load Load
51 67 67 67
Load
A B' B C' C
1.7
0.1 1.3 0.5 0.9
0.9 D'
0.5 D
A' E E'
1.7
0.1 1.3
F1
A B' B C' C
A'
F2 D D'
Option 1
Trip least important source instantaneously then treat as normal ring
main.
Option 2
Fit pilot wire protection to circuit A - B and consider as common source
busbar.
B
A 50
Option 1 Option 1 Option 1
PW PW
Option 2 Option 2
Non-Directional Relays :-
‘F’
51 A 51 C Load
51 B 51 D
Fault level
at ‘F’
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders
51 A I2 C 51 LOAD
51 B D 51
Relays ‘C’ and ‘D’ see the same fault current (I2).
As ‘C’ and ‘D’ have similar settings both feeders
will be tipped.
I1 + I2
I1
C
51 A I2 67 LOAD
51 B D 67
E
51 A C 67 Load
51
51 B D 67
Grading procedure :-
1. Grade ‘A’ (and ‘B’) with ‘E’ assuming one
feeder in service.
2. Grade ‘A’ with ‘D’ (and ‘B’ with ‘C’) assuming
both feeders in service.
If2/2. M M
If2/2 If1If2 If
S2 S2
S2
S2 S2
S2 S2
S1
S2 S2
S2 S2
S2 S2
S2
OPERATE SIGNAL = IA
Applied Voltage : VA
Applied Current : IA
VA
IA
Operate
IAF
VAF
Restrain
Question :
- is this connection suitable for a typical power system ?
VA
IA
IAF
IVBC
IA
VA
90°
VBC
The 90°Vconnection
C
VB overcurrent relays.
is now used for all
30° and 60° connections were also used in the past, but no
longer, as the 90° connection gives better performance.
RCA
45°
VBC
MAX SENSITIVITY
OPERATE LINE
IA
VA VA IA FOR MAX
RESTRAIN SENSITIVITY
45°
90° 45°
VBC VBC
135°
VC VB
OPERATE
MAX
SENSITIVITY
IA RESTRAIN
LINE
VA VA IA FOR MAX
30° SENSITIVITY
90° 30°
VBC VBC
150°
VC VB
Overcurrent Relays
Operating Signal
obtained from residual connection of line CT's
i.e. Iop = 3Io
Polarising Signal
The use of either phase-neutral or phase-phase
voltage as the reference becomes inappropriate for
the comparison with residual current.
Most appropriate polarising signal is the residual
voltage.
Application of Directional Overcurrent and Earthfault Protection - January 2004
Residual Voltage
May be obtained from ‘broken’ delta V.T. secondary.
A
B
C
VRES
Notes :
1. VT primary must be earthed.
2. VT must be of the '5 limb' construction (or 3 x single
phase units)
A-G
VA
VA
VC VB VC VB VC VB
VA VRES
VA VRES
VB VB VB
VC VC VC
ZE
A-G
G
VA-G
S S V S
A-G
R G.F R G.F
G.F
OP
POL
DEF Relay
51 I
67 I
Øc - 90° Øc Øc + 90°
-Is
Polarising
thresholds
Reverse start
Vp > 0.6V
Vop > 0.6 to 80V
in 0.2V steps
for example
Issue A Slide 1
Causes of failure:
¾ Environment
¾ System
¾ Mal operation
¾ Wrong design
¾ Manufacture
¾ Material
¾ Maintenance
Issue A Slide 2
Transformer failures classification :
1. Internal failure
Causes:
È Overheating faults
Issue A Slide 3
Transformer failures classification :
2. External failure
Causes:
Issue A Slide 4
Vector Groups
Group 1 Yy0
Dd0
0 Phase displacement Zd0
Group 2 Yy6
Dd6
180 Phase displacement Dz6
Group 3 Yd1
Dy1
30 Lag phase displacement Yz1
Group 4 Yd11
Dy11
30 Lead phase displacement Yz11
Issue A Slide 5
Vector Configurations
12
11
300
300
Issue A Slide 6
Vector Configurations
A
a
C B
c
Issue A Slide 7
Vector Configurations
A
a
a2
A2
a1
b
A
1
C B
c
Issue A Slide 8
Vector Configurations
A
a
a
2
C1 A2
a1
c b
b1 b2
C A 1
2 1
c
B B
C B 2
1 2 c
Issue A Slide 9
Fault current distribution
V2 V1
X
Fig.N
R
Fig.3 If
Issue A Slide 10
Fault current distribution
Therefore C.T.secondary current ( on primary side of transformer) =, X2
√3
20% 41%
30% 28%
40% 17%
50%. 7%
Issue A Slide 11
Fault current distribution
If Transformer star winding is solid earthed,
9
If as
8
multiple of
7
I F.L.
6
5
4
3 Delta side
2
1
Issue A Slide 12
Basic Protection
¾ Differential
¾ Restricted Earthfault
¾ Overfluxing
Issue A Slide 13
Differential Protection
Applied
Issue A Slide 14
Differential Protection
Consideration for applying differential
protection
¾ Phase correction
¾ Filtering of zero sequence currents
¾ Ratio correction
¾ Overfluxing
Issue A Slide 15
Differential Protection - Principle
I Diff = 0 : No tripping
R I diff = 0
Issue A Slide 16
Differential Protection - Principle
• Through fault current
I Diff = 0 : No tripping
R I diff = 0
Issue A Slide 17
Differential Protection - Principle
• Internal Fault
I Diff = 0 : Tripping
R I diff = 0
Issue A Slide 18
Biased differential protection
• Fast operation
• Adjustable characteristic
• CT ratio compensation
Issue A Slide 19
Biased differential protection
R 0A
I2
I1
R
0.1 A
Issue A Slide 21
Biased differential protection
100 / 1 100/50 KV 200 / 1
9A 10 A
2000 A
R
1A
2
Operate e
Differential current (x In)
l op
= I1+ I2 + I3 + I 4 S
%
80
1
Restrain
Setting range
lo pe
(0.1 - 0.5) 20% S
0 1 2 3 4
Issue A Slide 23
USE OF ICT
Dy1(-30 )
Interposing CT provides
Vector correction
Yd11(+30 ) Ratio correction
Zero sequence
compensation
R
R
R
PROTECTION TRANSFORMATEUR
CURRENT DIFFERENTIAL PROTECTION
sur défaut interne: Protection différentielle
Vector Group Correction - Static Relays
Yd11
Dy1(-30 ) R
R
R
R
R
R
Dy1 (-30 )
Yy0 Yd11
0 87 +30
Dy11 (+30 )
Yy0 Yd1
87
0 -30
CT RATIO MISMATCH CORRECTION
33kV : 11kV
200/1 I L = 175A 10 MVA I L = 525A 400/1
+VE SEQUENCE
CURRENTS
BALANCE
REQUIRE ZERO
SEQUENCE
CURRENT
TRAPS FOR A B C
STABILITY
High Impedance Principle
Issue A Slide 24
High Impedance Principle
RCT 2RL M 2RL RCT
ZM A ZM
RCT
2RL
M
2RL
TC
RCTsaturé
Issue A Slide 25
High Impedance Principle
RCT 2RL M 2RL RCT
ZM A ZM
Issue A Slide 26
High Impedance Principle
RCT 2RL M 2RL RCT
ZM A ZM
M
TC saturé
Issue A Slide 27
High Impedance Principle
RCT 2RL M 2RL RCT
ZM A ZM
Issue A Slide 28
High Impedance Principle
RCT 2RL M 2RL RCT
ZM A ZM
M
TC saturé
Issue A Slide 29
High Impedance Principle
ZM A ZM
Issue A Slide 30
High Impedance Principle
RCT 2RL M 2RL RCT
ZM A ZM
TC saturé
Issue A Slide 31
High Impedance Principle
ZM A ZM=0
False tripping
RCT
2RL
M
CT Saturation
2RL
RCT
TC saturé
Issue A Slide 32
High Impedance Principle
M
RCT 2RL 2RL RCT
RS
ZM A ZM=0
RCT
2RL
M
2RL
RCT
TC saturé
Issue A Slide 33
High Impedance Principle
RCT 2RL M 2RL RCT
RS
ZM A ZM=0
Stabilising resistor
RCT
2RL
M
2RL
RCT
TC saturé
Issue A Slide 34
High Impedance Principle
RCT 2RL M 2RL RCT
RS
ZM A ZM
RCT Vset
2RL
M
2RL
RCT
Issue A Slide 35
High Impedance Principle
RCT 2RL M 2RL RCT
RS
ZM A ZM=0
RCT
2RL ZM = 0
Vset
M (CT "short
2RL
RCT circuited" )
Issue A Slide 36
High Impedance Principle
RS
ZM A ZM
RCT RCT
2RL 2RL
M
Vset
Issue A Slide 37
High Impedance Principle
RS
ZM A ZM
RCT RCT
2RL 2RL
M
Vset
Issue A Slide 38
High Impedance Principle
RC 2R 2R RC
M
T L L T
RS
ZM A ZM
Metrosil may be
required for voltage
limitation RC RC
M
T 2R 2R T
L M L
Vset
Issue A Slide 39
Restricted Earthfault Protection
¾ Uses high impedance principle
¾ Increased sensitivity for earth faults
¾ REF elements for each transformer winding
64
64
64
Issue A Slide 40
Restricted Earthfault Protection
REF Case I : Normal Condition
Stability level : usually maximum through fault level of transformer
P1 P2
S1 S2
P1 P2
S1 S2
P1 P2
S1 S2
P1 S1
P2 S2
External earth fault - Current circulates between the phase & neutral CTs;
no current thro’ the relay
So, No Operation
Issue A Slide 42
Restricted Earthfault Protection
REF Case III : Internal Earth Fault
For an internal earth fault the unbalanced current flows thro’ the relay
Issue A Slide 44
Restricted Earthfault Protection
Issue A Slide 46
Restricted Earthfault Protection
3) Peak voltage = 2√2 √VK (VF - VK)
VF = 14.9 x VS = 14.9 x 936 = 13946 Volts
IS
For ‘Earth’ CT, VK = 1.4 x 236 = 330 Volts (from graph)
∴ VPEAK = 2√2 √330 (13946 - 330)
= 6kV
Thus, metrosil voltage limiter will be required.
Issue A Slide 47
Magnetising Inrush
• Transient condition - occurs when a
transformer is energised
Issue A Slide 48
Magnetising Inrush
Transformer Magnetising Characteristic
Twice
Normal
Flux
Normal
Flux
Normal
No Load Current
No Load Current
at Twice Normal
Flux
Issue A Slide 49
Magnetising Inrush
Inrush Current
V
+ Φm Φ
Im
STEADY STATE
- Φm
Im
2 Φm
Φ SWITCH ON AT VOLTAGE
V ZERO - NO RESIDUAL FLUX
Issue A Slide 50
Magnetising Inrush
Issue A Slide 51
Magnetising Inrush
Effect of magnetising current
Issue A Slide 52
Magnetising Inrush
IR
P1 P2
IS S1 S2
P1 P2
IT S1 S2
P1 P2
S1 S2
IR + IS + IT = 3Io = 0
Issue A Slide 53
Magnetising Inrush
Effect of magnetising current
Issue A Slide 54
Magnetising Inrush Restrain
Issue A Slide 55
Magnetising Inrush Restrain
Differential input
Comparator output
T1
Trip
T2 Reset
Issue A Slide 56
Overfluxing - Basic Theory
Overfluxing = V/F
Causes
Low frequency
High voltage
Geomagnetic disturbances
Issue A Slide 57
Overfluxing - Basic Theory
2Φm
V = kfΦ
Φm
Ie
Effects
Issue A Slide 58
Overfluxing - Condition
Differential element should be blocked
for transient overfluxing-+
Overfluxing waveform
contains very high 5th
Harmonic content
V α KΦ
f
Issue A Slide 60
BUCCHOLZ PROTECTION
Oil conservator
Bucholz Relay
Issue A Slide 60
BUCCHOLZ PROTECTION
76 mm typical
Transformer
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Petcock
Alarm bucket
Mercury switch
To oil
conservato
r
From
transformer Trip bucket
Deflector plate
Issue A Slide 60
BUCCHOLZ PROTECTION
Accumulation of gaz
Oil Leakage
Severe winding faults
Issue A Slide 60
BUCCHOLZ PROTECTION
Accumulation of Gaz
Interturn faults
Issue A Slide 60
BUCCHOLZ PROTECTION
Inter-Turn Fault
CT
E
Shorted Load
turn
Issue A Slide 60
BUCCHOLZ PROTECTION
Inter-Turn Fault
CT
E
Shorted
turn
Issue A Slide 60
BUCCHOLZ PROTECTION
Interturn Fault Current / Number
of Turns Short Circuited
Primary current
(multiples of
rated current)
100
Fault current
(multiples of
80
rated current)
60
40
20
Turn short-
circuited
5 10 15 20 25
(percentage of
winding)
Issue A Slide 60
BUCCHOLZ PROTECTION
Interturn Fault Current / Number
of Turns Short Circuited
Primary current
(multiples of
rated current)
100
Fault current
(multiples of
80
rated current)
20
Primary phase current very low
5 10 15 20 25
Not detected by current
operated relays
Issue A Slide 60
BUCCHOLZ PROTECTION
Accumulation of Gaz
Interturn faults
Issue A Slide 60
BUCCHOLZ PROTECTION
100
80
Fault current
60
40
20
Turn short-
circuited
5 10 15 20 25
(percentage of
Issue A winding) Slide 60
BUCCHOLZ PROTECTION
Accumulation of Gaz
Operating principle
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Accumulation
of gaz
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Accumulation
of gaz
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Accumulation
of gaz
Issue A Slide 60
BUCCHOLZ PROTECTION
of gaz
White or Yellow :
Insulation burnt
Grey :
Dissociated oil
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Gaz can be extracted
Accumulation for detailled analysis
of gaz
Issue A Slide 60
BUCCHOLZ PROTECTION
Issue A Slide 60
BUCCHOLZ PROTECTION
Accumulation of gaz
Oil Leakage
Severe winding faults
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Oil Leakage
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Oil Leakage
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Oil Leakage
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Oil Leakage
Issue A Slide 60
BUCCHOLZ PROTECTION
Accumulation of gaz
Oil Leakage
Severe winding faults
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Severe winding fault
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Severe winding fault
Issue A Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Severe winding fault
Issue A Slide 60
CONCLUSION
51 50
200/5 51 50 N N P121
1MVA
1500/5
3.3/0.44kV
51
P120 N
64 1500/5
MCAG14
CONCLUSION
51 50 P121
64 MCAG14
5MVA
1000/5
11/3.3kV
51
P120 N
64 1000/5
MCAG14
3.3kV
CONCLUSION
51 50 P141
200/5
P120
10MVA
33/11KV 51
N 87
600/5
P631
64 MCAG14
600/5
5/5A
CONCLUSION
50MVA
33KV
1000/5
Protection should operate for faults inside the protected zone (i.e.
the feeder) but must remain stable for faults outside the protected
zone.
Thus can be instantaneous in operation.
I1
10 1
(v) (v)
2 (i)
(i) → (v) represents
increasing time
9 setting
3
(i)
(iv)
8
(iv) 4 (ii)
I2
5
7 6 (iii)
(ii) (iii)
I1 I1
10 10
I2
I1 I1+I2
I1+I2
I2 2
4
8
8
I2
I1 I2
6 I1+I2 4
10
(iii)
1
9
(i)
8
(ii) 3
4
5
(iii)
7 (ii) 6 (i)
Protected Circuit
or Plant
Relay
End A End B
Relay
Basic mertz-price principle applies well where CT secondary circuit can be kept short, eg.
protection of transformers, busbars, machines.
For feeder protection where boundaries of protection are a distance apart, a communication channel is
7
required. > Title of presentation - Date - References 7
Unit Protection Involving Distance
Between Circuit Breakers (1)
A B
Relaying
R
Point
Trip B
Trip A
A B
Communication
Channel
Relaying Relaying
Point Point
R R
Trip A Trip B
R R
2 Problems :
(1) Maloperation due to unequal open circuit secondary voltages of the two
transformers for thro’ fault currents.
(2) High output voltages of CT’s cause capacitance currents to flow thro’ relay.
Since capacitive currents are proportional to pilot length, relay insensitive for
all but very short lines.
10 > Title of presentation - Date - References 10
Basic Pilot Wire Schemes with Bias (1)
B B
I
V
OP OP
V
I
Circulating Current
C
Summation
Winding
Secondary
Winding
Pilot
Bias Loop
12 > Title of presentation - Date - References 12
MBCI Feeder Protection Circuit Diagram
A A
B B
C C
T2 RPP RPP T2
T1 T1
Tr Tr
Tt ØC ØC T
t
To PILOT To
WIRES RS
RS
Ts RVO Ro Ro RVO Ts
v v
a
b
c
m output
IA
1
IB
1
IC Output for
operation = K
IN
(4) AB fault
for relay operation : IAB x (1) > K
IAB > 100%K
(5) BC fault
for relay operation : IBC x (1) > K
IBC > 100%K
(6) AC fault
for relay operation : IAC (1 + 1) > K
16 > Title of presentation - Date - References
IAC > 50%K 16
Type of Relay Sensitivity of
Fault Sensitivity E/M Pilot Wire
Relay
Fault Settings
N = 3 N = 6
A-N 0.19 x Ks x In 0.12 x Ks x In
B-N 0.25 x Ks x In 0.14 x Ks x In
C-N 0.33 x Ks x In 0.17 x Ks x In
A-B 0.80 x Ks x In
B-C 1.00 x Ks x In
C-A 0.44 x Ks x In
A-B-C 0.51 x Ks x In
Ks is a setting multiplier, variable from 0.5 to 2.0
In is the relay rated current 1 Amp or 5 Amps
18 > Title of presentation - Date - References 18
Selection of Ks & N
Values of Ks and N are chosen such that IS (C - N) < 0.3 x min. E/F current.
For systems where the steady state charging current is negligible select Ks
setting to give required primary sensitivity.
Resistance and shunt capacitance of pilots introduce magnitude and phase differences
in pilot terminal currents.
Pilot Resistance
To maintain constant operating levels for wide range of pilot resistance, padding
resistor used.
R Rp/2 R
Rp/2
Electromagnetic Induction
Field of any adjacent conductor may induce a voltage in the pilot circuit.
Relay Case
5kV 15kV
Pilot
Terminal
Relay
Input Relay
Circuit
Pilot
Wire
2kV 5kV
- Manual Interference
- Acts of Nature (storms, subsidence, etc.)
- Mechanical Damage (excavators, impacts)
Circulating Balanced
Current Voltage
Schemes Schemes
PILOT
Cross Pilot
Detector Box
Unbalance
Detector
Circuit
Supervision
Supply
A1 A1
PILOTS
A2 A2
A3 A3
LVAC AC
50
A
PILOT
50 WIRE
C RELAY
(87PW)
50
G
50A-1 87PW-1
+ TRIP CIRCUITS
50C-1
Source
Feeder
Protection
Busbar
Protection
P6 S2
17
PILOTS
P7 S1
MBCI
17 UN-1
18
18 UN-2
19
19
UN-3
20
I1 UN
V x (1) + 3
I2
V x (2) +
V x (3) + I3
- I4
MVTW01
MiCOM P521
End A End B
IF
IA IB
Communication Link
IA + IB = 0 Healthy
IA + IB ≠ 0 (= IF) Fault
0IIIIII0I0.....0I0IIIIII
Digital messages
0
End A End B
A/ µP Comms Channel
D
Digital communication interface
(electrical or fibre)
36 > Title of presentation - Date - References 36
Current Differential -
Advantages
Protection Comms
850 nm multi-mode
1300 nm multi-mode
1300 nm single mode
X Multiplexed communications
1.2km max
Tx 64kbps R
MT RS485 MT RS485
x
Rx T
2 Screened x
Twisted Pairs
Surge
Protection
40 > Title of presentation - Date - References 40
4 Wire EIA485 Up To 10km
10km max
19.2kbps R
Tx
PZ511 PZ511 x
Interface Interface
Rx 2 Screened T
Twisted Pairs x
EIA 485
NOTE:10/ 20kV isolation transformers available if required (4 required per
41 scheme)
> Title of presentation - Date - References 41
Pilot Wire Communications (1)
10km max
Tx 19.2kbp R
Leased s Leased x
Line Line
Modem Twiste Modem
Rx d Pair T
(Pilot x
Cable)
EIA 485 or EIA
232
NOTE:10/ 20kV isolation transformers available if required (2 required per
42 scheme)
> Title of presentation - Date - References 42
Pilot Wire Communications (2)
10km max
Same as
Tx Fibre..!!
64kbps R
MDSL MDSL x
Modem Twiste Modem
Rx d Pair T
(Pilot x
Cable)
EIA 485
NOTE:10/ 20kV isolation transformers available if required (2 required per
43 scheme)
> Title of presentation - Date - References 43
Condition Line Communications
No strict limits
Tx 9.6 kbps R
Dial-up Dial-up x
Modem Modem
Rx T
Conditioned
Telephone x
Line
EIA 485 or EIA
232
44 > Title of presentation - Date - References 44
Direct Optical Fibre Link
OPGW
T R
x x
R CH1 T
x x
End A End B
P591/2/3
interface Multiplexer
unit
Multiplexer Multiplexer
34 Mbit/s
64k Telephone
bits/s
Telecontrol
End A End B
Teleprotection
P521 current
differential protection
Multiplexer Multiplexer
Telephone
64k
bits/s Telecontrol
End A End B
Teleprotection
X Asynchronous sampling
Continual time difference measurement
Vector transformation in software
Relay A Relay B
Current at B
Propagation delay
52 > Title of presentation - Date - References 52
Propagation Delay Time
Measurement - 1
Relays
A B
Data
Curre mess
vecto nt ag e
tA1 rs
tA tB1
tp1 1
tA2 tB2
tB
tA3
tB3
*
tA4
tB4
tA5 tB5
I (tA4)
θ I (tB3 )
∆
*
θ
∆t = (tA4 - tB3 )
∆θ=ω∆
*
t
If I (tB3 ) = Is + j Ic
* = I cosθ + j I sinθ
then I (tA4) = I (tB3 ) . (cos ∆ θ + j sin
∆ θ) *
= I cos (θ + ∆ θ) + j I sin
55 > Title of presentation - Date - References
(θ + ∆ θ) 55
Current Differential
IA IB
Differential k2
ia s
current b
g e
ta
I diff =
rc en
Trip P e
I A + IB
b i a s k1
r c e ntage No trip
P e
I S1 I S2
Bias current
I bias = 1/2 ( IA + I B )
A/km A/km
30 1
1.2 0.3
600/1 500/1
0.83A
Max Load = 500A 1.0A
Power transformer
Ratio
correction
Vectorial
correction
V
+Φm Φ
Im
Steady state
- Φm
Im
2Φm
Φ Switch on at voltage
V zero - No residual flux
MiCOM-P540-62
End End
A B
IF
X Differential protection can be IDMT or
DT delayed to discriminate with tapped
feed protection:
Fused spurs
Tee-off transformer in-zone
Relay A Relay B
Transformer
Protection
DTT=1
Data Message
- + - +
IB
Relay Relay
A B Busbar
Relay
PIT=1
Data
Message
- + - +
2 2
Connection to the Power System
1. Direct :
2. Via Transformer :
3 3
Typical Generator Installations
Generator Generator
Transformer Transformer
Station
Trans-
Earthing former
Transformer
Unit / Unit
Station Trans-
Transformer former
1(b) 1(c)
4 4
Generator Protection Requirements
Faults include :-
Insulation Failure
Stator
Rotor
Excitation system failure
Prime mover / governor failure
Bearing Failure
Excessive vibration
Low steam pressure
etc.
6 6
System Conditions
Short circuits
Overloads
Loss of load
Unbalanced load
Loss of synchronism
7 7
Generator Protections to be Considered
8 8
Stator Earth Fault Protection
9 9
Method of Earthing (1)
Damage resulting from a stator earth fault will depend upon the earthing
arrangement
10 10
Method of Earthing (2)
11 11
Method of Earthing (3)
limits damage
reduces possibility of developing into phase-phase
fault
12 12
Method of Earthing : Limitation of
Earth Fault Current (1)
Less than 5A :
20A :
13 13
Method of Earthing : Limitation of
Earth Fault Current (2)
100A :
As for 20A, but higher current allows better discrimination and sensitivity.
14 14
Stator Earth Fault Protection and
Protection Against Earth Faults on
Generator Connections
15 15
Overcurrent Protection (1)
51
16 16
Overcurrent Protection (2)
51
17 17
Stator Earth Fault Protection
51N
50N 51N
xV
xV
ΙF =
250/1A IS R
For operation
Ι S(PRIMARY) < ΙF
R 33Ω xV
<
R
x.6600
< < x.200
33
1
Ι S(SECONDARY) < x.200 x < 0.8x
250
∴ For protection of 90% of winding; x = 1-0.9 = 0.1
Relay setting = 0.8 x 0.1 = 0.08A = 8% of 1A
19 19
Stator Earth Fault Protection (1)
Generators connected via step-up transformer (resistance earthed) :
51N 50N
System earth faults ARE not seen by generator earth fault protection ∴
instantaneous relay may be used.
Advantage : Fast
20 20
Stator Earth Fault Protection (2)
Advantage : Sensitive
RSTA
B High Impedance Principle
64
Instantaneous Protection
5 x CT’s required
RSTAB
64
24 24
Restricted Earthfault Protection for Generators on 4 Wire L.V.
Systems (2)
Earthing at Busbars
RSTAB
64
4 x CT’s required
25 25
Differential Protection (1)
Stabilising
Resistors
Relay
26 26
Differential Protection (2)
BIAS BIAS
OPERATE
INTERPOSING
C.T.
Two methods :
29 29
100% Stator Earth Fault
Protection
For Large Machines Only
Two methods :-
Low frequency injection – 12.5Hz to 20Hz Third harmonic voltage - various
Low Frequency Injection
Earthing
Trans- 59
former
Complete protection during start-up if source is
independent of generator, e.g. derived from
Injection station battery.
Transformer
Independent of system V, f and load current.
High cost due to injection equipment.
51 Alternative
Injection
Points
30 30
Third Harmonic Neutral Voltage Scheme
Relies on >1%
generated 3rd
harmonic volts
59 27
59P
27 - 3rd harmonic undervoltage relay.
59P - Terminal Voltage Check
59
Allows trip if circuit breaker is open but
terminal voltage present.
59P 27
TRIP 59 - Conventional neutral overvoltage protection.
27 OVERLAP
0 50 100
Earth Fault Position
31 31
100% Stator Earth Fault Protection
a) UTE
G
UTE
N T 0
N T
50% 100%
UNE m
UNE
b) UTE
G
UTE
N T 0 T
N
50% 100%
m
c)
G 0 50% 100%
N T N
UNE
m
UNE
P2175ena
Insulation failure
Flashover in terminal box
33 33
Stator Phase-Phase Fault Protection (2)
Single Generator
51 51 51
Type types :
35 35
Stator Phase-Phase Fault Protection (4)
Stabilising
Resistors
Relay
36 36
Stator Phase-Phase Fault
Protection
Small machines :
Star connection made inside machine
Winding neutral ends are not brought out
37 37
Stator Interturn Fault Protection
(1)
38 38
Stator Interturn Fault Protection (2)
VA
VB
VC
VA VB VC VR
FAUL
T
R
VR = VA + VB + VC
39 39
Stator Interturn Fault Protection (3)
Transverse Differential Protection
(Double Wound Machines) :
Bias
Coils
Operate
Coils
40 40
Prime Mover Failure (1)
Isolated Generators :
Machine slows down and stops. Other protection initiates shut down.
Parallel Sets :
41 41
Prime Mover Failure (2)
Gas Turbines :
Motoring power 100% rated for single shaft machine, 10% to 15% rated for
double shaft.
Hydro Sets :
42 42
Prime Mover Failure (3)
43 43
Reverse Power Protection (1)
Leading P.F.
Operate Restrain
-MW +MW
87.1°
Operate Restrain
Lagging P.F.
+MVARLAG
Exporting lagging VAR’s
44 44
Loss of Excitation (1)
EFFECTS
Single Generator :
Loses output volts and therefore load.
Parallel Generators :
Operate as induction motor (> synch speed)
Flux provided by reactive stator current drawn from
system-leading pf
Slip frequency current induced in rotor - abnormal
heating
Situation does not require immediate tripping,
however,
large machines have short thermal time constants - should be
unloaded in a few seconds.
45 45
Loss of Excitation (2)
Simple Protection Scheme
Field Exciter
Winding
Shunt Ie Requires access to
field connections.
DC relay Not suitable if
(setting < Ie min) generator operates
Aux Supply normally with low
excitation (large
T1
machines).
Alternative scheme
monitors impedance
T2
at generator
0.2 - 1 sec
Overcomes Alarm or terminals.
Slip Frequency Trip
Effects
2 - 10 secs
46 46
Loss of Excitation (3)
Alternative Scheme
XG XT XS
EG ES
47 47
Loss of Excitation (4)
Load Impedance
R
Impedance Offset – Prevents
Locus operation
on pole slips
Diameter
Typically : Relay Characteristic
Offset 50-75%X’d
Diameter 50-100% XS Time Delayed
48 48
Impedance Diagram for Various Operating Modes of
Machine
jx
-jx
Effects
50 50
Unbalanced Loading (2)
Protection
Machines are assigned NPS current withstand values :
* Continuous NPS rating, I2R
* Short time NPS rating, I22t
If possible level of system unbalance approaches machin
continuous withstand, protection is required.
Use negative sequence overcurrent relay.
Relay should have inverse time characteristic to match
generator I22t withstand.
Relay pick-up setting should be just below I2R rating.
Can use an alarm setting of 70% to 100% to pick-up.
51 51
Unbalanced Loading (3)
Machine NPS Withstand Values
53 53
Rotor Earth Fault Protection (2)
Potentiometer Method
Exciter
54 54
Rotor Earth Fault Protection (3)
AC Injection Method
AC Auxiliary
Supply
R
Brushless Machines
No access to rotor circuit
Require special slip rings for measurement
If slip rings not present, must use telemetering techniques
(expensive)
55 55
Overload Protection (1)
insulation failure
Governor Setting
56 56
Overload Protection (2)
Overcurrent Protection
57 57
Generator Back-Up Protection (1)
Overcurrent Protection
Typical use :
Very or extremely inverse for LV machines
Normal inverse for HV machines
10 x
FL
with AVR
Full
Load
no AVR
Cycles
58 58
Generator Back-Up Protection (2)
Overcurrent Protection
Voltage Restrained
Voltage Controlled
F
59 59
Voltage Controlled Overcurrent Protection
Overload
Characteristic
Is
Current Pick - up
t
Fault
Characteristic
Vs
I Voltage
60 60
Voltage Restrained Overcurrent Protection
Equivalent to impedance
Current Pick-up
devices I>
KI>
VS2 VS1
Voltage
61 61
10
O/L CHARAC
1.0
FAULT CHARAC
LARGEST
OUTGOING 6.6kV
t
se FEEDER
5MVA
c 115% XS
0.1 GENERATO
R 500/5
DECREMEN 200/5
T
CURVE
0.01
100 240 600 1000 3000 10,000 AMPS
62 62
Impedance Relay
jx
RELAY
CHARACTERISTI
C
MZTU
Set to operate at 70% rated load impedance when voltage drops to zero,
current required to operate relay is 10% rated current. Built-in timer for
co-ordination purposes.
63 63
Under & Over Frequency Conditions (1)
Over Frequency
64 64
Under & Over Frequency Conditions (2)
Under Frequency
65 65
Under & Over Voltage Conditions (1)
Protection
66 66
Under & Over Voltage Conditions (2)
Over Voltage
Under Voltage
67 67
Other Protection Considerations
68 68
Pole Slipping Protection
Rotor Stator
E E
G S
ZG9356
69 69
Pole Slipping Detection
E E = 2.8 (max) X
G S
R
E E = 1.2
G S
E E =1
G S
E E = 0.8
G S
E E = 0.19 (min)
G S
MIS9357
70 70
Pole Slipping Protection
71 71
72 72
73 73
74 74
75 75
Pole Slipping Protection - 78
76 76
Pole Slipping Protection - 78
77 77
Overfluxing
Often applied to :-
Generator transformers
Grid transformers
Flux Ø ∝ V / f
Caused by either :-
Increase in voltage
Reduction in frequency
Combination of both
Usually only a problem :-
during run-up or shut down
can be caused by loss of load / load shedding
78 78
Transformer Magnetising
Characteristic
Twice
Normal
Flux
Normal
Flux
Normal
No
Load No Load
Current Current at
Twice Normal
Flux
79 79
Magnetising Current with
Transformer Overfluxed
ZG0780C
80 80
Overfluxing
Effects of overfluxing :-
Increase in magnetising current
Increase in winding temperature
Increase in noise and vibration
Overheating of laminations and metal parts
(caused by stray flux)
81 81
Over-Fluxing Relay
Ex
G
VT
AVR RL
82 82
Low Forward Power Interlocking
Urgent Trip
Trip Directly to Circuit Breaker and Initiate shut down
Risk of overspeed
Examples :-
Generator Differential
stator ground fault
negative phase sequence.
83 83
Low Forward Power Interlocking
Non-Urgent Trip
Trip governor
Use low forward power interlocking to determine when main Circuit
Breaker is tripped
Reduced risk of overspeed, and consequential damage to the machine
Examples :-
Over voltage
Over load
Loss of synchronism
Field failure
84 84
Unintentional Energisation at
Standstill Scheme
Typical Approach
50
27 & Trip
tPU
&
tDO
VTS
ZG7965D
86 86
Synchronising Relays
Often applied to :-
Synchronising of Generators
Transmission line auto-reclose schemes
Synchronising of Generators
Check voltage magnitudes
Check slip frequency
Check phase angle difference
Synchroscope
Speed of rotation depends on slip frequency
If frequencies matched, phase angle displacement indicated
Does not indicate voltage magnitude
87 87
Voltage Checking & Comparators
Voltage monitors :-
- Undervoltage monitor (e.g. Transmission Line)
88 88
Auto-Synchronising Relays
Controls :-
Filed current to adjust voltage magnitude
Governor to adjust slip frequency
Governor to correct constant phase displacement
89 89
Typical Schemes
90 90
Tripping Modes
Class C HV breaker
91 91
Protection Package for Diesel Generator Connected Directly and Operating
in Parallel with a Supply Authority Infeed
87
G
64
R
32 51
V 32 Reverse Power MWTU01
64R Rotor Earth Fault MRSU01
64 64S Stator Earth Fault MCSU01
R
51V Voltage Dependent Overcurrent
MCVG31
87G Generator Differential MFAC34
92 92
Overall Protection of Directly Connected
Generator Installation
32 Reverse Power
40 Field Failure
81 Under / Over Frequency
93 93
Overall Protection of Generator Installation (1)
Generator
Feeder Protn.
Overcurrent
Voltage Restraint 51 V
Restricted
E/F
Buchholz
Winding Temp.
Reverse 32
Power
Field Failure 40
Generator Differential 87
Rotor E/F Prime Mover Protection
64R
Negative Phase Sequence 46
Overall
Gen/Trans Diffl
Protn. Stator E/F 64S
94 94
Overall Protection of Generator Installation (2)
Generator Feeder
Protection
O/C Circuit Breaker Fail
Busbar Protection
Restricted
E/F
Buchholz Winding
Temperature
O/C + E/F
Buchholz O/C V.T.s
Transformer
Overfluxing
Standby Permissive
E/F (Low Power)
Interlock
Restricted Pole Slipping
E/F Field Failure
Generator Differential
Stator E/F
Protection
95 95
Embedded Generation
96 96
Embedded Generation
USED TO PROVIDE:
97 97
Co-generation/Embedded
Machines
AR?
PES
system
Islanded load
fed unearthed
MiCOM-P340-98
98 98
Islanded Operation Must Be Avoided To Ensure:
99 99
PROTECTION
100 100
PROTECTION
Loss Of Mains
101 101
Protection
102 102
Protection
Loss Of Mains
∆θ(t) = πRf t2
104 104
MiCOM P341 Applications
G59 Protection Equipment
Single phase line diagram showing generator parameters
R jX
IL
E VT
IL X
VT I LR
IL
E
ILX
VT ILR
θ
IL VT
∆ILX”
∆IL
df/dt = ∆P.f
2GH
f = Rated frequency
H = Inertia constant
108 108
MiCOM P341 Applications
G59 Protection Equipment
P341 df/dt calculation
F n - f n - 3 cycle
df/dt =
3 cycle
f(i-2) - f(i-3)
(df/dt)i-2
= t(i-2) - t(i-3)
f(i-1) - f(i-2)
(df/dt)i-1 =
t(i-1) - t(i-2)
f(i) - f(i-1)
(df/dt)i =
t(i) - t(i-1)
The instantaneous ROCOF is measured
every cycle based upon frequencies being
insensitive to vector shift, phase jumps f(i+1) - f(i)
(df/dt)i+1 =
and harmonics t(i+1) - t(i)
110 110
Voltage and Frequency Relay
1 1
2 3
2 3
Average Values
df/dt)i-3 + df/dt)i-2 + df/dt)i-1
df/dt CYCLE df/dt =
BN = 3 3
df/dt)i-2 + df/dt)i-1 + df/dt)i
df/dt VALIDAT df/dt =
NB = 2 3
111 111
Voltage and Frequency Relay
1 21 31
2 31
2 32 3
Average Values
NB = 3
df/dt)i-2 + df/dt)i-1 + df/dt)i
df/dt =
3
df/dt VALIDAT
NB = 4
df/dt)i-1 + df/dt)i+ df/dt)i+1
df/dt = 3
Threshold : df/dt
112 112
Voltage and Frequency Relay
F<>
EQU.A=
AND Load SHED.
df/dt
aver.
f
50 Hz
49 Hz
Slow decay.
48.6 Hz
Rapid decay.
t
113 113
Voltage and Frequency Relay
114 114
MiCOM P341 Applications
G59 Protection Equipment
df/dt+t: Time Delayed ROCOF
t
Start
Pick up cycles
Trip
f
Time delay
df/dt Setting
115 115
Auto-Reclosing On Transmission Systems
Fault Shunts (1)
Z1 F1
E ZF
N1
ZF = Fault shunt
= Combined Impedance of -ve and zero sequence
network impedances for particular fault.
Ø/E ZF = Z2 + Z0
Ø/Ø ZF = Z2
Ø/Ø/E ZF = Z2 . Z0
Z2 + Z0
3Ø ZF = 0 (short circuit)
E1 E2 sin δ
Power Flow =
Z
Power
Power 3Ø Healthy
2Ø Healthy
1Ø Tripped
Ø/E Fault
Ø/Ø/E Fault
3Ø Fault
3Ø Tripped
X Y
Power
Normal Healthy
Operation
A
P0
Phase Angle
Difference
δ0
7 > Auto-Reclosing and System Stability – January 2004 7
During Fault
X Y
Power
Normal
A
P0
Ø/Ø/E Fault
P0 - P1
C
P1 B
δ0 Phase Difference
δ1
8 > Auto-Reclosing and System Stability – January 2004 8
Increased Power Level
X Y
Power
Normal
F
P2 ' Faulted Feeder
A E Disconnected
P0
D
P2
Ø/Ø/E Fault
C
B Phase Difference
δ0 δ2
δ1
9 > Auto-Reclosing and System Stability – January 2004 9
Damping
Power Normal
F Faulted Feeder
Disconnected
P0 E
Ø/Ø/E Fault
Phase Difference
Power
Normal
Faulted Feeder
E Disconnected
G
P0 '
A
D
C Ø/Ø/E Fault
B
δ2 Phase Angle
Difference
Power Normal
G
P0'' A H
F
E Faulted Feeder
D Disconnected
BC Ø/Ø/E Fault
Phase Angle
Difference
Successful 3Ø A/R at ‘E’.
H = Equal area when H lies on P0''
P0'' = Max. power transmitted for transient stability with 3Ø
A/R.
12 > Auto-Reclosing and System Stability – January 2004 12
3ph or 1ph A/R
X Y
Power
Normal
P3Ø(A/R)
Ø/E Fault
Line Open 3Ø
Phase
Angle
Difference
δ
P3Ø(A/R) = Power transfer limit for stability following
successful high speed 3Ø auto-reclose.
14 > Auto-Reclosing and System Stability – January 2004 14
High Speed 1Ø A/R Single Interconnector
Power Normal
P1Ø(A/R)
1Ø Open
Ø/E Fault
δ Phase Angle
Difference
2. 3Ø A/R.
Delayed 3Ø Auto-Reclose
Protection
High speed < 2 cycles
De-ionising time
1Ø A/R longer → special steps
Protection
High speed not critical for system stability
↓
desirable to limit fault damage
↓
improves probability of successful A/R
Dead Time
Allow for power swings and rotor oscillations to
die down.
Different settings for opposite feeder ends.
Typically 5 to 60 secs.
23 > Auto-Reclosing and System Stability – January 2004 23
Delayed Auto-Reclosing (D.A.R.) (2)
Reclaim Time
Allow c.b. capacity to recover to full interrupting
value.
Number of Shots
1 (invariably)
VB
VL
VL = 0
VB = live
∴ Dead Line Charge
REMEMBER :
The relay performance DEPENDS on the C.T which
drives it !
Is
P1 P2
Ip
S1 S2
P1 Î P2
S1 Î S2 Externally
P1
Is
Ip
S1 FWD kick on application,
+ REV kick on removal of
test lead.
V
- Battery (6V) + to P1
S2 AVO +ve lead to S1
P2
IS
IP
1 Primary Turn
N Secondary Turns
⇒ IP = N x IS
IS
IP
ES R
ES = IS x R
ES ∝ dØ
dt
9 > Current Transformers – January 2004 9
Basic Theory (3)
NP
IP
NS
IS EK
ZCT
ZB
Require EK > ES
+50% Iek
Iek
Exciting Current (Ie)
13 > Current Transformers – January 2004 13
C.T. Equivalent Circuit
ZCT
Ip
P1 Is
Ip/N Ie
S1
N Ze Es Vt Zb
Ip/N
Ie
Is Ie
Im
Es
Ep Ic
Ep = Primary voltage Im = Magnetising current
Es = Secondary voltage Ie = Excitation current
Φ = Flux Ip = Primary current
Ic = Iron losses (hysteresis & Is = Secondary current
eddy currents)
15 > Current Transformers – January 2004 15
Saturation
100A 100A E=
1A 1A 100V
100/1 100
100/1 E 1 ohm E ohm
E=
1V
v = VM sin (wt + σ)
R1 L1
Z1
i1
v = VM sin (wt + σ)
VM V
i1 = + sin (wt + σ - ∅ ) = M sin (σ - ∅ ) . e -R1t / L1
Z1 Z1 where : - Z1 = R12 + w 2L12
wL1
∅ = tan-1
= + Ιˆ1 sin (wt + σ - ∅ ) - Ιˆ1 sin (σ - ∅ ) . e -R1t / L1
R1
V
Ιˆ1 = M
= STEADY STATE + TRANSIENT Z1
Required Flux
ØSAT
FLUX
Actual Flux
Mag Current
0
Primary Current
Secondary Current
CURRENT
0
10 20 30 40 50 60 70 80 M
X Measurement C.T.s
Limits well defined
X Protection C.T.s
Operation over wide range of currents
Measuring C.T.s
B
X Require good accuracy up to
approx 120% rated current.
Protection C.T.
X Require low saturation level to
protect instruments, thus use
nickel iron alloy core with low
exciting current and knee
point at low flux density.
Protection C.T.s
X Accuracy not as important as
above.
Measuring C.T.
X Require accuracy up to many
times rated current, thus use
grain orientated silicon steel
with high saturation flux
density. H
22 > Current Transformers – January 2004 22
Current Transformer Ratings
Ratio of :-
IPEAK : IRATED
(IPEAK = Maximum current C.T. can withstand without
suffering any damage).
Ratio of :-
IPRIMARY : IRATED
Class “P”
Specified in terms of :-
i) Rated burden
ii) Class (5P or 10P)
iii) Accuracy limit factor (A.L.F.)
Example :-
15 VA 10P 20
To convert VA and A.L.F. into useful volts
Vuseful ≈ VA x ALF
IN
5P or 10P.
Value of burden in VA on which accuracy claims
are based.
(Preferred values :- 2.5, 5, 7.5, 10, 15, 30 VA)
ZB = rated burden in ohms
= Rated VA
IN2
28 > Current Transformers – January 2004 28
Interposing CT
LINE NP NS ZB
CT
ZCT
R
500/5 0.1Ω 0.4Ω 1VA @ 1A
≡ 1.0Ω
‘Seen’ by main ct :- 0.1 + (1)2 (2 x 0.5 + 0.4 + 1) = 0.196Ω
(5)
Burden on main ct :- I2R = 25 x 0.196 = 4.9VA
Burden on a main ct of required ratio :-
0.5Ω
R
500/1 1.0Ω
Total connected burden = 2 x 0.5 + 1 = 2Ω
Connected VA = I2R = 2
∴ The I/P ct consumption was about 3VA.
31 > Current Transformers – January 2004 31
Current Transformer Designation
Class “X”
Specified in terms of :-
X Differential Protection
Class X Specification
Protection relies on balanced C.T output
RCT RCT
RCT IF RCT
RCT RCT
IF
RL RL RL RL RL IF RL RL RL
IF
Rr Rr Rr Rr Rr Rr Rr Rr
C.T VK is adequate
38 > Current Transformers – January 2004 38
Voltage Transformers
Flux Density
‘B’ Saturation
X Electromagnetic VT`s
Similar to a power transformer
May not be economical above 132kV
NP / NS
= Kn RP LP RS LS
IP Ie IS
LM Re ZB
VP VS (burden)
EP = ES IM IC
C1
VP T
ZB
C2 VS
VC2 Vi
X Primary Earthing
Earth at neutral point
Required for phase-ground measurement at relay
X Secondary Earthing
Required for safety
Earth at neutral point
When no neutral available - earth yellow phase
(VERY COMMON)
No relevance for protection operation
X 5 Limb
Used when zero sequence measurement is
required (primary must also be earthed)
X Three Single Phase
Used when zero sequence measurement is
required (primary must also be earthed)
X 3 Limb
Used where no zero sequence measurement is
required
X V Connected (Open Delta)
No yellow phase
Cost effective
Two phase-phase voltages
No ground fault measurement
da dn
a b c
a b c n
X Use MCB
FUSES to RELAYS
Introduction
SIZE OF MOTOR,
TYPE & IMPORTANCE
OF THE LOAD
Motor Protection
Considerations :-
- Starting current
- Starting time
- Full load current
- Stall withstand time (hot & cold)
- Thermal withstand
Mechanical Overload
Mechanical Overload
OVERLOAD
HEATING
INSULATION
DETERIORATION
OVERLOAD PROTECTION
T = Tmax (1 - e-t/τ)
TMAX
Time
Rate of rise depend on motor
thermal time constant τ
I22 T2
I12 T1
IR2 TMAX
Time
t2 t1
Time
t1
t2 Thermal Withstand
Current
IR I1 I2
Motor Cooling
COOLING EQUATION :
Current2
Im
Im'
0 t Time
After time ‘t’ equivalent motor current is reduced from Im
to Im’.
Motor Heating
Temp
Trip
Tmax
T
t1 t2 Time
Cooling time
constant τr
t1 = Motor restart not possible
t2 = Motor restart possible
Emergency Restart
Required for :-
Stalling on start-up (locked rotor)
Stalling during running
Start
Thermal Hot Curve
IFL IST I
ISL
Dedicated Locked Rotor Protection
Definite Time
IST
IS
ISL
Hot Stall Protection
Time
tSL (HOT)
Time
Tacho opens at
∼ 10% speed
TD < Tstall
> Tacho opening
Start
Time Stall - Tstall
TD
where : n = typically 6
Results in :-
z I2 causes high rotor losses.
Heating considerably increased.
z Motor output reduced.
May stall depending on load.
z Motor current increases.
Reverse Phase Sequence Starting
Instantaneous I2 unit
z Reduced torque
z Increased stator current
z Reduced speed
z Failure to run-up
Undervoltage protection :-
z Disconnects motor from failed supply
z Disconnects motor after dip long enough to
prevent successful re-acceleration
Undervoltage Considerations
Rstab
TRIP
TIME
MPR
FUSE
M
Ts MPR
ELEMENT
Is Icont CURRENT
87 87 87
A B C
87
A
87
B
87
C
Bearings
Bearing Failure
Electrical Interference
Induced voltage
Results in circulating currents
May fuse the bearings
Remember to take precautions - earthing
Mechanical Failure
Increased Friction
Loss or Low Lubricant
Heating
Use of RTDs
z LOSS OF SUPPLY
On Loss Of Supply Motor Should Be
Disconnected If Supply Could Be Restored
Automatically.
Avoids Supply Being Restored Out Of Phase.
F1 F2
Argues
z There are fewer faults on busbars than on other parts of the
power system.
z No risk of dislocation of system due to accidental operation of
busbar protection.
2 05/02/03
08/02 2
Without Busbar Protection
F1 F2
Drawbacks
z Slow fault clearance.
Busbar faults at F1 and F2 are cleared by remote time
delayed protection on circuits feeding the faults:
Time Delayed Overcurrent or
Time Delayed Distance Protection
3 05/02/03
08/02 3
With Busbar Protection
BUSBAR
ZONE
F1
4 05/02/03
08/02 4
With Busbar Protection
BUSBAR
ZONE
F1 F2
5 05/02/03
08/02 5
With Busbar Protection
1/2
SS SS SS
1 87BB 2 3
87BB
21 21
6 05/02/03
08/02 6
With Busbar Protection
2/2
87BB
87BB
21 21
7 05/02/03
08/02 7
With No Busbar Protection
1/2
21 21 21
21 21
8 05/02/03
08/02 8
With No Busbar Protection
2/2
21 21 21
21 21
9 05/02/03
08/02 9
With Burbar protection
87BB
87BB
21 21
21 21 21
21 21
1005/02/03
08/02 10
Busbar Faults Are Usually Permanent
z Insulation failures
z Circuit breaker failures
z Current transformer failures
z Isolators switchs operated on load or outside their ratings
z Safety earths left connected
Therefore :
Circuit breakers should be tripped and locked out by busbar
protection
1105/02/03
08/02 11
Busbar Protection must be :
z RELIABLE
– Failure to trip could cause widespread damage to the substation
z STABLE
– False tripping can cause widespread interruption of supplies to
customers / possible power system instability
z DISCRIMINATING
– Should trip the minimum number of breakers to clear the fault
z FAST
– To limit damage and possible power system instability
1205/02/03
08/02 12
Methods of Providing Busbar Protection
z Frame to Earth (Leakage) Protection
>I
Insulation
1305/02/03
08/02 13
Frame Leakage Protection
>I
Insulation
1505/02/03
08/02 15
Frame Leakage Busbar Protection
>I
1605/02/03
08/02 16
Frame Leakage Busbar Protection
>I
1705/02/03
08/02 17
Frame Leakage Busbar Protection
>I >I
1805/02/03
08/02 18
Frame Leakage Busbar Protection
1905/02/03
08/02 19
Frame Leakage Busbar Protection
Neutral Check
False Operation
because induced
loop
>I
>I
No operation
prevents from
2005/02/03
08/02 false trip 20
Frame Leakage Busbar Protection
Neutral Check
>I
>I
2105/02/03
08/02 21
Frame Leakage Busbar Protection
Neutral Check
>I
>I
2205/02/03
08/02 22
Blocking Scheme Protection
2405/02/03
08/02 24
Blocking Scheme Busbar Protection
2505/02/03
08/02 25
Blocking Scheme Busbar Protection
2605/02/03
08/02 26
High Impedance Protection
2805/02/03
08/02 28
Single Bus Substation
P1 S1 P1 S1 P1 S1
P2 S2 P2 S2 P2 S2
2905/02/03
08/02 29
Single Bus Substation
3005/02/03
08/02 30
Single Bus Substation
3105/02/03
08/02 31
Single Bus Substation
3205/02/03
08/02 32
Double Bus Substation
3305/02/03
08/02 33
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
P1 S1
P2 S2
P1 S1 P1 S1 P1 S1 P2 S2
P2 S2 P2 S2 P2 S2 P1 S1
a Current
b
3405/02/03
08/02 34
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
Current
a
b
3505/02/03
08/02 35
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a Current
b
3605/02/03
08/02 36
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
Current
a
b
3705/02/03
08/02 37
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a Current
b
3805/02/03
08/02 38
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a Current
b
3905/02/03
08/02 39
Isolator Auxiliary Switches
Tripping switching
Bus A
Bus B
Tripping a
b
a
Current b
4005/02/03
08/02 40
Interposing CT are not acceptable
4105/02/03
08/02 41
Isolator Auxiliary Switches
Current switching
Bus A
Bus B
a
Current b
4205/02/03
08/02 42
Isolator Auxiliary Switches
Current switching
Bus A Bus A
Bus B Bus B
a a
Current b Current b
4305/02/03
08/02 43
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
Current b
4405/02/03
08/02 44
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
Current b
4505/02/03
08/02 45
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
Current b
4605/02/03
08/02 46
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
Current b
4705/02/03
08/02 47
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
Current a
b
4805/02/03
08/02 48
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
Current b
4905/02/03
08/02 49
Isolator Auxiliary Switches
On Load Transfer
Bus A
Bus B
a
Current b
5005/02/03
08/02 50
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip Bus B
Trip Bus A
Zone A
Zone B
5105/02/03
08/02 51
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip Bus B
Trip Bus A
Current
switching
failure
Zone A
Zone B
False
Tripping
5205/02/03
08/02 52
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip Bus B
Trip Bus A
Zone A
Zone B
Check
Zone
5305/02/03
08/02 53
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip Bus B
Trip Bus A
Zone A
Zone B
5405/02/03
08/02 54
Isolator Auxiliary Switches
Check Zone
Bus A
Bus B
Trip Bus B
Trip Bus A
Check
Zone
5505/02/03
08/02 55
One Breaker and a Half
Substation
5605/02/03
08/02 56
S1 P1
S2 P2
Bus A Bus
B
P1 P2 P2 P1
S1 S2 S2 S1
5705/02/03
08/02 57
Bus A Bus
B
5805/02/03
08/02 58
Bus A Bus
B
5905/02/03
08/02 59
Bus A Bus
B
6005/02/03
08/02 60
Bus A Bus
B
6105/02/03
08/02 61
Bus A Bus
B
6205/02/03
08/02 62
Bus A Bus
B
P1 P2 P2 P1
S1 S2 S2 S1
P1 P2 P2 P1
S1 S2 S2 S1
6305/02/03
08/02 63