Sei sulla pagina 1di 2

Alarm Monitor

Model 4400
The 4400 Alarm Monitor provides a direct reading multi-
channel monitoring system

Features
6, 12 or 24 channel capacity
simple, quick configuration
simultaneous monitoring on all channels
wide range of inputs
relay and current outputs
RS232/RS485 serial communications
multi-drop capability
time and date stamped alarms
single channel integrity
back up supply card & transmitter power rail

Applications
• temperature measurement • compressor monitoring • turbine monitoring • process control
• vibration measurement • pressure measurement • pump monitoring
Inputs & Outputs
INPUTS – ANY COMBINATION ACCEPTED INTO THE UNIVERSAL CHANNEL CARD OUTPUTS
RTD Range T/C Range Input Range Monitor System integrity relay

Ohm 0 to 450Ω J -180°C to +750°C Ohm 0 to 450Ω Visual indication (LED’s)


2 Common relays
Pt100 ~0.0385Ω/ºC -200°C to +850°C K -180°C to +1250°C Millivolt -10mv to 100mV
24 Vdc Transmitter power
Pt100 ~0.03916Ω/ºC -200°C to +645°C T -200°C to +400°C Volt 0V to 1V
Channel Dedicated relays (2 per
Ni120 -70°C to +300°C E -60°C to +1000°C 0V to 5V card channel)
Cu10 -50°C to +250°C N 0°C to +1210°C 1V to 5V Scaleable analogue
retransmission
Cu30 -50°C to +25°C R 0°C to +1600°C Milliamp 0mA to 10mA
Pt20 -50°C to +25°C S 0°C to +1560°C 0mA to 20mA Comms RS485 ModBus interface
interface
L -200°C to +900°C 4mA to 20mA card RS232 ModBus interface

U -200°C to +600°C Serial printer drivers

314mm
Dimensional drawing A 15mm 237.5mm

Model Front Panel Panel Cut Out Nominal


192mm

Width ‘A’ (mm) Width (mm) Height (mm) Weight (kg)

6 channel 192.0 186 (+10 –0) 186 (+10 –0) 6.5


12 channel 288.0 282 (+10 –0) 186 (+10 –0) 9.0
24 channel 432.0 426 (+10 –0) 186 (+10 –0) 15.0 Removable panel mounting clamps

ISSUE: 4400/MAR2001/UK
Specification
General: CSA listed: Class 2252 01
Accuracy: ±0.5ºC RTD LVD: EN61010-1
±1.0ºC Thermocouple EMC: Complies with the requirements:
±0.1% Span analogue EN 50081-1 Emissions
EN 50082-2 Immunity
Temperature (Operating) 0ºC to +50ºC
range: (Storage) -40ºC to +70ºC Weight: 6ch - 6.5kg nett, 10kg shipping
12ch - 9.0kg nett, 12kg shipping
Humidity: 0-95%RH in accordance with the 24ch - 15kg nett, 16kg shipping
requirements of IEC 68-2-3
Installation: Panel mounted
Vibration: Tested in accordance with IEC-2-6
Outputs:
Shock: Drop tested to IEC 68-2-31
H1 option: Two SPDT per channel (resistive loads
Delay time: Adjustable 0 to 60 seconds individually for only)
each set point
H2 option: Two SPDT per channel (resistive &
Dead-band: Adjustable 0 to 25% of span in 1% inductive loads)
increments for each set point
M1 option: DC analogue re-transmission output per
Response time: Less than 800 milliseconds with delay set channel
to zero
System: Local display
Alarm log: 256 alarm events and operator action LED for each channel
time-tagged and logged
Electrical:
Transmitter Up to 1 amp at 24Vdc available for P1 option: 18 - 36Vdc
power rail: powering transmitters P2 option: 90 - 260Vac 50/60Hz
P3 option: 110Vac 50/60Hz
Environmental: Complies with the requirements of EN61010-1 P4 option: 240Vac 50/60Hz

Environmental Note: P3 & P4 power supplies only available


protection: IP54 on 6 channel units

Ordering Information

Model code format Channel card code format


4400AM Alarm Monitor 4401AM Universal Channel Card
Chassis capacity Options
06 6 channel capacity H1 Channel alarm relay
12 12 channel capacity (resistive load only)
24 24 channel capacity H2 Channel alarm relay
Power supply (res & inductive load)
P1 18-36Vdc M1 Output current
P2 90-260Vac 50/60Hz (0-10, 0-20, 4-20mA)
P3 110Vac 50/60Hz
P4 240Vac 50/60Hz
Example: 1 x 4400AM24-P2-F1
Options
B1 24Vdc standby supply
Description: 24 channel alarm monitor with 90-260Vac
C1 Conduit cable box
power supply and bezel for panel mounting
D1 Adapter plate for 19” rack mounting
E1 IP54 sealing kit (includes F1)
F1 Bezel for panel mounting Example: 24 x 4401AM-H1-M1
G1 Communications interface
Description: Universal card with resistive relay card and
current output card.

Note:
Universal channel cards are required to operate each channel and must be ordered as a separate item from the unit.

Thermo Measurement Ltd Thermo Measurement Ltd


King’s Worthy 9303 W. Sam Houston Parkway South
Winchester, Hampshire Houston
SO23 7QA, United Kingdom Texas
77099 – 5298 USA
Tel: +44 (0) 1962 625000
Fax: +44 (0) 1962 885530 Tel: +1 (713) 272 2218
email: sales@thermomeasurement.com Fax: +1 (713) 272 2214
www.thermomeasurement.com

A Thermo Electron business

Potrebbero piacerti anche