Connecting with HART 475


How to use a HART
Communicator (Emerson The HART 475 leads have to be inserted into
the HART side of your communicator.
– 475)
Posted on : November 30,
2015 By denizen robo
Calibration How to Instrumentation

How to calibrate a Rosemount DP


(Differential Pressure) transmitter with a
HART Communicator ?

Steps involved in the calibration

1.Connect the DP transmitter (Rosemount)


to a power supply
2.Connect the HART
3.Connect test pressure gauge 3.Connect Test Gauge
4.Calibrate zero and span of transmitter
When dealing with a DP transmitter you
always want to connect to the “High side”
1.Connecting the power supply to DP with your pump to apply pressure (PSI).
transmitter

In order for you to be able to communicate


with the DP transmitter you have to install a
resistor in series with your power supply.

HART recommends a 250 ohm resistor

Make sure low side is vented to atmosphere .

Precautions need to be taken :

If you are dealing with a DP transmitter in the the


correct way to test is to always have the transmitter in
bypass and notify the control room operator of what is
about to be done.

The very first thing to do is equalize the manifold.

Isolate the process pressure.


After you have the resistor in series and the
power supply connected,connect your HART Vent the pressure
475 noting polarity.
Separate the high and low sided and connect Now start with your zero calibration.Make
to the high side and have the low side vented sure you are vented on low side and the high
to atmosphere side is vented on the test pump.

It is very important to follow these steps


Now its time to span the meter.
failure to properly equalize will most likely
result in deformation of the DP transmitter
sensing element. Make sure your test pump meter is reading
zero when open then close the vent on your
4.Connecting HART Communicator test pump.

When you are all powered up turn on your Select Upper using one on the the keypad or
HART 475 on the first screen select HART. while selected the right arrow and follow the
prompts on screen.

Now its time to apply the upper range


input.

Start slow with the pump up to see how


fast the pressure rises.Over ranging will
cause damage.
Next you want to press right arrow when the
HART 475 sees your instruments
Apply the correct pressure

Select “OK” and follow prompts on the


screen.

After you select OK when the pressure is


stable the next screen will allow you to tell
exactly what it is reading.

Enter in the text box the exact reading on


your test pump the moment you pressed ok
for the pressure being stable.

Use right arrow key to select your next Select “ENTER” and follow the prompts on
screen
option or OK button on touch screen. Go
to the following menu. Go to “Home” .Then go to “Overview” and
verify the calibration
Service tools>Maintenance >Pressure
Calibration> Related articles:-
What is HART transmitter ?
Brief idea about HART communication
DP transmitter calibration Calibration
range calculation tool