Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2875032, IE
EE Transactions on Power Systems
0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
Z The vector of maximum allowable action time DG’s reactive power be dispatched cooperatively with the
zi,t The normalized dates for i-th discrete operation of the OLTC and CB in the distribution network. Referenc
variables e [21] proposed a day-ahead coordinated dispatch
Si The number of adaptive segmentation for i-th method of reactive power. Meanwhile, reactive power outputs
discrete devices of DGs are used along with CBs to regulate distribution netwo
sn Cluster number rk voltage. However, the voltage adjustment ability of OLTC
was not considered in [20-21]. Reference [22] proposed a new
m Weighted index
successive linear approximation method to handle the nonlinea
pc Cluster center of class c rity of the power flow equations and then the reactive power o
k Lagrange multiplier ptimal dispatch problem was solved by it. In [23], a data-drive
I Unit matrix n stochastic reactive power optimization model was introduce
tn The duration of each period d to address uncertain DGs integrated into distribution networ
ks. However, the high penetration of DGs or their reactive po
II. INTRODUCTION wer adjustment ability was not considered in [22-23].
So far, there are three main shortcomings of the existing wo
R ECENTLY, as an important complement to the traditional
centralized power generation, DGs are rapidly embarking
on the stage of the world power industry [1-3]. With the large-
rks on this subject.
1) After adding DGs, the DRPO mathematical model and t
he system reactive power adjustment capacity will change obv
scale application of renewable energy such as photovoltaic (P iously. However, the coordinated dispatch with the traditional
V) and wind turbines (WT), energy consumption is becoming reactive power devices was rarely considered in the above rese
increasingly clean and renewable. Meanwhile, the high propor arch work.
tion of DGs incorporating to the power system has brought ne 2) The existing DRPO approaches did not ideally address t
w challenges to safe operation and coordinated dispatch [4-8]. he problem that allowable action time of discrete adjust device
Reactive power balance is the basic guarantee for the safe a s is inconsistent.
nd stable operation of power grid [8-10]. The voltage level and 3) The existing methods still have much room for improve
power quality depend directly on the rationality of reactive po ment in improving system network loss and node voltage, whi
wer distribution [10-11]. At present, the reactive power regulat ch deserves further study.
ion in the distribution network mainly depends on both shunt Aiming at the existing problems, this paper proposes a nove
CBs and OLTC [3]. However, as the slow regulation devices, t l two-stage method based on Heuristic search-Variable correct
hese devices cannot switch frequently for the physical constrai ion. The main contributions of this paper are summarized as fo
nts, which cause difficulty in achieving real-time adjustment o llows:
f reactive power. Due to the advantages of continuous, quick a 1) It is the first time to propose an objective function based
nd frequent adjustment, the reactive power outputs of DGs are on the membership function of Gauss-type and Z-type. By me
used along with CBs and OLTC to regulate voltage will have a ans of the concave-convex feature of Gaussian-type and Z- typ
broad application prospect. e membership functions, the network loss and node voltage de
The dynamic reactive power optimization (DRPO) of the di viation are better balanced.
stribution network with DG must not only handle the continuo 2) The SFCM method based on ABC is proposed innovati
us control variables such as reactive power output of DG, but a vely and solves time-space coupling problem in the DPRO. M
lso deal with discrete control variables such as capacitor bank g eanwhile, it is worth noting that the proposed method achieves
ear, on-load tap changer transformer tap, and so on. After takin the mutual independence of the sequential segmentation proce
g into account the switching times of discrete control variables, ss, which can be solved in parallel thereby, greatly reducing th
the dynamic reactive power optimization mathematical model i e computation time. Furthermore, compared with the previous
s a complex non-convex nonlinear mixed integer programming methods, this method solves the problem encountered when th
problem with strong space-time coupling. The whole time is su e allowable action time of discrete adjust devices is not consist
bject to discrete constraints of discrete control variables; in eac ent.
h time section, a nonlinear mixed integer programming is form 3) A novel two-stage (Heuristic search and Variable corre
ed in space [12-15].To solve this problem, various solutions ha ction) dynamic reactive power dispatch strategy is proposed to
ve been proposed. In [16-18], the discrete variables were relaxe solve the coordinated dispatch problem in the distribution net
d as continuous in the optimization model and then the continu work. Through the coordination of DG, OLTC and CBs, the pr
ous variables obtained from the optimization were rounded off oposed method improve the validity and feasibility of the day-
to the nearest integer, which may only lead to inequality constr ahead dispatch plan.
aints violations when rounding off discrete variables with large 4) The effects of adjustment step and action time on the opt
step sizes such as shunt capacitor banks [19]. Reference [20] pr imization results are discussed in detail, which will have some
oposes a novel two-stage dynamic reactive power coordination instructive significance for the related fields research and pract
dispatch strategy based on the Haar wavelet transform method, ical engineering application.
and The rest of the paper is organized as follows: In Section III,
a DPRO model considering reactive power output of DG is inn tic search and Variable correction) dynamic reactive power dispatch strate
ovatively built. Section IV proposes a novel two-stage (Heuris gy. Furthermore, simulation results obtained on IEEE 33-bus, IEEE 14-bu
s and PG&E 69-bus test systems demonstrate the practicality a upper and lower limits is not enough to meet the voltage qualit
nd efficiency of the proposed method by different schemes, str y requirements of the modern power system. Hence, in the da
ategies and methods in Section V. Finally, conclusions are pre y-ahead dispatch plan, it is necessary to make the node voltage
sented in Section VI. as close as possible to the expected value, which ensures adeq
uate reserve to control reactive power in the short-term dispatc
h. For this purpose, based on the Gauss-type membership func
tion, the satisfactory evaluation function of voltage deviation i
s proposed in this paper. It can be expressed as follows:
III. REACTIVE COORDINATION DISPATCH MODEL IN 2
/
DISTRIBUTION NETWORK WITH DGS
F av ) e(U c) (3)
(U e 2
min
c,t
t
k,
T zt ,mi zt zt ,max
f ( xt , yt , zt
n
B. Heuristic search
)
t 0
s.t. ht ( xt , yt , zt ) Based on the results of the pre-optimization, this paper prop
0 oses a SFCM method to realize sequential segmentation of eac
gt ( xt , yt , zt )
h OLTC switching gears and CBs switching capacity by
(13) (15)-(27). Then, based on the ABC algorithm [26-28], the
0
xt ,min xt xt ,max
yt ,min y t y t ,max sequential segmentation results are adjusted adaptively to meet
zt ,min zt zt ,max the constraints of OLTC and CBs allowable action time by (2
T 8)-(32). Finally, the equivalent OLTC switching gears and
zi,t zi,t 1 Z , i 1,... CBs switching capacity within each segment are calculated to
t 0 n complete their day-ahead dispatch plans. It should be noted tha
t each discrete device is adaptively segmented by allowable
IV. TWO-STAGE OPTIMIZATION STRATEGY BASED ON action time. Moreover, all devices are independent of each oth
HEURISTIC-CORRECTION er, so parallel computing technology can be adopted to improv
In the reactive power adjustment devices, the OLTC and C e the calculation efficiency dramatically.
Bs with large adjustment ability are suitable as basic adjustme The sequential segmentation-polymerization of the OLTC a
nt for physical performance constraints. However, nd CBs is described in detail in this section. The total discrete
DG, due to fast and continuous adjustment ability, can be used control variables are presented as
as a supplement to adjust real-time reactive power balance. Fu z z1 , z2 , i 1,...,nc nl
zi ,z (15)
rthermore, to address coordinated dispatch and time-space cou nc n l
pling problem, a two-stage optimization model is proposed to Each zi can be further presented as
coordinate the discrete and continuous adjustment devices zi zi,1 , zi,2 , zi,t , zi,T , (16)
t 1,...T
and find an optimal solution that can achieve the balance betw The specific form of zi can be expressed as follows:
een network loss and voltage deviation. Meanwhile, this z QC ,Q C , ,Q C , iN
method can hedge against some possible risks, such as, the
uncertainty of renewable energy. Therein, the Heuristic search i,1 i,2 nC ,T C
i
stage decisions (i.e., discrete reactive power compensators) are or (17)
served as the “here and-now” decisions, i.e., they cannot be
z , , iN
, nL ,T ,
adjusted after the uncertainty is revealed, while the variable co i i,t i,2 L
rrection stage decisions (i.e., continuous reactive power compe
The specific steps are as follows: 1)Origin
nsators) are represented as the “wait-and-see” decisions that ca al data standardization
n be adjusted after the first stage decisions are determined. To reduce the excessive impact of the maximum or
A. Pre-optimization maximum data for cluster results, the raw dates are standardize
d firstly. The normalized dates for i-th discrete variables are as
follows
The control variables in this section include the reactive po zi,t min{zi }
wer output of WT and PV, the compensation power of CBs, zi,t (18)
max{z } min{z
} i i
the switching gear of OLTC and the dispatch time of each
controllable devices. With (4)-(10) as the constraint conditions, 2 ) This paper takes the sum of the weighted distance
squares of the samples in the classes to each cluster center as t quadratic programming model with minimum variances of the
he objective function and calculates optimal fuzzy classificatio switching capacity series as the objective function is establishe
n matrix U and cluster center P [29-30]. The objective functio d based on the results of sequential segmentation. It is solved
n J (U, P) can be expressed as: by means of the efficient ABC algorithm. The mixed
24 sn
integer quadratic programming model of i-th discrete control
J (U , P) min{(s,t )m (ds,t )2} variable is expressed as follows:
t 1 s1 (19) Si
(zˆi,t
sn
24
Min zi,t (28)
)2
min{ (s,t ) m n
= (d s,t )2 } n1
t 1 s1
zˆi,tn / zi,step int (29)
Where sn Si
s1
s,t 1, t 1, ,T (20) tn 24 (30)
n1
2,
s,t [0,1], (21) 0 tn 24 (31)
sn
s 1, 2, sn ; t 1, 2,T Si zi,max (32)
s,t 24,
0 s1 s 1, (22) The optimization result obtained in the pre-optimization
2, sn
(d )2 z p
(z p )T A(z p (23) stage is marked with ξ = y, z . Next, the Heuristic search
)
i,t i,t
s,k i,t s A stage can be summarized as the following optimization model:
s s
Where s,t is the membership that zi,t belongs to class s; ps T
distance from zi,t to ps. This article takes m=2, A=I. s.t. ht ( xt , yt , zt )
Next, based on the Lagrangian multiplier method and
0 (28)
g t ( x t , y t , zt )
0
cluster quasi-side, the Lagrange function is constructed as x x x
follows.
t ,min t t ,max
zt ,min zt zt ,max
s s
Fn
( s,t )m (ds,t )2 t (
n
s,t (24)
T
1)
s1 s1 zi,t zi,t 1 Z , i 1,...n
According to the Kuhn-Tucker theorem, the partial derivati t 0
ves of all input parameters are obtained. The necessary conditi
ons to minimize objective function (24) are as follows: C. Variable correction
In this stage, the reactive power output of WT and PV and
sn
1 their dispatch time are used as the control variables. With fixin
s,t (ds,t / d j,t 2/(m1) (25)
g the optimal value of the OLTC and CBs obtained in the heur
) istic search stage, formulas (4)-(7) and formula (10) as the
j 1
T T
pi (s,t )m zi, (s,t ) (26) constraint conditions, (1) as the objective function, the reactive
t t 1 power output of DGs each period is calculated by
m
t 1
Then, based on (24)-(26), the optimal fuzzy classification NGA to complete its day-ahead reactive power dispatch plan.
matrix U and cluster center P can be obtained by primal-dual i
The built model in this section belongs to a non-integer non
nterior method.
linear programming problem. Here, the optimization result obt
3) sequential segmentation for discrete devices
Since the cluster results do not have sequential ained in the heuristic search stage is marked with ξˆ = yˆ , zˆ
characteristics, they need to be sorted in chronological order. S , then, the variable correction stage can be summarized as the f
pecific steps are as follows: Firstly, the cluster numbers of ollowing optimization model:
each discrete control variable at each time are marked
respectively. Secondly, the cluster results of same class and adj min f ( xt , yt , zˆt )
acent time are merged into a section in chronological order. t
0
After merging, the equivalent value of each segment for the i- s.t. ht ( xt , yt , zˆt ) (29)
0
th discrete control variable zi,t is expressed as follows: gt ( xt , yt , zˆt ) 0
xt ,min xt xt ,max
zi,t zi,t /
(27)
nt yt ,min yt yt ,max
tNt
Where Nt is the serial number of discrete control variables cont
ained in the time interval t and nt is the corresponding number. D. Solution Process
4) Adaptive timing segmentation Through the heuristic search and variable correction, the pr
For each discrete control variable, a mixed integer oblems of the coordinated dispatch and space-time coupling is
solved in the dynamic reactive power optimization of the
Load 、WT and PV Factors
shown in Fig. 1. 1
Start 0.8
0.6
Enter system parameters and 0.4
the forecast data of WT, PV, and load
0.2
0
Based on operational characteristics 0 3 6 9 12 15 18 21 24
Time Period (hours)
analysis of PV and WT, calculate their upp
er and lower limits of reactive Power output Fig. 2. Forecast coefficients of Load, WT and PV for next day
18 19 20 21 OLTC
CBs DG
0 123 456789 10 11 12 13 14 15 16 17
25 26 27 28 29 30 31 32
22 23 24
0.5
1.035
Reactive power output /(kvar)
0.4
0.3 1.03
continuous
0.2 1
1.025 2
0.1 4(This paper)
8
0 1.02
0 0 3 6 9 12 15 18 21 24
3 Time section/(h)
6
9
12
CB2 Fig. 5. Impact of action time limit on OLTC
15 CB1
PV2
Time section/ 18 PV1
(h) 21 WT2
24 WT1 1.07
1.03
1 ) The impact of action time and adjustment step of discr
ete devices on the result 1.02
continuous
0.01 p.u.(This paper)
1.01
The distribution system may be reconfigured due to the nee 0.025 p.u.
0.05 p.u.
d of transmission network operation by shifting loads, DGs 1
0 3 6 9 12 15 18 21 24
and CBs from substation to another substation. When the distri Time section/(h)
stics of the OLTC may be different, that is, the difference is its 1.06
OLTC secondaed voltage/(p.u.)
action time and adjustment step. To address this issue, this sec 1.05
The adjustment step of OLTC is still set to 0.01 p.u. The optim 1.02 continuous
0.01 p.u.(This paper)
ization results are shown in Fig.5 when the action time changi 1.01 0.025 p.u.
0 3 6 9 12 15 18 21 24
ladder curve gradually approaches ideal curve. It should be not Time section/(h)
ed that the ideal curve is the optimization results that the switc
hing gears of OLTC are taken the continuous variation without Fig. 7. Impact of adjustment step on OLTC (nk_max=8)
considering its action time constraints.
Further, the action time of OLTC is fixed to 4. The adjustm 22.12
0.01p.u.
ent step is set to 0.01 p.u, 0.025 p.u, and 0.05 p.u., 0.025p.u.
The satisfaction of dispatch results
0.05p.u.
respectively. The simulation results are shown in Fig. 6. Simil 21.12
120
110
adjustment results are relatively poor. However, the discrete d 120
evices can achieve frequent adjustment when having a large ac 110 100
tion time, so that the adjustment with small steps can be more 100
Network loss/(kwar)
90 90
refined and the adjustment effect is better. Besides, in the case 80
of the adjustment step increasing to 0.05 p.u., the switchable d 70 80
uration of OLTC does not change during the process of the all 60
70
owable action time changing from 4 to 8. OLTC is only adjust 50
40
ed twice during the whole process, though with more allowabl strategy 3 60
strategy 2
e action time. Meanwhile, it can be verified from Fig. 8, satisf strategy 1
15 18
21
24
50
action function is always 20.04 when action scheme 3
scheme 2 6
9
12
Time section/(h)
make the result worse, so OLTC is not adjusted when its allow
able action time changing from 2 to 8. It can also be clearly see Fig. 9. Comparison of network loss in different dispatch schemes and
n from Fig. 8 that the larger adjustment step can achieve better strategies
results in the case of few allowable action time. For example,
when the allowable action time is set as 1, the satisfaction is 18.
22, 18.72 and 18.97 respectively for the adjustment step being 1.035
0.01 p.u., 0.025 p.u. and 0.05 p.u.. On the contrary, the smaller 1.04
1.03
adjustment steps can get better results. For example, when the 1.03
1.025
1.02
and 20.04 respectively for the adjustment step being 0.01 p.u., 1.015
1.01
0.025p.u. and 0.05 p.u.. 1.01
1
2)Comparison between different schemes or strategies 0.99
1.005
strategy 2
Scheme 1: DGs do not participate in reactive power dispatc strategy 1 24
28
32 0.99
20
h; scheme 3
scheme 2
12
16 0.985
8
Scheme 2: DGs participate in reactive power dispatch with scheme 1 0
4
System node
the constant power factor 0.95;
Scheme 3: DGs participate in the optimization dispatch wit
Fig. 10. Comparison of node voltage amplitude in different dispatch schemes
hin the reactive power output limit. and strategies
Strategy 1: Network loss is set as the objective function to
perform reactive power dispatch; 0.75
Strategy 2: Voltage deviation is set as the objective functio scheme 1
n to perform reactive power dispatch; 0.675 scheme 2
Voltage deviation/(p.u.)
TABLEⅠ
COMPREHENSIVE COMPARISON OF DIFFERENT SCHEMES
AND STRATEGIES (IEEE 33)
and PV can output inductive reactive power to reduce the
system node voltage, which will ensure safe and stable Schemes/ Network voltage
Satisfaction
operation of power system. This just shows that DG participatin strategies loss/(kW) deviation/(p.u.)
g in reactive power dispatch within its reactive output range can scheme1 2048.8 14.0570 18.6441
better improve the running performance of power system, and i scheme2 1859.7 12.4621 19.7159
mprove its utilization rate and exert greater value. scheme3 1559.2 9.8339 21.6893
Future, compared with the strategy 1 and strategy 2, strateg strategy1 1591.6 10.9485 21.0876
y 3 proposed in this paper better achieves the balance between strategy2 1604.4 10.6200 21.0680
network loss and voltage deviation, and the strategy3 1598.0 10.6842 21.3319
satisfaction is improved by 0.2443 and 0.2639, respectively. It TABLE Ⅱ
is worth noting that the satisfaction here is the average value i COMPREHENSIVE COMPARISION OF DIFFERENT SCHEMES
n a dispatch cycle. Hence, the optimization effect will be more AND STRATEGIES (IEEE 14)
prominent when the analysis is done by the total increments of
the satisfaction in a dispatch cycle. From fig. 12, compared wit Voltage d
h the line-type satisfaction function, in the case of the same net Scheme/ Strat Network lo
eviation Satisfaction
work loss (input parameter), the built Z-type satisfaction functi egy ss/MW
/p.u.
on will have a better satisfaction value during the [a, a+b]. In scheme 1 13.5763 5.9636 18.8627
contrast, it will have a worse satisfaction value in the [a+b, b]. scheme 2 11.6738 5.7112 19.4422
Specifically, it can improve the satisfaction of the smaller net 19.8496 4.3932 21.9187
scheme 3
work loss and reduce the satisfaction of the larger network los 10.1133 4.6448 21.2948
strategy1
s. Similar to the Z-type satisfaction function, the gauss-type sa
strategy2 10.2214 4.5049 21.2650
tisfaction function of voltage deviation has the same effect. Co
strategy3 10.1610 4.5509 21.5192
mpared with the line- type satisfaction function, in the case of
the same node voltage amplitude (input parameter), the built g
auss-type satisfaction function will have a worse satisfaction v TABLE Ⅲ
alue at the time of unqualified voltage, such as [0.9, 0.95] and COMPREHENSIVE COMPARISION OF DIFFERENT SCHEMES
AND STRATEGIES (PG&E 69)
[1.05, 1.1]. In
contrast, it will have a better satisfaction value in the period of
voltage qualification [0.95, 1.05]. Hence, in order to achieve Scheme/ Network Voltage
Satisfaction
greater satisfaction, the unqualified node voltage will be better o Strategy loss/(kW) deviation/(p.u.)
ptimized. In short, the Z-type satisfaction function of network l scheme1 3761.29 29.3919 17.3712
oss and the gauss-type satisfaction function of voltage deviation scheme2 3302.56 26.0751 18.5247
can be adjusted adaptively by means of its convexity and conca scheme3 2817.86 20.5618 19.8926
ve, which better achieve the balance between network loss and strategy1 2900.33 22.8923 19.0876
voltage deviation of the distribution system. Through the compa strategy2 2925.71 22.2051 19.0583
rison and analysis, it can be clearly seen that the optimization strategy3 2911.30 22.4300 19.1389
effect of the proposed strategy is
close to that of the scheme 3, which well explain the feasibili Feeder node1
CBs DG
ty and superiority of the proposed strategy.
node3 node4
node11
node2
node8 node12
node6 node10
node9
node7node14
node5 node13
40 4157 58
the proposed strategy 3 better achieves the balance between ne
twork loss and voltage deviation, and the satisfaction is impro
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 ved by 0.2244 and 0.2542 respectively. The causes associated
36 37 38 39 55 56 to what is happening physically have been explained in detail i
42 43 44 45 46 47 48 49 50 51 52 53 54 n section A of numerical simulation. Here, it will not be descri
Fig. 14. Diagram of modified PG&E-69 bus distribution network bed in detail. Similarly, through the comparison and analyses
between three strategies and scheme 3, it can be clearly seen th
B. Simulation analyses of IEEE 14-bus and PG&E 69-bu at the optimization effect of proposed strategy is close to that o
s test systems f scheme 3, so optimization results are ideal. At the same time,
The IEEE 14-bus distribution network has 3 feeders and 16 through the three schemes
branches. The reference capacity of the system is 100 MVA w and three strategies in Table Ⅲ, it can be clearly seen that the
hile the reference voltage is 23 kV. With the removal of the thr simulation results of PG&E-69 bus distribution system are
ee branches (14, 15 and 16), it will lead to a radiation typical d similar to those of the IEEE-33 and IEEE-14 bus distribution s
istribution network structure with 14 nodes and 13 branches, w ystem. The validity and feasibility of the proposed strategy is a
hich can operate in the form of open loop. Among them, the O lso verified. Due to limited space, it will not be analyzed in det
LTC in the substation accesses to the root node 0, and its step i ail in this section.
s 0.025 and the switchable range is [0.95, 1.05]. The switchabl C. Comparative analysis of multiple optimization methods
e capacitors, with the capacity of [0, +2.0] Mvar and the step o
In order to further verify the practicability of the proposed
f 0.1 Mvar, are connected to bus #3. Besides, the maximum all
optimization method, comparisons with two most effective an
owable action time over 24 hours is 5. The DFIGs are connect
d recently reported optimization approaches from the referenc
ed with node 19 and node 24, respectively, whose rated capaci
es [13], [15] and [20] are carried out. It is worth noting that the
ty are both 2 MVA. The PV connected to grid by inverters are
same coordinated scheduling strategy is adopted in [13] and [1
installed at buses #9 and #14, whose rated capacity are both 1.
5]. Therefore, the following will mainly compare with the met
5 MVA. The topology of IEEE-14 bus distribution system is s
hod of reference [13]. Before comparing with the optimization
hown in Fig. 13.
method in [13], we first develop the Matlab program based on
The PG&E 69-bus distribution network has 69 nodes and 7
the optimization method and test system described in [13], and
3 branches and 5 contact switches. Its base capacity is 10 MV
strictly verify the correctness of our program by comparison w
A and reference voltage is 12.66 kV. Among them, the OLTC
ith the simulation results in [13]. Then, in order to ensure the s
in the substation accesses to the root node 1, and its step is 0.0
trictness of the comparative analysis, here we change the objec
1 and the switchable range is [0.95, 1.05]. The switchable capa
tive function in [20] to the formula (1) in our manuscript, and
citors are connected to buses {#21, #61}, whose capacity are b
OLTC's switching gear as a control variable is considered. Fin
oth [0, +0.5] Mvar, and the steps are 0.02 Mvar. Besides, the
ally, we compare the proposed optimization method with the li
maximum allowable action time over 24 hours for both is 5. T
terature [13] and [20] based on the modified IEEE 33-bus test
he DFIGs are connected to buses {#16, #28, #51, #66}, whos
system in our manuscript that is the most commonly used stan
e rated capacity are all 0.5 MVA. The
dard test system in the distribution network. The three method
PVs are installed at buses #41, #54, #56 and #58, whose rated
s used for comparative analysis are as follows:
capacity are all 0.5 MVA. The topology of PG&E 69-bus distr
Method 1: optimization method in [13];
ibution system is shown in Fig. 14. Method 2: optimization method in [20];
To further verify the proposed model, we use IEEE 14-bus Method 3: the proposed optimization method in our man
and PG&E 69-bus distribution network as the simulation syste uscript.
ms in this section. Considering that the feasibility of the propo The detailed results are shown in Table IV below.
sed strategy has been fully verified by the IEEE 33-bus distrib
ution network, here, based on the spatial constraints, the analy TABLE IV
sis for IEEE 14-bus and PG&E 69-bus test systems are perfor COMPARATIVE ANALYSIS OFMULTIPLE OPTIMIZATION
METHODS
med from three aspects of voltage amplitude, network
loss and satisfaction to further verify the universality and
efficiency of the proposed strategy. Then, comparative Action time of OLTC and CB
Method Satisfaction
analyses on optimization results in different schemes and strateg OLTC CB1 CB2
ies are done in voltage amplitude, network loss and Method 1 5 6 10 21.3681
5
satisfaction, as shown in Table Ⅱ and Table Ⅲ . The used Method 2 5 5 20.1927
schemes and strategies are remain the same as section 4.1 in Method 3 4 3 4 21.9187
this section.
In Table Ⅱ , three schemes are compared in terms of opti As can be seen from Tab. IV, the method 1 requires freque
mizing network loss and voltage deviation, the scheme 3 is nt adjustments of OLTC and CB to cope with system fluctuati
ons without the limit of the action time, which affects
the service life of OLTC and CB. The method 2 uses the segm entation static method to divide the dynamic net load curve into 5 segmen
ts, and both OLTC and CB are adjusted 5 times in the scheduli power regulation ability of DGs. Meanwhile, based on the anal
ng cycle. Moreover, this method is difficult to handle the case ysis of Gauss-type and Z-type membership function, a new obj
where the OLTC and the CB have different action times. Com ective function is put forward to better balance both network l
pared with the method 1 and method 2, the method 3 proposed oss and voltage deviation. The comparison with the traditional
in this paper has better satisfaction within the maximum allow dispatch schemes, strategies and optimization approaches thro
able action number of discrete devices, and the satisfaction is i ugh IEEE 33-bus, IEEE 14-bus and PG&E 69 test systems pro
mproved by 0.1638 and 0.5392, respectively. Since the satisfa ve that the proposed method can achieve better optimal solutio
ction is determined by the network loss and node voltage, it ca n and computational performance than existing methods. More
n be known that the method 3 better improves network loss an over, Numerical results also demonstrate that making full use
d the node voltage of the system. Therefore, the method 3 prop of DGs reactive power adjustment potential is conducive to im
osed in this paper has good practicability and feasibility. proving the system security and economy.
D. Selection criteria of weighting factors
REFERENCES
For the multi-objective functions to be converted into sin
[1] B. Zhu, H. Tazvinga, X. Xia, “Switched model predictive control for ener
gle-objective functions, we first solve the problem of dimensio gy dispatching of a photovoltaic-diesel-battery hybrid power system,” IE
EE Trans. on Control Syst. Technol., vol. 23, no. 3, pp. 1229- 1236, May
nal inconsistency by standardizing the F(Ploss ) and 2015.
[2] S. Gill, I. Kockar, G. W. Ault. “Dynamic optimal power flow for active d
F(Uave ) , and then transform the multi-objective function into istribution networks,” IEEE Trans Power Syst., vol. 29, no.1: 121-131, Ja
n. 2014.
a single objective function based on the weighting method. Alt [3] T. Ding, S. Liu, W. Yuan Z. Bie and B. Zeng, “A two-stage robust reactiv
hough the weighting method is currently the most common an e power optimization considering uncertain wind power integration in act
ive distribution networks,” IEEE Trans. Sustain. Energy, vol.7, no.1, pp.
d practical method, it faces the problem of how to select the w 301-311, Jan. 2016.
[4] A. Cagnano, E. De Tuglie, M. Liserre, and R. A. Mastromauro, “On-line
eighting factors. Here, the criteria of weighting factors selecte optimal reactive power control strategy of PV-inverters,” IEEE Trans. In
d in equation (1) is: under the premise of ensuring the safe and d. Electron., vol. 58, no. 10, pp. 4549-4558, Oct. 2011.
[5] A. V. Stiphout, K. D. Vos, G. Deconinck, “The Impact of Operating Rese
stable operation, taking 0.05 as the step size, the weighting fac rves on Investment Planning of Renewable Power Systems,” IEEE Trans .
Power Syst., vol. 32, no. 1, pp. 378-388, Jan. 2017.
tors that ultimately makes the satisfaction function the largest i [6] T. Niu, Q. Guo, H. Jin, et al, “Dynamic reactive power optimal allocation
to decrease wind power curtailment in a largescale wind power integratio
s selected as the weighting factors. Finally, the results of three n area,” IET Renew. Power Gener., vol. 11, no.13, pp. 1667- 1678, Nov.
IEEE test systems show that this method can achieve satisfact 2017.
[7] S. Eftekharnejad, V. Vittal, G. T. Heydt, B. Keel; J. Loehr. “Impact of in
ory effect. By this method, the weighting factors for each creased penetration of photovoltaic generation on power systems,” IEEE
Trans. Power Syst., vol.28, no. 2, pp.893-901, May 2013.
test system are as follows: [8] J. V. Paatero, P. D. Lund, “Effects of large-scale photovoltaic power integ
ration on electricity distribution networks,” Renewable Energy, vol. 32, n
1 0.55 and 2 0.45 in the IEEE 33-bus test system; o. 2, pp.216-234, Feb. 2007.
1 0.65 and 2 0.35 in the IEEE 14-bus test system; [9] C. G. Kaloudas, L.F. Ochoa, B. Marshall, et al., “Assessing the future tre
nds of reactive power demand of distribution networks,” IEEE Trans. Po
1 0.35 and 2 0.65 in the PG&E 69-bus test system. Due t wer Syst., vol.32, no.6, pp.4278-4288, Nov. 2017.
[10] L. Chen, H. Li, “Optimized reactive power supports using transformer ta
o space limitations, the following is an example of the satisfact p stagger in distribution networks,” IEEE Trans. on Smart Grid, vol. 8, n
ion of IEEE 33-bus test system under different weights, which o. 4, pp. 1987-1996, July 2017.
[11] Z. Yang, A. Bose, H. Zhong, N. Zhang, Q, Xia, C, Kang, “Optimal reacti
is shown in Fig. 15. ve power dispatch with accurately modeled discrete control devices: A su
ccessive linear approximation approach,” IEEE Trans. Power Syst., vol. 3
2, no.3, pp. 2435-2444, May 2017.
[12] K. Zou, A. P. Agalgaonkar, K. M. Muttaqi, “Distribution system plannin
g with incorporating DG reactive capability and system uncertainties,” I
EEE Trans. Power Syst., vol.3, no.1, pp.112-123, Jan. 2012.
[13] Y. J. Kim, P. Hwang, G. Pyo, S. M. Kim, “Coordinated control of a DG a
nd voltage control devicesusing a dynamic programming algorithm,” IEE
Fig. 15 the satisfaction of the IEEE 33-bus test system under different weight f E Trans on Power Syst., vol. 28, no. 1, pp.42-51, Feb. 2013.
actors [14] Y. Deng, X. Ren, C. Zhao, “A heuristic and algorithmic combined approa
ch for reactive power optimization with time-varying load demand in dist
ribution systems,” IEEE Trans. Power Syst., vol.17, no.4, pp.1068- 1072,
VI. CONCLUSION Nov. 2002.
[15] Y. J. Kim, J. L. Kirtley, L. K. Norford, “Reactive power ancillary service
This paper proposes a two-stage (Heuristic search and Vari of synchronous DGs in coordination with voltage control devices,” IEEE
able correction) dynamic reactive power coordinated dispatch Trans on Smart Grid, vol. 8, no. 2, pp.515-527, Mar. 2017.
method to solve the problem of coordinated dispatch and time- [16] W. Yan, J. Yu, D. C. Yu, and K. Bhattarai, “A new optimal reactive pow
er flow model in rectangular form and its solution by predictor corrector
space coupling in the DRPO considering the reactive primal dual interior point method,” IEEE Trans. Power Syst., vol. 21, no.
1, pp. 61-67, Feb. 2006.
[17] A. A. A. Esmin, G. Lambert-Torres and A. C. Z. De Souza, “A hybrid pa
rticle swarm optimization applied to loss power minimization,” IEEE Tr
ans. Power Syst., vol. 20, no. 2, pp. 859-866, May 2005.
[18] Y. Li, M. Li, and Q. Wu, “Optimal reactive power dispatch with wind po 8-318, Dec. 2014.
wer integrated using group search optimizer with intraspecific competitio [19] W. H. E. Liu, A. D. Papalexopoulos, and W. F. Tinney, “Discrete shunt controls in a N
n and levy walk,” J. Mod. Power Syst. Clean Energy, vol. 2. no. 4, pp. 30 ewton optimal power flow,” IEEE Trans. Power Syst., vol. 7, no. 4, pp. 1509-1518, No
v. 1992.
[20] C. Wang, L. Xiang, Z. Deng, et al., “Reactive power optimization dispatc
h strategy in distribution network with distributed generators,” The Journ
al of Engineering, 2017(13): 1418-1422, 2017. Xiaohui Xu received the B.Sc. (Eng.) and Ph.D. degre
[21] L. Zhang, W. Tang, J, Liang, et al., “Coordinated day-ahead reactive pow es in Precision Machinery and Precision Instrumentati
er dispatch in distribution network based on real power forecast errors,” I on from the University of Science and Technology of
EEE Trans. Power Syst., vol. 31, no. 3, pp. 2472-2480, May 2016. China, Hefei, China, in 2003 and 2008, respectively. H
[22] Z. Yang, A. Bose, H. Zhong, et al., “Optimal reactive power dispatch wit e engaged in the postdoctoral work in the Jiangsu Pow
h accurately modeled discrete control devices: a successive linear approx er Company and Southeast University from 2009 to 20
imation approach,” IEEE Trans. Power Syst., vol 32, no. 3, pp. 2435-244 11. He worked at Jiangxi Power Company from 2008 t
4, May 2017. o 2009. Since 2011, he has been employed at China El
[23] T. Ding, Q. Yang, Y. Yang, et al., “A data-driven stochastic reactive pow ectric Power Research Institute (CEPRI). He is the aut
er optimization considering uncertainties in active distribution networks a hor or coauthor of more than 50
nd decomposition method,” IEEE Trans. on Smart Grid, IEEE Early Acc published papers and 3 textbooks. His research interests include smart distribu
ess Articles, 2017. tion grid, grid integration of renewable energy sources and demand response.
[24] S. Liu, J, Zhang, Z. Liu, “Reactive power optimization and voltage contr
ol using an improved genetic algorithm,”//2010 International Conference
on Power System Technology, IEEE/PES and CSEE, pp. 24- 28, Oct. 20
10.
[25] D. H. Cho, J. K. Kin, H. K. Jung, C. G. Lee, “Optimal design of permane
nt-magnet motor using autotuning niching genetic algorithm,” IEEE Tra
ns. Magn., vol. 39, no.3, pp. 1265-1268, May 2003.
[26] D. Karaboga, “An Idea Based on Honey Bee Swarm for Numerical Optim
ization,” Technical Report-TRO6, Erciyes University, Kasyeri, Jan. 2005.
[27] D. Karaboga, B, Basturk, “On the performance of artiflcial bee colony (A
BC) algorithm,” Applied Soft Computing, vol.8, no.1, pp. 687-697, Jan. 2
008.
[28] X. Wang, X. Xu, Q. Sheng Z. Wang and L. Yao, “Novel artificial bee col
ony algorithms for QoS-aware service selection,” IEEE Trans. Services
Computing, IEEE Early Access Articles, 2016.
[29] B. Lami, K. Bhattacharya, “Clustering Technique Applied to Nodal Relia
bility Indices for Optimal Planning of Energy Resources,” IEEE Trans. P
ower Syst., vol. 31, no.6, pp. 4679-4690, Nov. 2016.
[30] Y. Wang, F. Li, Q. Wan, and H. Chen, “Reactive power planning based o
n fuzzy clustering, gray code, and simulated annealing,” IEEE Trans. Po
wer Syst., vol. 26, no. 4, pp. 2246-2255, Nov. 2011.