Sei sulla pagina 1di 37

Operation Manual

for the
EDSplus

S.O. E598018

March 13, 2007


TABLE OF CONTENTS

1. General Description........................................................................................................................3
2. Operator Interface...........................................................................................................................4
3. Start-Up Description: .....................................................................................................................5
4. Acknowledging Alarms & Trips: ...................................................................................................5
5. General Status Screen:....................................................................................................................6
Table 1. Menu Key descriptions.................................................................................................................................. 7
5.1. EDSplus LOG IN Window................................................................................................................................ 8
5.2. Start Permissives ............................................................................................................................................. 9
6. Oil System Detail Screen .............................................................................................................10
7. Header Oil Piping Screen .............................................................................................................12
8. Wash Oil Piping Screen ...............................................................................................................13
9. Dry Gas Seal Screen.....................................................................................................................14
10. HP Dry Gas Seal Screen ...........................................................................................................15
11. MP Dry Gas Seal Screen...........................................................................................................16
12. LP Dry Gas Seal Screen............................................................................................................17
13. Compressor Details Screen .......................................................................................................18
14. HP Compressor Details Screen.................................................................................................19
15. MP Compressor Details Screen ................................................................................................20
16. LP Compressor Details Screen .................................................................................................21
17. Antisurge Controller Screen .....................................................................................................22
18. Motor Bearings Details Screen .................................................................................................23
19. Compressor Bearings Details Screen........................................................................................24
20. Gear Bearings Details Screen ...................................................................................................25
21. Historical Trend Screen ............................................................................................................26
Table 2. Historical Trend Key / Indicator Descriptions ............................................................................................ 29
22. Active Alarms and Trips Screen ...............................................................................................30
23. Real Time Trend Screens..........................................................................................................31
24. Maintenance Screen ..................................................................................................................33
25. Alarm History Screen ...............................................................................................................34
26. Current Operating Data Screens ...............................................................................................35
27. Ethernet Communication Failure Window ...............................................................................36
28. Accessories ...............................................................................................................................37

2
1. General Description
The EDSplus is a networked PLC system designed to monitor engineered products and to present this
information to the operator in an easy to interpret format. An Allen Bradley ControlLogix PLC located
in the Main Panel performs all of the I/O functions. An Industrial PC (IPC) performs the operator
interface functions. Features of the EDSplus include:

First Out Annunciation - When an alarm occurs, the Title Bar on the Screen will flash red. After
acknowledging the alarm, the operator may view the alarms by pressing the Active Alarm and
Trips button to display the Active Alarms & Trips Screen. These will indicate the time and date
of the alarm, the type of alarm (Hi, HiHi, etc.), the Alarm Group for the Tagname and the
tagname of the parameter. The final item in the alarm window gives the status of the alarm
(i.e. Unacknowledged Alarm, Acknowledged Alarm, or Unacknowledged Return to Normal). A
record of all alarm status’s are kept in an alarm log on the hard disk for thirty days after which
time the oldest alarm log file is overwritten by the current days alarm log. Once the alarms are
acknowledged, they are reset when the parameter returns to normal and the Alarm Clear
button is pressed.

Historical Data Trending/Logging - The software on the IPC reads the data collected by
the PLC (via Ethernet) and if the information has changed by more than the log dead band,
stores the information on the hard disk. This information is stored as trend data that can later
be used to plot historical trend charts. The Historical Trend Screen allows the operator to
trend eight selectable inputs versus time. The historical data files will be kept for thirty days
after which the current log file will overwrite the oldest history log file. This older file can be
down loaded to removable media via the Maintenance Screen. If longer term data storage is
desired, it is recommended that the data be monitored by the DCS via the Host Port and
archived by the plant computer

Real Time Data Trending - Two-minute windows of live data provides the operator a means to trend
up to twelve data points simultaneously. This information can be used to observe relationships
between the monitored points.

Remote Data Access (option) - The EDSplus has the capability of transferring information via modem
to service personnel. The service person can download pertinent historical information and
operating parameters so that the proper corrective action can be prescribed. This will help
provide customers with a quick response to their service needs. The modem may be
permanently connected to a phone line or connected as needed.

Host Computer Communication - All information monitored by the EDSplus is made available to a host
computer via serial communications supporting the MODBUS protocol. In addition, alarm set
points may be changed via this link. Refer to Appendix A for MODBUS interface register
information.

3
2. Operator Interface
The EDSplus operator interface consists of a 17" XGA color LCD with touchscreen.
The interface is driven by a PC compatible computer running the operator interface software
package. It communicates with the PLCs via an Ethernet connection. The LCD display operates
independently of the control system and provides for first out annunciation, data acquisition, historical
and real-time trending, and remote communications. The screens include:

General Status Screen


Oil System Detail Screen
Header Oil Piping Screen
Wash Oil Piping Screen
Dry Gas Seal Screen
HP Dry Gas Seal Screen
MP Dry Gas Seal Screen
LP Dry Gas Seal Screen
Compressor Details Screen
HP Compressor Details Screen
MP Compressor Details Screen
LP Compressor Details Screen
Antisurge Controller Screen
Motor Bearings Details Screen
Compressor Bearings Details Screen
Gear Bearings Details Screen
Historical Trend Screen
Active Alarms & Trips Screen
Real Time Trend Screens
Alarm History Screen
Current Operating Data Screens

In addition to the above screens are various "windows" that are used to relay further information to
the operator. These "windows" include:

Maintenance Window
Log In Window
Start Permissives Window
Ethernet Communications Failure Window

4
3. Start-Up Description:
When power is first applied to the panel, various programs are loaded and executed on both the
PLC(s) and the IPC(s) found in the EDSplus. After the initial check out, the LCD will display the
General Status Screen. The other screens can be selected by pressing the button that corresponds
to the screen requested.

4. Acknowledging Alarms & Trips:


Alarm – The alarm action is activated when a monitored parameter has reached an unacceptable but
not critical level of operation. This unacceptable level of operation will be brought to the
attention of the operator for corrective action via the horn, an amber alarm light, and the title
bar on the screen will flash red.
Trip – The trip function is activated by external devices when a monitored parameter has reached a
critical and unsafe level of operation. A trip will also occur when the operator pushes the
Emergency Stop Button located near each unit. The trip function will sound the horn, turn on
the red light and title bar on the screen will flash red.
To acknowledge an alarm, danger or trip, the operator must press the Alarm Acknowledge
button on the Menu. This will silence the horn and the title bar on the screen will stop
flashing and become a steady red color. In the Alarm windows, the text will change from red
to blue to indicate an acknowledged alarm.

Note: If a monitored parameter should momentarily enter an alarm range and return to normal,
the above actions (horn, light) will still occur. The text in the alarm window will be green to
indicate an unacknowledged return to normal. The operator must press the Alarm
Acknowledge button to silence the horn and turn off the light.
A record is kept of when an alarm, danger or trip has occurred, when it was acknowledged,
and when the condition has returned to normal.

5
5. General Status Screen:
The main information screen and the first screen to be displayed after power is applied to the panel is
the General Status Screen (Figure 1).

Figure 1. General Status Screen

As can be seen in Figure 1, near the center of the screen is a simplified mimic diagram of the motor –
gear – compressor string with various indications of measured parameters. Below the equipment
mimics are the lube oil and Bently Nevada 3500 information areas. The system’s pumps and heater
status are also displayed below the mimic.

On the bottom left is the lube oil system information area. This area displays the readings of the
header pressure and lube oil supply pressure and temperature. The current status of the oil heater
and the main and auxiliary lube oil pumps is displayed to the right of this area.

Next to the pump status information is the drive motor start and stop buttons. From this area, the
drive motor may be started or stopped.

6
On the bottom right of the screen is an area titled Bently Nevada 3500. This area displays the status
of the Bently Nevada Vibration and Temperature monitors.

Along the bottom of the screen is the Menu Screen (Figure 2). It consists of two rows of buttons
(rectangles) that correspond to the detail screens indicated on the buttons. Table 1 explains the
operation of these buttons. The Menu Screen is displayed on the bottom of every screen of the HMI.

Figure 2. Menu Screen

Key Description
Active Alarms Displays the Active Alarms & Trips Screen.
and Trips
Alarm History Displays the Alarm History Screen.
General Status Displays the General Status Screen.
Maintenance Displays Maintenance window. (Password protected)
Screen
Oil System Displays the Lube Oil System Detail Screen.
Header Oil Displays the Header Piping Detail Screen.
Oil Seal Details Displays the Oil Seal Details Screen.
Compressor Displays the Compressor Detail Screen.
Details
A-S Controller Displays the Antisurge Controller Detail Screen.
Motor Bearings Displays the Motor Bearings Detail Screen.
Compressor Displays the Compressor Bearings Detail Screen.
Bearings
Gear Bearings Displays the Gear Bearings Detail Screen.
Data Screens Displays the run-time Data Screen #1.
Real Time Trend Displays the Real Time Trend Selection Screen.
Historical Trend Displays the Historical Trend screen.
Start Permissives Displays the parameters that must be met before starting the unit.
(Button will turn RED to indicate permissives not met.)
RESET Used to reset the PLC and Bently Rack. Button will turn RED to
indicate that there is a Trippresent that must be Reset.
Alarm Used to acknowledge alarms. (Silences the horn) Button will
Acknowledge turn RED when there is an unacknowledged Alarm present.
Alarm Clear Used to clear PLC alarms. Button will turn RED to indicate
there is an Alarm present which needs to be cleared.

Table 1. Menu Key descriptions

Along the top of the screen is the Title Bar (Figure 3). Located on the Title Bar is the current logged
on user (Left), Screen Name (Center) and the Time & Date (Right). The Title bar is also an indicator
of Alarm/Trip. The title bar blinks red if there is an unacknowledged Alarm or Trip. If the Title Bar is a
7
solid RED, there is an acknowledged Alarm/Trip present. When there are no Alarms or Trips present,
the Title Bar will appear grey in color.

Figure 3. Title Bar

5.1. EDSplus LOG IN Window

When the unit first powers up, the default User ID is OPERATOR. This allows the user the ability to
operate the unit but little else. If the user wants to change the OPERATOR password or to log in as
MAINTENANCE, it is necessary to select the block in the upper left of the screen’s title bar. This will
display the LOG IN window as shown below (Figure 4).

Figure 4. EDSplus LOG IN Window

Once in the LOG IN window, it is possible to change your password. This is done by pressing the
NEW PASSWORD button. Once this is pressed, it will display the Change Password Window (Figure
5). You can only change a password for the user type that is logged in (e.g. OPERATOR,
MAINTENANCE).

To change the password, enter the current password for the user in the Old Password entry field.
The default password for OPERATOR is “1234”. You must then enter the desired password in the
New Password entry field. To verify the new password, you must re-enter it in the Verify New
Password entry field and click OK. Your new password will now be in effect.

Figure 5. EDSplus Change Password Window

8
5.2. Start Permissives

On the Menu screen is a Start Permissives button which when pressed, will display the Permissives
Start Window (Figure 6). If the start permissives are not met, this button will turn red.

Figure 6. Start Permissives

If a permissive is not met, the circular indicator to the left of the corresponding text will appear blank;
otherwise the indicator will turn green to indicate that the permissive condition has been satisfied.

Once all of the PLC Start Permissives have been met, the PLC shall send a discrete output signal to
the customer’s control room. The status of this “Permissive Start” output signal is shown at the
bottom center of this window.

9
6. Oil System Detail Screen
On the Menu screen is an Oil System button which when pressed, will display the Oil System Detail
Screen (Figure 7). This screen shows a simplified mimic diagram of the lube oil system. If the pump
is running, the pump mimic will be green. Otherwise, it will be black to indicate the pump is not
running. If the pump is alarmed, then the corresponding pump mimic will be red. Other mimics on
this screen include the lube oil system control valve and temperature, pressure, level and differential
pressure transmitters. Nearby each of them are the tag names for the corresponding points along
with the current readings of the measured value (MV) for the transmitters. If the readings are in the
alarm range, the mimic will turn red ( e.g. 54PD448-T and 54T447-T in Figure 7). Otherwise, the
mimic will remain black to indicate a normal operating condition (e.g. 54PD449-T in Figure 7). For the
control valve, a 100% reading means completely open, while a 0% reading means completely closed.

Figure 7. Lube Oil System Detail Screen

The states of the main and aux. oil pumps can be changed from this screen by clicking on their
corresponding buttons. Each pump has a section with Start, Stop and Auto buttons (Figure 8). The
state of the pump can be changed by clicking on the respective button. When the pump is in auto
mode, the Auto button will be yellow. When the pump is not running, all of the buttons will be grey.
The lube oil reservoir heater may also be controlled in this manner.
10
Figure 8. Pump Control Buttons

11
7. Header Oil Piping Screen
On the Menu screen is a Header Oil button which when pressed, will display the Header Oil Piping
Screen (Figure 9). This screen shows a simplified mimic diagram of the header oil piping. Along the
top of the screen are mimics of level and pressure transmitters. Nearby each of them are the tag
names for those points, as well as the current readings of the measured value (MV) for the
transmitter. If the readings are in the alarm range, the mimic will turn red. Otherwise, the mimic will
remain black to indicate a normal operating condition.

Figure 9. Header Oil Piping Screen

12
8. Wash Oil Piping Screen
On the Menu screen is a Wash Oil Piping button which when pressed, will display the Wash Oil
Piping Screen (Figure 10). This screen shows a simplified mimic diagram of the wash oil piping.
Along the top of the screen are mimics of pressure transmitters. Nearby each of them are the tag
names for those points, as well as the current readings of the measured value (MV) for the
transmitter. If the readings are in the alarm range, the mimic will turn red. Otherwise, the mimic will
remain black to indicate a normal operating condition.

Figure 10. Wash Oil Piping Screen

13
9. Dry Gas Seal Screen
On the Menu screen is a Dry Gas Seal Details button which when pressed, will display the Dry Gas
Seal Screen (Figure 11). This screen displays a simplified mimic diagram of the dry gas seal
package and shows the approximate location of the differential pressure and pressure transmitters.
Nearby each of the transmitter mimics are the tag names for those points as well as the current
readings of the measured value (MV). If the readings are in the alarm range, the mimic will turn red.
Otherwise, the mimic will remain black to indicate a normal operating condition.

Along the bottom of the screen are buttons labeled HP, MP, and LP Details. By selecting each
button, the corresponding dry gas seal screen will be displayed.

Figure 11. Dry Gas Seal Screen

14
10. HP Dry Gas Seal Screen
On the bottom of the Dry Gas Seal Screen, there is a Details - HP button which when pressed, will
display the HP Dry Gas Seal Screen (Figure 12). This screen displays a simplified mimic diagram of
the HP dry gas seal package and shows the approximate location of the differential pressure and
pressure transmitters. Nearby each of the transmitter mimics are the tag names for those points as
well as the current readings of the measured value (MV). If the readings are in the alarm range, the
mimic will turn red. Otherwise, the mimic will remain black to indicate a normal operating condition.

The lower left corner of the screen has buttons to access the MP and LP Dry Gas Seal Screens.
There, also, is a button to view the 521-PDIC-1251 PID loop.

Figure 12. HP Dry Gas Seal Screen

15
11. MP Dry Gas Seal Screen
On the bottom of the Dry Gas Seal Screen, there is a Details - MP button which when pressed, will
display the MP Dry Gas Seal Screen (Figure 13). This screen displays a simplified mimic diagram of
the MP dry gas seal package and shows the approximate location of the differential pressure and
pressure transmitters. Nearby each of the transmitter mimics are the tag names for those points as
well as the current readings of the measured value (MV). If the readings are in the alarm range, the
mimic will turn red. Otherwise, the mimic will remain black to indicate a normal operating condition.

The lower left corner of the screen has buttons to access the HP and LP Dry Gas Seal Screens.
There, also, is a button to view the 521-PDIC-1271 PID loop.

Figure 13. MP Dry Gas Seal Screen

16
12. LP Dry Gas Seal Screen
On the bottom of the Dry Gas Seal Screen, there is a Details - LP button which when pressed, will
display the LP Dry Gas Seal Screen (Figure 14). This screen displays a simplified mimic diagram of
the LP dry gas seal package and shows the approximate location of the differential pressure and
pressure transmitters. Nearby each of the transmitter mimics are the tag names for those points as
well as the current readings of the measured value (MV). If the readings are in the alarm range, the
mimic will turn red. Otherwise, the mimic will remain black to indicate a normal operating condition.

The lower left corner of the screen has buttons to access the HP and MP Dry Gas Seal Screens.
There, also, is a button to view the 521-PDIC-1261 PID loop.

Figure 14. LP Dry Gas Seal Screen

17
13. Compressor Details Screen
On the Menu screen is a Compressor Details button which when pressed, will display the
Compressor Details Screen (Figure 15). This screen displays a general view of the various process
readings found on the compressor. The mimic diagrams are used to show the approximate location
of the various control valves. The mimics of the transmitters provide the tagnames and present
readings (MV) at that location. A 100% reading means the valve is fully open, while a 0% reading
means the valve is fully closed.

On the bottom of the screen there are buttons labeled HP, LP and MP. When selecting the proper
button, the corresponding Compressor Details screen will be displayed. When selecting the 521-
FCV-1600 button, the 521-FCV-1600 PID screen is displayed.

Figure 15. Compressor Details Screen

18
14. HP Compressor Details Screen
Along the bottom of the Compressor Details Screen, a Compressor-HP button which when pressed,
will display the HP Compressor Details Screen (Figure 16). This screen displays various process
readings found on the 32M7I Compressor. The mimic diagrams are used to show the approximate
location of the various temperature, pressure and flow sensors. The mimics of the transmitters
provide the tagnames and present readings (MV) at that location. If the readings are in the alarm
range, the mimic will turn red. Otherwise, the mimic will remain black to indicate a normal operating
condition. There is also a mimic of the process valve that reads 0% when fully closed and 100%
when fully open.

On the bottom of the screen there are buttons labeled LP and MP. When selecting the proper button,
the corresponding Compressor Details screen will be displayed.

Figure 16. HP Compressor Details Screen

19
15. MP Compressor Details Screen
Along the bottom of the Compressor Details Screen, a Compressor-MP button which when pressed,
will display the MP Compressor Details Screen (Figure 17). This screen displays various process
readings found on the 38M6I Compressor. The mimic diagrams are used to show the approximate
location of the various temperature, pressure and flow sensors. The mimics of the transmitters
provide the tagnames and present readings (MV) at that location. If the readings are in the alarm
range, the mimic will turn red. Otherwise, the mimic will remain black to indicate a normal operating
condition. There is also a mimic of the process valve that reads 0% when fully closed and 100%
when fully open.

On the bottom of the screen there are buttons labeled LP and HP. When selecting the proper button,
the corresponding Compressor Details screen will be displayed.

Figure 17. MP Compressor Details Screen

20
16. LP Compressor Details Screen
Along the bottom of the Compressor Details Screen is a Compressor-LP button, which when
pressed, will display the LP Compressor Details Screen (Figure 18). This screen displays various
process readings found on the 33MD3-3 Compressor. The mimic diagrams are used to show the
approximate location of the various temperature and pressure sensors. The mimics of the
transmitters provide the tagnames and present readings (MV) at that location. If the readings are in
the alarm range, the mimic will turn red. Otherwise, the mimic will remain black to indicate a normal
operating condition. There are also mimics of a process and control valve that reads 0% when fully
closed and 100% when fully open.

On the bottom of the screen there are buttons labeled HP and MP. When selecting the proper button,
the corresponding Compressor Details screen will be displayed.

Figure 18. LP Compressor Details Screen

21
17. Antisurge Controller Screen
On the Menu screen is an A-S Controller button which when pressed, will display the Antisurge
Controller Screen (Figure 19). The Antisurge Controller Screen gives the operator information to
prevent the system from going into surge. This screen, also, allows the operator to put the Antisurge
valve in safe manual mode. For more information on this screen refer to the Antisurge Control
manual.

Figure 19. Antisurge Controller

22
18. Motor Bearings Details Screen
On the Menu screen is a Motor Bearings button which when pressed, will display the Motor Bearings
Details Screen (Figure 20). This screen details the temperature and vibration of the motor bearings.
The status of the two Bently Nevada 3500 racks is displayed in the box on the right side of the
screen. Along the top of the screen, the temperatures of the motor bearings are displayed. While
along the bottom of the screen, the vibration readings of the motor bearings are displayed.

Figure 20. Motor Bearings Details Screen

23
19. Compressor Bearings Details Screen

On the Menu screen is a Compressor Bearings button which when pressed, will display the
Compressor Bearings Details Screen (Figure 21). This screen details the temperature and vibration
of the compressor bearings. The status of the two Bently Nevada 3500 racks is displayed in the box
on the right side of the screen. Along the top of the screen, the temperature readings of the
compressor bearings are displayed. Along the bottom and on the left side of the screen, the vibration
readings are displayed.

Figure 21. Compressor Bearings Details Screen

24
20. Gear Bearings Details Screen
The Gear Bearings Details Screen (Figure 22) is displayed when the Gear Bearings Button is
pressed. This screen details the temperature and vibration of the gear bearings. The status of the
two Bently Nevada 3500 racks is displayed in the box on the right side of the screen. Along the top of
the screen, the temperature readings of the gear bearings are displayed. On the left side and along
the bottom of the screen, the vibration readings of the gear bearings are displayed.

Figure 22. Gear Bearings Details Screen

25
21. Historical Trend Screen
On the Menu screen is a Historical Trend button which when pressed, will display the Historical
Trend Screen (Figure 23).This screen provides the operator the ablility to trend eight historical data
points versus time. This trend display is located in the center section of the screen. The eight color
lines on the graph represent the output of the corresponding tagname buttons located to the right of
the trend display. Each tagname is represented by the color displayed on the tagname’s respective
button. The tagname button also displays the data point’s value at the start of the trend and data
point’s value at the end of the trend. This is respectively represented by the values displayed on the
left side and right side of the button.

The “Y” axis displays the range of the currently selected data point. The range (0 - 100%) is a
function of each data point’s full-scale output. This permits the simultaneous trending of variables
with widely differing scales (e.g. temperature and pressure). The color of the “Y” axis and hash
marks corresponds to the data point’s range which is currently being displayed. For example, in
Figure 23, the “Y” axis corresponds to 521_XE_1400, which has a scale of 0 – 8,000 RPM. The
operator can view the range for any of the eight data points by pressing the desired tagname button
to the right of the trend display. Alternatively, the operator can, also, toggle through the eight data
point ranges by pressing the “Y” axis until the color of the desired range is displayed.

Figure 23. Historical Trend Screen


26
In order for the operator to change which signals are displayed on the Historical Trend screen, the
operator must first press anywhere inside of the trend display section of the screen. This will cause
Historical Trend Setup window (Figure 24) to be displayed on top of the trend screen.

Figure 24. Historical Trend Setup Window

At this time, the operator can select a particular pen color in order to change its corresponding
tagname. For example, if the operator wants to re-assign pen #3 from the tagname 521_XE_1420 to
some other tagname, the Pen #3 button must first be pressed. This will display the Select Tag
window (Figure 25) on top of the trend screen.

Next, the operator can select the new tagname that they want to correspond with the yellow pen #3
by highlighting the desired tagname and verifying their selection by pressing the OK button. This
new tagname will then appear on the “yellow” tagname button.

27
Figure 25. Select Tag Window

Just below the trend display are two time positioning bars with the starting trend time on the top bar
and the ending trend time on the bottom bar. The positioning bars may be moved to pinpoint a
specific location on the trend graph (Figure 23 & 26). This can be accomplished by selecting the
cursor keys and “dragging” them across the positioning bars. The top bar corresponds to the left
cursor and the bottom bar corresponds to the right cursor. When finished, release the cursor key.
Alternatively, the and buttons (at opposite ends of the time positioning bars) can be utilized to
move the two time position cursor keys. Once the cursors have been moved to the desired position,
the operator can select the Zoom In button to display the newly selected time frame in detail.
Alternatively, the Zoom In button can also be used to reduce the time scale by one-half of the current
value. This will happen if the Zoom In button is pressed while the time positioning cursors are at the
extreme ends of the trend. Conversely, if the Zoom Out button is selected, then the new time scale
will be double the previous value.

In addition to the time positioning bars, the buttons / indicators on the next two rows may also be
utilized to obtain the desired time scaling for the graph. The operator can choose a desired “panning
time” increment “x”, by selecting the 4 Hours, 1 Hour, 30 Minutes or 10 Minutes button.
Alternatively, the operator can select a custom “panning time” (“x”) up to 10,000 minutes by selecting
the Minutes button. The color of the text within the currently selected “panning time” button shall
turn red to indicate that this is the currently selected “panning time”. Once the “panning time” is
selected, and buttons should be pressed to move the respective start and end trend time
in increments of the “panning time”. Table 2 explains the operation of these buttons / indicators.

28
Figure 26. Historical Trend Buttons

The numbers in the description area of Table 2 correspond to the numbers located on the buttons in
Figure 26.
Key / Indicator Description
1 Moves the left edge of the graph by panning time “x” minutes to the
left.
xx:xx:xx 2 Displays time coordinates for left edge of the trend display.
3 Moves the left edge of the graph by panning time x minutes to the
right.
4 Expands the trend to more detail dependant on the position of the
time postioning cursors. If the cursors are at the complete opposite
ends of the trend, the trended time will be cut in half.
5 Displays the current time scale. This is the chart length time between
the left and right edge of the trend display.
6 Contracts the display by doubling the trend’s current time scale.
7 Moves the right edge of the graph by panning time “x” minutes to the
left.
yy:yy:yy 8 Displays time coordinates for right edge of the trend display.
9 Moves the right edge of the graph by panning time “x” minutes to the
right.
10 Sets the “panning time” (“x”) to 4 hours (240 minutes).
11 Sets the “panning time” (“x”) to 1 hour (60 minutes).
12 Moves the entire graph double panning time “x” minutes to the left.
13 Moves the entire graph panning time “x” minutes to the left.
14 Utilized to set the “panning time” (“x”) to a non-standard value (other
than 4 hours, 1 hour, 30 minutes and 10 minutes which are selectable
via dedicated keys). Once the new “panning time” value has been
entered, select OK to verify entry. (Any integer number of minutes
between 1 and 10,000 may be selected.)
15 Moves the entire graph panning time “x” minutes to the right.
16 Moves the entire graph double panning time “x” minutes to the right
17 Sets the “panning time” (“x”) to 30 minutes.
18 Sets the “panning time” (“x”) to 10 minutes.
19 Sets the right edge of the graph to the current time.
20 Saves the current trend data to the filename currently displayed.

Table 2. Historical Trend Key / Indicator Descriptions

29
22. Active Alarms and Trips Screen
On the Menu screen is an Active Alarms and Trips button which when pressed, will display the
Active Alarms and Trips Screen (Figure 27). This screen displays all of the active alarms and trips
that are present on the system. The alarm information is presented in the grey upper section, while
the trip information is displayed in the black lower section. The information shown includes the date
and time of the alarm or trip, the tagname of the point in alarm or trip, the system to which the
tagname is related (e.g. Oil_System) and the state of the alarm (UNACK or ACK). When an alarm
point returns to the normal operating condition, it will be removed from this screen when it is
acknowledged and the Alarm Clear button is pressed. If there is more than one screen’s worth of
alarms or trips, they can be accessed using the Up and Down arrow buttons located on the scroll bars
on the right side of the screen.

Figure 27. Active Alarms Screen

30
23. Real Time Trend Screens
These screens provide the operator the ability to trend up to twelve monitored inputs in real time
(Figure 21). The graph is scaled 0 to 100 percent in order to allow comparisons of inputs with widely
different ranges (e.g. temperature and pressure). The upper left portion of the screen is the trend
display. The color lines represent the output of the tagnames located above the corresponding colors
on the tagname indicators, which are located to the right of the trend display. The current readings
of the tagnames are also displayed within these tagname indicators.

Figure 28. Real Time Trend Screen

Unlike the Historical Trend Screen, the operator cannot change which signals are displayed on the
Real Time Trend Screens. Instead, eleven separate Real Time Trend Screens are utilized, providing
the operator with the ability to monitor the real time behavior of 87 different transmitters. The data on
these screens is divided by equipment groups (Gear Bearing Temperatures, Motor Bearing
Vibrations, etc.).

When the operator selects the Real Time Trend button, the Real Time Trend Selection Screen
(Figure 28) will be displayed.
31
Figure 29. Real Time Trend Selection Screen

The operator can then select the appropriate button adjacent to the desired trend screen description.
For example, by pressing T1 the Real Time Trend Screen corresponding with the Motor Bearing and
Stator Temperatures data will be displayed (refer back to Figure 28).

32
24. Maintenance Screen
On the Menu screen is a Maintenance Screen button which when pressed, will display the
Maintenance Window (Figure 30). The Maintenance window will only be displayed if logged on with
the Maintenance password.

Figure 30. Maintenance Screen


This window provides the operator a means to perform various functions. These functions include:

Restart Modbus Reboots the modbus card in the PLC rack


Close Window Removes Maintenance Window from screen
English Changes the text on the HMI screens to English
Restart Disk Logs Restarts the Disk Logging (History & Alarm)
Set Clock Time & Date adjustment (changes internal clock)
Lamp & Horn Test Performs a three second lamp & horn test
Configure Users Adds users to the system

Historical data file names are made up of the date in which they occurred. The format is
YYMMDD00.lgh where YY is the year, MM is the month, DD is the day, followed by two zeros (00)
and a .lgh extension. If the file is too large to fit on a single 3.5” floppy disk, it is recommended to
burn it to CD-R/RW.
NOTE: It is advisable to only change the clock when the system is initially commissioned.

33
25. Alarm History Screen
On the Menu screen is an Alarm History button which when pressed, will display the Alarm History
Screen (Figure 31). The Alarm History Screen provides the operator with a history of the alarms that
have occurred and a record of setpoint changes. It maintains a chronological record of when an
alarm has occurred, when it was acknowledged, and when it returned to normal. The layout of the
information is similar to that of the Active Alarms and Trips Screen. The difference between the two
is when the alarm value returns to normal, it is not removed from the Alarm History screen. When the
Alarm History screen becomes full, new alarms are added to the bottom of the list and the oldest
alarm is scrolled off the top of the screen. To view alarms that have scrolled off screen, they can be
accessed using the Up and Down arrow buttons to scroll up and down, respectively. The buttons are
located on the vertical scroll bar on the right side of the screen. The Alarm History can maintain up to
1000 events in memory after which the oldest event is overwritten by the newest entry in a scrolling
buffer.

Figure 31. Alarm History Screen

34
26. Current Operating Data Screens
These screens display the current operating conditions as they are being monitored by the EDSplus
(Figure 32). These screens are divided by equipment groups (Motor, Gear, etc.). Within each group,
the data is further organized by type of reading (Temperature, Vibration etc.). This information is
continuously updated by the EDSplus and can be used by the operator to fill out shift reports, etc.
Since there is more than one screen’s worth of data, selecting the Screen 2 button will display the
Screen 2 data screen, selecting the Screen 3 button will display the Screen 3 data screen, and
selecting the Screen 4 button will display the Screen 4 data screen. These buttons are located on
the bottom center area of the screen.

Figure 32. Data Screen

35
27. Ethernet Communication Failure Window
This window appears when the EDSplus detects a fault in the Ethernet communications between the
PLC and HMI computer (Figure 33). If this window appears, the Ethernet fault should be quickly
found and corrected.

Figure 33. Ethernet Communications Failure Window

36
28. Accessories
The EDSplus may be supplied with various pieces of equipment used to provide additional capabilities.
This equipment includes:
Removable Media - There is a 3.5" floppy disk with a storage capacity of 1.44
megabytes (MB) and a CD-RW drive. The floppy disk is the A: drive while the CD-RW disk is
the D: drive. They are located in the IPC and are located behind the front door of the unit. The
disk drives are used to download data for storage and/or as a means to provide a software
upgrade. For more information, refer to the description of the Maintenance Screen.

Modem - This device is used to provide a remote location with a means to access historical data on
the EDSplus. This information can be used as an aid in troubleshooting possible problems with the
equipment operation.

37

Potrebbero piacerti anche