Data sheets: MV / LV transformers

PROYECTO: ISCC Kuraymat


IDENTIFIC.: 15PG-09-BFT-EHP-IME-001 REV.: 1 HOJA 10 DE 12

ITEM DESCRIPTION REQUIRED BY SUPPLIER

58 Cooling consumption Not applied Not applied


Total Losses at 75 ºC: short circuit losses at the
59 power AN and 75 ºC+Iron losses a 105 ºC of the 3005
rated voltage (W)

HEATING AND INSULATION THERMAL


CLASS
Material and type of insulation of primary wiring Cast resin Cast resin
60
6,6 kV (encapsulado) (encapsulated)

Material and type of insulation of secondary Cast resin


61
wiring 0,433 kV (impregnated)

62 Thermal class of insulation MV F F

63 Thermal class insulation of LV F F

64 Maximum temperature of insulation MV (ºC) F(155 ºC)

65 Maximum temperature of insulation LV (ºC) F(155 ºC)

Increment average temperature in the HV


66 windings above ambient temperature, measured 100
by resistance

Maximum temperature of the MV windings at the


67 110
hottest point

Increment average temperature of the LV


68 windings above ambient temperature, measured 100
by resistance

Maximum temperature of the LV windings at the


69 110
hottest point

Reference of the curve of power of transformer


70
depending the external ambient temperature

TAP CHANGER
Manufacturer and regulator type of the off-load
71 Off-load
tap changer
72 Regulation margins in % ±2x2.5% ±2x2,5%

ACCESSORIES

Possibility of installation of fans for forzed


cooling in future (Yes/No)
73 YES Yes
− Drawing with modifications to realize in the
transformer