Sei sulla pagina 1di 2

59.

qcm:

Test Object - Device Settings

Substation/Bay:
Substation: KPS_GT4 Substation address: POWER STATION
Bay: GT4 Bay address:

Device:
Name/description: 59 Manufacturer: Delle Alsthom
Device type: TMV311 Device address: T2
Serial/model number: 01813958
Additional info 1: Un = 100V; Supply Voltage =
125V;
Additional info 2: Setting = 120 V sec; Delay = 1
sec;

Nominal Values:
f nom: 50.00 Hz Number of phases: 3
V nom (secondary): 110.0 V V primary: 11.00 kV
I nom (secondary): 3.610 A I primary: 144.4 A

Residual Voltage/Current Factors:


VLN / VN: 1.732 IN / I nom: 1.000

Limits:
V max: 200.0 V I max: 50.00 A

Debounce/Deglitch Filters:
Debounce time: 3.000 ms Deglitch time: 0.000 s

Overload Detection:
Suppression time: 50.00 ms

Other Device Properties:


Drop-out time: 20.00 ms

Test Module
Name: OMICRON QuickCMC Version: 3.20
Test Start: 13-Mar-2020 18:10:04 Test End: 13-Mar-2020 18:15:33
User Name: Manager:
Company:

Test Results

Title: Setting & Delay

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct V L1-E 69.80 V 0.00 ° 50.000 Hz
V L2-E 69.80 V -120.00 ° 50.000 Hz
V L3-E 69.80 V 120.00 ° 50.000 Hz
Generator Settings
V L1-E 69.800V 0.00° +90°
V L2-E 69.800V -120.00° V L3-E
V L3-E 69.800V 120.00°

V L1-E
180° 0°

V L2-E
80.0 V -90°

Binary Outputs
Name State
Bin. out 1 0
Bin. out 2 0
Bin. out 3 0
Bin. out 4 0

Binary Inputs
Name Slope Time
59_3,4 0->1 1.031s

Analog Inputs
VDCin IDCin
-0.0000V -0.0001mA

Comment
Setting 120 V (ph-Ph) OK;
Delay OK;

Synchronized mode (Synchronization to external signal failed)

Assessment
Passed 13-Mar-2020 18:15:33

Comment
Note:

Summary
1 tests passed, 0 tests failed, 0 tests not assessed 100.00% passed
Test passed

Potrebbero piacerti anche