印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia

Relay protection setting value list

发电机保护屏定值清单
发电机保护屏定值清单 REV2
REV2

Generator protection Panel setting value list REV2


发电机参数 Generator parameters:
15MW 11kV COS∮=0.8(滞后 lag) I1n=985A I2n = 985/300 = 3.28 A
Xd=2.1058 Xd’=0.2294 Xd”=0.1356
CT 1500/5A PT 11/0.1kV
zero sequence CT 50/5,
50/5,该 CT 变比现场应再次实测
The zero sequence CT changes should be measured again
Brushless excitation data :
Generator side 空载励磁电流 No-load excitation current 94.5A
空载励磁电压 No-load excitation voltage 58.6V
Generator side 满载励磁电流 Full-load excitation current 255.9A
满载励磁电压 Full-load excitation voltage 238V
Exciter side 空载励磁电流 No-load excitation current 1.2A
空载励磁电压 No-load excitation voltage 10V
Exciter side 满载励磁电流 Full-load excitation current 6.7A
满载励磁电压 Full-load excitation voltage 70V

一、 NSP711
NSP711 发电机保护定值清单
发电机保护定值清单:
定值清单:
Generator protection setting value list

NSP711
NSP711 Setting List
System parameter
Step setting
Parameter description Display Text Range
size value
TATV parameter
1 Rated frequency Rated Frequency 50, 60 Hz ----- 50Hz
2 Rated Generator Active Power Generator Power 0-1000.0 MW 0.1 MW 15MW
3 Generator power factor Gen.Pow.Factor 0.000-1.000 0.001 0.8
4 Rated primary voltage Gen.Pri.Un 0-500.00 kV 0.01 kV 11KV
5 Generator TV primary value TV Pri. Un 0-500.00 kV 0.01 V 11KV
6 Generator TV secondary value TV Sec Un 0-100.00 V 0.01 V 100V
7 Generator TV zero sequence secondary value Zero.TV Sec Un 0-100.00 V 0.01 V 100V
8 Neutral point TV primary value Neutr. TV. Prim. Un 0-500.00 kV 0.01 kV

第 1 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

9 Neutral point TV secondary value Neutr. TV. Sec Un 0-100.00 V 0.01 V


10 Generator TA primary value Gen.TA Prim. In 0-60000 A 1A 1500A
11 Generator TA secondary value Gen. TA Sec. In 1A,5A 1A 5A
12 Transverse differential TA primary value T.D .TA Prim. In 0-60000 A 1A
13 Transverse differential TA secondary value T.D .TA Sec. In 1A,5A 1A
14 Rotor current rated value Rotor In. 0-60000 A 1A
15 Secondary rated value of current shunt Rotor Div.Sec.Un 0-100.00 mV 0.01mV
238V
16 Rated voltage of excitor Excitation Un 0-600.00 V 0.01V
REV2
17 Voltage connection mode Vol.Connect Type 0-Y type/1-V type ----- Y
Protection function configuration
87 Differential protection Diff.Prot. Open/close OPEN
88 Phase-Phase Fault Protection Ph-Ph Flt.Prot Open/close OPEN
Stator earth protection-current, voltage power OPEN
89 3Io> Stator.E.F. Open/close
direction principle
90 100% stator earth 100% Stator.E.F. Open/close CLOSE
91 Rotor earthed protection Rotor E.F.Prot Open/close OPEN
92 Field-loss protection Field Loss Prot Open/close OPEN
93 Over-excitation protection Over-excitation Open/close OPEN
94 Rotor negative sequence overload Neg.Seq.O.L.Prot Open/close OPEN
95 Voltage protection Voltage Prot. Open/close OPEN
96 Frequency protection Frequence Prot. Open/close OPEN
97 Stator overload Stator O.L.Prot. Open/close OPEN
98 Power protection Power Prot. Open/close OPEN
99 Non-electrical protection Non.Electrical. Open/close OPEN
100 Inter-turn protection Interturn Prot Open/close CLOSE
101 Out-of-step protection Out-of-Step Prot Open/close CLOSE
102 Heat overload protection Thermal O.L. Open/close CLOSE
103 TA fault check TA Fault Check Open/close OPEN
104 TV fault check TV Fault Check Open/close OPEN
Current valid setting value group
105 Current activesetting group Act.Group 1 (A-D)
Only protection function is configured, corresponding protection setting value menu can be entered.If it's not configured,
corresponding protection program module won't be called under DSP program internal processing, and only initialization
function of each protection module is called.
Protection setting value
Differential protection
High-set value differential current protection ON
1 Switch-Id>> On/off
switch
2 Ratio differential current switch Switch-Id> On/off ON
3 Ratio differential protection blocked by TA fault TA Fault Blk Id> On/off ON
4 Pick-up value of high-set differential Protection Id>> Value 1.00 – 20.00 In 0.01In 4
5 Pick-up value of ratio differential protection Id> Value 0.10 – 2.00 In 0.01In 0.2
6 Ratio Differential Current Starting Slope k1 Start Slope k1 0.00 - 0.80 0.01 0.25
第 2 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

7 Ratio Differential Maximal Slope k2 Max Slope k2 0.20 – 1.20 0.01 0.4
Compound voltage over-current protection
8 Over-current stage I switch Switch-I>> On/off ----- ON
9 Compound voltage blocked over-current stage I I>>Blk.by.U</U2> On/off ----- ON
10 Over-current stage II switch Switch-I> On/off ----- ON
11 Compound voltage blocked over-current stage II I>Blk.by.U</U2> On/off ----- OFF
12 Over-current memory function Switch-I> Mem. On/off ----- ON
13 TV break block over-current TV Fail.Blk.OC On/off ----- OFF
14 Impendence Protection Stage 1 Switch Switch-Zp1 On/off ----- OFF
15 Impendence Protection Stage 1 Switch Switch-Zp2 On/off ----- OFF
16 Negative sequence voltage setting value U2> Value 1.00 – 60.00V 0.01V 6V
17 Under voltage setting value U< Value 10.00 –100.00V 0.01V 70V
18 Over-current stage I setting value I>> Value 0.10 –100.00A 0.01A 4A
19 Over-current stage I time delay T-I>> 0.00 – 100.00S 0.01S 0.7S
20 Over-current stage II setting value I> Value 0.10 –100.00A 0.01A 5.25A
21 Over-current stage II time delay T-I>> 0.00 – 100.00S 0.01S 1S
22 Setting Value of Impendence Protection Stage 1 Zp1 0.00 –300.00 Ω 0.01Ω
Reverse Setting Value of Impendence Protection
23 Zp1-Reverse 0.00 –300.00 Ω 0.01Ω
Stage 1
24 Time Delay of Impendence Protection Stage 1 T-Zp1 0.00 – 10.00 S 0.01S
25 Setting value of Impendence Protection Stage 1 Zp2 0.00 –300.00 Ω 0.01Ω
Reverse Setting Value of Impendence Protection
26 Zp2-Reverse 0.00 –300.00 Ω 0.01Ω
Stage 2
27 Time Delay of Impendence Protection Stage 2 T-Zp2 0.00 – 10.00 S 0.01S
Stator earth fault protection--zero sequence current, voltage power direction principle
28 Zero sequence power direction trip switch 3Io>Trip Switch On/off ----- OFF
29 Zero sequence power direction alarm switch 3Io>Alarm Switch On/off ----- OFF
Zero-voltage zero-voltage
/zero-current and
30 Criterion of zero sequence power direction Dir.3Io> Switch -----
/zero-voltage and zero-current
zero-current
31 Zero sequence voltage setting value 3Uo> Value 1.00 – 150.00V 0.01V 10V
80mA 1.5s
32 Zero-sequence current setting value 3Io> Value 50 – 5000mA 1mA
TRIP
0.01
33 Angle between Uo and Io Angle of Uo/Io 0.00 – 360.00 degree
degree
34 Zero-sequence power direction time delay T- Dir.3Io 0.00 – 100.00S 0.01S
Stator earth fault protection-100% stator earth
35 Zero sequence voltage protection alarm switch 3Uo>Alarm Switch On/off ----- OFF
36 Zero sequence voltage protection trip switch 3Uo>Trip Switch On/off ----- OFF
3Harmonic Voltage Ratio of U3e/U3o Protection
37 3 Harm.U3e/U3o. On/off -----
Switch
3Harmonic Voltage Differential Protection
38 3 Harm.Diff. On/off -----
Switch

第 3 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

39 3 harmonic voltage alarm Switch 3 Harm.Vol.Alarm On/off -----


40 3 harmonic voltage trip Switch 3 Harm.Vol.Trip On/off -----
41 Zero sequence voltage setting value 3Uo> Value 1.00 – 20.00V 0.01V
42 Zero sequence voltage high setting value 3Uo>> Value 1.00 – 30.00V 0.01V
43 Zero sequence voltage time delay T-3Uo 0.00 – 100.00S 0.01S
44 Ratio U3e/U3o of 3 Harmonic Before Connection U3e/U3o Bef.Clo. 0.50 – 5.00 0.01
45 Ratio U3e/U3o of 3 Harmonic after Connection U3e/U3o Aft.Clo. 0.50 – 5.00 0.01
46 3 harmonic differential ratio 3 Harm.Diff. Rat. 0.10 – 1.00 0.01
47 3 harmonic protection time delay T-3 Harm Prot. 0.00 – 100.00S 0.01S
Rotor earth fault protection
Rotor One Point Earth Fault Sensitive Alarm ON
48 Rf1.Re<Alarm On/off -----
stage switch
49 Rotor One Point Earth Fault Alarm stage switch Rf1.Re<<Alarm On/off ----- ON
50 Rotor One Point Earth Fault Trip stage switch Rf1.Re<<Trip On/off ----- OFF
51 Two Point Earth Fault Protection switch Rf2.Re< Trip On/off ----- ON
Two Point Earth Secondary Harmonic Voltage OFF
52 2 Harm.Vol. Swi. On/off -----
switch
Sensitive Resistance Setting Value of Rotor One 0.01 20 KΩ
53 Rf1.Re< 0.10 –100.00 KΩ
Point Earth Fault KΩ
Resistance Setting Value of Rotor One Point 0.01 15 KΩ
54 Rf1.Re<< 0.10 –100.00 KΩ
Earth Fault KΩ
55 Time-delay of Rotor One Point Earth Fault T- Rf1 0.00 – 100.00 S 0.01S 3S
56 Position Change of Rotor Two Point Earth Fault Pos.Change Value 1.0% – 10.0% 0.1% 5%
Secondary harmonic voltage setting value of Two
57 2 Harm.Vol.Rf2 0.10 – 10.00 V 0.01V
Point Earth Fault
58 Two point earth time delay T-Rf2.Re< 0.00 - 100.00 S 0.01S 1.5S
Field-loss protection
59 Field-loss protection stage I switch Field-LossⅠSwi. On/off ----- OFF
60 Stage I impedance criterion switch StageⅠZ Swi. On/off -----
61 Stage I rotor voltage criterion switch StageⅠUr Swi. On/off -----
62 Stage I reduce output switch StageⅠR.O. Swi. On/off -----
63 Field-loss protection stage II switch Field-LossⅡSwi. On/off ----- OFF
64 Stage II bus voltage criterion switch StageⅡ Bus Vol.Swi. On/off -----
65 Stage II impedance criterion switch StageⅡ Z Swi. On/off -----
66 Stage II rotor voltage criterion switch StageⅡ Ur. Swi. On/off -----
67 Field-loss protection stage III switch Field-Loss Ⅲ Swi. On/off ----- OFF
68 Stage III impedance criterion switch Stage Ⅲ Z.Swi. On/off -----
69 Stage III rotor voltage criterion switch Stage Ⅲ Ur. Swi. On/off -----
70 Field-loss protection stage IV switch Field-Loss Ⅳ Swi. On/off ----- ON
71 Stage IV impedance criterion switch Stage Ⅳ Z Swi. On/off ----- ON
72 Stage IV rotor voltage criterion switch Stage Ⅳ Ur.Swi. On/off ----- ON
73 Switch of Stage Ⅲ Alarm Stage Ⅲ Alarm Swi. On/off ----- ON
0: static circle/1: 1
74 Circle Impedance Characteristic Im. Circle Char. 1
asynchronous circle
第 4 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

75 Reverse Reactive Power switch Reverse Q Swi. On/off ----- ON


76 Impedance setting value 1 Z1 Value 0.00 -300.00Ω 0.01Ω 2Ω
77 Impedance setting value 2 Z2 Value 0.00 -300.00Ω 0.01Ω 45Ω
78 Reserve Reactive Power setting Value Reverse Q 0.01 – 50.00% 0.01% 2%
41V
79 Under Voltage Setting Value of Rotor Rotor Ur< 1.0 –1000.0V 0.1V
REV2
58.6V
80 Non-load Voltage of Rotor Rotor No-load Vol. 1.0 –1000.0V 0.1V
REV2
81 Under Voltage Ratio of Rotor Ratio of Ur< 0.10 – 10.00 0.01 0.1
82 Power of Generator Salient Pole Gen.Salient Pole Pow. 0.00 – 30.00% 0.01%
83 Under Voltage Setting Value U< Value 10.00 –100.00V 0.01V
84 Power Setting Value of Reduce Output Reduce Output P< 10.00 – 100.00% 0.01%
85 Time-delay of Stage Ⅰ T-StageⅠ 0.00 – 100.00S 0.01S
86 Time-delay of Stage Ⅱ T-Stage Ⅱ 0.00 – 100.00S 0.01S
87 Time-delay of Stage Ⅲ T-Stage Ⅲ 0.00 – 100.00S 0.01S 0.5S Alarm
0.01 0.03min Trip
88 Time-delay of Stage Ⅳ T-Stage Ⅳ 0.00 – 600.00 minute
minute
Over-excitation protection
89 Time limited stage I switch V/f>> Swi. On/off ----- ON
90 Time limited stage II switch V/f> Swi. On/off ----- ON
91 Alarm stage on/off V/f Alarm Swi. On/off ----- ON
92 Inverse time limited stage on/off Inverse T.L V/f Swi. On/off ----- OFF
93 Time limited stage I V/f V/f>> Value 1.00 – 2.00 0.01 1.2
Time-delay of Over Excitation Setting Value 5S
94 T-V/f>> 0.0 – 6000.0 0.1S
Setting Value Stage 1
Over Excitation Setting Value Setting Value 1.4
95 V/f> Value 1.00 – 2.00 0.01
Stage Ⅱ
Time-delay of Over Excitation Setting Value 1S
96 T-V/f> 0.0 –6000.0 0.1S
Setting Value Stage Ⅱ
97 Over Excitation Alarm Setting Value V/f Alarm. Value 1.00 – 2.00 0.01 1.1
98 Time-delay of Over Excitation Alarm T-V/f Alarm 0.0 – 6000.0 S 0.1S 10S
Upper Limit Over Excitation Setting Value of
99 U.L.Val.Inverse.V/f 1.00 – 2.00 0.01
Inverse Time Limited
Time-delay of Inverse Time Limited Upper Limit
100 T-U.L.Inverse. V/f 0.0– 6000.0 S 0.1S
Over Excitation
Over Excitation Point 1 Setting Value of Inverse
101 V/f1 Inverse.T.L 1.00 – 2.00 0.01
Time Limited
Time-delay of Inverse Time Limited Over
102 T-V/f1 Inverse 0.0 – 6000.0 S 0.1S
Excitation Point 1
Over Excitation Point 2 Setting Value of Inverse
103 V/f2 Inverse.T.L 1.00 – 2.00 0.01
Time Limited
Time-delay of Inverse Time Limited Over
104 T-V/f2 Inverse 0.0 – 6000.0 S 0.1S
Excitation Point 2
105 Over Excitation Point 3 Setting Value of Inverse V/f3 Inverse.T.L 1.00 – 2.00 0.01

第 5 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

Time Limited
Time-delay of Inverse Time Limited Over
106 T-V/f3 Inverse 0.0 – 6000.0 S 0.1S
Excitation Point 3
Over Excitation Point 4 Setting Value of Inverse
107 V/f4 Inverse.T.L 1.00 – 2.00 0.01
Time Limited
Time-delay of Inverse Time Limited Over
108 T-V/f4 Inverse 0.0 – 6000.0 S 0.1S
Excitation Point 4
Over Excitation Point 5 Setting Value of Inverse
109 V/f5 Inverse.T.L 1.00 – 2.00 0.01
Time Limited
Time-delay of Inverse Time Limited Over
110 T-V/f5 Inverse 0.0 – 6000.0 S 0.1S
Excitation Point 5
Over Excitation Point 6 Setting Value of Inverse
111 V/f6 Inverse.T.L 0.50 – 2.00 0.01
Time Limited
Time-delay of Inverse Time Limited Over
112 T-V/f6 Inverse 0.0 – 6000.0 S 0.1S
Excitation Point 6
Lower Limit Over Excitation Setting Value of
113 L.L.Val.Inverse. V/f 1.00 – 2.00 0.01
Inverse Time Limited
Time-delay of Inverse Time Limited Lower Limit
114 T-L.L.Inverse. V/f 0.0 – 6000.0 S 0.1S
Over Excitation
Rotor negative sequence over-load protection
Negative Sequence Over Load Current Trip Stage ON
115 I2>> Trip. Swi. On/off -----
Ⅰ switch
Negative Sequence Over Load Current Trip Stage ON
116 I2> Trip. Swi. On/off -----
Ⅱ switch
Negative Sequence Over Load Current Alarm ON
117 I2 Alarm Swi. On/off -----
switch
Negative Sequence Over Load Current Trip of OFF
118 Inverse.T.L I2 Swi. On/off -----
Inverse Time Limited switch
Negative Sequence Over Load Current Setting 1.64A
119 I2>> Value 0.10 –100.00 A 0.01A
Value of StageⅠ
Time-delay of Negative Sequence Over Load 2S
120 T-I2>> 0.00 – 100.00 S 0.01S
Current of StageⅠ
Negative Sequence Over Load Current Setting 1A
121 I2> Value 0.10 –100.00 A 0.01A
Value of StageⅡ
Time-delay of Negative Sequence Over Load 4S
122 T-I2> 0.00 – 100.00 S 0.01S
Current of StageⅡ
Negative Sequence Over Load Alarm Current 0.3A
123 I2 Alarm Value 0.10 –100.00 A 0.01A
Setting Value
Time-delay of Negative Sequence Over Load 0.5S
124 T-I2 Alarm 0.00 – 100.00 S 0.01S
Alarm
Starting Negative Sequence Over Load Current
125 Inverse.T.L. I2 0.10 – 10.00 A 0.01A
Setting Value of Inverse Time Limited
Long-Time Permitting Negative Sequence Over
126 Long-Time I2 0.10 – 10.00 A 0.01A
Load Current Value of Generator

第 6 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

Time-delay of Upper-Limit I2 Inverse Time


127 T-U.L.Inverse T.L.I2 0.00 – 100.00 S 0.01S
Limited
Heat Constant of Negative Sequence Over Load
128 Rotor N.Seq.Heat Con. 1.00 - 100.00 0.01
Current of Rotor
Voltage protection
129 Switch of Over Voltage Setting Value of Stage Ⅰ U>> Swicth On/off ----- ON
130 Switch of Over Voltage Setting Value of Stage Ⅱ U> Swicth On/off ----- ON
131 Switch of Under Voltage setting Value U< Swicth On/off ----- OFF
132 Over voltage stage I setting value U>> Value 10.0 –170.00 V 0.01V 115V
133 Over voltage stage I time delay T-U>> 0.00 – 100.00 S 0.01S 3S
134 Over voltage stage II setting value U> Value 10.0 –170.00 V 0.01V 125V
135 Over voltage stage II time delay T-U> 0.00 – 100.00 S 0.01S 0.5S
136 Under voltage setting value U< Value 10.0 –100.00 V 0.01V
137 Under voltage time delay T-U< 0.00 – 100.00 S 0.01S
Frequency protection
138 Switch of Under Frequency of Stage Ⅰ f<ⅠAlarm Swi. On/off ----- ON
139 Switch of Under Frequency Trip of Stage Ⅰ f<ⅠTrip Swi. On/off ----- OFF
140 Switch of Under Frequency of Stage Ⅱ f<Ⅱ Alarm Swi. On/off ----- OFF
141 Switch of Under Frequency Trip of Stage Ⅱ f<ⅡTrip Swi. On/off ----- OFF
142 Switch of Under Frequency of Stage Ⅲ f<Ⅲ Alarm Swi. On/off ----- OFF
143 Switch of Under Frequency Trip of Stage Ⅲ f<Ⅲ Trip Swi. On/off ----- ON
144 Switch of Under Frequency of Stage Ⅳ f<Ⅳ Alarm Swi. On/off ----- OFF
145 Switch of Under Frequency Trip of Stage Ⅳ f<ⅣTrip Swi. On/off ----- OFF
146 Switch of Over Frequency of Stage Ⅰ f>ⅠAlarm Swi. On/off ----- ON
147 Switch of Over Frequency Trip of StageⅠ f>ⅠTrip Swi. On/off ----- OFF
148 Switch of Over Frequency of Stage Ⅱ f>ⅡAlarm Swi. On/off ----- OFF
149 Switch of Over Frequency Trip of StageⅡ f>ⅡTrip Swi. On/off ----- ON
150 Under Frequency Setting Value Stage Ⅰ f<ⅠValue 45.00 – 50.00 Hz 0.01Hz 49
0.01 30min
151 Time-delay of Under Frequency Stage Ⅰ T- f<Ⅰ 0.00 –300.00 minute
minute
152 Under Frequency Setting Value Stage Ⅱ f<Ⅱ Value 45.00 – 50.00 Hz 0.01Hz
0.01
153 Time-delay of Under Frequency Stage Ⅱ T- f<Ⅱ 0.00 –300.00 minute
minute
154 Under Frequency Setting Value Stage Ⅲ f<Ⅲ Value 40.00 – 50.00 Hz 0.01Hz 46.5
155 Time-delay of Under Frequency Stage Ⅲ T- f<Ⅲ 0.00 –100.00 S 0.01S 1.2S
156 Under Frequency Setting Value Stage Ⅳ f<Ⅳ Value 40.00 – 50.00 Hz 0.01Hz
157 Time-delay of Under Frequency Stage Ⅳ T- f<Ⅳ 0.00 –100.00 S 0.01S
158 Over Frequency setting Value Stage Ⅰ f>ⅠValue 50.00 – 55.00 Hz 0.01Hz 50.5
0.01 30min
159 Time-delay of Over Frequency Stage Ⅰ T- f>Ⅰ 0.00 –300.00 minute
minute
160 Over Frequency setting Value Stage Ⅱ f>ⅡValue 50.00 – 55.00 Hz 0.01Hz 51
161 Time-delay of Over Frequency Stage Ⅱ T- f>Ⅱ 0.00 –100.00 S 0.01S 1.2s
Stator Over Load Protection
162 Definite Time Overload Trip Stage Switch D.T.OL.Trip Swi. On/off ----- OFF
第 7 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

163 Definite Time Overload Alarm Stage Switch D.T.OL.Alarm Swi On/off ----- ON
164 Inverse Time Overload Trip Stage Switch I.T.OL.Trip Swi. On/off ----- OFF
165 Stator Overload Current Trip Setting Value O.L.Trip Value 0.10 –100.00 A 0.01A
166 Stator Overload Current Trip Time Delay T-O.L.Trip 0.00 – 100.00 S 0.01S
167 Overload Current Alarm Setting Value O.L.Alarm Value 0.10 –100.00 A 0.01A 4A
Time-delay of Overload Current Alarm Setting 9S
168 T-O.L. Alarm 0.00 – 100.00 S 0.01S
Value
Stator Overload Current Setting Value of Inverse
169 O.L.Inverse T.L.Value 0.10 – 10.00 A 0.01A
Time Limited
Time-delay of Upper-Limit Current for Inverse
170 T-U.L.Inverse T.L. 0.00 – 100.00 S 0.01S
Time Limited
171 Heat Capacity of Stator Stator Wind.Heat Cap. 1.00 –100.00 0.01
172 Heat loss effect factor Heat-Dissipation Fact. 0.10 - 2.00 0.01
Power protection
173 Reverse Power Stage Alarm Switch Rev.Power Alarm Swi. On/off ----- ON
174 Reverse Power Stage Trip Switch Rev.Power Trip. Swi. On/off ----- ON
175 Program Reverse Power Stage Trip Switch P.Rev.Power Trip Swi. On/off ----- OFF
176 Reverse Power Setting Value Rev.Power Value 1.00 – 10.00 % 0.01% 2%
177 Time-delay of Reverse Power Alarm T-Rev.Power Alarm 0.00 – 100.00 S 0.01S 0.5S
178 Time-delay of Reverse Power Trip T-Rev.Power Trip 0.00 –600.00 S 0.01S 3S
179 Program Reverse Power Setting Value P.Rev.Power Val. 1.00 – 10.00 % 0.01%
180 Time-delay of Reverse Power in Program T-P.Rev.Power 0.00 – 100.00 S 0.01S
Non-electricity protection
181 Themotechnical protection Switch Themo.Prot. Swi. On/off ----- ON
182 Water-break protection Switch Water Brk.Prot. On/off ----- OFF
183 Excitation system fault protection Switch Excit.Flt. Prot. On/off ----- ON
184 Reserved non-electricity protection Switch Non.Elect.1 Swi. On/off ----- OFF
185 Themotechnical protection time delay T-Themo.Prot. 0.00 – 6000.0 S 0.1S 0.2S
186 Water-break protection time delay T-Water Brk.Prot 0.00 – 6000.0 S 0.1S
187 Excitation system fault protection time delay T-Excit.Flt.Prot 0.00 – 6000.0 S 0.1S 0.2S
188 Reserved non-electricity protection time delay T-Non.Elect.1 0.00 – 6000.0 S 0.1S
Interturn protection
Transverse differential current high setting value OFF
189 Id_t>> Prot.Swi. On/off -----
stage switch
Transverse differential current ratio protection
190 Id_t> Prot.Swi. On/off -----
switch
Longitudinal Zero sequence voltage high setting
191 3Uo_l>> Prot.Swi On/off -----
value stage switch
Longitudinal Zero sequence voltage ratio
192 3Uo_l> Prot.Swi. On/off -----
protection switch
Longitudinal Zero sequence voltage protection
193 3Uo_l Res.by Iph On/off -----
restraint by phase current
Longitudinal zero sequence voltage protection
194 3Uo_l Blk.by I2 Dir. On/off -----
blocked by negative-sequence direction

第 8 页 共 9 页
印尼 Sinergy Power Plant 热电厂 Sinergy Power Source Power Plant, Indonesia
Relay protection setting value list

195 Transverse differential current high setting value Id_t>> Value 0.10 –50.00 A 0.01A
Pick-up Value of transverse differential ratio
196 Id_t> Value 0.10 –50.00 A 0.01A
protection
197 Slope of transverse differential ratio protection Slope of Id_t> 0.10 –10.00 0.01
198 Transverse differential time delay T- Id_t Prot. 0.00 – 100.00S 0.01S
Longitudinal zero sequence voltage high setting
199 3Uo_l>> Value 0.10 – 20.00V 0.01V
value
Pick-up Value of longitudinal zero sequence
200 3Uo_l> Value 0.10 – 20.00V 0.01V
voltage ratio protection
Slope of longitudinal zero sequence voltage ratio
201 Slope of 3Uo_l> 0.10 – 10.00 0.01
protection
202 Longitudinal zero sequence voltage time delay T- 3Uo_l Prot. 0.00 – 100.00S 0.01S
Out-of-step protection
203 External out-of-step alarm switch Ext.Out-of-step Alarm On/off ----- OFF
204 External out-of-step trip switch Ext.Out-of-step Trip On/off -----
205 Internal out-of-step alarm switch Int.Out-of-step Alarm On/off -----
206 Internal out-of-step trip switch Int.Out-of-step Trip On/off -----
207 Impedance setting value ZA ZA Value 0.00 –100.00Ω 0.01Ω
208 Impedance setting value ZB ZB Value 0.00 –100.00Ω 0.01Ω
209 Impedance setting value ZC ZC Value 0.00 –100.00Ω 0.01Ω
210 Sensitive angle Sensitive angle 60.00 – 90.00° 0.1°
211 Lens internal angle Lens Int. Angle 60.00 – 150.00° 0.1°
212 External slip pole cross times Ext.Cross Times 1-1000 1
213 Internal slip pole cross times Int.Cross Times 1-1000 1
214 Trip permitting current Curr.of Permit. Trip 1.00 – 50.00 0.01A
Heat overload protection
215 Thermal overload trip stage switch Thermal OL Trip Swi. On/off ----- OFF
216 Thermal overload alarm stage switch Thermal OL Alarm Swi. On/off -----
217 Thermal overload pickup current P.U.Val.of OL 0.1~100 0.01A
218 Thermal overload time constant T-Constant 60s~3000s 1s
219 Pick-up of Thermal overload alarm stage P.U.Val.of OL Alarm 0.50~0.99 0.01
220 Negative-sequence current effect factor I2 Effect Factor 3.00~10.00 0.01

第 9 页 共 9 页