REINFORCEMENT AT PIPE PENETRATIONS THROUGH

TS-COL-01
STEEL COLUMN
d
3589

MAX
1370

d/3

532
50 (2")
TYP

PLATE TO MATCH COLUMN


WEB THICKNESS AT EACH SIDE
EQ
1795
EQ
1795
JAN 2017
PROVISION FOR FUTURE STEEL COLUMN EXTENSION TS-COL-02

CL

FUTURE STEEL COLUMN

20 (3/4") THICK PLATE


25 (1") MIN CONNECT TO COLUMN BELOW
FOR FULL COLUMN TENSILE CAPACITY
604

ALL AROUND
TOP OF CONCRETE SLAB/
STEEL ROOF DECK
(AS APPLICABLE)
OCT 2016
ANCHORAGE OF ABUTTING MASONRY
TS-COL-03
WALLS TO STEEL COLUMNS

STEEL COLUMNS
COL WEB
OR FLANGE
38 (1 1/2") x 5 (1/4") PLATE @ 800 (2'-8")
AT MASONRY JOINTS.
400 (1'-4") STRAP ANCHORS SUPPLIED
BY STRUCT. STEEL TRADE
04

U/N
(2")
50 753

100 (4")

50 (2") x 12 (1/2") x 3 (1/8") BAR


13

CHANNELS
x 50 (2") LONG WELDED TO COLUMN
12 02

(1/2") WELD TO FLANGE FOR


CORNER COLUMNS AND WHERE
ORIENTATION OF COLUMNS IS
OCT 2016

REVERSED
WIND COLUMNS WITH VERTICALLY SLOTTED
TS-COL-04
CONNECTION
FLOOR OR ROOF (TYP)

PERIMETER WALL
(TYP)

VERTICALLY SLOTTED HOLES TO BEAM OR JOIST


ALLOW FOR DEFLECTION. NUTS TO (TYP)
BE FINGER TIGHT WITH THREADS
BURRED. SEE DETAIL 'X' (TYP).


FOR HORIZONTAL MEMBER AND DECK

180
ATTACHMENT SEE PLANS AND SECTIONS
W COLUMN (WHERE APPLICABLE)
L 89x89x6.4 Af=±100kN (UNLESS
OTHERWISE NOTED ON DRAWINGS
A1 TYP)

END PLATE
∆ 081
∆ 281

W OR HSS COLUMN

A2 ∆ 042

BOLT POSITION
51

∆/2 AT ROOF FOR DETAILING


BEAMS ONLY;
ZERO AT FLOOR
BEAMS

COPE AND EXTEND IF REQUIRED


FOR CLADDING SUPPORT
∆ 521

W OR HSS COLUMN
∆ 146

A3

A DECK PERPENDICULAR TO BUILDING EDGE

UNLESS NOTED OTHERWISE NOTED ON


MIN 1200 (4'-0") DRAWINGS, ADD HSS 203x203x8 BETWEEN
4186

JOISTS / BEAMS. LOCATE AT JOIST NODES.

JOISTS OR BEAMS BEYOND


AND BEHIND

AS SHOWN IN A1, A2 OR A3.

B DECK PARALLEL TO BUILDING EDGE


JAN 2017

DEFLECTION GAP '∆' = 25 (1") UNLESS OTHERWISE NOTED ON DRAWINGS