F.A.I.

TOTAL SHEET
SECTION COUNTY
RTE. SHEETS NO.

74 * CHAMPAIGN 93 39
STEEL FOUNDATION CONCRETE FOUNDATION
STA. TO STA.

LIGHT POLE BOLT CIRCLE SHAFT SHAFT SHAFT SHAFT ANCHOR ROD FED. ROAD DIST. NO. ILLINOIS FED. AID PROJECT
TOP PLATE (min)
MOUNTING HEIGHT DIAMETER DIAMETER DEPTH DIAMETER DEPTH LENGTH 1 * (10,92-8 HB-1)BR
CONTRACT NO. 70695
9.1 m
< 292 220 1.83 m 300 x 300 x 25 610 1.52 m 1.45 m
(30’) (11.5) (8 5/8 ) (6’) 12 x 12 x 1 (24) (5’-0") (4’-9")
9.4 m - 10.7 m 292 220 1.83 m 300 x 300 x 25 610 1.67 m 1.60 m
(31’-35’) (11.5) (8 5/8 ) (6’) 12 x 12 x 1 (24) (5’-6") (5’-3")
610 (24) min. dia. with
10.9 m - 12.2 m 381 220 1.83 m 375 x 375 x 31 762 1.83 m 1.75 m Or
292 (11.5) bolt circle
(36’-40’) (15) 3 (8 5/8 ) (6’) 2 15 x 15 x 1 1/4 (30) (6’-0") (5’-9")
762 (30) min. dia. with
12.5 m - 13.7 m 381 220 1.83 m 375 x 375 x 31 762 1.98 m 1.90 m
2 15 x 15 x 1 1/4 381 (15) or 432 (17)
bolt
(41’-45’) (15) 3 (8 5/8 ) (6’) (30) (6’-6") (6’-3")
circle
14.0 m - 15.2 m 381 220 2.44 m 375 x 375 x 31 762 2.13m 2.00 m
(46’-50’) (15) 3 (8 5/8 ) (8’) 15 x 15 x 1 1/4 (30) (7’-0") (6’-9") 125 (5)
I.D.
Pole Foundation Setback:
1 Length does not include100 (4)
hook P.V.C. wiring
2 220 mm x 2.44 m (8 5/8 "x
for8’-0")
Twin luminaires window
For horizontal mounted luminaires, setback
3 Bolt circle diam. shall be
430 (17)when a TB3-17 transformer base is used shall 6.1 m (20’)from edge
be a minimum of
Plate to be of pavement.
installed when
required (See ring For vertical mount luminaires, setback shall
plate detail) 9 m
be a minimum of (30’) from edge of
pavement. Poles shall be located 1.5 m (5’)
Bolt circle 75 (3)
Min. concrete cover behind guardrail or other protective
Length above foundation
diameter Fill with fine on all steel barriers, or as directed by the Engineer.
shall be adjusted to accomodate
(See table) aggregate
breakaway devices furnished by
Anchor rod 230 (9) threads.
25 (1) diameter with
the contractor for a specific
Anchor rod shall extend through nut 25 (1) .
installation.
For barrier or foundation behind guardrail, use
self-locking nut and flat washer. Do not use lock washer.

Wireway location identification


19 ( 3/4 ) Chamfer
marks shall be notched in side
of plate or stamped on top. Varies
Finished grade

Formed
(24) min.

(15)
Finished

Anchor rod length (See table)

381
grade

Shaft dia.

610
Use dirt removed from
(See table)
305
(12)

foundation to meet

Shaft depth (See table)


Two, 65x305 (2 1/2 x12)
1.52m (5 ft.)
chord
wiring windows
(24)
610

fill around foundation


180 apart Pole Setback
top. Grade dirt level
with bottom of concrete 125 I.D. P.V.C.
(5)
Shaft depth (See table)

chamfer. wireway window. Notes:


Fill with fine
aggregate 1) Wireway may be on front, back or side of foundation as required
6( 1/4 ) Thick min. by the trenching. Place door of transformer base on wireway side
4 If the required anchor rod length to minimize the number of unit duct bends.
above top of foundation is less than
75 (3)
, anchor rods may be lowered 2) Top of schedule 40 125 I.D.
(5) PVC wiring window, shall
380 (15) O.D.
150 (6) .
below #6 Bare be flush with the top of foundation for drainage.
450 (18) O.D.
508 (20) O.D. copper
wire 3) All foundations are designed to be located on slopes not exceeding
2:1 where soils have an unconfined compressive strength of at
least 1.0 TSF. The contractor shall verify the soil strength during
drilling for concrete foundations or by monitoring installation
150 min. resistance on steel foundations and notify the engineer if other
conditions are encountered.
230 (9)
I.D. with292 (11.5)
bolt circle (6)
305 (12)
I.D. with381 (15) bolt circle 4) Anchor rod shall be increased31to
(1 1/4 ) 15.24
diameter for (50’)
Cutting Or Helix & I.D. with432 (17)bolt circle
356 (14) mounting height or above.
4

teeth pilot point


TOP VIEW
5) TB3-17 transformer base is not to be used on metal foundation
Cast bronze clamp See Ring
All dimensions are in millimeters (inches)
( 1/4 )
6

Plate Detail
STEEL FOUNDATION unless otherwise shown.
16 mm x 3 m ( 5/8 "x 10’)
Copperclad grounding
DATE REVISIONS
electrode. When foundation
is set in rock, install ground 10/7/02 Bridge Office depth calc. LIGHT POLE
electrode in cable trench.
RING PLATE DETAIL FOUNDATION
(When rock is encountered
and foundation is shallower)
CONCRETE FOUNDATION

LGT007-836