Sei sulla pagina 1di 21

Concealed Chilled Water

Fan Coil Units


CWX Series
CWX02 thru CWX14
200 CFM thru 1400 CFM
Company Business
Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabia
and today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.

Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.

The company’s operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and
service brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:


1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance,
retrofit & operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHU’s.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operations
from the corporate headquarters in Dammam, Saudi Arabia.

Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.

Factories and Productions


Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facility
in Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard Organization)
Certificate for Room Air Conditioners. ZAC’s products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (Certified Performance)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)
7. ASME (American Quality of Mechanical Engineers)

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed
bin Fahd Al Saud Award for Factory Safety.

Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Condition-
ers manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the
Concealed Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin
Air Handling Units up to 138,316 CFM and the Water Chillers up to 500 TR cooling capacity.
INDEX
Contents Page

Model decoding ........................................................................................................................................ 2

Unit features ............................................................................................................................................. 2

Standard specifications ......................................................................................................................... 2-3

Options ..................................................................................................................................................... 3

Physical data ............................................................................................................................................ 4

Cooling capacities ................................................................................................................................. 5-8

Fan performance data ......................................................................................................................... 9-10

Sound power data .................................................................................................................................. 11

Hot water capacities ............................................................................................................................... 11

Unit dimensions ...................................................................................................................................... 12

Coil connection dimensions .................................................................................................................... 13

Heater box dimensions & arrangements ................................................................................................ 14

Valve packages ...................................................................................................................................... 14

Typical schematic wiring diagram ...................................................................................................... 15-16

Installation .............................................................................................................................................. 17

Electrical ................................................................................................................................................. 17

Maintenance ........................................................................................................................................... 17

Recommended spare parts .............................................................................................................. . 17

Parts list ................................................................................................................... ......................... 18

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1
MODEL DECODING
1, 2 & 3 4&5 6 7 8 9 10 11 12 13
BASIC (SERIES) SIZE ELECTRICAL COIL HEATER ACCESSORIES FIN COIL FILTER OPTION
(x 100 CFM) SUPPLY (V-Ph-Hz) CONNECTION
CWX 02 C : 208/230-1-60 A : 3 ROW CHILLED N : NO HEATER N : STANDARD A : ALUMINUM R : RH SIDE, N : NONE N : STANDARD
HORIZONTAL WATER B : 1 kW FIN STANDARD UNIT
03 D : 2 kW B : 3D VALVE PACKAGE (FACING AIR A : ALUMINUM, (WITHOUT
CONCEALED B : 4 ROW CHILLED E : 3 kW
(COOL ONLY) B : COATED DISCHARGE) 1/2" THICK THERMO-
CHILLED WATER F : 4 kW
04 ALUMINUM STAT)
WATER FAN J : 3 ROW CHILLED G: 5 kW K : 4D VALVE PACKAGE FIN L : LH SIDE, C : SYNTHETIC,
COIL UNITS 06 WATER + 1 ROW N : NO HEATER (HEAT & COOL) OPTIONAL 1/2" THICK T : UNIT WITH
HEATING C : COPPER FIN (FACING AIR (OPTION) THERMO-
08 D : 2 kW DISCHARGE) STAT
E : 3 kW
10 F : 4 kW
G: 5 kW
12
J : 7 kW
14 M: 10 kW

UNIT FEATURES
LOW HEIGHT UNITS
Good for spaces with low ceiling height.

COMPACT DIMENSIONS
Ideal to fit into tight spaces.

EASY MAINTENANCE / ONE SIDE ACCESS


Filters can be easily removed by sliding. Piping and controls are on one side for easy access.

BACK AND BOTTOM RETURN AIR OPTIONS


SINGLE COIL FOR RH & LH APPLICATIONS (FIELD CHANGEABLE FOR RH & LH APPLICATIONS)
SPLIT COILS, CHILLED + HOT WATER OPTIONS
VALVE PACKAGES FOR 2 PIPE & 4 PIPE SYSTEMS
WIDE RANGE OF HEATER SIZES
QUIET, PULSE FREE AIR DELIVERY
Centrifugal fans that are statically and dynamically balanced, handle up to 0.5" w.g. external static pressure allowing you
to keep the unit away from your comfort zone.

STANDARD SPECIFICATIONS
UNIT CONSTRUCTION
These units are fabricated of heavy gauge galvanized steel to ensure lasting durability and dependable performance with
minimum maintenance. The panels are insulated to provide positive protection against sweating and maximum damping
of air noise.
This unit is designed for those concealed overhead installations which require supply ductwork. A 1" duct collar is
provided into the front panel for supply air duct connection. The standard arrangement provides return air from the rear
side. This arrangement may be reversed to provide bottom return air by simply interchanging the bottom and rear panel.
This reversal can be easily accomplished in the field.
Access to the blower motor assembly is provided through the removable bottom panel from where the complete fan/
motor can be removed for servicing.
FANS
The centrifugal, forward curved, double width fan wheels are statically and dynamically balanced for quiet and smooth
performance. Blower housing is rugged galvanized steel to provide added rigidity and assure quiet & smooth operation.

2
MOTORS
Motors are permanent split capacitor type with three speed windings and built-in thermal overload protection. The bear-
ings are of sleeve type.
FILTERS
All models are furnished with 1/2" thick permanent washable type aluminum filters as standard.
COILS
Coils are 3/8" OD copper tubing, constructed of enhanced copper tubes and mechanically bonded to aluminum fins. As
an option, corrugated copper fins or coated aluminum fins may be provided. Manual air vents are provided on all
chilled water coils. The standard chilled water coil is 3 rows for all models & 4 row chilled water coil is also provided as an
option. A 4 pipe coil consisting of 3 rows of cooling coil and 1 row of heating coil is used for heating application. Each coil
is pressure tested in the factory at not less than 300 psi (2070 kpa) air pressure. Coils conform to ARI 410.
DRAIN PAN
The condensate drain pan is fabricated of 18 gauge galvanized steel. The drain pan is powder coat painted. The outer
surface is thermally insulated.
DRIP LIP
The purpose of a 'drip-lip' is to capture any condensate from the valve packages and direct it to the drain pan. It is
fabricated of a single metal formed to fit on the side of the drain pan. They may be installed in the field and should always
be pitched towards the drain pan to assure proper drainage. This will be supplied loose for field installations along with
valve packages.

OPTIONS
ELECTRIC HEATERS
The heater element is of the resistance open coil type. Thermal overheat cut-outs and fusible links are provided to shut-
off power to heaters in case of airflow failure.
VALVE PACKAGES
Valve packages are available as an option (3D for two pipe system and 4D for four pipe systems). These valves can be
factory installed or supplied loose for field installation.
THERMOSTAT
An attractive wall mount three speed electronic thermostat with all required functions and features for safe and smooth
operation which can be used for cooling & heating requirements. This thermostat can be supplied loose through separate
Kit number.

TYPICAL THERMOSTAT

3
PHYSICAL DATA
MODEL NUMBER CWX02 CWX03 CWX04 CWX06 CWX08 CWX10 CWX12 CWX14

POWER SUPPLY, V-Ph-Hz 208/230-1-60

BLOWER Type Forward Curved

Size (mm) 146x192 146x192 146x192 146x232 146x232 185x232 185x232 185x232

Quantity 1 1 1 2 2 2 2 2

BLOWER MOTOR Quantity 1 1 1 1 1 1 1 1

FLA 0.66 0.66 0.66 1.16 1.16 2.52 2.52 2.52

Watts @ 0.0 ESP, high speed 100 116 134 171 280 396 487 565

COOLING COIL Type Corrugated Fin & Tube

Tube dia. - Rows - FPI 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14

Face area, Sq. ft. (Sq. m.) 1.22(0.113) 1.22(0.113) 1.22(0.113) 2.11(0.196) 2.11(0.196) 3.54(0.329) 3.54(0.329) 3.54(0.329)

HOT WATER COIL Type Corrugated Fin & Tube

Tube dia. - Rows - FPI 3/8 - 1 - 14 3/8 - 1 - 14 3/8 - 1 - 14 3/8 - 1 - 14 3/8 - 1 - 14 3/8 - 1 - 14 3/8 - 1 - 14 3/8 - 1 - 14

Face area, Sq. ft. (Sq. m.) 1.22(0.113) 1.22(0.113) 1.22(0.113) 2.11(0.196) 2.11(0.196) 3.54(0.329) 3.54(0.329) 3.54(0.329)

COIL CONNECTIONS Chilled water, Inlet - Outlet (inch) 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8

Hot water, Inlet - Outlet (inch) 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8 5/8 - 5/8

DRAIN CONNECTION Size (inch) 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8

RETURN AIR FILTER Size (inch) 8 x 23-3/8 8 x 23-3/8 8 x 23-3/8 8 x 19-5/8 8 x 19-5/8 10 x 26-1/8 10 x 26-1/8 10 x 26-1/8
(1/2'' THICK)
Quantity 1 1 1 2 2 2 2 2

SHIPPING WEIGHT kg. (approx.) 30 30 30 40 40 54 54 54

4
CHILLED WATER COOLING CAPACITIES - 3 ROW COIL (ENGLISH UNITS) E
0 0 0 0
ENTERING AIR TEMP. = 76 F DB/63 F WB (@ HIGH SPEED) ENTERING AIR TEMP. = 80 F DB/67 F WB (@ HIGH SPEED) N
400F EWT 450F EWT 500F EWT 400F EWT 450F EWT 500F EWT
WTR UNIT
(0F) SIZE
WTR UNIT
(0F) SIZE
G
TC SC GPM TC SC GPM TC SC GPM TC SC GPM TC SC GPM TC SC GPM
02 9.05 6.43 2.26 6.99 5.51 1.75 5.16 4.88 1.29 02 14.73 8.96 3.68 12.35 7.92 3.09 10.04 7.07 2.51 L
03
04
10.25
11.20
7.39
8.12
2.56
2.80
8.05
8.78
6.45
7.09
2.01
2.19
5.91
6.43
5.72
6.29
1.48
1.61
03
04
16.99 10.44
18.59 11.48
4.25
4.65
14.17 9.23
15.43 10.13
3.54
3.86
11.42
12.38
8.22
9.02
2.85
3.09
I
8 06 17.61 12.60 4.40 13.63 10.85 3.41 9.98 9.57 2.49 8 06 29.47 17.99 7.37 24.45 15.79 6.11 19.64 13.98 4.91 S
08 21.61 15.69 5.40 16.80 13.60 4.20 12.20 11.99 3.05 08 36.84 22.72 9.21 30.24 19.83 7.56 23.97 17.47 5.99
10 30.02 21.47 7.50 23.04 18.36 5.76 16.75 16.12 4.19 10 51.54 31.39 12.88 42.33 27.27 10.58 33.65 23.93 8.41
H
12 32.65 23.50 8.16 25.20 20.23 6.30 18.25 17.73 4.56 12 56.90 34.79 14.22 46.47 30.13 11.62 36.71 26.35 9.18
14 36.14 25.99 9.03 27.78 22.29 6.95 20.05 19.49 5.01 14 63.68 38.85 15.92 51.78 33.50 12.94 40.73 29.18 10.18
02 8.64 6.17 1.73 6.81 5.39 1.36 5.02 4.76 1.00 02 13.90 8.50 2.78 11.61 7.51 2.32 9.45 6.73 1.89 U
03
04
9.94
10.84
7.19
7.89
1.99
2.17
7.81
8.50
6.29
6.89
1.56
1.70
5.72
6.20
5.57
6.11
1.15
1.24
03
04
15.88 9.82
17.26 10.74
3.17
3.45
13.17
14.32
8.66
9.49
2.63
2.86
10.89
11.89
7.91
8.72
2.18
2.38
N
10 06 16.84 12.10 3.37 13.18 10.54 2.64 9.64 9.31 1.93 10 06 27.35 16.82 5.47 22.62 14.76 4.52 18.46 13.29 3.69 I
08 20.75 15.12 4.15 16.14 13.14 3.23 11.70 11.58 2.34 08 33.60 20.91 6.72 27.67 18.35 5.53 22.80 16.78 4.56
10 28.46 20.48 5.69 22.15 17.75 4.43 16.09 15.60 3.22 10 47.09 28.92 9.42 38.62 25.19 7.72 31.29 22.55 6.26
T
12 31.13 22.53 6.22 24.15 19.51 4.83 17.46 17.11 3.49 12 51.54 31.79 10.31 42.03 27.61 8.40 34.26 24.90 6.85 S
14 34.31 24.83 6.86 26.55 21.45 5.31 19.15 18.77 3.83 14 57.29 35.32 11.46 46.56 30.55 9.31 37.80 27.47 7.56
02 8.46 6.05 1.41 6.66 5.29 1.11 4.88 4.66 0.81 02 13.19 8.10 2.20 11.10 7.22 1.85 9.25 6.61 1.54
03 9.70 7.04 1.62 7.60 6.15 1.27 5.54 5.43 0.92 03 14.98 9.32 2.50 12.78 8.44 2.13 10.63 7.75 1.77
04 10.56 7.71 1.76 8.26 6.73 1.38 5.99 5.93 1.00 04 16.38 10.24 2.73 13.95 9.28 2.32 11.58 8.53 1.93
12 06 16.39 11.82 2.73 12.82 10.30 2.14 9.33 9.06 1.56 12 06 25.62 15.85 4.27 21.66 14.21 3.61 17.97 13.00 2.99
08 20.08 14.69 3.35 15.60 12.77 2.60 11.24 11.22 1.87 08 31.58 19.76 5.26 26.75 17.83 4.46 22.07 16.32 3.68
10 27.56 19.91 4.59 21.44 17.27 3.57 15.51 15.14 2.59 10 43.62 26.99 7.27 36.70 24.10 6.12 30.28 21.95 5.05
12 30.05 21.84 5.01 23.31 18.91 3.88 16.78 16.56 2.80 12 47.56 29.57 7.93 40.17 26.54 6.69 33.06 24.17 5.51
14 33.05 24.02 5.51 25.58 20.76 4.26 18.37 18.14 3.06 14 52.57 32.67 8.76 44.31 29.27 7.38 36.40 26.61 6.07

ENTERING AIR TEMP. = 840F DB/710F WB (@ HIGH SPEED)


WTR UNIT 400F EWT 450F EWT 500F EWT NOTE:
(0F) SIZE TC SC GPM TC SC GPM TC SC GPM For any other conditions, please use selection software for fan coil units.
Apart from capacities, this software provides;
02 20.84 11.28 5.21 18.27 10.14 4.57 15.79 9.18 3.95
a) Sensible heat ratio
03 24.33 13.25 6.08 21.23 11.90 5.31 18.26 10.78 4.56
b) Leaving air temperature (DB/WB) - 0F
04 26.81 14.64 6.70 23.34 13.15 5.83 20.00 11.89 5.00
c) Leaving water temperature - 0F
8 06 42.72 23.14 10.68 37.08 20.62 9.27 31.72 18.53 7.93
d) Leaving water velocities (FPM)
08 54.64 29.75 13.66 47.00 26.39 11.75 39.83 23.61 9.96
e) Water pressure drop (feet of water)
10 76.70 41.44 19.17 65.86 36.49 16.46 55.73 32.41 13.93
12 85.70 46.37 21.42 73.23 40.70 18.30 61.67 36.07 15.42
14 97.05 52.43 24.26 82.51 45.75 20.63 69.15 40.33 17.29 LEGEND:
02 19.68 10.69 3.94 17.27 9.63 3.45 14.91 8.74 2.98 TC - Total Capacity (MBH)
03 22.76 12.45 4.55 19.88 11.22 3.97 17.08 10.18 3.41 SC - Sensible Heat Capacity (MBH)
04 24.93 13.68 4.99 21.72 12.32 4.34 18.59 11.17 3.72 WTR - Water Temperature Rise (0F)
10 06 39.54 21.52 7.91 34.41 19.28 6.88 29.45 17.39 5.89
EWT - Entering Water Temperature (0F)
08 49.64 27.20 9.93 42.84 24.28 8.57 36.34 21.83 7.27
GPM - Water flow (Gallons Per Minute)
10 69.47 37.74 13.89 59.94 33.50 11.99 50.89 29.99 10.18
12 76.85 41.85 15.37 66.04 37.08 13.21 55.81 33.10 11.16
14 86.18 46.88 17.23 73.79 41.35 14.76 62.14 36.80 12.43
02 18.79 10.23 3.13 16.46 9.23 2.74 14.17 8.37 2.36
03 21.56 11.83 3.59 18.79 10.67 3.13 16.08 9.67 2.68
04 23.50 12.94 3.92 20.42 11.66 3.40 17.45 10.58 2.91

12 06 37.22 20.34 6.20 32.37 18.25 5.39 27.64 16.47 4.61


08 46.07 25.37 7.68 39.73 22.69 6.62 33.72 20.48 5.62
10 64.48 35.19 10.75 55.69 31.37 9.28 47.22 28.12 7.87
12 70.83 38.78 11.80 60.92 34.49 10.15 51.41 30.86 8.57
14 78.95 43.18 13.16 67.71 38.30 11.28 56.97 34.16 9.49

5
E CHILLED WATER COOLING CAPACITIES - 4 ROW COIL (ENGLISH UNITS)
N ENTERING AIR TEMP. = 760F DB/630F WB (@ HIGH SPEED) ENTERING AIR TEMP. = 800F DB/670F WB (@ HIGH SPEED)
0 0 0
40 F EWT 45 F EWT 50 F EWT 400F EWT 450F EWT 500F EWT
G WTR UNIT
(0F) SIZE
WTR UNIT
(0F) SIZE
TC SC GPM TC SC GPM TC SC GPM TC SC GPM TC SC GPM TC SC GPM
L 02 10.61 7.37 2.65 8.05 6.18 2.01 5.92 5.40 1.48 02 17.16 10.27 4.29 14.41 9.02 3.60 11.74 7.98 2.93

I 03
04
12.24
13.30
8.64
9.46
3.06
3.32
9.35
10.21
7.32
8.07
2.33
2.55
6.87
7.49
6.45
7.10
1.72
1.87
03
04
20.17 12.21
22.15 13.45
5.04
5.54
16.82 10.71
18.40 11.80
4.20
4.60
13.61 9.49
14.81 10.44
3.40
3.70
S 8 06 21.08 14.76 5.27 15.86 12.33 3.97 11.62 10.79 2.90 8 06 35.16 21.11 8.79 29.16 18.38 7.29 23.47 16.16 5.87
08 25.83 18.38 6.46 19.64 15.54 4.91 14.26 13.59 3.56 08 44.43 26.91 11.10 36.44 23.31 9.11 28.95 20.39 7.24
H 10 36.23 25.33 9.06 26.95 20.95 6.74 19.57 18.21 4.89 10 62.21 37.23 15.55 50.98 31.58 12.74 40.54 27.84 10.13
12 39.60 27.87 9.90 29.54 23.15 7.38 21.36 20.09 5.34 12 69.05 41.45 17.26 56.26 35.54 14.06 44.46 30.81 11.11
14 44.00 30.93 11.00 32.62 25.54 8.15 23.50 22.11 5.87 14 77.68 46.54 19.42 62.95 39.67 15.74 49.49 34.22 12.37
U 02 9.93 6.95 1.99 7.80 6.01 1.56 5.76 5.29 1.15 02 16.23 9.76 3.25 13.60 8.59 2.72 11.03 7.60 2.21

N 03
04
11.55
12.62
8.21
9.02
2.31
2.52
9.07
9.89
7.14
7.85
1.81
1.98
6.66
7.24
6.29
6.91
1.33
1.45
03
04
18.88 11.49
20.61 12.61
3.77
4.12
15.72 10.10
17.08 11.06
3.14
3.41
12.65
13.83
8.94
9.87
2.53
2.77
I 10 06 19.60 13.85 3.92 15.35 11.99 3.07 11.23 10.51 2.25 10 06 32.64 19.75 6.53 27.07 17.24 5.41 21.69 15.16 4.34
08 24.25 17.38 4.85 18.86 15.03 3.77 13.69 13.17 2.74 08 40.52 24.77 8.10 33.23 21.52 6.64 26.67 19.07 5.33
T 10 33.28 23.53 6.66 25.88 20.25 5.17 18.81 17.65 3.76 10 56.70 34.22 11.34 46.58 29.62 9.31 36.95 25.83 7.39
S 12 36.47 25.94 7.29 28.26 22.29 5.65 20.46 19.42 4.09 12 62.37 37.79 12.47 50.96 32.61 10.19 40.16 28.37 8.03
14 40.28 28.63 8.05 31.12 24.54 6.22 22.46 21.33 4.49 14 69.60 42.12 13.92 56.63 36.21 11.33 44.46 31.36 8.89
02 9.68 6.80 1.61 7.63 5.91 1.27 5.62 5.19 0.94 02 15.47 9.35 2.58 12.91 8.21 2.15 10.59 7.35 1.76
03 11.27 8.04 1.88 8.85 6.99 1.47 6.47 6.14 1.08 03 17.83 10.91 2.97 14.85 9.61 2.47 12.34 8.76 2.06
04 12.29 8.82 2.05 9.62 7.67 1.60 7.01 6.75 1.17 04 19.35 11.91 3.22 16.23 10.58 2.70 13.47 9.66 2.24
12 06 19.07 13.52 3.18 14.93 11.72 2.49 10.90 10.26 1.82 12 06 30.69 18.67 5.11 25.34 16.29 4.22 20.91 14.72 3.48
08 23.47 16.87 3.91 18.25 14.61 3.04 13.21 12.79 2.20 08 37.54 23.12 6.26 31.28 20.43 5.21 25.79 18.55 4.30
10 32.20 22.84 5.36 25.06 19.70 4.18 18.18 17.18 3.03 10 52.67 32.01 8.78 43.13 27.72 7.19 35.39 24.93 5.90
12 35.18 25.11 5.86 27.30 21.65 4.55 19.72 18.86 3.29 12 57.52 35.13 9.59 47.10 30.47 7.85 38.71 27.52 6.45
14 38.75 27.65 6.46 29.99 23.80 5.00 21.61 20.68 3.60 14 63.86 38.95 10.64 52.07 33.67 8.68 42.69 30.33 7.11

ENTERING AIR TEMP. = 840F DB/710F WB (@ HIGH SPEED)


WTR UNIT 400F EWT 450F EWT 500F EWT NOTE:
(0F) SIZE TC SC GPM TC SC GPM TC SC GPM For any other conditions, please use selection software for fan coil units.
Apart from capacities, this software provides;
02 24.31 13.05 6.08 21.29 11.62 5.32 18.39 10.41 4.60
a) Sensible heat ratio
03 28.95 15.61 7.24 25.23 13.90 6.31 21.67 12.48 5.42
b) Leaving air temperature (DB/WB) - 0F
04 32.04 17.31 8.01 27.83 15.40 6.96 23.83 13.82 5.96
c) Leaving water temperature - 0F
8 06 51.27 27.54 12.81 44.38 24.27 11.09 37.88 21.55 9.47
d) Leaving water velocities (FPM)
08 66.42 35.78 16.60 56.91 31.35 14.23 48.07 27.73 12.02
e) Water pressure drop (feet of water)
10 91.52 49.23 22.90 79.94 43.51 19.98 67.37 38.11 16.84
12 105.29 56.46 26.32 89.45 48.80 22.36 74.96 42.60 18.74
14 114.80 61.77 28.50 101.43 55.20 25.36 84.53 47.85 21.13 LEGEND:
02 22.93 12.34 4.58 20.12 11.04 4.02 17.39 9.93 3.48 TC - Total Capacity (MBH)
03 27.02 14.62 5.40 23.60 13.09 4.72 20.29 11.80 4.06 SC - Sensible Heat Capacity (MBH)
04 29.70 16.12 5.94 25.87 14.42 5.17 22.17 13.00 4.43 WTR - Water Temperature Rise (0F)
10 06 47.22 25.45 9.44 41.04 22.60 8.21 35.13 20.21 7.03
EWT - Entering Water Temperature (0F)
08 59.92 32.45 11.98 51.64 28.72 10.33 43.80 25.62 8.76
GPM - Water flow (Gallons Per Minute)
10 83.97 45.18 16.79 72.28 39.68 14.46 61.28 35.13 12.26
12 93.42 50.32 18.68 80.05 44.10 16.01 67.56 38.97 13.51
14 105.33 56.68 21.06 89.87 49.42 17.97 75.52 43.46 15.10
02 21.91 11.82 3.65 19.23 10.59 3.20 16.60 9.54 2.77
03 25.60 13.90 4.27 22.35 12.47 3.72 19.19 11.25 3.20
04 28.01 15.25 4.67 24.39 13.67 4.06 20.86 12.33 3.48

12 06 44.39 24.00 7.40 38.63 21.41 6.44 33.06 19.20 5.51


08 55.51 30.21 9.25 47.92 26.85 7.99 40.63 24.02 6.77
10 77.68 41.94 12.95 67.06 36.63 11.18 56.93 33.00 9.49
12 85.76 46.40 14.29 73.73 40.95 12.29 62.31 36.39 10.38
14 95.99 51.89 16.00 82.25 45.62 13.71 69.28 40.40 11.55

6
CHILLED WATER COOLING CAPACITIES - 3 ROW COIL (METRIC UNITS) M
0 0 0 0
ENTERING AIR TEMP. = 25 C DB/17 C WB (@ HIGH SPEED) ENTERING AIR TEMP. = 27 C DB/19.5 C WB (@ HIGH SPEED) E
40C EWT 70C EWT 100C EWT 40C EWT 70C EWT 100C EWT
WTR UNIT
(0C) SIZE
WTR UNIT
(0C) SIZE
T
TC SC LPS TC SC LPS TC SC LPS TC SC LPS TC SC LPS TC SC LPS
02 2.52 1.89 0.12 1.93 1.64 0.09 1.36 1.36 0.07 02 4.34 2.66 0.21 3.60 2.34 0.17 2.88 2.07 0.14 R
03
04
2.90
3.17
2.21
2.43
0.14
0.15
2.22
2.42
1.91
2.10
0.11
0.12
1.56
1.69
1.56
1.69
0.07
0.08
03
04
4.99
5.44
3.09
3.39
0.24
0.26
4.11
4.47
2.71
2.97
0.20
0.21
3.27
3.58
2.41
2.66
0.16
0.17
I
5 06 4.92 3.72 0.23 3.75 3.21 0.18 2.62 2.62 0.13 5 06 8.62 5.31 0.41 7.08 4.63 0.34 5.59 4.07 0.27 C
08 6.08 4.67 0.29 4.60 4.01 0.22 3.18 3.18 0.15 08 10.71 6.66 0.51 8.69 5.77 0.42 6.90 5.13 0.33
10 8.34 6.32 0.40 6.31 5.41 0.30 4.38 4.38 0.21 10 14.98 9.21 0.72 12.18 7.95 0.58 9.52 6.92 0.45
12 9.13 6.96 0.44 6.89 5.95 0.33 4.75 4.75 0.23 12 16.48 10.17 0.79 13.32 8.75 0.64 10.39 7.63 0.50 U
14 10.08 7.68 0.48 7.58 6.54 0.36 5.21 5.21 0.25 14 18.39 11.34 0.88 14.80 9.71 0.71 11.49 8.43 0.55
02 2.46 1.86 0.10 1.89 1.61 0.08 1.33 1.33 0.05 02 4.13 2.55 0.16 3.41 2.23 0.14 2.78 2.01 0.11 N
03
04
2.83
3.08
2.16
2.37
0.11
0.12
2.16
2.35
1.87
2.05
0.09
0.09
1.51
1.63
1.51
1.63
0.06
0.07
03
04
4.71
5.11
2.94
3.20
0.19
0.20
3.89
4.25
2.58
2.84
0.15
0.17
3.20
3.49
2.36
2.60
0.13
0.14
I
6 06 4.79 3.64 0.19 3.65 3.14 0.15 2.54 2.54 0.10 6 06 8.11 5.02 0.32 6.63 4.37 0.26 5.41 3.96 0.22 T
08 5.88 4.53 0.23 4.45 3.90 0.18 3.06 3.06 0.12 08 9.92 6.22 0.39 8.19 5.48 0.33 6.67 4.99 0.27
10 8.07 6.14 0.32 6.11 5.27 0.24 4.22 4.22 0.17 10 13.92 8.61 0.55 11.28 7.43 0.45 9.15 6.71 0.36
S
12 8.81 6.74 0.35 6.65 5.77 0.26 4.57 4.57 0.18 12 15.20 9.45 0.61 12.33 8.19 0.49 10.01 7.40 0.40
14 9.70 7.42 0.39 7.30 6.34 0.29 5.01 5.01 0.20 14 16.88 10.49 0.67 13.63 9.05 0.54 11.04 8.16 0.44
02 2.42 1.83 0.08 1.85 1.58 0.06 1.29 1.29 0.04 02 3.95 2.44 0.13 3.31 2.17 0.11 2.73 1.98 0.09
03 2.77 2.12 0.09 2.11 1.83 0.07 1.46 1.46 0.05 03 4.50 2.82 0.15 3.81 2.54 0.13 3.13 2.32 0.11
04 3.02 2.32 0.10 2.29 2.01 0.08 1.58 1.58 0.05 04 4.92 3.09 0.17 4.16 2.79 0.14 3.41 2.55 0.12
7 06 4.68 3.56 0.16 3.56 3.07 0.12 2.46 2.46 0.08 7 06 7.66 4.77 0.26 6.46 4.27 0.22 5.29 3.89 0.18
08 5.72 4.42 0.20 4.32 3.80 0.15 2.95 2.95 0.10 08 9.48 5.97 0.32 7.96 5.35 0.27 6.49 4.88 0.22
10 7.86 5.99 0.27 5.94 5.14 0.20 4.08 4.08 0.14 10 13.03 8.12 0.44 10.92 7.24 0.37 8.91 6.56 0.30
12 8.56 6.57 0.29 6.45 5.63 0.22 4.40 4.40 0.15 12 14.28 8.93 0.49 11.95 7.97 0.41 9.72 7.22 0.33
14 9.41 7.22 0.32 7.07 6.17 0.24 4.81 4.81 0.16 14 15.78 9.86 0.54 13.18 8.78 0.45 10.70 7.95 0.37

ENTERING AIR TEMP. = 290C DB/21.50C WB (@ HIGH SPEED)


WTR UNIT 40C EWT 70C EWT 100C EWT NOTE:
(0C) SIZE TC SC LPS TC SC LPS TC SC LPS For any other conditions, please use selection software for fan coil units.
Apart from capacities, this software provides;
02 5.91 3.26 0.28 5.12 2.91 0.24 4.36 2.62 0.21
a) Sensible heat ratio
03 6.86 3.81 0.33 5.92 3.40 0.28 5.01 3.07 0.24
b) Leaving air temperature (DB/WB) - 0C
04 7.54 4.20 0.36 6.48 3.75 0.31 5.47 3.38 0.26
c) Leaving water temperature - 0C
5 06 11.97 6.62 0.57 10.28 5.87 0.49 8.67 5.25 0.41
d) Leaving water velocities (m/s)
08 15.15 8.43 0.72 12.90 7.44 0.62 10.77 6.63 0.51
e) Water pressure drop (kp)
10 21.23 11.71 1.01 18.05 10.27 0.86 15.07 9.09 0.72
12 23.59 13.04 1.13 19.96 11.40 0.95 16.58 10.07 0.79
14 26.56 14.66 1.27 22.37 12.75 1.07 18.50 11.21 0.88 LEGEND:
02 5.64 3.12 0.22 4.89 2.79 0.19 4.16 2.52 0.17 TC - Total Capacity (kW)
03 6.50 3.62 0.26 5.61 3.24 0.22 4.74 2.92 0.19 SC - Sensible Heat Capacity (kW)
04 7.11 3.98 0.28 6.11 3.55 0.24 5.14 3.20 0.20 WTR - Water Temperature Rise (0C)
6 06 11.26 6.25 0.45 9.68 5.56 0.39 8.15 4.98 0.32
EWT - Entering Water Temperature (0C)
08 14.05 7.86 0.56 11.97 6.96 0.48 9.98 6.21 0.40
LPS - Water flow (Liters Per Second)
10 19.65 10.89 0.78 16.76 9.60 0.67 14.00 8.54 0.56
12 21.68 12.05 0.86 18.40 10.60 0.73 15.29 9.40 0.61
14 24.24 13.45 0.97 20.50 11.79 0.82 16.98 10.42 0.68
02 5.42 3.01 0.18 4.69 2.69 0.16 3.97 2.42 0.14
03 6.20 3.47 0.21 5.34 3.10 0.18 4.52 2.81 0.15
04 6.75 3.79 0.23 5.79 3.39 0.20 4.94 3.10 0.17

7 06 10.70 5.96 0.37 9.18 5.30 0.31 7.70 4.75 0.26


08 13.19 7.40 0.45 11.21 6.56 0.38 9.53 5.98 0.33
10 18.47 10.28 0.63 15.74 9.08 0.54 13.11 8.08 0.45
12 20.24 11.30 0.69 17.18 9.97 0.59 14.34 8.91 0.49
14 22.53 12.57 0.77 19.06 11.05 0.65 15.85 9.83 0.54

7
M CHILLED WATER COOLING CAPACITIES - 4 ROW COIL (METRIC UNITS)
E ENTERING AIR TEMP. = 250C DB/170C WB (@ HIGH SPEED) ENTERING AIR TEMP. = 270C DB/19.50C WB (@ HIGH SPEED)
0 0 0
4 C EWT 7 C EWT 10 C EWT 40C EWT 70C EWT 100C EWT
T WTR UNIT
(0C) SIZE
WTR UNIT
(0C) SIZE
TC SC LPS TC SC LPS TC SC LPS TC SC LPS TC SC LPS TC SC LPS
R 02 2.94 2.16 0.14 2.21 1.82 0.11 1.56 1.56 0.07 02 5.06 3.05 0.24 4.21 2.66 0.20 3.38 2.34 0.16

I 03
04
3.37
3.68
2.52
2.78
0.16
0.18
2.58
2.81
2.17
2.39
0.12
0.13
1.81
1.97
1.81
1.97
0.09
0.09
03
04
5.92
6.49
3.61
3.98
0.28
0.31
4.89
5.33
3.15
3.46
0.23
0.25
3.89
4.23
2.77
3.04
0.19
0.20
C 5 06 5.79 4.30 0.28 4.36 3.64 0.21 3.05 3.05 0.15 5 06 10.29 6.23 0.49 8.45 5.39 0.40 6.70 4.71 0.32
08 7.11 5.36 0.34 5.37 4.57 0.26 3.73 3.73 0.18 08 12.90 7.89 0.62 10.48 6.79 0.50 8.19 5.90 0.39
10 9.87 7.33 0.47 7.37 6.16 0.35 5.12 5.12 0.24 10 18.06 10.91 0.86 14.67 9.32 0.70 11.50 8.07 0.55
U 12 10.73 8.02 0.51 8.06 6.79 0.39 5.57 5.57 0.27 12 19.97 12.11 0.95 16.12 10.32 0.77 12.55 8.90 0.60
14 11.88 8.88 0.57 8.88 7.48 0.42 6.12 6.12 0.29 14 22.38 13.55 1.07 17.98 11.50 0.86 13.93 9.86 0.67
N 02 2.82 2.08 0.11 2.17 1.79 0.09 1.53 1.53 0.06 02 4.83 2.93 0.19 4.01 2.56 0.16 3.20 2.24 0.13

I 03
04
3.29
3.59
2.47
2.71
0.13
0.14
2.52
2.74
2.13
2.33
0.10
0.11
1.76
1.91
1.76
1.91
0.07
0.08
03
04
5.61
6.11
3.44
3.77
0.22
0.24
4.62
5.01
3.00
3.28
0.18
0.20
3.71
4.06
2.67
2.94
0.15
0.16
T 6 06 5.57 4.15 0.22 4.25 3.56 0.17 2.97 2.97 0.12 6 06 9.68 5.90 0.39 7.94 5.11 0.32 6.30 4.48 0.25
08 6.87 5.20 0.27 5.20 4.45 0.21 3.60 3.60 0.14 08 11.97 7.38 0.48 9.70 6.36 0.39 7.80 5.67 0.31
S 10 9.43 7.04 0.38 7.14 6.00 0.28 4.95 4.95 0.20 10 16.76 10.19 0.67 13.62 8.76 0.54 10.71 7.62 0.43
12 10.32 7.75 0.41 7.78 6.60 0.31 5.37 5.37 0.21 12 18.40 11.24 0.73 14.87 9.63 0.59 11.74 8.43 0.47
14 11.38 8.54 0.45 8.56 7.26 0.34 5.89 5.89 0.23 14 20.51 12.51 0.82 16.50 10.67 0.66 12.96 9.30 0.52
02 2.77 2.05 0.09 2.13 1.76 0.07 1.49 1.49 0.05 02 4.64 2.82 0.16 3.83 2.46 0.13 3.12 2.20 0.11
03 3.22 2.42 0.11 2.46 2.09 0.08 1.71 1.71 0.06 03 5.34 3.29 0.18 4.43 2.89 0.15 3.64 2.62 0.12
04 3.51 2.66 0.12 2.67 2.29 0.09 1.85 1.85 0.06 04 5.79 3.59 0.20 4.84 3.18 0.17 3.97 2.89 0.14
7 06 5.45 4.07 0.19 4.15 3.49 0.14 2.88 2.88 0.10 7 06 9.18 5.62 0.31 7.52 4.87 0.26 6.16 4.40 0.21
08 6.69 5.08 0.23 5.06 4.35 0.17 3.48 3.48 0.12 08 11.22 6.95 0.38 9.31 6.13 0.32 7.59 5.54 0.26
10 9.18 6.87 0.31 6.95 5.86 0.24 4.80 4.80 0.16 10 15.74 9.63 0.54 12.78 8.28 0.44 10.41 7.45 0.36
12 10.02 7.55 0.34 7.56 6.43 0.26 5.19 5.19 0.18 12 17.18 10.56 0.59 14.01 9.14 0.48 11.38 8.22 0.39
14 11.02 8.31 0.38 8.30 7.06 0.28 5.68 5.68 0.19 14 19.07 11.71 0.65 15.48 10.09 0.53 12.54 9.05 0.43

ENTERING AIR TEMP. = 290C DB/21.50C WB (@ HIGH SPEED)


WTR UNIT 40C EWT 70C EWT 100C EWT NOTE:
(0C) SIZE TC SC LPS TC SC LPS TC SC LPS For any other conditions, please use selection software for fan coil units.
Apart from capacities, this software provides;
02 6.88 3.76 0.33 5.97 3.33 0.29 5.08 2.97 0.24
a) Sensible heat ratio
03 8.15 4.48 0.39 7.03 3.97 0.34 5.95 3.55 0.28
b) Leaving air temperature (DB/WB) - 0C
04 8.98 4.95 0.43 7.73 4.38 0.37 6.52 3.92 0.31
c) Leaving water temperature - 0C
5 06 14.32 7.84 0.68 12.28 6.88 0.59 10.34 6.09 0.49
d) Leaving water velocities (m/s)
08 18.34 10.08 0.88 15.57 8.78 0.74 12.98 7.76 0.62
e) Water pressure drop (kp)
10 25.75 14.07 1.23 21.81 12.17 1.04 18.16 10.64 0.87
12 28.79 15.74 1.38 24.25 13.58 1.16 20.08 11.83 0.96
14 32.62 17.82 1.56 27.33 15.27 1.31 22.51 13.23 1.08 LEGEND:
02 6.57 3.60 0.26 5.70 3.20 0.23 4.86 2.86 0.19 TC - Total Capacity (kW)
03 7.72 4.26 0.31 6.66 3.78 0.27 5.64 3.39 0.22 SC - Sensible Heat Capacity (kW)
04 8.46 4.68 0.34 7.28 4.16 0.29 6.15 3.72 0.24 WTR - Water Temperature Rise (0C)
6 06 13.43 7.38 0.53 11.54 6.51 0.46 9.73 5.78 0.39
EWT - Entering Water Temperature (0C)
08 16.94 9.35 0.67 14.42 8.22 0.57 12.04 7.29 0.48
LPS - Water flow (Liters Per Second)
10 23.71 13.00 0.94 20.18 11.35 0.80 16.86 9.99 0.67
12 26.29 14.44 1.05 22.27 12.57 0.89 18.51 11.05 0.74
14 29.54 16.21 1.18 24.92 14.04 0.99 20.63 12.29 0.82
02 6.32 3.47 0.22 5.48 3.09 0.19 4.66 2.76 0.16
03 7.37 4.08 0.25 6.36 3.63 0.22 5.37 3.25 0.18
04 8.05 4.47 0.27 6.92 3.97 0.24 5.82 3.56 0.20

7 06 12.76 7.03 0.44 10.97 6.22 0.37 9.23 5.53 0.32


08 15.89 8.81 0.54 13.54 7.77 0.46 11.28 6.89 0.38
10 22.24 12.23 0.76 18.96 10.57 0.65 15.83 9.48 0.54
12 24.50 13.51 0.84 20.80 11.83 0.71 17.28 10.43 0.59
14 27.38 15.09 0.93 23.16 13.16 0.79 19.18 11.56 0.65

8
FAN PERFORMANCE DATA - 3 ROW COILS (ENGLISH UNITS) E
CFM @ EXTERNAL STATIC PRESSURE (Inches of water)
MODEL
NUMBER
BLOWER MOTOR
SPEED 0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.4 0.5
N
HIGH 295 288 280 266 252 239 225 195 180 G
CWX02 MEDIUM 266 253 240 235 230 223 215 175 160
LOW 225 218 210 203 195 188 180 165 -
L
HIGH 380 369 358 343 327 307 287 250 197 I
CWX03 MEDIUM 330 324 318 311 303 288 272 234 180
LOW 266 253 240 235 230 223 215 175 160
S
HIGH 438 422 405 390 374 355 335 288 224 H
CWX04 MEDIUM 401 389 377 361 345 324 303 264 208
LOW 330 324 318 311 303 288 272 234 180
HIGH 613 592 571 548 525 479 432 355 221 U
CWX06 MEDIUM 567 546 525 503 481 438 395 288 175
LOW 505 485 465 426 386 355 323 241 160 N
HIGH 853 822 790 755 720 681 641 505 368 I
CWX08 MEDIUM 730 703 675 651 627 576 525 420 276
LOW 613 592 571 548 525 479 432 355 221 T
HIGH 1044 1022 1000 980 960 928 895 870 770
CWX10 MEDIUM 880 860 840 831 821 799 776 715 645
S
LOW 805 781 756 736 715 688 661 615 560
HIGH 1200 1178 1156 1129 1102 1068 1033 960 870
CWX12 MEDIUM 995 973 950 933 915 883 850 830 730
LOW 880 860 840 831 821 799 776 715 645
HIGH 1320 1286 1251 1221 1190 1157 1123 1040 940
CWX14 MEDIUM 1200 1178 1156 1129 1102 1068 1033 960 870
LOW 995 973 950 933 915 883 850 830 730

FAN PERFORMANCE DATA - 4 ROW COILS (ENGLISH UNITS)


MODEL BLOWER MOTOR CFM @ EXTERNAL STATIC PRESSURE (Inches of water)
NUMBER SPEED 0.0 0.05 0.1 0.15 0.2 0.25 0.3 0.4 0.5
HIGH 288 280 266 252 239 225 210 188 165
CWX02 MEDIUM 253 240 235 230 223 215 195 168 139
LOW 218 210 203 195 188 180 173 - -
HIGH 369 358 343 327 307 287 269 224 170
CWX03 MEDIUM 324 318 311 303 288 272 253 207 145
LOW 253 240 235 230 223 215 195 168 115
HIGH 422 405 390 374 355 335 312 256 190
CWX04 MEDIUM 389 377 361 345 324 303 284 236 159
LOW 324 318 311 303 288 272 253 207 135
HIGH 592 571 548 525 479 432 394 288 201
CWX06 MEDIUM 546 525 503 481 438 395 342 232 165
LOW 485 465 426 386 355 323 282 201 146
HIGH 822 790 755 720 681 641 573 437 285
CWX08 MEDIUM 703 675 651 627 576 525 473 348 204
LOW 592 571 548 525 479 432 394 288 160
HIGH 1022 1000 980 960 928 895 883 820 680
CWX10 MEDIUM 860 840 831 821 799 776 746 680 602
LOW 781 756 736 715 688 661 638 588 530
HIGH 1178 1156 1129 1102 1068 1033 997 915 810
CWX12 MEDIUM 973 950 933 915 883 850 840 780 670
LOW 860 840 831 821 799 776 746 680 620
HIGH 1286 1251 1221 1190 1157 1123 1082 990 880
CWX14 MEDIUM 1178 1156 1129 1102 1068 1033 997 915 830
LOW 973 950 933 915 883 850 840 780 680
NOTE: 1. Values include losses for dry coil and filters.
2. Airflow values are in CFM.
9
M FAN PERFORMANCE DATA - 3 ROW COILS (METRIC UNITS)
LITERS PER SECOND @ EXTERNAL STATIC PRESSURE (Pascal)
E MODEL
NUMBER
BLOWER MOTOR
SPEED 0.0 12.5 25 37.5 50 62.5 75 100 125
T HIGH 139 136 132 126 119 113 106 92 85
CWX02 MEDIUM 126 119 113 111 109 105 101 83 76
R LOW 106 103 99 96 92 88 85 78 0
I HIGH 179 174 169 162 154 145 135 118 93
CWX03 MEDIUM 156 153 150 147 143 136 128 110 85
C LOW 126 119 113 111 109 105 101 83 76
HIGH 207 199 191 184 177 167 158 136 106
CWX04 MEDIUM 189 184 178 170 163 153 143 125 98
U LOW 156 153 150 147 143 136 128 110 85
N HIGH 289 279 269 259 248 226 204 168 104
CWX06 MEDIUM 268 258 248 237 227 207 186 136 83
I LOW 238 229 219 201 182 167 152 114 76
T HIGH 403 388 373 356 340 321 303 238 174
CWX08 MEDIUM 345 332 319 307 296 272 248 198 130
S LOW 289 279 269 259 248 226 204 168 104
HIGH 493 482 472 463 453 438 422 411 363
CWX10 MEDIUM 415 406 396 392 387 377 366 337 304
LOW 380 368 357 347 337 325 312 290 264
HIGH 566 556 546 533 520 504 488 453 411
CWX12 MEDIUM 470 459 448 440 432 417 401 392 345
LOW 415 406 396 392 387 377 366 337 304
HIGH 623 607 590 576 562 546 530 491 444
CWX14 MEDIUM 566 556 546 533 520 504 488 453 411
LOW 470 459 448 440 432 417 401 392 345

FAN PERFORMANCE DATA - 4 ROW COILS (METRIC UNITS)


MODEL BLOWER MOTOR LITERS PER SECOND @ EXTERNAL STATIC PRESSURE (Pascal)
NUMBER SPEED 0.0 12.5 25 37.5 50 62.5 75 100 125
HIGH 136 132 126 119 113 106 99 88 78
CWX02 MEDIUM 119 113 111 109 105 101 92 79 66
LOW 103 99 96 92 88 85 81 39 0
HIGH 174 169 162 154 145 135 127 105 80
CWX03 MEDIUM 153 150 147 143 136 128 119 98 68
LOW 119 113 111 109 105 101 92 79 54
HIGH 199 191 184 177 167 158 147 121 90
CWX04 MEDIUM 184 178 170 163 153 143 134 111 75
LOW 153 150 147 143 136 128 119 98 64
HIGH 279 269 259 248 226 204 186 136 95
CWX06 MEDIUM 258 248 237 227 207 186 161 109 78
LOW 229 219 201 182 167 152 133 95 69
HIGH 388 373 356 340 321 303 270 206 135
CWX08 MEDIUM 332 319 307 296 272 248 223 164 96
LOW 279 269 259 248 226 204 186 136 76
HIGH 482 472 463 453 438 422 417 387 321
CWX10 MEDIUM 406 396 392 387 377 366 352 321 284
LOW 368 357 347 337 325 312 301 277 250
HIGH 556 546 533 520 504 488 470 432 382
CWX12 MEDIUM 459 448 440 432 417 401 396 368 316
LOW 406 396 392 387 377 366 352 321 293
HIGH 607 590 576 562 546 530 510 467 415
CWX14 MEDIUM 556 546 533 520 504 488 470 432 392
LOW 459 448 440 432 417 401 396 368 321
NOTE: 1. Values include losses for dry coil and filters.
2. Airflow values are in Liters per second.
10
SOUND POWER LEVEL (dB re 10–12 Watts )
AT 0.15 ESP
MODEL BLOWER MOTOR OCTAVE BAND CENTER FREQUENCY - Hz
NUMBER SPEED 125 250 500 1000 2000 4000 8000
HIGH 55 46 41 37 36 30 26
CWX02 MEDIUM 52 47 40 38 37 32 26
LOW 50 46 37 35 33 31 25
HIGH 57 53 47 47 46 42 36
CWX03 MEDIUM 54 46 39 37 35 30 26
LOW 51 46 38 37 35 31 26
HIGH 61 56 51 50 49 43 38
CWX04 MEDIUM 60 56 51 50 48 42 37
LOW 57 53 46 47 47 42 35
HIGH 66 63 58 55 55 51 45
CWX06 MEDIUM 64 58 55 51 53 48 41
LOW 61 54 53 49 51 45 40
HIGH 67 65 62 57 58 55 48
CWX08 MEDIUM 66 63 58 55 55 51 45
LOW 64 58 55 53 53 48 41
HIGH 69 67 63 63 62 59 53
CWX10 MEDIUM 68 64 60 59 58 54 47
LOW 66 63 59 58 57 53 45
HIGH 71 70 67 66 65 62 56
CWX12 MEDIUM 69 67 63 63 62 59 53
LOW 68 64 60 59 58 54 47
HIGH 72 71 70 69 68 65 61
CWX14 MEDIUM 71 70 67 66 65 62 56
LOW 69 67 63 63 62 59 53

HOT WATER CAPACITIES


EWT - 1500F (650C) EWT - 1800F (820C)
MODEL
NUMBER CAPACITIES CAPACITIES
GPM (LPS) GPM (LPS)
MBH (kW) MBH (kW)

CWX02 0.68 (0.043) 6.9 (2.02) 1.056 (0.066) 10.57 (3.09)

CWX03 0.72 (0.046) 7.3 (2.13) 1.1 (0.07) 11.45 (3.35)

CWX04 0.75 (0.047) 7.5 (2.20) 1.19 (0.075) 11.92 (3.5)

CWX06 1.15 (0.072) 11.3 (3.31) 1.8 (0.113) 17.64 (5.16)

CWX08 1.23 (0.077) 12.3 (3.60) 2.0 (0.126) 19.81 (5.8)

CWX10 1.83 (0.115) 18.3 (5.36) 3.0 (0.19) 28.9 (8.46)

CWX12 1.9 (0.120) 19.0 (5.56) 3.1 (0.196) 30.4 (8.9)

CWX14 2.0 (0.126) 19.5 (5.71) 3.2 (0.20) 31.5 (9.22)


0 0 0 0
NOTE: Capacities @ 70 F (21 C) Entering Air Temperature & 20 F (11 C) Water Temperature Drop and @high speed.
LEGEND: EWT - Entering Water Temperature; MBH - 1000 BTUH; GPM - Gallons Per Minute; LPS - Liters Per Second

11
DIMENSIONS
MODELS: CWX02 - CWX14

A 109 (4.281)
H
D J
4 15 (0.590)

5
E

25 (1.000)

184 (7.250)
7
TOP VIEW END VIEW

LEGEND:
F
1. Blower & motor assembly
2. Cooling coil
3. Control box
G 4. Filter rack
C
5. Mounting holes
6. Drain pan
7. Duct connector

2 6
FRONT VIEW

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS NO. OF NO. OF


MODEL MOTORS BLOWERS
A B C D E F G H J
CWX02 622 (24.5) 591 (23.3) 254 (10) 591 (23.25) 287 (11.3) 529 (20.8) 176 (6.93) 611 (24.04) 212 (8.33) 1 1

CWX03 622 (24.5) 591 (23.3) 254 (10) 591 (23.25) 287 (11.3) 529 (20.8) 176 (6.93) 611 (24.04) 212 (8.33) 1 1

CWX04 622 (24.5) 591 (23.3) 254 (10) 591 (23.25) 287 (11.3) 529 (20.8) 176 (6.93) 611 (24.04) 212 (8.33) 1 1

CWX06 1029 (40.5) 591 (23.3) 254 (10) 997 (39.25) 287 (11.3) 934 (36.8) 176 (6.93) 1017 (40.04) 212 (8.33) 1 2

CWX08 1029 (40.5) 591 (23.3) 254 (10) 997 (39.25) 287 (11.3) 934 (36.8) 176 (6.93) 1017 (40.04) 212 (8.33) 1 2

CWX10 1359 (53.5) 652 (25.7) 305 (12) 1327 (52.25) 298 (11.75) 1265 (49.8) 227 (8.93) 1347 (53.04) 262 (10.33) 1 2

CWX12 1359 (53.5) 652 (25.7) 305 (12) 1327 (52.25) 298 (11.75) 1265 (49.8) 227 (8.93) 1347 (53.04) 262 (10.33) 1 2

CWX14 1359 (53.5) 652 (25.7) 305 (12) 1327 (52.25) 298 (11.75) 1265 (49.8) 227 (8.93) 1347 (53.04) 262 (10.33) 1 2

12
DIMENSIONAL DATA - COIL CONNECTIONS
CHILLED WATER COIL

DIMENSIONS

3 ROW COIL 4 ROW COIL


MODEL
A B C A B C
CWX02 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

CWX03 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

CWX04 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)
OUTLET
CWX06 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

CWX08 100 (3.91) 118 (4.63) 38 (1.5) 90 (3.53) 118 (4.63) 57 (2.25)

C CWX10 100 (3.91) 143 (5.61) 38 (1.5) 90 (3.53) 130 (5.11) 57 (2.25)

CWX12 100 (3.91) 143 (5.61) 38 (1.5) 90 (3.53) 130 (5.11) 57 (2.25)
A
CWX14 100 (3.91) 143 (5.61) 38 (1.5) 90 (3.53) 130 (5.11) 57 (2.25)
INLET NOTE: All dimensions are in mm (dimensions in brackets are in inches).
25 (1.00") B

HOT WATER COIL

DIMENSIONS
MODEL A B C D
CWX02 168 (6.63) 56 (2.22) 41 (1.63) 90 (3.53)

CWX03 168 (6.63) 56 (2.22) 41 (1.63) 90 (3.53)

CWX04 168 (6.63) 56 (2.22) 41 (1.63) 90 (3.53)

CWX06 168 (6.63) 56 (2.22) 41 (1.63) 90 (3.53)

CWX08 168 (6.63) 56 (2.22) 41 (1.63) 90 (3.53)

CWX10 219 (8.63) 56 (2.22) 41 (1.63) 90 (3.53)


OUTLET
INLET CWX12 219 (8.63) 56 (2.22) 41 (1.63) 90 (3.53)

CWX14 219 (8.63) 56 (2.22) 41 (1.63) 90 (3.53)


D B 25 (1.00")
NOTE: All dimensions are in mm (dimensions in brackets are in inches).

C
A

13
HEATER ARRANGEMENTS

HEATER BOX

SLIDING FRAME WITH HEATER

DIMENSIONS - HEATER BOX


A
DIMENSIONS
MODEL
A B C
CWX 02/03/04 685 (27) 180 (7.1) 223 (8.8)
CWX 06/08 939 (37) 180 (7.1) 223 (8.8)
CWX 10/12/14 1269 (50) 231 (9.1) 150 (5.9)
NOTE: All dimensions are in mm (dimensions in brackets are in inches).

VALVE PACKAGES
VALVE PACKAGE 3-D (for 2-pipe) VALVE PACKAGE 4-D (for 4-pipe)

1 Two gate shut off valves 1 Four gate shut off valves

2 One balancing valve 2 Two balancing valves

3 One 3-way motor valve 3 Two 3-way motor valves




1 Two gate valves )&< 

2 One balancing valve &+ ,


//(5

3 One 3-way motor valve




14
TYPICAL SCHEMATIC WIRING DIAGRAM
HEAT/COOL MODELS - ELECTRIC HEATER

TO FUSE DISCONNECT SWITCH


LEGEND
ATB AUXILIARY TERMINAL BLOCK
CAP CAPACITOR
HEATER OPTION
EV ELECTRIC VALVE
HC 0HT1 HTR1 FM FAN MOTOR
T1F
T2F GND LUG GROUND
T1G 0HT2 HTR2
HC HEATER CONTACTOR
T2G
HTR HEATER
HVTB HIGH VOLTAGE TERMINAL BLOCK
GND HVTB L/L1 LINE OR LINE 1
L/L1 L2/N
L2/N LINE 2 OR NEUTRAL
OHT OVER HEAT THERMOSTAT
___
FIELD WIRING
T'STAT ATB
FACTORY WIRING
1 1
N NOTES
N N
6 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
6 6 2. MOTORS THERMALLY PROTECTED.
7
7 7 3. HVTB IS NOT REQUIRED FOR HEATER MODELS.
20 4. USE HEATER AS PER OPTION REQUIRED. IF EV
20 20
& HEATERS ARE FACTORY INSTALLED, PLEASE
21 READ DASHED LINE AS CONTINUOUS LINE.
21 21
22
22 22

Refer to table below for Speed Connections.

SPEED HI MED-HI MED LOW LOWEST COM APPLICABLE


WIRE COLOR BLK BLU RED YEL ORG WHT FREQUENCY
IN HERTZ
MODEL
CWX 02 60
CWX 03 60
CWX 04 60
CWX 06 60
CWX 08 60
CWX 10 60
CWX 12 60
CWX 14 60

15
TYPICAL SCHEMATIC WIRING DIAGRAM
HEAT/COOL MODELS - HOT WATER

TO FUSE DISCONNECT SWITCH


LEGEND
ATB AUXILIARY TERMINAL BLOCK
CAP CAPACITOR
EV ELECTRIC VALVE (COOLING)
EV1 ELECTRIC VALVE (HEATING)
FM FAN MOTOR
GND
HVTB GND LUG GROUND
L/L1 L2/N
HVTB HIGH VOLTAGE TERMINAL BLOCK
L/L1 LINE OR LINE 1
L2/N LINE 2 OR NEUTRAL
T'STAT
___
ATB FIELD WIRING
FACTORY WIRING
1 1
N
N N NOTES
6 1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
EV1
6 6 2. MOTORS THERMALLY PROTECTED.
7
7 7 EV 3. USE COPPER CONDUCTOR WIRES ONLY.
20 4. IF EV & EV1 ARE FACTORY INSTALLED, PLEASE
20 20 READ DASHED LINE AS CONTINUOUS LINE.
21 COM
21 21 FM
22
22 22
BRN
CAP WHT

Refer to table below for Speed Connections.

FM SPEED CONNECTIONS
SPEED HI MED-HI MED LOW LOWEST COM APPLICABLE
WIRE COLOR BLK BLU RED YEL ORG WHT FREQUENCY
IN HERTZ
MODEL
CWX 02 60
CWX 03 60
CWX 04 60
CWX 06 60
CWX 08 60
CWX 10 60
CWX 12 60
CWX 14 60

16
INSTALLATION
The complete shipment should be inspected for damage. Any damage, visible or concealed, should be reported immedi-
ately to the delivery man or driver and noted on the shipping invoice.

Place unit in position and make sure that unit is level. This is important to assure proper drainage and operation. Slots
provided in the mounting brackets should be used for installing the units.

ELECTRICAL
Please ensure power supply (V-Ph-Hz) to the unit is as per unit nameplate requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
Warning: Before installation or servicing, always TURN OFF all power to the unit. There may be more than one discon-
nect switch. Ensure all of them are turned off.

GROUND & POWER WIRES


Connect power wires as per wiring diagram. Connect ground wire to the ground lug inside the control box.

MAINTENANCE
COIL
Coil may be cleaned by removing and brushing between fins with a stiff wire brush. Brushing should be followed by cleaning
with vacuum cleaner. The coil may also be cleaned by using a high pressure air, if compressed air source is available. It
should be pointed out that if air filters are used and periodically cleaned, the coils will not be clogged up prematurely.

DRAIN PIPE
Drain pipe should be checked before summer operation of unit. If it is clogged, steps should be taken to clear the debris
so that condensate will flow out easily. A standard pipe cleaner for 1/2" ID pipe may be used. Periodic checks of the drain
pipe should be taken during summer operation, as there is a possibility of it becoming clogged with dirt.

FILTER CLEANING
Remove access panel, slide filter out of filter rack, and clean as follows:
Tap filter on solid surface to dislodge heavy particles. Wash under stream of hot water. If filter has been put to exceptional
service, a mild solution of Sal-Soda, Tri-Sodium Phosphate or any other commercial solvent can be used. Set filter on
end with slots in frame down, which allows it to drain. Filters should dry thoroughly before reuse.

REPLACEMENT PARTS
When writing for replacement parts, refer to model number and serial number on the nameplate of the unit.

RECOMMENDED SPARE PARTS


PERCENTAGE OF SPARE PARTS
ITEM ONE YEAR SUPPLY TWO YEAR SUPPLY
100 UNITS 1000 UNITS 100 UNITS 1000 UNITS
EVAPORATOR BLOWER MOTOR 4 2 8 4
HEATER CONTACTOR 2 1 3 2
ELECTRIC HEATER 2 1 4 2
BLOWER WHEEL 2 1 4 2
THERMOSTAT 4 2 8 4
FILTER 4 2 6 4
NOTE : When ordering spare parts, please quote the complete model number on the unit nameplate.

17
PARTS LIST
DESCRIPTION CWX02/03/04 CWX06/08 CWX10/12/14
BLOWER WHEEL 800-711-54 800-711-51/800-711-55 800-711-52/800-711-56

BLOWER MOTOR 800-827-17 800-547-65 800-547-66

RETURN AIR FILTERS 800-250-42 800-250-40 800-250-41

THERMOSTAT 800-646-21 800-646-21 800-646-21

VALVE PACKAGE (3D) 700-364-92 700-364-92 700-364-92

NOTE: For 4D type valve package, order 2 x 3D valve packages.

18