SAFETY PRECAUTIONS

POSITIVE
RE
AD

TU
LE

Disposal Action
RN

RECYCLE Pb

Charger settings are given in page No. 10 of this manual


HBL

CONTENTS
Page No.
1. Introduction 1
2. Receiving the Shipment 1
3. Storage 2
4. Shifting of Batteries 3
5. Unpacking 3
6. Battery Installation & Commissioning 4
7. Power Plant Compatibility 8
8. Charge Settings & Recharge Durations 9
9. Acceptance Test 14

10. Performance of Batteries 14


11. Battery Monitoring 16
12. Important Points to avoid Premature Failure 17
of the Battery
13. Maintenance Procedures 19
14. Service Records 22
15. Conditions 24

APPENDICES

* Safety Precautions (Inside Front Cover)


* Do’s & Don’ts (Inside Rear Cover)
HBL

1
HBL

Table 3.2.1
Ambient temperatre Storage period (Max)
27° C 6 months
36° C 3 months
45° C 2 months

2
HBL

3
HBL

HBL
Sh Su Po
Ma erip rve
hab all y No
we
oo y Vill . 15 r sy ING
Ph
bna age 5 ste OAD
one gar Dis , Bh & 156 m UNL
: 085 t, oot s
hpu Pa rt, Lt OP P FOR
USE 42- Pin:
509 r Ma
d T DR RAM
R AMP 23 nd DO
NO USE
620 382 al
FO 5/2
R
UN CON 06 , A.P
LOA
SIG & 20 -IN
8 DIA
DIN
NE
G
E E UP
S SID
Ord THI
er T HIS
BAT SID
E UP
SET TER
Y TYP
SKI E
D

OF

HB
L
Sh Su P ow
Ma er rv
ha ipally ey No er
ob Vil lag . 15 syst
bo
Ph naga e, 5 em ING
on r Di B ho& 15 AD
6 Pa s
LO
e:
rt, Ltd
08 st, Pi othpu R
UN
54 FO
U SE 2-23 n: 50 r M OP MP
RA an T DR RA
62 9 E
05 382, dal
MP NO US
FO DO
R UN /2 06 A.
LO
CO
NS & P-IN
AD 20
GIN IGN
EE 8 DI A
UP
E
Or TH IS
SID
der TH
IS
BA SID
TT E UP
SE ER
T Y TY
SK PE
ID

OF

4
HBL

5
HBL

6
HBL

7
HBL

8
HBL

9
HBL

Table 8.3.1
Description Float application Cyclic application
Float charge
voltage @27° C 2.250 V/cell 2.270 V/cell

Boost charge
2.300 V/cell 2.350 V/cell
voltage @27° C
Equalizing charge 2.350 V/cell 2.350 V/cell
voltage @27° C
Charge current with
respect to rated C10 Min: 10% to Max: 20%
capacity
Logic for Float to Current drawn by the battery is > 3% of battery
Boost change over capacity
Logic for Boost to Current drawn by the battery is < 1% of battery
Float change over capacity
Low voltage
Shall be set @ 1.850 V/cell
disconnect
High voltage
Shall be set @ 2.400 V/cell
disconnect

10
HBL

Recommended interval for


Application
giving equalizing charge
Float For every 6 months
Cyclic For every 1 month

11
HBL

Table 8.5.1
Temperature Float charge voltage / Boost charge voltage /
cell (Volts) cell (Volts)
(° C)
± 0.005 ± 0.005
-10 to -20 2.350 2.370 2.400 2.450
0 2.331 2.351 2.381 2.431
5 2.316 2.336 2.366 2.416
10 2.301 2.321 2.351 2.401
15 2.286 2.306 2.336 2.386
20 2.271 2.291 2.321 2.371
27 2.250 2.270 2.300 2.350
30 2.241 2.261 2.291 2.341
35 2.226 2.246 2.276 2.326
40 2.231 2.261
45 to 55 2.200 2.220 2.250 2.300

12
HBL

Recharge time to attain (Hrs)


Current: 10 % Current: 15 % Current: 20 %
0 43.3 41.1 38.8
20 40.8 39.1 37.4
40 38.6 37.4 36.1
60 35.8 35.4 34.9
80 33.0 32.9 32.8

Recharge time to attain (Hrs)


Current: 10 % Current: 15 % Current: 20 %
0 24.0 21.8 19.5
20 21.5 19.8 18.1
40 19.3 18.1 16.8
60 16.5 16.1 15.6
80 13.7 13.6 13.5

Recharge time to attain (Hrs)


Current: 10 % Current: 15 % Current: 20 %
0 12.8 11.5 10.2
20 11.4 10.4 9.4
40 10.1 9.4 8.7
60 8.5 8.2 8.0
80 6.9 6.8 6.7

13
HBL

14
HBL

Discharge C/10 & C/9 C/8 C/7 C/6 C/5 C/4 C/3
Rate Above
0.43 0.45 0.47 0.50 0.54 0.58 0.62 0.68

15
HBL

2.200
Open Circuit Voltage (Volts)

2.150

2.100

2.050

2.000

1.950

1.900
0 10 20 30 40 50 60 70 80 90 100 110

% State of Charge

Graph 11.1

16
HBL
2.150
2.100
2.050
2.000
1.950
1.900
1.850
1.800
1.750
1.700
0 10 20 30 40 50 60 70 80 90 100 110

17
HBL

18
HBL

19
HBL

Sl.No. Event /Activity

I - Fort night / Monthly checks

Measurement of battery terminal voltage (both on oat & boost


1
charge)
2 Checking of charge settings
3 Cleaning of battery bank
4 Measurement of individual cell voltage

1 Equalizing charge

2 Re-torquing of terminal bolts

4 Load current and typical duty cycle

1 Checking for error in measuring instruments of Charger/Power plant

3 Applying of petroleum jelly to cell terminals

20
HBL

21
HBL
(To be generated & maintained by the user)
14.1.
1. Name of the Customer / User : _______________________
2. Address of the Customer / User : _______________________
3. Battery rating (Voltage & Capacity) : _______________________
4. Date of installation of the battery : _______________________
5. Application details : _______________________

6. Details of load / Duty cycle : _______________________

7. Expected backup time : _______________________

8. Power plant / Charger settings


Float Voltage: _________ Actual value (On battery): __________
Boost Voltage: _________ Actual value (On battery): _________
Battery path current limit: ________________________________
Logic used for Float to Boost &
Boost to Float change over:_______________________________
9. Average ambient temperature : _______________________
Following readings shall be measured with a calibrated Digital
Voltmeter for each cell.

Cell. Sl. No. Open circuit voltage in Float voltage in


Off-line condition (volts) On-line condition (volts)
1
2
,,
,,
24
Remarks : _________________________________________
Readings taken by: _________________________________________

22
HBL
1. Name of the Customer / User : _______________________

2. Address of the Customer / User : _______________________

3. Battery rating (Voltage & Capacity) : _______________________

4. Date of installation of the battery : _______________________

5. Application details : _______________________

6. Details of load / Duty cycle : _______________________

7. Expected backup time : _______________________

8. Power plant / Charger settings

Float Voltage: _________ Actual value (On battery): __________

Boost Voltage: _________ Actual value (On battery): _________

Battery path current limit: ________________________________

Logic used for Float to Boost &


Boost to Float change over:_______________________________

9. Average ambient temperature : _______________________


Following readings shall be measured with a calibrated Digital
Voltmeter for each cell.

Float voltage (Volts) Onload voltages (Volts)


Cell. Sl. No.
Load Current: Amps
1
2
,,
,,

24

Remarks : _________________________________________
Readings taken by: _________________________________________
Make a photocopy of the form shown above so that additional
copies may be made at subsequent inspections.
Note: On - load voltages shall be recorded after a minimum period
of 15 min from the time of applying the load.

23
HBL

24
HBL
DO’s & DON’Ts
Do ’ s
01.

02. Store the batteries in a cool and dry location.


03. Charge the batteries within 6 months for extending the storage
period.
04. Unpack the batteries as per the unpacking instructions.
05. Install the batteries in a cool and dry location.
06. Monitor the Charge and Float voltages of the Power Plant at
monthly intervals and adjust if required.
07. Check the tightness of all electrical connections at monthly intervals.
08. Check compatibility of Power Plant and replace/modify if
required before commissioning the battery.
09. Maintain monthly Service Record as per the format enclosed.
10. Provide adequate ventilation and illumination.
11. Ensure the cell orientation is as per the General Arrangement
Drawing.
12.
guidance.

Don'ts
01. Do not expose the packed batteries to rain.
02. Do not expose the packed batteries to sunlight.
03. Do not exceed the storage period without charging the batteries.
04. Do not install the batteries in rooms with varying temperature
pockets due to sunlight or ventilation ducts.
05. Do not short-circuit the battery or cells during assembly.
06. Do not charge the batteries in sealed cubicles.
07. Do not mix batteries of different types or makes.
08. Do not make tap connections.
09. Do not tamper with the cell vents.