Project: EKFC

CAP ID: 4P-PC1


Engineer: SZ Date: 20 Mar 2013
Review: Date:
Devision: Design REF#: 0
KEO: Abu Dhabi Page:
Code: ACI 318-08M
Units: SI

CRITERIA:
f'c 50 MPa
Ec 33234.02 MPa
fy 414 MPa
Es 200000 MPa
Concrete Cover = 75 mm
Reinforcement Bar size = 16 mm
Number of layers = 1
Pile Embadement = 150 mm
Reinforcement Type b S= Straight
B=Bent
Ultimate Factor = 1.60
Ø Shear = 0.85
INPUTS:
Column Dead Load, Nd = 17,643 KN
Column Live Load, NL = 0 KN
Column Dimension X = 900 mm
Column Dimension, Y = 900 mm
Pile Diameter, dp = 900 mm
Pile Capacity, P = 4,411 KN
Pile Spacing, L = 2,250 mm
Pile Length = 12,000 mm
Cap Dimension, A = 3,750 mm
Cap Dimension, B = 3,750 mm
Cap Dimension, D = 2,200 mm
# Dia. # Layers
As (A)= 5 19 1 1,418 mm2 Increase Reinforcement
As (B)= 5 16 1 1,005 mm 2
Increase Reinforcement
Project: EKFC
CAP ID: 4P-PC1
Engineer: SZ Date: 20 Mar 2013
Review: Date:
Devision: Design REF#: 0
KEO: Abu Dhabi Page:

CHECKS:
Minimum Pile Spacing 2.5Ø OK
Clearance/Length OK
Absolute spacing OK
Minimum Edge Distance 0.75Ø OK
Absolute Minimum OK
Clear Edge Distance OK
Number of Piles OK
Number of Reinforcement Layers OK

CALCULATIONS:
Average to center of bars, dcx = 251 mm
Average to center of bars, dcy = 233 mm
Edge distance, E = 750 mm
Horizontal Componant, wx = 675 mm
Horizontal Componant, wy = 849 mm

Finding Flexure Section


Section width, b = 3,750 mm
Section depth, dx = 1,950 mm
Section depth, dy = 1,967 mm

Finding Straining Actions


Maximum applied bending moment, M ux = 10,586 KN-m
Maximum applied bending moment, M uy = 13,043 KN-m
Maximum 1-way Shear Force,Vu = 14,115 KN
Maximum 2-way Shear Force,Vu = 28,230 KN
wx/dx ratio = 0.35
wy/dy ratio = 0.43

Finding the Critical Shear Sections


2-way at d/2 from face of column Found
2-way at face of column Critical Section at d/2
1-way at d from face of column (x) Critical Section at Column Face
1-way at d from face of column (y) Critical Section at Column Face
Project: EKFC
CAP ID: 4P-PC1
Engineer: SZ Date: 20 Mar 2013
Review: Date:
Devision: Design REF#: 0
KEO: Abu Dhabi Page:
1-way at face of column (x) Found
1-way at face of column (y) Found

Design:
Finding Applied Shear Force
2-way at d/2 from face of column 28230 KN
2-way at face of column N/A, Critical Section at d/2
1-way at d from face of column, V u (x) N/A, Critical Section at Column Face
1-way at d from face of column, V u (y) N/A, Critical Section at Column Face
1-way at face of column, Vu (x) 7058 KN
1-way at face of column, Vu (y) 7058 KN

Finding the Concrete Shear Strength (Special Investigations)


2-way at d/2 from face of column 49304 KN
2-way at face of column Critical Section at d/2
1-way at d from face of column, ØVn(x) N/A, Critical Section at Column Face
1-way at d from face of column, ØVn(y) N/A, Critical Section at Column Face
1-way at face of column, ØVn(x) 36470 KN
1-way at face of column, ØVn(y) 36797 KN

Check of Shear
2-way at d/2 from face of column OK
2-way at face of column Critical Section at d/2
1-way at d from face of column (x) N/A, Critical Section at Column Face
1-way at d from face of column (y) N/A, Critical Section at Column Face
1-way at face of column (x) OK
1-way at face of column (y) OK
Vu/ØVn Ratio (x)= 0.194
Vu/ØVn Ratio (y)= 0.192
Vu/ØVn Ratio (2-way)= 0.573