Contactors
NA10TOC1T 001222
10 Contactors
PRODUCT HIGHLIGHTS
1594
NA10TOC2T 001222
Contactors 10
Table of contents
1595
S000003 000623
Voltage codes
to be added to the contactor
Product Name Product Highlights order reference number
Product
Picture
Approvals
Characteristics
Notes
Supplements
1607
1596
S000005 000731
Overview
Contactors + Thermal overload relays 2.2 kW...270 kW
Technical details Power
Ie max. AC 3 3 ~ AC 3 at 460 V Thermal overload relays
(Ve ≤ 440 V) 380...415 V 3 ph.
in A in kW in HP
KL 2 S - 10
KL 2 S - 01 6 2.2 3
M 06
KL 4 S - 10 9 4 5
KL 4 S - 01
DL 4 K - 10
DL 4 K - 01 9 4 5
DL 4 K - 22
DL 5 K - 10
DL 5 K - 01 12 5.5 7.5
DL 5 K - 22
M 23 K
DL 7 K - 10
DL 7 K - 01 16 7.5 10
DL 7 K - 22
DL 11 K - 10
DL 11 K - 01 23 11 15
DL 11 K - 22
DL 15 K 30 15 20
DL 15 K - 22
Contactors
M 40 K
DL 18 K 37 18.5 25
DL 18 K - 22
DL 22 N - 22 44 22 30
DL 30 N - 22 60 30 40
M 80 N
DL 42 N - 22 79 40 50
1597
S011001 000919
Control relays HL 4 K, HL 8 K
Contactors 4-18.5 kW at 380 V, 3 ph.
(5-25 HP at 460 V, 3 ph.)
Accessories and spares
Contactors
22-270 kW at 380 V, 3 ph.
(30-400 HP at 460 V, 3 ph.)
Technical details
DL 22 N to DL 270 N
Pages 1619-1629 Standards, fusing
Contact life
Dimensions
See individual section
Reversing and
star-delta contactors
Mini contactors
2.2 + 4 kW at 380 V, 3 ph.
(3 + 5 HP at 460 V, 3 ph.)
Reversing contactors
DLW 4 K - 90 N
Star-delta contactors
DLDAe 7.5 k - 500 N Control relays and contactors
Pages 1624-1627 KH and KL, AC + DC
Pages 1635-1654
1598
NOTES
1599
S011003 000623
Characteristics of Switchgear
Explanations of the new terms as defined in IEC 947-1 / EN 60947-1
Terms Definition
Rated control supply voltage Vs The voltage which is applied to the input terminals of the control circuit of a switching
(IEC 947-1; 4.5.1) device.
Rated operational voltage ve The voltage to which the characteristic values of a switching device are referred. In no
(IEC 947-1; 4.3.1.1) case shall the maximum rated operational voltage exceed the rated insulation
voltage.
Rated insulation voltage Vi The voltage to which dielectric tests and creepage distance are referred. In no case
(IEC 947-1; 4.3.1.2) shall the maximum rated operational voltage exceed the rated insulation
voltage.
Rated impulse withstand voltage Vimp Indicates the resistance of the clearances inside a switching device to impulse voltages.
(IEC 947-1; 4.3.1.3) By using appropriate switchgear it can be ensured that no overvoltage from the supply
voltage in which the devices are employed can be transferred to parts which have been
switched off.
Rated operational current Ie The current which a switching device can carry taking into account the rated operational
(IEC 947-1; 4.3.2.3) voltage, the rated duty, the utilization category and the ambient temperature.
Convertional free air thermal current Ith The maximum current a switching device can carry over a duty cycle of at least 8 hours
(IEC 947-1; 4.3.2.1) without the temperature rise exceeding specified levels. It normally corresponds to the
maximum rated operational current.
Rated uninterrupted current IU The current a switching device can carry without interruption (for periods of weeks) (IEC
947-1; 4.3.2.4) months, or years).
Rated conditional short-circuit current Iq The short-circuit current which a switching device (e.g. contactor) protected by a short-
(IEC 947-1; 4.3.6.4) circuit protective device (e.g., manual motor starter) can carry during the breaking time of
the protective device.
Rated short-time withstand current ICW Of a switching device is its capability to carry the short-time current during a specified
(IEC 947-1;4.3.6.1) time without impairment (e.g., by excessive rise of temperature).
Rated breaking capacity Indicates the current which a switching device can break in accordance with its utilization
(IEC 947-1; 4.3.5.3) category. The rated breaking capacity is stated by reference to the rated operational
voltage and rated operational current.
Rated making capacity The current stated by the manufacturer which the switching device can make in
(IEC 947-1; 4.3.5.2) accordance with its utilization category. The rated making capacity is stated by reference
to the rated operational voltage and rated operational current.
Utilization category The utilization category of a switching device determines its intended application and
(IEC 947-1; 4.4) gives information on its suitability regarding making and breaking and short-circuit
capacities, e.g., AC 3: Starting, switching off three-phase AC motors during running.
Rated frequency The frequency for which a switching device is designed and to which the other
(IEC 947-1; 4.3.3) characteristics are referred.
Protection against contact - Covers all design features to prevent direct contact (without the use of a tool) with live
direct contact system parts (finger proof, back-of-hand proof).
(IEC 536)
Fingerproof A switching device is considered to be finger proof if its live parts cannot be touched
(IEC 536) when actuating the operating elements. This also applies when neighboring switching
devices are operated. The fingerproof area of a push-actuated mechanism is a circular
area having a radius of 30 mm min. around the operating element at right angles related
to the direction of operation. Within this area, all hazardous parts should be located at
least 80 mm below the operating level.
Back-of-hand proof A switching device is considered to be back-of-hand proof it its live parts cannot be
(IEC 536) touched by a ball having a diameter of 50 mm.
Creepage distance The shortest distance along the surface of an insulating material between two conducting
(IEC 947-1; 2.5.51 / IEV 151-03-37) parts. It is determined by the rated insulation voltage, pollution degree and creep
resistance of the material.
Clearance The distance between two conducting parts along a string stretched the shortest way
(IEC 947-1; 2.5.46 / IEV 441-17-31) between these conducting parts. It is determined by the rated impulse voltage, over-
voltage category and the pollution degree.
1600
S011004 000623
Characteristics of Switchgear
Explanations of the new terms as defined in IEC 947-1 / EN 60947-1
Terms Definition
Opening delay The time between operating and first opening of a contact.
Closing delay The time between operating and first closing of a contact.
Safe isolation Reinforced or double insulation which reliably prevents voltage transfer from one circuit to
(VDE 0106 Teil 101; 2) another. Safe isolation is of particular significance between main and auxiliary circuits of switchgear.
Separating function A switching device whose switch contacts, when in the open position, achieve the prescribed
(IEC 947-1; 2.1.19) opening gap (separating gap) which is required to separate circuits. The entire system or part of it
can thus be disconnected from power supply for safety reasons.
Shock resistance The property of a switching device to withstand pulse-like motion without changing the operating
state and remain undamaged. Contacts shall not lift off while the switching devices are in the ON
position; the main contacts shall not strike together in the OFF position.
Overvoltage category In accordance with overvoltages (e.g. by lightning or during switching on/off) which might occur
(IEC 947-1; 2.5.60) at the location where switchgear is installed, the following overvoltage categories have been
(IEC 664) established.
(VDE 0109 part 1, preliminary) Overvoltage category IV:
Applies to the use directly at the connecting point of the installation (direct lightning influence may
occur) e.g., on an overhead cable connection.
Overvoltage category III: (applies to switchgear for industrial use)
Equipment for connection in stationary installations which are protected by overvoltage suppressing
equipment, e.g., switches employed in low voltage distribution plants or controls for industrial use.
Overvoltage category II:
Power consumption equipment for connection to stationary installations, e.g. household appliances,
power-driven tools.
Overvoltage category I:
Equipment for connection to circuits using overvoltage protective equipment, e.g., electronic
equipment.
Ambient temperature, open The temperature of the room in which a switching device is installed.
(IEC 947-1; 2.1.9 / IEV 441-11-13)
Ambient temperature, enclosed The temperature at which an enclosed switching device can be operated, taking into account that
(IEC 947-1; 2.1.9 / IEV 441-11-13) power consumption of the switching device will cause additional rise of temperature inside the
enclosure.
Pollution degree Indicates the expected amount of conductive dust and humidity which might reduce the electric
(IEC 947-1; 6.1.3.2) strength of a switching device. The degrees of pollution are characterized as follows:
Pollution degree 1:
None or only dry nonconducting pollution, not having any influence.
Pollution degree 2:
Normally nonconducting pollution only. Temporary conductivity due to condensation, however, is
to be expected.
Pollution degree 3: (switchgear for industrial use)
Conducting pollution or dry non-conducting pollution which turns conductive by condensing.
Pollution degree 4:
Pollution will lead to continuous conductivity, e.g., caused by conducting dust, rain, or snow.
Power consumption The energy inside equipment, e.g., by contact resistance of current paths, operating coils,
power supplies, or similar, which is converted to heat.
Coordination type Describes the condition of a switchgear assembly (motor starter) during and after the test carried
(IEC 947-4-1; 8.3.4.2.3) out with the rated conditional short-circuit current:
Type "1" coordination:
- No danger to persons and systems.
- No immediate readiness for service required.
- Damage to starter is acceptable.
Type "2" coordination:
- No danger to persons and systems.
- Starter is suitable for further service.
- No damage to starter except slightly welded switch contacts after these have easily been
separated without significant deformation.
Positively driven operation The auxiliary contacts of a switching device are always in the same (open or closed) switch
(IEC 947-1; 2.4.11 / IEV 441-16-12) position as the supply voltage contacts.
1601
S011005 000731
ENTRELEC-SCHIELE products are designed and manufactured in conformity with all relevant national and international specifications and standards.
Control relays VDE 0660, IEC 337, IEC 947-1, IEC 947-5-1, EN-60 947-1 / EN-60 947-5-1
Contactors VDE 0660, IEC 947-1, IEC 947-4-1, EN-60 947-1 / EN-60 947-4-1
The products have been approved "E" by the following official test authorities, or approval has been applied for and is pending "B".
Germanischer
DL 90 N E E E
DL 110 N E E E
DL 132 N E E E
DL 165 N E E E
DL 245 N E E E
DL 270 N
Control relays
HL 4 K- E E E E E
HL 4 K DC E E E
HLg 4 K- E E E E
KH .. E E E E
Accessories
RM-K module E E E
Pneumatic
E
timer PZ
Electromechanical
E
latch head MV-BN
Aux. con. bl. S11/S20 E E E E E
1602
S011006 000623
They have been approved (E) by following official test authorities, or approval has been applied for and is pending (B).
Germanischer
USA Canada Switzerland Finland Norway DEMKO Lloyd
(Denmark) Germany
M 23 K E E E E E E
M 40 K E E E E E
M 80 N E E E E E
M 06 E E B B
Mb - 177 S E E E E
Comments
Certain product groups are subject to testing and approval in various countries. The products obtain a certificate of conformity and must bear the mark of
conformity of the responsible test authority.
"Recognized" ( ) The devices are approved for factory wiring, i.e., they must be handled by skilled personnel. The devices may not necessarily bear
the ( ) sign.
"Listed" (UL) The devices are approved for field wiring and factory wiring and also for sale as loose items in the U.S.A. The devices must bear the
listing mark.
Marine classifications
When using electrical switchgear on shipboard, the relevant rules for building of vessels of the following marine classifications societies must be taken into
consideration:
1603
S011007 000919
General
Contactors and control relays K range contactors up to 18.5 kW, KL 2, KL 4 mini contactors and
KH control relays include 50/60 Hz coils as standard. All other
Contactors and control relays, now as ever, play a vital role even contactor sizes are fitted with 50 Hz coils.
though modern electronics are increasingly spreading into the domain Non-standard coil voltages are available on request.
of traditional controls. ENTRELEC-SCHIELE contactors feature long Order reference
mechanical life, high switching capacity, and operational reliability.
Control relays are employed in control circuits while contactors are Each device uses a 9-digit order reference. The first 7 digits define
designed to switch three-phase and DC motors and for use in power device type, the last 2 digits, the coil voltage.
factor correction systems as well as in heating and lighting power Example: 7.5 kW contactor (10 HP)
circuits. As motor protection and monitoring is gaining increasing DL 7K-10, 230 V, 50/60 Hz
significance, the product range has been extended to include new order ref. 1 366 201 40
motor protection equipment.
The table below shows standard coil voltages of contactors and ALPHA
control relays. Special code numbers are used for their identification,
e.g. 06 for 24 V. ENTRELEC-SCHIELE is a member of the Society for Testing and
Certification of Low Voltage Switchgear e.V. ALPHA, Frankfurt/
Main, Germany.
Code no. Voltage (AC) Voltage (DC)
06 24 V 24 V The responsibility of the manufacturers and the assurance of high
13 42 V - product quality is supported by ALPHA and assisted by procedure
25 110 V 110 V directives for product testing according to existing standards.
29 127 V -
Having fulfilled specified requirements, ALPHA will issue, on
request, state-registered product certificates.
40 230 V 220 V
ALPHA also strives towards an international recognition of the
59 400 V - declarations of conformity and certification.
1604
S012003 000623
Compact-contactors
45 mm wide
✓ powerful
✓ modular
Control relays and contactors
fingerproof
Contact reliability
selective coil termination connections
Contact reliability
High contact reliability of control circuit by the
use of ENTRELEC-SCHIELE-twin aux. contacts
Contact reliability increased by a factor of 1.000
to 10.000 compared to standard contacts
Connection
Large terminal space for cables up to
2 x 6 mm2 / ...25 mm2
Coil terminations for one-sided or diagonal wiring
Safety in operation Coil suppressor snaps directly to coil terminal
Colored coil voltage marking acc. to 309-1
Safety in operation
Fingerproof to VDE 0106: Pt. 100
Approvals
Designed to comply with all major national and
international standards
Handling
Ergonomic, user-friendly design
Approvals Active and passive control elements are colored
differently
Large clip-on front label for identification
purposes
Terminals arranged for quick and simple mounting
Cost / performance
Handling Favorable cost / performance ratio
Comprehensive range of components to
complete the system family
Cost / Performance
1605
S012004 000919
HL 4 K
✔ Relay interface module DL 4 K
the interfacing element from
programmable controller to contactor
DL 5 K
(other modules on pages 1616-1617)
DL 7
7K
DL 11 K
DL11
DL 15 K
DL15
DL 18 K
DL18
see pages 1607-1613
✔ Coil suppressor ✔ Contactors
snaps on directly
types : RC-K, D-K, V-K 4 to 18.5 kW at 380 V, 3 ph.
5 to 25 HP at 460 V, 3 ph.
✔ AC coil - 50/60 Hz
✔ Mechanical
interlock
for side mounting
✔ Electromechanical
type : MV-e latch head
clips on to front of contactor
type : MV-BN
✔ Pneumatic timer
clips on to front of contactor
delay on energization or
de-energization up to 180 secs
types : PZ-a, PZ-r
1606
S012005 000623
Approvals:
Further notes at the bottom of this page.
Characteristics
Control relays HL 4 K-, AC-operated
Rated current Ith Type Order ref.: Contact Circuit diagram / Weight
see supple- configuration numbering to kg
For dimensions see page 1674
ments at the DIN EN 50 011
A top right N/O N/C E/M L/B
HL 4 K-31 1 366 404 .. 3 1 0.38
* Use control relay HL 4 K-40 + aux. contact block Hi ... when designing control to DIN EN 50 011.
Characteristics
Control relays HLg 4 K-, DC-operated
(separate pull-in/hold windings)
Rated current Ith Type Order ref.: Contact Circuit diagram / Weight
see supple- configuration numbering to kg
ments at the DIN EN 50 011 For dimensions see page 1674
A top right N/O N/C
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact blocks - page 1613
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Further system components - pages 1613-1617
1)
Color code to IEC 309-1 printed on the coil. Technical details - page 1671
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
Possible auxiliary contact block combinations - page 1615
1607
S012006 000731
Control relays
HL 4 K DC and HL 8 K DC
DC-operated
Approvals:
Characteristics
Control relays HL 4 K DC, HL 8 K DC, HL 100 DC, DC-operated
Rated current Ith Type Order ref.: Contact Circuit diagram / Weight
see supple- configuration numbering to kg
ments at the DIN EN 50 011 For dimensions see page 1675
A top right N/O N/C E/M L/B
16 HL 4 K DC-31 1 367 361 .. 3 1 0.72
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact blocks - page 1613
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Further system components - pages 1613-1617
1)
Color code to IEC 309-1 printed on the coil. Technical details - page 1671
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
Possible auxiliary contact block combinations - page 1615
1608
S012008 000919
Contactors
DL 4 K to DL 18 K
4-18.5 kW / 5-25 HP at 460 V, 3 ph. (AC 3),
AC-operated,
3 main contacts,
Versatile compact contactors
integral aux. contacts Auxiliary contacts are ENTRELEC-SCHIELE-twin
on sizes up to 11 kW aux. contacts
Simple mounting with integral snap-on mount,
with provision for screw attachment
Ample wiring space and connecting terminals
with plus/minus screws and self-lifting clamps
which are supplied in the "open" position allow
fast and economic wiring
Finger protection to VDE 01060 Part 100
Bi-frequency coils - 50/60 Hz
Expandable due to comprehensive system
components - 2- and 4-pole contact blocks,
mechanical interlock, electromechanical latch
head and pneumatic timer
Safety isolation up to 400 V AC of coil and
contact elements to DIN VDE 0106:
Part 101 and A1
Our control relays and compact contactors are
delivered with bi-frequency coils for 50/60 Hz.
Approvals: Further notes at the bottom of this page.
Characteristics
Max. AC 3 ratings Rated Contactor Order ref.: Circuit diagram / Weight Suitable
of 3-phases motors (kW) operational type numbering to kg therm.
For dimensions
current Ie see supple- DIN EN 50 005 and overload
see page 1674
AC 1 / AC 3 ments at the DIN EN 50 012 relay
230 V 400 V 500 V 690 V A top right
DL 4 K-10 1 366 001 .. 0.38
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Type DL 4 K-22 to DL 18 K-22 contactors are supplied with the auxiliary contacts fitted.
(Short-term availability) DC: 24, 110 and 220 V Auxiliary contact blocks - page 1613
Other coil voltages on request
Further system components - pages 1613-1617
1)
Color code to IEC 309-1 printed on the coil.
Technical details - page 1667
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
Possible auxiliary contact block combinations - page 1615
1609
S012009 000919
Contactors
DL 4K to DL 18 K
4-18.5 kW / 5-25 HP at 460 V, 3 ph. (AC 3),
AC-operated,
3 or 4 main contacts,
no integral aux. contacts Versatile compact contactors
Auxiliary contacts are ENTRELEC-SCHIELE-
twin aux. contacts
Simple mounting with integral snap-on mount, with
provision for screw attachment
Ample wiring space and connecting terminals with
plus/minus screws and self-lifting clamps which
are supplied in the "open" position allow fast and
economic wiring
Finger protection to VDE 01060 Part 100
Bi-frequency coils - 50/60 Hz
Expandable, due to comprehensive system
components - 2- and 4-pole contact blocks,
mechanical interlock, electromechanical latch head
and pneumatic timer
Safety isolation up to 400 V AC of coil and contact
elements to DIN VDE 0106: Part 101 and A1
(draft 2/98) Our control relays and compact contactors are
delivered with bi-frequency coils for 50/60 Hz.
Approvals : Further notes at the bottom of this page.
Characteristics
Max. AC 3 ratings Rated Contactor Order ref.: Circuit diagram / Weight Suitable
of 3-phase motors (kW) operational type numbering to kg therm. For dimensions
current Ie see supple- DIN EN 50 005 overload see page 1674
AC 1 / AC 3 ments at the relay
230 V 400 V 500 V 690 V A top right
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact blocks - page 1613
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Further system components - pages 1613-1617
1)
Color code to IEC 309-1 printed on the coil. Technical details - page 1667
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
Possible auxiliary contact block combinations - page 1615
1610
S012010 000919
Contactors
DL 4 K DC to DL 18 K DC
4-18.5 kW / 5-25 HP at 460 V, 3 ph. (AC 3),
DC-operated
Versatile compact contactors
Auxiliary contacts are ENTRELEC-SCHIELE-twin
aux. contacts
Simple mounting with integral snap-on mount, with
provision for screw attachment
Ample wiring space and connecting terminals with
plus/minus screws and self-lifting clamps which
are supplied in the "open" position allow fast and
economic wiring
Finger protection to VDE 01060 Part 100
Expandable, due to comprehensive system
components - 2- and 4-pole contact blocks,
mechanical interlock, electromechanical latch head
and pneumatic timer
Safety isolation up to 400 V AC of coil and contact Further notes at the bottom of this page.
elements to DIN VDE 0106: Part 101 and A1
(draft 2/98)
Approvals:
Characteristics
Max. AC 3 ratings Rated Contactor order ref.: Circuit diagram / Weight Suitable
of 3-phase motors (kW) operational type numbering to kg therm.
For dimensions
current Ie see supple- DIN EN 50 005 and overload
see page 1675
AC 1 / AC 3 ments at the DIN EN 50 012 relay
230 V 400 V 500 V 690 V A top right
DL 4 K DC-10 1 367 001 .. 0.72
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact blocks - page 1613
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Further system components - pages 1613-1617
1)
Color code to IEC 309-1 printed on the coil. Technical details - page 1667
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
Possible auxiliary contact block combinations - page 1615
1611
S012011 000919
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact blocks - page 1613
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Further system components - pages 1613-1617
1)
Color code to IEC 309-1 printed on the coil. Technical details - page 1667, 1669
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
Possible auxiliary contact block combinations - page 1615
1612
S012012 000919
Approval:
Characteristics
Auxiliary contact blocks "without plunger" Auxiliary contact blocks "with plunger" for manual operation
Front mounting Front mounting
for contactor Type Circuit diagram Order ref.: for contactor Type Circuit diagram Order ref.:
1)
DL 15 K 1) DL 15 K
Li-11 3 369 031 01 Li-11 3 369 231 01
DL 18 K DL 18 K
and contactors and contactors
Li-22 3 369 208 01
on page 1610 Li-22 3 369 008 01 on page 1610
1) 4)
1) 4)
DLg 15 K
DLg 15 K
DLg 18 K Lig-22 3 369 221 01
DLg 18 K Lig-22 3 369 021 01
on page 1612
on page 1612
3)
2)
DL 4 K to Hi-11 3 369 211 01
DL 4 K-10 to Li-11 E 3 369 035 01
3)
HLg 4 K Hi-20 3 369 212 01
DL 4 K to Hi-11 3 369 011 01
Notes
1)
Li-11 ... Lig-22 for use with contactors having no integral auxiliary contact. Technical details - page 1671
Circuit diagram to DIN 50012
2)
Permissible auxiliary switch combinations on K range contactors - page 1615
Li-11 E ... Li-31 E for use with contactors with an integral N/O auxiliary
contact. Circuit diagram to DIN 50012 Hints regarding terminal numbering - page 1615
3)
Hi-11 ... Hi-31 for use with contactors and control relays
4)
Numbers put into brackets = old terminal numbering Dimensions - page 1674
1613
S012013 000919
Characteristics
Coil suppressors
RC-coil suppressors (for use with AC operated contactors) Pneumatic timer PZ
Type Voltage range Order ref.: Type Time range Order ref.:
2)
RC-K 01 24...48 V AC/DC 3 366 035 01 PZ-a 0.1...3 s 3 357 019 01
Notes
1)
Detailed information - page 1615 Use of system components - page 1615
2)
Not suitable for use with DL 4 K DC and DL 5 K DC contactors
Further accessories - pages 1616-1617
1614
S012015 000919
Type : Hi (4 pole) ✘ ✘
Type : Li (2 pole) ✘ ✘ ✘
Type : Li (4 pole) ✘
Timer
Type : PZ-a (delay on energization) ✘ ✘ ✘ ✘ ✘ ✘1) ✘ ✘ ✘
Timer
Type : PZ-r (delay on de-energization) ✘ ✘ ✘ ✘ ✘ ✘1) ✘ ✘ ✘
1615
S012016 000919
Characteristics
Modules1)2)
Low-signal module (with integral coil suppressor) Timer module
Type Voltage range Order ref.: Type Voltage and time range Order ref.:
24 V AC/DC 3 366 214 01 24...240 V AC/DC
ZM-K ... 0.2...4 s 3 366 207 01
42 V AC/DC on request delay on energization ... 1.5...30 s 3 366 207 02
NP-K ... 12.5...250 s 3 366 207 03
230 V AC/DC 3 366 214 31
400 V AC on request
Application :
Reliable switching of low level voltages and currents in uninterrupted Application :
duty. Panel building, simple control sequences.
Application :
Application : Interface between programmable controller and AC operated K range
Star-delta starters up to 30 kW/400 V. contactors up to 18.5 kW and K range control relays.
Notes
1)
Technical specification - page 1617
2)
Safety isolation of coil and contact elements as defined by DIN VDE 0106
Part 101 and A1 (draft 2/89) is not possible with these modules.
1616
S012017 000919
Dimensions
module
contactor
Max. load curve at Circuit diagram
Function
resistive load "Delay on energization"
Timing starts when the supply is
applied - via an external control
contact, for ex. - to contactor
and timer which are connected in
series. The thyristor triggers and
energizes the contactor once the
set delay time has elapsed. The
Approvals : RM-K module ZM-K works as a "switch delay
unit"
Technical data NP-K module YZ-K module ZM-K module RM-K module
Output circuit Thyristor Thyristor RM-K 01
Min. load current 20 mA 20 mA Input: 19...40 V DC
Max. load current 0.5 A at 20°C amb. temp. 0,5 A at 20°C amb. temp. 15...30 mA
Load current de-rating 10 mA/°C 10 mA/°C Output: 415 V AC
Max. surge current ≤ 20 A for t ≤ 20 ms ≤ 20 A for t ≤ 20 ms AC 11 : 1.5 A
Relay 1 N/O contact 470 Ω
Relay contact Ruthenium reed contact 0.15 µF
Contact resistance 200 mΩ max. (initial value)
Max. switching voltage 200 V =/∼ (peak)
Max. switching current V > 12 V : 0.05 A =/∼ (peak) RM-K 02
V ≤ 12 V : 0.75 A =/∼ (peak) Input: 19...40 V DC
Max. switching capacity 10 V A 15...30 mA
Dielectric strength 350 V =/∼ min. between Output: 250 V AC
open contacts AC 11 : 1.5 A
2000 V ~ min. between 220 Ω
input - output circuit 0.22 µF
Input circuit
Supply voltage and power consumption 24 V AC/DC - 0.072 W
42 V AC/DC - 0.132 W Contact life:
230 V AC/DC - 0.800 W 2 million operations (approx.)
Supply voltage range A1-A2 24...240 V AC 24...240 V AC/DC
Voltages loss while timing (A1/A2) ≤ 3 V (A1/A2) ≤ 3 V
Power consumption while timing ≤ 2 mA (24...60 V AC) ≤ 2 mA (24...60 V AC/DC) Function :
≤ 8 mA (60...240 V AC) ≤ 8 mA (60...240 V AC/DC) 1. A DC voltage, e.g. 24 V, to
Supply voltage tolerance -15 %, +10 % energize the RM-K coil is
Supply voltage frequency 50...60 Hz applied to terminals - and +.
Ambient temperature range -20°C ... +60°C 2. An AC voltage, e.g. 230 V,
Switch position indication LED red LED red LED red is applied to terminals A0
Time circuit and A2. The contactor coil is
Recovery time 150 ms 150 ms energized by the RM-K
Repetitive accuracy ± 0.2 % ± 0.2 % contact.
Timing error within tolerance of supply voltage ≤ 0.5 % ≤ 0.5 %
Timing error within tolerance of ambient temperature ≤ 0.07 % / °C ≤ 0.07 % / °C LED green
Ambient temperature range -20°C ... +60°C -20°C ... +60°C
Time range (delay on energization) 1.5...30 s 1.5...30 s
Notes
1)
Safety isolation of coil and contact elements as defined by DIN VDE 0106
Part 101 and A1 (draft 2/89) is not possible on modules.
1617
S012018 000623
Our control relays, compact contactors and mini contactors are delivered
with bi-frequency coils for 50/60 Hz.
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request
1)
Color code to IEC 309-1 printed on the coil. Only for compact contactors HL 4 K / HL 8 K and DL 4 K - DL 18 K
1618
NA10FC1T 001222
Contactors
high power
1619
S013003 000919
Contactors
DL 22 N to DL 270 N
22-270 kW / 30-400 HP at 460 v, 3 ph. (AC 3),
AC-operated
Robust 3-pole motor contactors for AC 3 ratings
from 22 kW to 270 kW
Types DL 22 N to DL 90 N are creep resistant as
standard
Expandable by the use of additional auxiliary contacts
N/O contacts, N/C contacts, E/M contacts,
L/B contacts
Safety isolation up to AC 400 V of coil and contact
elements to DIN VDE 0106 Part 101 and A1
(draft 2/89)
Terminals shrouds to VDE 0106 Part 100
integral on sizes DL 22 N to DL 42 N
supplied as loose items with sizes DL 65 N
to DL 90 N* to be ordered separately for sizes
DL 110 N to DL 270 N - page 1623
* If required to be ordered
under Ref. no.: 3 284 148 04. Our N-contactors are available with mono-
Delivery free of charge (page 1623) frequency coils for 50 or 60 Hz. Please refer to
the listing below for the corresponding order
Approvals: reference.
Further notes at the bottom of this page.
Characteristics
Max. AC 3 ratings Rated Contactor Order ref.: Order ref.: Circuit diagram / Weight Suitable
For
of 3-phase motors operational type for 50 Hz for 60 Hz numbering kg therm.
dimensions
current Ie see supple- see supple- DIN EN 50 005 and overload
see pages
AC 1 / AC 3 ments at the ments at the DIN EN 50 012 relay
1676-1678
230 V 400 V 500 V 690 V A top right top right
50 90 110 110 260/170 DL 90 N-22 1 284 531 .. 1 284 533 .. 3.2 M-b 177 S
60 110 132 160 290/205 DL 110 N-22 1 243 501 .. 1 243 503 .. 9.0 M-bw 207 S
75 132 160 180 360/245 DL 132 N-22 1 292 001 .. 1 292 003 .. 9.0 M-bw 207 S
M-bw 320 S
90 160 180 180 380/295 DL 165 N-22 1 208 772 .. 1 208 774 .. 18 M-bw 320 S
115 250 250 270 500/460 DL 245 N-22 1 283 332 .. 1 283 334 .. 18 M-b 721 Sw
160 270 345 270 600/499 DL 270 N-22 1 184 501 .. 1 184 503 .. 30 M-b 721 Sw
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V (50Hz) Technical details - page 1668
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors HL 4 K / HL 8 K and DL 4 K - DL 18 K
1620
S013005 000919
100/60 DL 30 N-22 1 212 506 .. 1.2 90 90 95 90 90 25 DLg 32 N-22 1 244 081 .. 1 244 075 .. 1 244 077 ..
130/79 DL 42 N-22 1 244 261 .. 2.1 115 115 115 115 115 60 DLg 42 N-22 1 244 309 .. 1 244 303 .. 1 244 305 ..
230/119 DL 65 N-22 1 284 351 .. 3.2 200 200 200 200 200 90 DLg 65 N-22 1 284 399 .. 1 284 393 .. 1 284 395 ..
260/170 DL 90 N-22 1 284 537 .. 3.2 230 230 230 230 230 150 DLg 90 N-22 1 284 605 .. 1 284 599 .. 1 284 601 ..
290/205 DL 110 N-22 1 243 507 .. 9.0 260 260 260 260 260 200 DLg 110 N-22 1 243 605 .. 1 243 591 .. 1 243 593 ..
360/245 DL 132 N-22 1 292 015 .. 9.0 315 315 315 315 315 200 DLg 132 N-22 1 292 097 .. 1 292 091 .. 1 292 093 ..
380/295 DL 165 N-22 1 208 778 .. 8 340 340 340 340 340 250 DLg 165 N-22 1 208 838 .. 1 208 832 .. 1 208 834 ..
500/460 DL 245 N-22 1 283 338 .. 18 460 460 460 460 460 300 DLg 245 N-22 1 283 398 .. 1 283 391 .. 1 283 394 ..
600/499 DL 270 N-22 1 184 507 .. 30 540 540 540 540 540 350 DLg 270 N-22 1 184 627 .. 1 184 621 .. 1 184 623 ..
Main circuit
to be wired by customer
to be connected by customer
to be wired by customer
to be connected by customer
Notes
1)
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Color code to IEC 309-1 printed on the coil.
(Short-term availability) DC: 24, 110 and 220 V Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
Other coil voltages on request
1621
S013004 000919
Approvals:
Characteristics
It is possible to increase the number of auxiliary contacts by factory-fitted contacts
Aux. contact : 2 N/O + 2 N/C + 1 N/O + 1 N/C + 2 N/O + 2 N/C
Notes
The distinctive number should be added to the contactor type when orders are ❐ width remains unchanged !
placed. Example: DL 22 N-22.
Specials with E/M and L/B contacts can be supplied such that both contacts are fitted
in place of standard N/C and N/O contacts, or they can be additionally incorporated.
1622
S013019 000731
Accessories :
Links, RC coil suppressors,
terminal shrouds and mechanical interlock
Pairs of links, single pole
Pairs of links are used to bridge the main contact terminals of 3 pole
contactors so that they can be used as single pole contactors for higher
ratings (approx. twice the value)
For use with contactor type Order ref.:
DL 22 N / DL 30 N 3 212 315 00
DL 42 N 3 244 080 01
Terminal cover for use with contactors and thermal overload relays
to protect against accidental contact to VDE 0106 Part 100
For use with contactor type Order ref.: Notes
DL 65 N / DL 90 N 3 284 148 04 to be ordered separately
DL 90 N + M-b 177 S / DL 65 N + M-b 177 S 3 284 148 05 to be ordered separately
DL 110 / 132 N + M-bw 207 S 3 243 049 01 to be ordered separately
DL 110 N ... 270 N 3 284 156 02 shroud with M 12 connecting screw (1 set = 6 off)
M-bw 17 S ... M-bw 207 S 3 222 019 01 to be ordered separately
M-b 177 S 3 222 018 01 to be ordered separately
DLDAe 110 / 160 N 3 284 148 03 to be ordered separately
Mechanical interlocks
Possible combination
DL 22 N / 30 N DL 42 N DL 65 N / 90 N DL 110 N / DL 132 N DL 165 N / DL 245 N DL 270 N
DL 65 N / 90 N - - 3 244 077 02 - - -
1623
S013008 000919
Reversing contactors
DLW 4 K ... DLW 65 N
4...63 kW / 5-75 HP at 460 V, 3 ph. (AC 3),
AC-operated
Special contactor assemblies designed to reverse
direction of rotation of three-phase motors
Available for ratings from 4 kW to 63 kW; higher
ratings on request
Available with or without thermal overload relay
Mounted on DIN rail or base-plate
Types DLW 4 to DLW 18 K mechanically interlocked
as standard
50 90 110 110 170 DLW 90 N - 1 284 657 .. 1 284 659 .. 2 2 M-b 177 S 11
Note: Enclosed contactors with higher power ratings are available on request.
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V The reversing contactors up to DLW 18 K are factory fitted with 2-pole aux. contact blocks.
(Short-term availability) DC: 24, 110 and 220 V Free contacts, see table. Additional free contacts on request at extra cost.
Other coil voltages on request The voltage code number has to be added according to the above table to the contactor
order reference number.
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
2)
Delivery: Reversing contactors to DLW 18 K mounted on DIN rail.
3)
The selected thermal overload relays have to be set to the rated motor
current. They have to be ordered separately, see pages 1682-1683.
1624
S013010 000919
45 75 90 100 140 DLDAe 75 N - 1 284 285 .. 1 284 287 .. M-b 177 S 7.9
63 110 132 132 200 DLDAe 110 N - 1 284 223 .. 1 284 225 .. M-b 177 S 12.8
90 160 160 132 300 DLDAe 160 N - 1 284 723 .. 1 284 725 .. M-b 177 S 20.0
110 200 200 200 370 DLDAe 200 N - 1 243 301 .. 1 243 303 .. M-bw 320 S 20.4
150 250 250 250 460 DLDAe 250 N - 1 292 271 .. 1 292 273 .. M-bw 320 S 25.0
180 360 420 420 610 DLDAe 360 N - 1 283 241 .. 1 283 243 .. M-b 721 Sw 57.0
300 500 550 550 890 DLDAe 500 N - 1 184 801 .. 1 184 803 .. M-b 721 Sw 85.5
Notes
3)
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V The selected thermal overload relays are normally set to 0.58 times the value of
(Short-term availability) DC: 24, 110 and 220 V the rated motor current. They have to be ordered separately.
Other coil voltages on request See pages 1682-1683.
4)
Separate terminals are required for the connection to the supply.
1)
Color code to IEC 309-1 printed on the coil. Delivery : up to DLDAe 30 K mounted on DIN rail
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K from DLDAe 37 N mounted on base plate
2)
The control contacts built into the contactor are first used.
1625
S013011 000919
Contactor configuration of
star-delta assemblies1)
Type Main contactor + block reserved free Delta contactor + block reserved free Star contactor + block reserved free
N con- contacts ∆ con- contacts Y contacts contacts
tacts tacts
DLDAe 65 N2) DL 42 N-22 1 N/O 1N/O+2N/C DL 42 N-22 1 N/C 2N/O+1N/C DL 22 N-22 1N/O,1N/C 1N/O+1N/C
DLDAe 75 N DL 65 N-22 1 N/O 1N/O+2N/C DL 42 N-22 1 N/C 2N/O+1N/C DL 22 N-22 1N/O,1N/C 1N/O+1N/C
DLDAe 110 N DL 65 N-22 1 N/O 1N/O+2N/C DL 65 N-22 1 N/C 2N/O+1N/C DL 42 N-22 1N/O,1N/C 1N/O+1N/C
DLDAe 160 N DL 90 N-22 1 N/O 1N/O+2N/C DL 90 N-22 1 N/C 2N/O+1N/C DL 65 N-22 1N/O,1N/C 1N/O+1N/C
DLDAe 200 N DL 110 N-22 1 N/O 1N/O+2N/C DL 110 N-22 1 N/C 2N/O+1N/C DL 65 N-22 1N/O,1N/C 1N/O+1N/C
DLDAe 250 N DL 132 N-22 1 N/O 1N/O+2N/C DL 132 N-22 1 N/C 2N/O+1N/C DL 90 N-22 1N/O,1N/C 1N/O+1N/C
DLDAe 360 N DL 245 N-22 1 N/O 1N/O+2N/C DL 245 N-22 1 N/C 2N/O+1N/C DL 110 N-22 1N/O,1N/C 1N/O+1N/C
DLDAe 500 N DL 270 N-22 1 N/O 1N/O+2N/C DL 270 N-22 1 N/C 2N/O+1N/C DL 165 N-22 1N/O,1N/C 1N/O+1N/C
Notes
1)
Control contacts built into the contactor are first used.
2)
Separate terminals are required for connection to the supply.
1626
S013015 000919
Accessories:
Sets of links for star-delta contactors
Complete sets of links for wiring the main contacts of supply voltage, delta and star contactors of a contactor assembly.
* massive copper conductor, round insulated, connecting end pieces flattened and bared / ** massive copper conductor, round insulated, connecting end pieces bared
Spares:
Main contact sets for contactors sizes DL 22 N to DL 270 N
The main contact sets listed below are intended for incorporation in types DL One main contact set consists of three moving contacts and six fixed contacts.
and DLg contactors. They can also be used for DLW and DLDAe contactor Main contacts are only supplied as complete sets which come in transparent
assemblies. packs. No main contact sets are available for contactors below 22 kW.
Figure for contactor type Order ref.: Weight
Main contact sets kg
DL 22 N / DL 30 N 3 212 383 00 0.120
DL 110 N
3 292 041 00 0.630
DL 132 N
DL 165 N
without a figure 3 283 031 00 1.200
DL 245 N
Notes
For quality reasons, the contact material used for spare contact sets is always that of the
larger contactor.
Main contact sets for contactors no longer in production are available on request.
1627
S013016 000731
HL 4 K .. 3 366 040 .. - - -
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1628
S013013 000623
Our control relays, compact contactors, and mini contactors are delivered
with bi-frequency coils for 50/60 Hz.
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request
1)
Color code to IEC 309-1 printed on the coil. Only for compact contactors HL 4 K / HL 8 K and DL 4 K - DL 18 K
1629
hsla-1L 000919
Lighting contactors HSLa 22 ... HSLa 24 ... HSLa 44 ... HSLa 64 ...
2 poles 4 poles 4 poles 4 poles
Hum-free, 110-120 V AC, 220-240 V AC
DIN 3 Spacing 17.5 mm .689" Spacing 35 mm 1.38" Spacing 52.5 mm 2.07" Spacing 52.5 mm 2.07"
Standard : IEC 947 VDE 0660 1 module 2 modules 3 modules 3 modules
IEC 1095 VDE 0637 * *
protection protection
UL 94 UP V0
PC V2
PA V0
IP 20
*
Switching
noise : 80 dB
Part numbers on this page are for 220-240 VAC rated contactors.
2NO HSLa 22-20 F 011101301
Part numbers for 24 VAC and 110-120 VAC rated contactors
are on page 1634.
2NC HSLa 22-02 F 011101302
4NO HSLa 24-10 F 011101275 HSLa 44-10 F 011101092 HSLa 64-10 F 011101093
3NO - 1NC HSLa 24-01 F 011101276 HSLa 44-01 F 011101687 HSLa 64-01 F 011101690
2NO - 2NC HSLa 24-22 F 011101277 HSLa 44-22 F 011101688 HSLa 64-22 F 011101691
4NC HSLa 24-04 F 011101278 HSLa 44-04 F 011101689 HSLa 64-04 F 011101692
Characteristics
Rated thermal current Ith AC1 20 A 24 A 40 A 63 A
Rated voltage, 50/60 Hz 110-120 VAC or 220-230 VAC 110-120 VAC or 220-240 VAC 110-120 VAC or 220-240 VAC 110-120 VAC or 220-240 VAC
Max. power - Typ AC1 4 kW 16 kW 26 kW 40 kW
- Typ AC3 1.3 kW 4 kW 11 kW 15 kW
Coil power consumption 2.2 W 3.5 W 5W 5W
Switching time C/O 15 to 30 / 40 to 45 ms 20 to 30 / 60 to 80 ms 15 to 20 / 35 to 45 ms 15 to 20 / 35 to 45 ms
Current switching min. 5 mA 5 mA 10 mA 10 mA
Max. permissible capacitive load 30 µF 36 µF 220 µF 300 µF
Load current - Starting 93 A 96 A 200 A 305 A
cos φ = 45° maxi. in AC3 - Breaking 74 A 85 A 160 A 240 A
Rated insulation voltage / Impulse test voltage 440 V (Vi) - 4 kV (Vimp) 440 V (Vi) - 4 kV (Vimp) 440 V (Vi) - 4 kV (Vimp) 440 V (Vi) - 4 kV (Vimp)
Number of full-load operations AC1 / AC3 1 x 105 / 1 x 105 1 x 105 / 1.5 x 105 1 x 105 / 1.5 x 105 1 x 105 / 1.5 x 105
Mechanical life O/F 3 x 106 3 x 106 3 x 106 3 x 106
Max. switching frequency 120 / hour 120 / hour 120 / hour 120 / hour
Wire Contact terminals solid / stranded 1 to 4 mm² / 1 to 4 mm² 1 to 6 mm² / 2x1 to 4 mm² 1 to 25 mm² / 1 to 25 mm² 1 to 25 mm² / 1 to 25 mm²
size Coil terminals solid / stranded 18 to 14 AWG (1 to 2.5 mm²) 18 to 14 AWG (1 to 2.5 mm²) 18 to 14 AWG (1 to 2.5 mm²) 18 to 14 AWG (1 to 2.5 mm²)
Recommended torque Contact terminals / Coil terminals 1.2 / 1.2 Nm 1.2 / 1.2 Nm 1.2 / 2 Nm 1.2 /2 Nm
Weight 4.4 oz (0.125 Kg) 9.5 oz (0.270 Kg) 12.2 oz (0.345 Kg) 12.2 oz (0.345 Kg)
Operating temperature / Storage temperature -5 ... +55° C / -30 ... +80° C -5 ... +55° C / -30 ... +80° C -5 ... +55° C / -30 ... +80° C -5 ... +40° C / -30 ... +80° C
Accessories
Auxiliary contact blocks for contactors HSLa 24, 44, 64... Protection for terminals
63 53
Emission Limiter: Limit emissions to EN55 015/1993 and VDE 874/4. Contact Entrelec for specifications.
1630
hsla-1R 000919
Supply voltage (230 V AC) Number of lamps that can be connected per pole
NO NC NO NC NO NC NO NC
Incandescent lamps 60 W 21 18 25 16 65 30 85 50 - -
100 W 13 10 15 10 40 20 50 30 - -
200 W 7 5 7 5 20 10 25 15 - -
500 W 3 2 3 2 8 4 10 6 - -
1000 W 1 0 1 1 4 2 5 3 - -
Energy-saving lamps 7W 10 7 15 10 100 50 150 75 - -
11 W 10 7 15 10 100 50 150 75 - -
15 W 5 3 15 10 100 50 150 75 - -
20 W 3 1 10 6 70 35 100 50 - -
Halogen lamps 200 W 4 2 5 4 15 10 20 14 - -
300 W 2 1 3 2 10 7 13 9 - -
500 W 1 - 2 1 6 4 8 6 - -
1000 W - - 1 1 3 1 4 2 - -
Low-pressure sodium vapor lamps 35 W 5 3 6 4 13 6 20 11 1,5 -
uncompensated 55 W 5 3 6 4 13 6 20 11 1,5 -
90 W 3 2 4 3 9 4 14 6 2,4 -
135 W 2 1 3 2 6 2 9 4 3,5 -
180 W 1 1 3 2 6 2 9 4 3,3 -
Low-pressure sodium vapor lamps 35 W 1 1 1 1 10 6 16 7 0,31 20
with parallel compensation 55 W 1 1 1 1 10 6 16 7 0,42 20
90 W - - 1 - 8 4 12 5 0,63 30
135 W - - - - 4 2 7 3 0,94 45
180 W - - - - 4 2 7 3 1,16 40
High-pressure sodium vapor lamps 50 W 12 10 16 10 28 21 44 31 0,77 -
uncompensated 70 W 10 8 13 8 22 14 34 19 1 -
110 W 8 6 10 6 18 11 28 13 1,2 -
150 W 6 4 7 4 12 7 19 8 1,8 -
250 W 3 2 4 2 7 4 11 5 3 -
400 W 2 1 3 2 5 2 7 3 4,4 -
1000 W 1 - 1 - 2 1 3 2 10 -
High-pressure sodium vapor lamps 50 W 3 2 3 2 22 16 33 18 0,28 8
with parallel compensation 70 W 2 1 3 2 18 10 27 12 0,38 12
110 W 2 1 2 1 18 10 27 12 0,53 12
150 W 1 1 1 1 10 6 16 7 0,77 20
250 W - - 1 - 6 3 9 4 1,25 36
400 W - - - - 4 2 7 3 2,05 45
1000 W - - - - 2 1 3 1 4,96 100
High-pressure metal vapor 50 W 22 17 28 18 47 42 74 49 0,6 -
and mercury-vapor lamps (HQL) 80 W 16 13 21 14 36 28 56 31 0,8 -
uncompensated 125 W 12 9 15 10 25 19 39 22 1,15 -
250 W 6 4 8 6 13 10 21 11 2,15 -
400 W 4 2 5 3 8 6 13 9 3,25 -
700 W 2 1 3 2 5 3 8 4 5,4 -
1000 W 1 - 2 1 3 1 6 2 7,5 -
High-pressure metal vapor 50 W 4 3 5 3 30 18 45 21 0,27 7
and mercury-vapor lamps (HQL) 80 W 3 2 4 3 25 16 40 18 0,41 8
with parallel compensation 125 W 3 2 3 2 20 13 33 15 0,62 10
250 W 1 1 2 1 12 7 18 8 1,24 18
400 W 1 - 1 - 8 5 13 6 1,93 25
700 W - - 1 - 5 3 8 3 3,34 40
1000 W - - - - 3 2 5 2 4,75 60
High-pressure metal-halide lamps (HQI) 70 W 12 9 15 10 25 19 39 23 1 -
uncompensated 150 W 6 4 8 6 14 10 22 13 1,8 -
250 W 4 3 5 3 8 5 13 9 3 -
400 W 2 1 3 2 7 3 11 7 3,5 -
1000 W - - - - 1 1 2 1 9,5 -
2000 W - - - - 1 1 1 1 19 -
High-pressure metal-halide lamps (HQI) 70 W 2 1 3 2 18 10 26 12 1 12
with parallel compensation 150 W 1 - 2 1 10 6 16 7 1,8 20
250 W - - 1 - 6 4 10 4 3,0 32
400 W - - 1 - 6 3 9 4 4,4 35
1000 W - - - - 2 1 4 1 10,3 85
Fluorescent lamps 18 W 24 16 24 16 90 78 140 122 0,37 -
uncompensated 36 W 17 11 20 13 65 57 95 79 0,43 -
58 W 10 7 13 6 40 28 60 49 0,67 -
Fluorescent lamps 18 W 6 4 8 5 45 28 70 32 0,11 4,5
with parallel compensation 36 W 6 4 8 5 45 28 70 32 0,21 4,5
58 W 4 3 5 3 25 18 43 21 0,32 7
Fluorescent lamps 18 W 2 x 22 2 x 14 2 x 48 2 x 32 2 x 100 2 x 78 2 x 150 2 x 136 2 x 0,11 -
connected in pairs 36 W 2 x 17 2 x 12 2 x 24 2 x 16 2 x 65 2 x 53 2 x 95 2 x 79 2 x 0,21 -
58 W 2 x 10 2x4 2 x 15 2 x 10 2 x 40 2 x 28 2 x 60 2 x 53 2 x 0,32 -
Fluorescent lamps AC operation 1 x 18 W 22 11 30 10 60 19 80 22 0,1 6,8
with electronic ballasts 1 x 36 W 12 9 16 9 30 19 42 22 0,18 6,8
1 x 58 W 8 8 12 8 22 13 30 15 0,27 10
AC operation 2 x 18 W* 23 8 32 8 40 13 48 15 0,18 10
2 x 36 W* 12 8 16 8 20 13 26 15 0,35 10
1 electronic ballast=2 lamps 2 x 58 W* 7 3 10 4 10 5 18 6 0,52 22
* DC operation, 1 lamp 18 W 15 11 25 19 50 42 75 61 - -
(3 poles in series) 36 W 8 5 14 10 30 23 40 33 - -
58 W 3 1 9 6 16 11 25 19 - -
* DC operation, 2 lamps 18 W 2x5 2x3 2 x 12 2x9 2 x 25 2 x 20 2 x 38 2 x 32 - -
(3 poles in series) 36 W 2x3 2x2 2x6 2x4 2 x 15 2 x 11 2 x 20 2 x 14 - -
58 W 2x2 2x1 2x4 2x2 2x8 2x5 2 x 12 2x8 - -
* Values for 220 V DC and the complete device (not per pole)
All the specified values may vary considerably, depending on the lamp manufacturer.
1631
hsla-2L 000919
UL 94 UP V0
PC V2
PA V0
IP 20
Switching
noise : 80 dB
Rated volage: 220-240 VAC
2 modules
DC solenoid system providing hum-free continuous
operation. AC supply is rectified through built-in diodes. * Dimension includes the terminal block cover P-HSLa 24.
Coil protected against transients. This cover can be mounted only on modular HSLa 24...
Contact Entrelec for UL / CSA. types.
Contact type
Characteristics
Rated thermal current Ith AC1 21 A
Rated voltage, 50/60 Hz 220...240 VAC
Max. power - Typ AC1 16 kW
- Typ AC3 4 kW
Coil power consumption 2.3 W
Switching time C/O 20 to 30 / 60 to 80 ms
Current switching min. 5 mA
Max. permissible capacitive load 150 µF
Load current - Starting 96 A
cos φ = 45° max. in AC3 - Breaking 85 A
Rated insulation voltage / Impulse test voltage 440 V (Vi) - 4 kV (Vimp)
Number of full-load operations AC1 / AC3 50,000
Mechanical life O/F 3 x 106
Max. switching frequency 120 / hour
Wire Contact terminals solid / Stranded 1 to 6 mm² / 2x1 to 4 mm²
size Coil terminals solid / Stranded 18 to 14 AWG (1 to 2.5 mm²)
Recommended torque Contact terminals / Coil terminals 1.2 / 1.2 Nm
Weight 9.5 oz (0.270 Kg)
Operating temperature / Storage temperature -5 ... +55° C / -30 ... +80° C
Accessories
Auxiliary contact blocks for contactors HSLa 24, 44, 64... Protection for terminals
63 53
Characteristics P-HSLa 24
Weight : 1.3 oz (0.036 Kg)
Max. current Ith AC15 : 3A
To be mounted on the left side of modular contactor. Rated temperature : -5 ... +55° C
Emission Limiter: Limit emissions to EN55 015/1993 and VDE 874/4. Contact Entrelec for specifications.
1632
hsla-2R 000919
All the specified values may vary considerably, depending on the lamp manufacturer.
1633
1001T 010313
Lighting contactors HSLa 22 ... HSLa 24 ... HSLa 44 ... HSLa 64 ...
2 poles 4 poles 4 poles 4 poles
Hum-free, 24 V AC, 110-120 V AC
DIN 3 Spacing 17.5 mm .689" Spacing 35 mm 1.38" Spacing 52.5 mm 2.07" Spacing 52.5 mm 2.07"
Standard : IEC 947 VDE 0660 1 module 2 modules 3 modules 3 modules
IEC 1095 VDE 0637 * *
protection protection
UL 94 UP V0
PC V2
PA V0
IP 20
*
Switching
noise : 80 dB
References Configuration Type P/N 24 VAC, 50/60 Hz P/N 110-120 VAC, 50/60 Hz
Contact type
1NO 1 pole, 25 A HSLa 22-10 F011102606
1NC
1 pole, 25 A HSLa 22-01 F011102605
4NC
4 pole, 40 A HSLa 44-04 F011101717 F011102611
1634
S014003 000623
Mini contactors
Mini contactors • control relays, contactors, reversing contactors
KH ... CONTROL RELAY
... the benefits at a glance ... KL ..., KLW ... CONTACTORS
PLUS SYSTEM COMPONENTS
Control relay
4 basic coil versions Versions : Screw terminals, Faston
✓ AC : 4.5 VA connectors or solder pins
AC, DC, interface or
DC : 2.4 W hum-free coils
DC : 1.5 W
✓ AC with rectifier : 3.5 VA
Contactors
(hum-free, silent, no peak currents
on make, insensitive to short
voltage cutoffs). Thermal overload relay
Suitable for resistive loads (AC 1): contacts are designed for Ith
= 29 A at 50°C
1635
S014004 000919
- 50/60 Hz coil
10 KHS-22 1 309 070 .. 2 2 - without integral 0.180
coil suppressor
- 50/60 Hz coil
10 KHF-22 1 309 170 .. 2 2 - without integral 0.180
coil suppressor
- 50/60 Hz coil
10 KHL-22 1 309 270 .. 2 2 - without integral 0.210
coil suppressor
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1641
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1641
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664, 1666
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1636
S014005 000919
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1641
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1641
AC-coils available with integral coil suppressor to max. 230 V
Technical details - pages 1664, 1666
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1637
S014006 000919
Approvals:
- without integral
10 KHDCS-22 1 309 075 .. 2 2 coil suppressor 0.225
- without integral
10 KHDCF-22 1 309 175 .. 2 2 coil suppressor 0.225
- without integral
10 KHDCL-22 1 309 275 .. 2 2 coil suppressor 0.225
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1641
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1641
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664, 1666
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1638
S014007 000919
Approvals:
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1641
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1641
DC-coils available with integral coil suppressor to max. 220 V Technical details - pages 1664, 1666
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1639
S014008 000919
Approvals:
Characteristics for contol relays KHiS ..., DC operated, interface, 1.8 W coil
Version with screw terminals
Rated thermal Type Order ref.: Contact Circuit diagram to Features Weight
current Ith see supplements configuration DIN EN 50 011 kg For dimensions
A at the top right N/O N/C see page 1673
- built-in LED to indicate
KHiS-31 1 309 067 06 3 1 operational state 0.235
- Coil operating voltage
rangs 0.7 to 1.3 VC
10 KHiS-22 1 309 077 06 2 2 - integral coil 0.235
suppressor
- only 2 pole aux.
KHiS-40 1 309 057 06 4 0 contact block 0.235
permitted
Notes
Normal/Standard voltages are: DC: 24 and 48 V Auxiliary contact block - page 1641
(Short-term availability)
Other coil voltages on request Other system components - page 1641
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664, 1666
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1640
S014009 000919
Approvals:
Characteristics
Auxiliary contact blocks Coil suppressors with built-in LED indicator
for use with KL ..., KLW contactors
for use with KH ..., KHDC ..., KHi control relays RC coil suppressor (for AC operated contactor)
Top mounting Type Voltage range Order ref.:
for contactors Type Circuit diagram Order ref.: RC-2501) 220...250 V 3 309 062 01
DIN EN 50 012 LS-11 3 309 001 01
Diode coil suppressor (for DC operated contactor)
LS-02 3 309 002 01 Type Voltage range Order ref.:
D-242) 12...24 = 3 309 061 01
KL ... LS-13 3 309 005 01
D-482) 32...48 = 3 309 061 02
KLW ...
LS-22 3 309 004 01 Varistor coil suppressor (for AC or DC operated contactor)
Type Voltage range Order ref.:
LS-31 3 309 003 01
3)
V-24 12...24 AC/DC 3 309 060 01
HS-02 3 309 033 01 V-483) 32...48 AC/DC 3 309 060 02
HF-02 3 309 043 01 V-1303) 40...129 AC/DC 3 309 060 04
HS-04 3 309 038 01 V-2503) 130...250 AC/DC 3 309 060 05
Weight : 0.010 kg
HF-04 3 309 048 01
HS-11 3 309 032 01
Timer module snaps to the front of contactor
Type Timer range Voltage range Order ref.:
HF-11 3 309 042 01
input/coil
KH, KHDC, HS-13 3 309 037 01
HV-48 1...30 24...48 V AC/DC 3 309 050 01
KHi HF-13 3 309 047 01 HV-240 1...30 110...240 V AC 3 309 050 02
HS-20 3 309 031 01 Weight : 0.040 kg
HF-20 3 309 041 01 Technical details : Circuit diagram :
HS-22 3 309 036 01 Relay outputs 1W
240 V AC/DC, 2 A max.
HF-22 3 309 046 01 Max. switching capacity
HS-31 3 309 035 01 250 VA / 150 W
Control voltage range 0.85...1.1 VC
HF-31 3 309 045 01
Permissible ambient temperature Explanation :
HS-40 3 309 034 01 -10°C ... +60°C ... S = screw terminals
Reset time : ... F = Faston connectors
HF-40 3 309 044 01
1.5 secs while timing on KHi only 2-pole versions
Weight : 0.045 kg
0.5 secs after timing permitted !
Notes
1)
Limits transient voltage to max. 3 Vc. Slight increase in drop-out time Technical details - pages 1664-1666
(1.2 to 2 times the normal time).
2)
No interference by transient voltages and high frequency. Observe polarity when
Dimensions - page 1673
connecting. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
3)
Limits transient voltages to max. 2 Vc. Max. reduction of transient voltage
peaks. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
1641
S014010 000623
Contactors KL ...,
2.2 and 4 kW / 3 and 5 HP at 460 V, 3 ph. (AC 3)
AC operated,
without integral coil suppressor Terminal numbering to DIN EN 50 005 and
DIN EN 50 012
Compact design
Available in 3 versions:
- with screw terminals
- Faston connectors
- solder pins
Version with solder pins includes front face screw
terminals for direct connection to load
Low power consumption coils
Bi-frequency AC coils 50/60 Hz
High contact reliability
Switch position indication
Safety isolation up to 400 V to VDE 0106, IEC 536
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1653
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1653
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664-1665
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1642
000919
S014011
Contactors KL ...,
2.2 and 4 kW / 3 and 5 HP at 460 V, 3 ph. (AC 3)
AC operated,
with integral coil suppressor
Terminal numbering to DIN EN 50 005 and
DIN EN 50 012
Compact design
Available in 3 versions:
- with screw terminals
- Faston connectors
- solder pins
Version with solder pins includes front face screw
terminals for direct connection to load
Low power consumption coils
Bi-frequency AC coils 50/60 Hz
High contact reliability
Switch position indication
Safety isolation up to 400 V to VDE 0106, IEC 536
KL contactors are designed to switch three-phase and
AC loads. Applications include building automation,
air conditioning, heating and ventilation, and switching
resistive loads such as heaters, lamps, and inductive
loads, e.g., valves, couplings, etc.
Our mini contactors are delivered with
bi-frequency coils for 50/60 Hz.
Approvals:
Further notes at the bottom of this page.
Characteristics for contactors KL ..., AC operated, 4.5 VA coils
Max. AC 3 ratings Rated opera- Contactor Order ref.: Circuit diagram to Features Weight Suitable
of 3-phase motors tional current type DIN EN 50 005 and kg thermal For dimensions
(kW) Ie AC 1/AC 3 see supple- DIN EN 50 012 overload see page 1673
380... up to 440 V ments at the relay
230 V 415 V 500 V 690 V A top right
Version with screw terminals
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1653
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1653
AC-coils available with integral coil suppressor to max. 230 V Technical details - pages 1664-1665
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1643
000919
S014012
Approvals:
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1653
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1653
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664-1665
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1644
S014013 000919
Approvals:
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1653
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1653
DC-coils available with integral coil suppressor to max. 220 V Technical details - pages 1664-1665
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1645
S014014 000731
Approvals:
Notes
Normal/Standard voltages are: DC: 24 and 48 V Auxiliary contact block - page 1653
(Short-term availability)
Other coil voltages on request Other system components - page 1653
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664-1665
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1646
S014015 000623
50/60 Hz coil
24 V
110 V
KLb4S-10 1 309 021 .. 230 V
2.2 4 4 4 20/9 0.225 M 06
permitted
KLb4S-01 1 309 031 ..
50/60 Hz coil
24 V
110 V
KLb4F-10 1 309 121 .. 230 V
2.2 4 4 4 20/9 0.225 M 06
permitted
KLb4F-01 1 309 131 ..
50/60 Hz coil
24 V
110 V
KLb4L-10 1 309 221 ..
230 V
2.2 4 4 4 20/9 0.225 M 06
permitted
KLb4L-01 1 309 231 ..
Notes
Normal/Standard voltages are: AC: 24, 110 and 230 V Auxiliary contact block - page 1653
(Short-term availability)
Other coil voltages on request Other system components - page 1653
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664-1665
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1647
S014016 000623
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V Auxiliary contact block - page 1653
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request Other system components - page 1653
1)
Color code to IEC 309-1 printed on the coil. Technical details - pages 1664-1665
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1648
S014017 000623
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V
(Short-term availability) DC: 24, 110 and 220 V Auxiliary contact block - page 1653
Other coil voltages on request
Other system components - page 1653
AC-coils available with integral coil suppressor to max. 230 V
1)
Technical details - pages 1664-1665
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1649
S014018 000731
Notes
Normal/Standard voltages are: DC: 24, 110 and 220 V Auxiliary contact block - page 1653
(Short-term availability)
Other coil voltages on request
Other system components - page 1653
1650
S014019 000731
Notes
Normal/Standard voltages are: DC: 24, 110 and 220 V Auxiliary contact block - page 1653
(Short-term availability)
Other coil voltages on request Other system components - page 1653
DC-coils available with integral coil suppressor to max. 220 V Technical details - pages 1664-1665
1)
Color code to IEC 309-1 printed on the coil.
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1651
S014020 000623
50/60 Hz
coil
... 24 V 0.48 M 06
KLWb4S-10 1 309 321 .. ... 110 V
2.2 4 4 4 20/9 ... 230 V
KLWb4S-01 1 309 331 .. permitted
50/60 Hz
coil
... 24 V
0.46 M 06
... 110 V
KLWb4F-10 1 309 421 ..
2.2 4 4 4 20/9 ... 230 V
KLWb4F-01 1 309 431 .. permitted
50/60 Hz
coil
... 24 V
0.52 M 06
KLWb4L-10 1 309 521 .. ... 110 V
2.2 4 4 4 20/9 ... 230 V
KLWb4L-01 1 309 531 .. permitted
Notes
Normal/Standard voltages are: AC: 24, 110 and 230 V Auxiliary contact block - page 1653
(Short-term availability)
Other coil voltages on request Other system components - page 1653
1)
Color code to IEC 309-1 printed on the coil. Technical details - page 1664-1665
Only for compact contactors, HL 4 K / HL 8 K and DL 4 K - DL 18 K
1652
S014022 000623
Approvals:
Characteristics
Auxiliary contact blocks Coil suppressors with built in LED indicator
for use with KL ..., KLW contactors
for use with KH ..., KHDC ..., KHi control relays RC coil suppressor (for AC operated contactor)
Top mounting Type Voltage range Order ref.:
for contactors Type Circuit diagram Order ref.: RC-2501) 220...250 V 3 309 062 01
DIN EN 50 012 LS-11 3 309 001 01
Diode coil suppressor (for DC operated contactor)
LS-02 3 309 002 01 Type Voltage range Order ref.:
D-242) 12...24 = 3 309 061 01
KL ... LS-13 3 309 005 01
D-482) 32...48 = 3 309 061 02
KLW ...
LS-22 3 309 004 01 Varistor coil suppressor (for AC or DC operated contactor)
Type Voltage range Order ref.:
LS-31 3 309 003 01
3)
V-24 12...24 AC/DC 3 309 060 01
HS-02 3 309 033 01 V-483) 32...48 AC/DC 3 309 060 02
HF-02 3 309 043 01 V-1303) 40...129 AC/DC 3 309 060 04
HS-04 3 309 038 01 V-2503) 130...250 AC/DC 3 309 060 05
Weight : 0.010 kg
HF-04 3 309 048 01
HS-11 3 309 032 01
Timer module snaps to the front of contactor
Type Timer range Voltage range Order ref.:
HF-11 3 309 042 01
input/coil
KH, KHDC, HS-13 3 309 037 01
HV-48 1...30 24...48 V AC/DC 3 309 050 01
KHi HF-13 3 309 047 01 HV-240 1...30 110...240 V AC 3 309 050 02
HS-20 3 309 031 01 Weight : 0.040 kg
HF-20 3 309 041 01 Technical details : Circuit diagram :
HS-22 3 309 036 01 Relay outputs 1W
240 V AC/DC, 2 A max.
HF-22 3 309 046 01 Max. switching capacity
HS-31 3 309 035 01 250 VA / 150 W
Control voltage range 0.85...1.1 VC
HF-31 3 309 045 01
Permissible ambient temperature Explanation :
HS-40 3 309 034 01 -10°C ... +60°C ... S = screw terminals
Reset time : ... F = Faston connectors
HF-40 3 309 044 01
1.5 secs while timing on KHi only 2-pole versions
Weight : 0.045 kg
0.5 secs after timing permitted !
Notes
1)
Limits transient voltage to max. 3 Vc. Slight increase in drop-out time Technical details - pages 1664-1666
(1.2 to 2 times the normal time).
2)
No interference by transient voltages and high frequency. Observe polarity when
Dimensions - page 1673
connecting. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
3)
Limits transient voltages to max. 2 Vc. Max. reduction of transient voltage
peaks. Slight increase in drop-out time (1.1 to 1.5 times the normal time).
1653
000919
S014021
Our control relays, compact contactors and mini contactors are delivered
with bi-frequency coils for 50/60 Hz.
Notes
Normal/Standard voltages are: AC: 24, 42, 110, 230 and 400 V
(Short-term availability) DC: 24, 110 and 220 V
Other coil voltages on request
1)
Color code to IEC 309-1 printed on the coil. Only for compact contactors HL 4 K / HL 8 K and DL 4 K - DL 18 K
1654
NOTES
1655
1002T 010329
Motor Controls
DuoSoft DuoSoft and PowerSoft electronic soft starters provide smooth acceleration and
deceleration of three phase motors, reducing mechanical and electrical stress which
shorten a motor’s life. DuoSoft starters are suitable for motors up to 15 kW.
DuoSoft
• Suitable for motors up to 15 kW
• Ideal alternative to Star Delta starters
• Integral bypass relay
• Compact size
• Two or three wire control
• LED status indication
ZNTF
Fuse Switches
ZNTF
• Up to 100A rating.
• Door interlocked handle standard
• Two auxiliary contacts can be mounted
• Auxiliaries feature early break/late make
ZTF
ZTF
• Larger fuse switch to 800A rating
• Includes door interlocked handle and fuse barriers
• Four auxiliary contacts can be mounted
• Fourth pole not fused
• Auxiliaries feature early break/late make
1656
1003T 010329
DC Injection Brakes
Our DC Injection brakes reduce the time for a machine to come to rest resulting in
an increased production output and increased safety in hazardous machines.
Available in three formats with DOL starter, with Star Delta starter, and without
starter (for use with existing DOL or Star Delta starter).
Power Manager
• Simple to install
Quick fit clamps for panel mounting
and large cable terminals
• Easy to use
Four menu buttons allow information
to be accessed easily and quickly
• Accurate and comprehensive
parameter measurement
• Easy to read
Large clear backlit LCD display
• Compact size
1657
NOTES
1658
S015003 000623
Motor rating Motor rated current Motor rated current Motor rated current Motor rated current Motor rated current
at 415 V at 440 V at 500 V at 600 V at 660 V
Fusing Fusing Fusing Fusing Fusing
DOL Y∆ DOL Y∆ DOL Y∆ DOL Y∆ DOL Y∆
kW PS ≈ hp cos ϕ η% A A A A A A A A A A A A A A A
0.06 0.08 0.7 59 - - - 0.19 1 1 0.16 1 1 0.12 1 1 - - -
0.09 0.12 0.7 60 - - - 0.28 1 1 0.24 1 1 0.21 1 1 - - -
0.12 0.16 0.7 61 - - - 0.37 1 1 0.33 1 1 0.27 1 1 - - -
0.18 0.24 0.7 61 - - - 0.55 1 1 0.46 1 1 0.4 1 1 - - -
0.25 0.34 0.7 62 - - - 0.76 2 2 0.59 2 2 0.56 1 1 - - -
0.37 0.5 0.72 64 - - - 1.06 2 2 0.85 2 2 0.77 2 2 0.7 2 2
0.55 0.75 0.75 69 - - - 1.25 4 2 1.2 4 2 1.02 2 2 0.9 2 2
0.75 1 10.8 74 2 4 4 1.67 4 2 1.48 4 2 1.22 4 2 1.1 2 2
0.8 1.1 0.8 74 - - - 1.78 4 2 1.57 4 2 1.31 4 2 - - -
1.1 1.5 0.83 77 2.5 4 4 2.26 4 4 2.1 4 4 1.66 4 2 1.5 4 2
1.5 2 0.83 78 3.5 6 4 3.03 6 4 2.6 4 4 2.22 4 4 2 4 4
2.2 3 0.83 81 5 10 6 4.31 6 6 3.8 6 6 3.16 6 4 2.9 6 4
2.5 3.4 0.83 81 - - - 4.9 10 6 4.3 6 6 3.59 6 4 - - -
3 4 0.84 81 6.5 16 10 5.8 10 10 5.1 10 10 4.25 6 6 3.5 6 4
3.7 5 0.84 82 7.5 16 10 7.1 16 10 6.2 16 10 5.2 10 10 - - -
4 5.5 0.84 82 - - - 7.6 16 10 6.5 16 10 5.6 10 10 4.9 10 6
5 6.8 0.84 83 - - - 9.4 16 16 8.1 16 10 6.9 16 10 - - -
5.5 7.5 0.85 83 11 20 16 10.3 20 16 8.9 16 10 7.5 16 10 6.7 16 10
6.5 8.8 0.85 84 - - - 12 20 16 10.4 20 16 8.7 16 10 - - -
7.5 10 0.86 85 14 25 16 13.5 25 16 11.9 20 16 9.9 16 16 9 16 10
8 11 0.86 85 - - - 14.4 25 20 12.7 20 16 10.6 20 16 - - -
11 15 0.86 87 21 35 25 19.3 35 25 16.7 25 20 14.1 25 20 13 25 16
12.5 17 0.86 87 - - - 21.9 35 25 19 35 25 16.1 25 20 - - -
15 20 0.86 87 28 35 35 26.3 35 35 22.5 35 25 19.3 35 25 17.5 25 20
18.5 25 0.86 88 35 50 50 32 50 35 28.5 50 35 23.5 35 25 21 35 25
20 27 0.86 88 - - - 34.6 50 50 30.6 50 35 25.4 35 35 - - -
22 30 0.87 89 40 63 50 37.1 63 50 33 50 50 72.2 35 35 25 35 35
25 34 0.87 89 - - - 42.1 63 50 38 63 50 30.9 50 35 - - -
The motor rated currents are valid for normal internal and surface cooled-down three-phase current motors of 1500 r. p. m.
Direct-on-line-starting: Starting current max. 6 x motor rated current. Starting time: max. 5 sec.
Y/∆-current: Starting current max. 2 x motor rated current. Starting time max. 15 s. Thermal overload relay in the delta circuit to be set at 0.58 x motor rated current.
The rated currents of the fuse at Y/∆ -starting are also applicable for asynchronous slip-ring motors. At higher motor rated currents, starting currents, and/or longer starting times a
higher-rated fuse has to be applied. This table is also applicable for "gL" fuses (DIN VDE 0636).
Using NH-fuses in aM-characteristics fuse rating = motor rated current has to be selected.
1659
S015004 000919
Motor rating Motor rated current Motor rated current Motor rated current Motor rated current Motor rated current
at 415 V at 440 V at 500 V at 600 V at 660 V
Fusing Fusing Fusing Fusing Fusing
DOL Y∆ DOL Y∆ DOL Y∆ DOL Y∆ DOL Y∆
kW PS ≈ hp cos ϕ η% A A A A A A A A A A A A A A A
30 40 0.87 90 55 80 63 50.1 80 63 44 63 50 37.1 63 50 33 50 35
37 50 0.87 90 66 100 80 61.9 80 80 54 80 63 45.4 63 50 42 63 50
40 54 0.87 90 - - - 67 100 80 60 80 63 49.1 80 63 - - -
45 60 0.88 91 80 100 100 37.9 100 80 64.5 100 80 54.2 80 63 49 63 63
51 70 0.88 91 - - - 83.8 125 100 73.7 100 80 61.4 80 80 - - -
55 75 0.88 91 - - - 90.3 125 100 79 125 100 66.2 100 80 60 80 63
63 85 0.88 91 112,5 160 125 103.5 125 100 90.5 125 100 76 100 80 - - -
75 100 0.88 91 135 200 160 123 160 160 106 160 125 90.3 125 100 82 125 100
80 110 0.88 91 - - - 131 160 160 112 160 125 96.3 125 100 - - -
90 125 0.88 92 165 200 200 146 200 160 128 160 160 107 160 125 98 125 125
100 136 0.88 92 - - - 162 200 200 143 200 160 119 160 160 - - -
110 150 0.88 92 200 250 250 178 250 200 156 200 200 131 160 160 118 160 125
129 175 0.88 92 230 315 250 209 250 250 184 250 200 153 200 200 - - -
132 180 0.88 92 - - - 214 250 250 186 250 200 157 200 200 140 200 160
140 190 0.88 92 - - - 227 315 250 200 250 250 167 200 200 - - -
147 200 0.88 93 260 315 315 236 315 250 207 250 250 173 250 200 - - -
160 220 0.88 93 - - - 256 315 315 220 315 250 188 250 250 170 200 200
180 245 0.88 93 - - - 289 400 315 254 315 315 212 250 250 - - -
184 250 0.88 93 325 400 400 295 400 315 259 315 315 217 250 250 - - -
200 270 0.88 93 - - - 321 400 400 278 315 315 325 315 250 215 250 250
220 300 0.88 93 385 500 400 353 500 400 310 400 400 260 315 315 - - -
250 340 0.88 93 - - - 401 500 500 353 500 400 295 400 315 268 315 315
257 350 0.88 93 450 630 500 412 500 500 363 500 400 302 400 400 - - -
270 367 0.88 93 467 630 500 433 500 500 381 500 400 317 400 400 - - -
315 430 0.88 93 - - - 505 630 630 445 630 500 370 500 400 337 400 400
355 483 0.89 95 - - - 549 800 630 483 630 630 405 500 500 366 500 400
400 545 0.89 96 - - - 611 800 800 538 630 630 450 630 500 410 500 500
450 612 0.89 96 - - - 688 800 800 608 800 630 508 630 630 460 630 500
1660
000919
S015005
Method of installation A B1 B2 C E
conduit-wired in heat conduit-wired cables (or cable channel)
insulating walls inside or outside of walls or concealed
No. of wires 2 3 2 3 2 3 2 3 2 3
Recommended values for the permissible rating Iz of cables and wires with Cu-conductors and PVC-insulation,
(operating temperature 70° C) at fixed installation in buildings, continuous operation, ambient temperature
25°C, correspondence of the rated current in In of overcurrent protective gear for protection at overload with
high testing current Iz ≤ 1.45 In to E DIN VDE 0298 Part 4/1996 and DIN VDE 0100 Part 430 supplement 1/01.91
Cross section
Cu-conductor in mm2 Iz In Iz In Iz In Iz In Iz In Iz In Iz In Iz In Iz In Iz In
For underground laying of cables and wires and for cross sections > 120 mm2 in air, VDE 0298 Part 2 will apply.
Adjustable protection devices (motor controllers, circuit breakers) have to be set to the rated operational current of the wire. Overcurrent protective gear for
which the rated current In does not correspond to the values stipulated in the table, the next lower available rated current has to be selected.
NR/SR = natural rubber or soft rubber, PVC = polyvinyl chloride, EPR = ethylen-propylen-rubber, VPE = vulcanized polyethylene
1661
S015006 000731
W A V µF
Incandescent lamps
60 0.27 230 - 24 45 66 93 129 140 161 229 277 370 433 462 567
100 0.45 230 14 28 40 55 77 84 97 137 166 222 260 277 340
200 0.91 230 7 14 19 27 38 41 48 68 82 109 128 137 168
300 1.36 230 4 9 13 18 25 28 32 45 55 73 86 91 112
500 2.27 230 2 5 7 11 15 16 19 27 33 44 51 55 67
1000 4.5 230 1 2 4 5 7 8 9 13 16 22 26 27 34
2000 9.1 230 - 1 2 2 3 3 4 6 8 10 12 13 16
Electronic incandescent lamps (Dulux EL;
Circolux EL,- SL- bzw. PL-lamps)
9/10 0.054 230 16 16 24 39 46 51 55 79 111 127 150 158 182
11 0.064 239 13 13 20 33 39 43 47 67 93 107 127 133 153
18 0.09 230 9 9 14 24 27 30 33 47 66 76 90 95 109
26 0.125 230 7 7 10 17 20 22 24 34 48 55 65 68 79
32 0.155 230 5 5 8 14 16 18 19 27 38 44 52 55 63
42 0.2 230 4 4 6 11 12 14 15 21 30 34 40 43 49
Fluorescent uncompensated
Individual circuit
40 0.43 230 41 43 46 67 81 90 113 167 209 279 544 544 606
65 0.7 230 25 26 28 35 50 60 70 102 128 170 334 334 372
100 1.5 230 12 12 13 16 23 25 32 48 60 79 156 156 174
120 1.5 230 12 12 13 15 23 25 32 48 60 79 156 156 174
215 1.5 400 6 7 7.5 10 15 15 18 27 34 38 90 90 100
compensated
40 0.3 230 4.5 20 30 60 90 116 125 145 206 250 330 390 416 510
65 0.45 230 7 14 20 40 60 77 85 97 137 166 220 260 277 340
100 0.7 230 18 9 15 25 40 50 55 62 88 107 142 167 178 218
120 0.8 230 18.5 7 12 22 35 43 46 54 77 93 125 146 156 191
215 0.8 400 10 4 10 12 20 25 28 31 43 53 71 83 90 110
Double circuit by switching Number of double units
2 x 40 2 x 0.3 230 30 31 33 40 58 70 81 120 150 198 390 390 435
2 x 65 2 x 0.45 230 20 21 22 30 38 45 54 80 100 132 260 260 290
2 x 100 2 x 0.7 230 12 11 14 20 25 30 35 51 64 85 167 167 186
2 x 120 2 x 0.8 230 11 10 12 18 21 27 30 45 56 74 146 146 163
Maximum making current peak (crest value) A 300 400 700 850 900 1000 1400 1700 2200 2600
Notes
The values given in the above tables are values for AC- and DC-operated contactors (economy circuit coils).
Because of the switching behavior and the moved masses, no DL 4 K-DC...DL 5 K-DC contactors should be used in "DC" systems.
DL 7 K-DC, DL 11 K-DC, DL 15 K-DC and DL 18 K-DC can be used as these contacts withstand electrical welding.
Order reference : see contactors. When ordering, add voltage code number to order reference.
Voltage codes: page 1654. Technical details: pages 1664-1665.
1662
S015007 000623
Standards
Utilization categories for contactors to IEC 947-4-1, EN 60 947, DIN VDE 0660 Part 102
Utilization categories for auxiliary contact blocks to IEC 947-5-1, EN 60 947, DIN VDE 0660 Part 200
Alternating current AC-12 Control of resistive load and solid-state loads with isolation by optocouplers
AC-14 (so far AC-11) Control of small electromagnetic loads (max. 72 VA)
AC-15 (so far AC-11) Control of electromagnetic loads (higher than 72 VA)
Direct current DC-12 (so far DC-11) Control of resistive load and solid-state loads with isolation by optocouplers
DC-14 (so far DC-11) Control of electromagnetic loads having economy resistors in circuit
Degree of protection of electrical equipment by enclosures and covers acc. to IEC 529, DIN 40 050
IP 41 Against ingress of tools and small wires Against foreign bodies > 1 mm Ø No damaging effect from dripping water
IP 43 Against ingress of tools and small wires Against foreign bodies > 1 mm Ø No damaging effect from spraying water
IP 54 Complete protection Against internal dust deposit No damaging effect from splash water
IP 55 Complete protection Against internal dust deposit No damaging effect from water jets
Notes
Protection against accidental contacts acc. to IEC 536, DIN VDE 0106 Part 100
Design of electrical equipment and its arrangement in electrical installations with a rated operational voltage of up to 1000 V ~ and 1500 V ~ in respect to protection
against direct contact, when operating elements (pushbuttons, toggle switches etc.) are close to hazardous parts.
Contact protection "fingerproof" only refers to the operating element in the direction of operation. In this case, a distance from the operating element to hazardous
parts in the radius of r = 30 mm from the central point has to be assured.
The degree of protection IP 20 is more than contact protection "fingerproof." A protection against contacts with electrical equipment from all directions is included.
On request, an extended protection against contact can be achieved for products with contact protection "fingerproof" and degree of protection IP 00, by using
covers.
1663
S015008 000623
1)
Min. operational voltage: 0.85 x VC
1) 1)
without restriction
1664
S015009 000623
(Ve ≤ 440 V)
million operations
On AC-1 the breaking current Ia normally equals
the rated operational current Ie
Example :
Ve = 220 V
Ie = 10 A on AC-1
Θ = 40° C
Ia = Ie = 10 A
Electrical life taken from the curve opposite:
500.000 operations.
Example :
Asynchronous motor
P = 2.2 kW
Ve = 400 V
Ie = 4.8 A
Ia = Ie = 4.8 A
(Ve ≤ 440 V)
KL 2 ... KL 4 ...
Switching squirrel-cage motors.
Switching off during start of motor.
On AC 4 the breaking current Ia is 6 times
the motor rated current Ie.
million operations
Example :
Asynchronous motor
P = 2.2 kW
Ve = 400 V
Ie = 4.8 A
Ia = 6 x Ie = 28.8 A
Increasing the rated current Multiply the above rated currents by the following coefficients (K)
Additional information
which take into account the often unbalanced current
by paralleling main poles distribution between poles.
1665
S015010 000623
to IEC 947 Electrical life (up to 3.600 ops/hr) at Electrical life (up to 1.200 ops/hr) at
inductive load in circuits with magnetic inductive load in circuits with magnetic
drives : drives, without economy resistor, time
making capacity (cos ϕ 0.7) constant of which increases with rating.
= 10 times the breaking capacity (cos ϕ 0.4).
*)
at operations ... V 110/ 220/ 380/ 600/
24 48 127 230 400 440 690 V 24 48 110 220 440 600
1 x 106 operations VA 48 96 240 440 800 880 1200 W 120 80 60 52 51 50
3 x 106 operations VA 17 34 86 158 288 317 500 W 55 38 30 28 26 25
10 x 106 operations VA 7 14 36 66 120 132 200 W 15 11 9 8 7 6
Making capacity for VA 1000 2050 5000 10000 14000 13000 9000 W 720 600 400 300 230 200
occasional switching
*)
Electrical life of contacts
1666
S015011 000919
Notes
1)
Screws for compact contactors Phillips H2
2)
Short-circuit withstand of contactor without overload relay corresponding to type 2 coordination (No damage to device, except light welding of contacts).
1667
S015012 000731
Rated insulation VDE 0110 V 750 750 750 750 750 750 750 1000 1000 750
voltage Vi IEC 947-1, EN 60 947, VDE 0660 V 690 690 690 690 690 690 750 1000 750 690
CSA 22,2, Nr. 14 UL 508 V 600 600 600 600 600 600 600 600 600 600
Rated operating voltage VC minimum/maximum V 12/660 12/660 12/660 12/660 12/660 24/660 24/660 80/660 80/660 80/660
Permissible range of operating voltage Vc 0.8...1.1
Rated operational current Ie on AC 1/AC 3 ≤ 40° C A 80/44 100/60 130/79 230/119 260/170 290/205 360/245 380/295 500/460 600/499
Rated thermal current Ith/Ithe open/enclosed 55°C A 80/75 100/90 130/115 230/200 260/230 290/260 360/315 380/340 500/460 600/540
Permissible overcurrent 3 min / 1 min A 200/300 300/500 300/500 500/700 600/800 750/1250 750/1500 1000/1600 2000/2200 2500/2800
at overload time of 10 secs / 5 secs A 500/600 1000/1200 1000/1200 1300/1500 1600/1700 1500/1900 2000/2300 2500/3000 3000/3400 4000/4600
(open type) 2 secs / 1 secs A 800/1000 1400/1600 1400/1600 1700/1900 1800/2000 2000/2300 2600/2900 3200/3500 3600/4000 5000/5500
Three-phase power when switching resistive load open/enclosed kW 53/50 66/59 86/76 171/151 191/171 191/171 237/207 250/224 329/303 395/355
on AC 1 at 400 V
Motor rating when switching slipring 230 V kW 12.5 18.5 22 37 50 60 75 90 115 160
(on AC2) or squirrel cage 400 V kW 22 30 40 63 90 110 132 160 250 270
(on AC3) motors 500 V kW 30 37 50 75 110 132 160 180 250 345
at 50/60 Hz 690 V kW 30 37 55 75 110 160 180 180 270 270
Rated breaking capacity 415 V A 450 800 1000 1200 1400 1700 2100 2400 3700 4000
at cos ϕ 0.35 500 V A 440 730 900 1200 1300 1600 2100 2100 3100 4000
690 V A 330 670 700 800 1100 1500 2100 2100 3100 2400
Rated making capacity at cos ϕ = 0,35 A 1000 1600 1600 1900 2000 2300 2900 3500 4000 5500
Switching times at 20° C Making:
- N/O closes after ms 14-19 14-19 11-28 12-20 12-20 12-25 12-25 20-60 20-60 35-110
AC
Breaking:
- N/O opens after ms 16-20 16-20 10-15 10-17 10-17 12-18 12-18 20-35 20-35 35-55
Making:
A = economy circuit coil - N/O closes after ms 10-20 10-20 20-40 20-30 20-30 35-55 35-55 35-65 35-56 50-60
DC
Breaking:
B = true DC coil at -15/+10 % - N/O opens after ms 12-18 12-18 7-12 10-14 10-14 10-18 10-18 18-28 18-28 30-60
Switching times for direct change over ms 14-18 14-18 11-16 10-15 10-15 21-25 21-25 26-33 26-33 58-83
of reversing and star-delta contactors (at 110 % Vc)
Power consumption of AC coil inrush/hold VA 146/22 146/22 336/44 430/44 430/44 950/77 950/77 1750/88 1750/88 2500/132
economy circuit coil W 220/2 220/2 260/6 280/6 280/6 400/9 400/9 1150/11 1150/11 1150/11
true DC coil W - - - - - - - - - -
Impedance per pole mΩ 0.8 0.5 0.6 0.46 0.46 0.45 0.28 0.2 0.2 0.15
Power dissipation per pole Ith W 5.1 5 10.2 31.1 31.1 37.9 36.3 28.9 50 54
Switching frequency - no load operations/hour AC/DC coil 3000/1500 2000/1200
contactor without overload relay to AC 1 1000
to AC 2 500
to AC 3 750 500
to AC 4 750 250
Mechanical life no. of operations 10 million
Electrical life of contacts see diagram page 1672
Permissible ambient operating °C -25° C ... +55° C
temperature range storage °C -50° C ... +80° C
Size of connecting screws/tightening torque - main terminals Nm4) M5/3,5 M6/4 M6/4 M10 M10 M10 M 12 M12 M12 M12
caged caged caged
term. term. term.
2
Terminal capacities - main and aux. terminals mm 35 35 35 120 120 185 185 185 2x150 1) 2x185 2)
Mounting position to DIN 40 046 IEC 68 vertical mounting plane ± 22.5°
Shock resistance, normal mounting position, half sine shock,
shock duration 20 ms N/O /N/C g 5.5/4 5.5/4 6.5/5.5 5/4 4.5/3.5 4/3 4/3 5/3 5/3 3.5/3
Climatic conditions humid warmth, constant, acc. to DIN IEC 68 Part 2-3
humid warmth, cyclic, acc. to DIN IEC 68 Part 2-30
Weight kg 1.2 1.3 2.1 3.2 3.2 9.0 9.0 18 18 30
Rated operational current Ie 230/400 A 10/6 10/6 10/6 10/6 10/6 10/6 10/6 10/6 10/6 10/6
for auxiliary contacts on AC 15 duty 500/690 A 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2
Rated thermal current of auxiliary switches Ith /Ithe A 16 16 16 16 16 16 16 16 16 16
Rated insulation voltage of auxiliary VDE 0110 V 690 690 690 690 690 750 750 750 750 750
Short-circuit protection of contactor without thermal relay type 1 or 2 3) A 125/100 125/100 200/160 250/224 315/250 400/355 500/355 630/500 800/630 800/630
Short-circuit protection of auxiliary switches fuse gL/gI A 16 16 16 16 16 16 16 16 16 16
Capacitor contactor on request
Notes
1)
Also suitable for 2 x 30 x 5 mm
2)
Also suitable for 2 x 40 x 5 mm
3)
Short-circuit withstand of contactor without overload relay corresponding to type 2 coordination (No damage to device, except light welding of contacts).
4)
Slotted screwdriver up to DL 42 N
1668
S015013 000623
Power consumption (economy circuit coil)1) inrush W 105 105 105 105 105 105
hold W 1 1 1 1 1 1
Permissible range of operating voltage Vc 0.8...1.25 DC / 0.8...1.1 AC
Minimum and maximum rated minimum V 12 12 12 12 12 12
operating voltages maximum V 220 220 220 220 220 220
Switching times at 20° C Making:
- N/O closes after ms 12...30 11...20
AC
Breaking:
- N/O opens after ms 10...20 5...20
Making:
- N/O closes after ms 20...30 15...30
(economy circuit coil) DC
Breaking:
- N/O opens after ms 10...16 10...30
Rated thermal current for auxiliary contact Ith/Ithe A 16 16 16 16 - -
Rated operational current Ie on DC 13 at 24 V A 10 10 10 10 - -
110 V A 2 2 2 2 - -
220 V A 0.75 0.75 0.75 0.75 - -
on DC 12 at 24 V A 10 10 10 10 - -
resistive 110 V A 6 6 6 6 - -
load 220 V A 1 1 1 1 - -
Maximum cable size for auxiliary contacts mm2 2.5 2.5 2.5 2.5 - -
Short-circuit protection of auxiliary switches gL A 16 16 16 16 - -
Notes
1)
Power consumption of AC and true DC coils see page 1667.
2)
Main contacts connected parallel, see accessories on page 1614.
1669
S015014 000623
Rated insulation voltage Vi V 900 900 900 900 900 900 900 1200 1200 1200
Rated thermal current Ith open A 80 100 130 230 260 290 360 380 500 600
Ithe enclosed A 75 90 115 200 230 260 315 340 460 540
Rated operational current Ie on DC 1 24 V A 75 90 115 200 230 260 315 340 460 540
with series wiring of main contacts 110 V A 75 90 115 200 230 260 315 340 460 540
220 V A 75 90 115 200 230 260 315 340 460 540
circuit (L/R ≤ 15 ms) 24 V A 75 90 115 200 230 260 315 340 460 540
diagram on 110 V A 75 90 115 200 230 260 315 340 460 540
DC 3 + DC 5 220 V A 12 25 60 90 150 200 200 250 300 350
Permissible DC load up to 60 V DC, L/R ≤ 5 ms, A 160 200 240 360 460 500 - - - -
single pole version2)
Terminal capacities - Main terminals at single pole mm 2 70 95 95 150 150 240 - - - -
switching
Power consumption (economy circuit coil)1) inrush W 186 260 260 280 280 400 400 1150 1150 1320
hold W 8 6 6 6 6 9 9 11 11 11
Permissible range of operating voltage Vc 0.8...1.1 Vc (from warm)
Minimum and maximum rated min. V 12 12 12 12 12 24 24 42 42 42
operating voltages max. V 220 220 220 220 220 220 220 220 220 220
Switching times at 20° C Making:
- N/O closes after ms 14-19 11-16 11-28 12-20 12-20 12-25 12-25 20-60 20-60 35-110
AC
Breaking:
- N/O opens after ms 16-20 10-15 10-15 10-17 10-17 12-18 12-18 20-35 20-35 35-55
Making:
- N/O closes after ms 10-20 20-40 20-40 20-30 20-30 35-55 35-55 35-65 35-65 50-60
(economy circuit coil) DC
Breaking:
- N/O opens after ms 12-18 7-12 7-12 10-14 10-14 10-18 10-18 18-28 18-28 30-60
Rated thermal current for auxiliary contact Ith/Ithe A 16 16 16 16 16 16 16 16 16 16
Rated operational current Ie on DC 13 at 24 V A 10 10 10 10 10 10 10 10 10 10
110 V A 5 5 5 5 5 5 5 5 5 5
220 V A 1 1 1 1 1 1 1 1 1 1
on DC 12 at 24 V A 10 10 10 16 10 16 16 16 16 16
resistive 0110 V A 6 8 8 8 6 8 8 8 8 8
load 220 V A 1 1 1 2 2 2 2 2 2 2
Maximum cable size for auxiliary contacts mm2 4 4 4 4 4 4 4 4 4 4
Short-circuit protection of auxiliary switches gL A 16 16 16 16 16 16 16 16 16 16
Notes
1)
Power consumption of AC coils - page 1668
2)
Main contacts connected parallel, see accessories on page 1623.
1670
S015015 000623
1671
S015016D 000623
Electrical life
on AC 2 to AC 4
VDE 0660, Part 102
Typical values:
Example: DL 22 N
Three-phase motor 22 kW
rated operational current 44 A
= max. breaking current on AC 3
Electrical life
106 operations
Three-phase motor 22 kW
6 times rated operational current
6 x 44 A = 264 A
= max. breaking current on AC 4
Electrical life PN = Rating of IA = Breaking current Ie = Rated operational
5 x 104 operations 3-phase squirrel current
cage motor
Electrical life
Utilization category
100 % AC 1 - VDE 0660, Part 102-4.3.6
switching resistive loads (cos ϕ 0.95)
e.g., resistance furnaces
DL 4 K / DL 5 K 75 %
DL 22 N to DL 110 N 90 %
DL 132 N 85 %
DL 165 N to DL 270 N 90 %
1672
000919
S015017
Base mount
Base mount
To 35 mm mounting rail (AM 1-DP 200 or AM 1-DE 200) DIN 50 022 To 35 mm mounting rail (AM 1-DP 200 or AM 1-DE 200) DIN 50 022
Mounting on printed circuit board Mounting reversing contactors or 2 contactors side by side on printed circuit board
1673
000919
S015018
HL 4 K control relay
HLg 4 K control relay
HL 8 K control relay (HL 4 K + aux. contact: H = 120 mm)
Dimension H :
120 mm with aux. contact
125 mm with latch head
137 mm with timer
127 mm with aux. contact with plunger
Contactors DL 4 K...-DL 11 K, DLg 4 K..-DLg 11 K, DLW 4 K...DLW 18 K, with M 23 K thermal relay attached
Dimension H : Dimension B :
120 mm with aux. contact with 2 side mounted aux. contact blocks = 68+1
125 mm with latch head Dimension L :
137 mm with timer with relay interface module RM-K
127 mm with aux. contact with plunger
Contactors DL 15 K...DL 18 K, DLg 15 K...DLg 18 K, star-delta contactors DLDAe 7,5 K...DLDAe 30 K, with M 40 K thermal relay attached
Type : supply ∆ Y
voltage
Dimension H : Dimension B :
DLDAe 7.5 K 4K 4K 4K
132 mm with aux. contact with 2 side mounted aux. contact blocks = 68+1
12.5 K 7K 7K 4K
139 mm with latch head Dimension L :
15 K 7K 7K 5K
150 mm with timer with relay interface module RM-K
18.5 K 15 K 11 K 7K
139 mm with aux. contact with plunger
22 K 15 K 15 K 7K
30 K 15 K 15 K 11 K
1674
S015019 000623
DL 4 K DC..., DL 11 K DC... + M 23 K
HL 4 K DC, HL 8 K DC
Dimension H :
159 mm with aux. contact
166 mm with aux. contact with plunger
166 mm with latch head
177 mm with timer
with module = 106 mm high
DL 15 K DC / DL 18 K DC + M 40 K
Dimension H :
171 mm with aux. contact
178 mm with aux. contact with plunger
178 mm with latch head
189 mm with timer
with module = 106 mm high
1675
S015020 000731
1 2
1676
S015021 000623
2
1
1677
S015022 000623
1678
NA10FC3T 001222
1679
S022003 000623
Approvals:
Characteristics
Thermal overload relay M 06
Type Current range Order ref.: Contact Fuse size Weight Dimensions
configuration kg page
aM1) gL2)
M 06 ... A A A
Accessories:
Adapter block to mount M 06 thermal overload relay separately
snaps on to 35 mm DIN rail (DIN EN 50 022).
Type Order ref.: Weight Dimensions
kg page
EM 3 310 001 01 0.100 1688
Notes
1)
Use of the back-up fuse quoted will give type 2 short-circuit protection to IEC 947-4. aM-fuse 10.3 x 38 mm to be used
2)
Extract from IEC 947-4 : No damage shall occur to the motor protection relay. gL-fuse up to 2 A, fuse terminal to be used
Welding of contactor contacts is acceptable provided contacts can be easily separated.
1680
S022004 000623
Wiring
There are two ways to wire the M 06 thermal overload relay in the control
cirucit
Description:
Description: Internal wiring is not required when building up a control in the normal
Terminal 95 and terminal 96 are internally wired and connected to the pins on configuration. N/C contact 95/96 can be connected to coil termination A1.
the right hand side of the relay. The pins go to terminals 14 (22) and A2 on the When doing this, remove the two connecting pins using side cutting
contactor. pliers. This applies also where voltages applied to contactor and thermal
overload relay are different.
N/C contact 95/96 is connected in series with coil termination A2.
Lift off transparent cover. The desired reset mode can now be set on a
2 position switch:
Lift off transparent cover. Settings are now accessible. - left hand position: ("H") = hand reset
Set desired value using potentiometer with ampere dial plate. - right hand position: ("A") = automatic reset
Setting can be locked by sealing the cover. The cover, when closed, will lock the selector in position.
To reset the overload relay by hand, press the blue RESET/STOP
button.
The test function is carried out by pressing the red TEST button with the
2 position switch in the "H" position.
Pressing this button will simulate tripping of the overload relay:
Press blue RESET/STOP pushbutton to stop the relay. - both N/C and N/O auxiliary contacts will operate
Pressing this button will only operate the N/C contact. The N/O button - the mechanical indicator will appear
will remain unaffected. The cover, when closed, will lock the TEST function.
To reset the overload relay, operate the blue RESET/STOP button.
1681
000919
S022005
Approvals:
M 23 K also approved
Characteristics
Type Setting range Max. permissible Order ref.: Contact Max. fuse Weight Terminal
setting value configuration size kg capacities
for contactor type DL numbering class gL
A to A A
M 23 K 0.12...0.18 1 245 501 27 0.75 flink
1682
S022006 000731
Approvals:
Characteristics
Type Setting range Max. permissible Order ref.: Contact Max. fuse Weight Terminal
setting value configuration size kg capacities
for contactor type DL numbering class gL
A to A A
caged terminals
M 80 N 32...50 44 DL 22 N 1 245 741 27 100
1 x 6...35 mm2
40...57 1 245 851 27 100
screws M 6,
Main poles:
50...63 60 DL 30 N 1 245 852 27 100 0.27
57...70 1 245 853 27 125
63...80 79 DL 42 N 1 245 854 27 125
M-b 177 S 63...90 1 222 221 27 200
80...110 1 222 222 27 200
1 x 4...120 mm2,
90...120 119 DL 65 N 1 222 110 27 224 0.75
110...135 1 222 111 27 315
terminal lug
Main poles:
M 8 x 20
120...150 1 222 112 27 315
135...160 170 DL 90 N 1 222 113 27 315
150...180 205 DL 110 N 1 222 114 27 315
M-bw 17 S 4...6.3 1 222 100 27 25
5.6...8 1 222 101 27 40 1.3
1683
S022007 000623
Terminal shrouds for use with contactors and thermal overload relays to VDE 0106, Part 100 (VBG-4)
Type Order ref.: Notes
DL 65 N / DL 90 N 3 284 148 04 retrofitting
DL 90 N + M-b 177 S / DL 65 N + M-b 177 S 3 284 148 05 not fitted as standard
DL 110 / 132 N + M-bw 207 -S 3 243 049 01 not fitted as standard
DL 110 N ... 270 N 3 284 156 02 shroud with M 12 connecting screw (1 set = 6 off)
M-bw 17 S ... M-bw 207 S 3 222 019 01 not fitted as standard
M-b 177 S 3 222 018 01 not fitted as standard
DLDAe 110 / 160 N (1 set = 3 off) 3 284 148 03 not fitted as standard
Fitting/supply at extra cost
LED
antiparallel
1684
S022008 000623
Full protection
Continuous overloading
1)
Single phasing and
current unbalance
Voltage and
frequency fluctuations
Rotor locked
Stator-critical motors
rotor-critical motors
1)
When using phase-failure sensitive overload relay
1685
S022009 000623
General information
for thermal overload relays
General
Contactors and contactor assemblies can be supplied
with thermal overload relays for the protection of
motors against excessive high currents. When ordering,
care must be taken to ensure that the correct relay
current range is selected in conformity with the rated
motor current. The overload relays are designed for
a switching frequency of 15 to 30 ops/hr. Higher
switching frequencies heat up the bi-metal strips,
thereby causing premature tripping.
Technical details
Trip class of the thermal overload relays
Trip class 10 A 10 20 30
Max. trip time at 1.5 x current setting (s) 120 240 480 720
(warm state)
Trip time at 7.2 x current setting (s) 2...10 4...10 6...20 9...30
(cold state)
Notes
When the tripping time of 30 s is exceeded (at 7.2 x setting current from cold state) instead of the tripping class the maximum tripping time in seconds is indicated.
Our thermal overload relays can also be used for protection of motors in the degree of protection EExe. For the selection of the thermal overload relays, please
provide the following information: IA / IN and the TE-time. Information can be taken from the motor rating label.
When thermal overload relays are used in star-delta assemblies, set relay pointer to 0.58 times the value of the rated motor current or select suitable model.
1686
S022010 000623
Main circuits
Overload type M 06 M 23 K M 80 N M-b 177 S M-bw 17 S M-bw 320 S M-bw 721 Sw
M 40 K bw 207 S
Rated insulation voltage Vi 690 690 690 690 690 690 690
Auxiliary circuits
Overload type M 06 M 23 K M 80 N M-b 177 S M-bw 17 S M-bw 320 S M-bw 721 Sw
M 40 K bw 207 S
Rated insulation voltage Vi 690 400 400 400 400 400 400
DC 13 24 V 1 1 1 1 1 1 1
Rated operational current Ie 60 V 0.5 0.5 0.75 0.5 0.5 0.5 0.5
of c/o : A 110 V 0.4 0.25 0.4 0.25 0.25 0.25 0.25
L/R ≤ 15 ms 220 V 0.2 0.1 0.2 0.1 0.1 0.1 0.1
1) 1)
Pressing H Hand Auto A
the button :
Hints for setting Red function selection Gently turn red State in Press grey button Gently turn red
knob which shipped (R), Gently turn knob
red knob
1) 2)
N/C contact cannot inadvertently be operated in positions H and A. Allow unit a short time to cool in the tripped state.
More technical information available on request.
Brief description
In safety positions -A- and -H- the button functions for switching are locked whereas in positions -HAND- and -AUTO- the switching and the simulation of tripping
directly at the relay is possible by operating the multi-function button.
In positions -H- and -HAND- the tripped relay must be reset manually, whereas in positions -AUTO- and -A- the tripped relay is reset automatically.
The setting of the functions is done by gently turning the red function selection knob (FWK) to the marks of the grey RESET-button (R). Passing from -HAND- to -AUTO-
the grey RESET-button must be slightly pressed at the same time.
1687
S022011 000623
b 177 S Dimensions
b I n n1 Ør i n2 n3 n4 Øf m
63...90 A 104 87.5 15 13.5 8.6 26.5 10 14 7 6.5 85.5
80...160 A 102 79 15 13.5 8.6 37/42 15 5.5 13 8.6 -
150...180 A 96.5 76.5 20 11.5 9 37/42 20 5 10 9 -
1688
S022012 000623
bw 77 S with caged
terminal
bw 77 S with FASTON
connector
1689
S021004 000623
✔ Molded
enclosure
✔ Short-circuit limiter
✔ Busbar
adapter
✔ Three phase busbar
to accept four units
incoming supply block ✔ Internal mounting :
electric trip device
alarm signaling switch
auxiliary switch block
1690
S021005 000623
Short-circuit
limiter MSU-L 20 X X X
2 N/O MSU-A 2
2 E/M MSU-A 5
as above,
key release MSU-K 2
as above, MSU-K 3
spring return
options X
alternative options
1691
S021006 000623
Approvals :
Accessories only MSU-L 20 ... MSU-A 5 approved
Characteristics
Selection table Manual motor starters with thermal and magnetic trip devices
Max. AC 3 ratings of Setting range Ir Tripping current Type P/N Weight
3-phase motors 50...60 Hz Short-circuit kg
220 V 380 V 415 V 440 V 500 V 660 V limiter
240 V 400 V 690 V Irm
kW kW kW kW kW kW A A
- - - - - - 0.1 ... 0.16 1,9 MSU-K 0016 1 364 101 01 0.25
- - - - - - 0.16 ... 0.25 3 MSU-K 0025 1 364 102 01 0.25
- - - - - - 0.25 ... 0.40 4,8 MSU-K 0040 1 364 103 01 0.25
- - - - - 0.37 0.40 ... 0.63 7,5 MSU-K 0063 1 364 104 01 0.25
- - - - 0.37 0.75 0.63 ... 1 12 MSU-K 010 1 364 105 01 0.25
- 0.37 - - 0.75 1 1 ... 1.6 19 MSU-K 016 1 364 106 01 0.25
0.37 0.75 1.1 1.1 1.1 1.5 1.6 ... 2.5 30 MSU-K 025 1 364 107 01 0.25
0.75 1.5 1.1 1.5 2 3 2.5 ... 4 48 MSU-K 040 1 364 108 01 0.25
1.1 2.2 2.2 2.2 3 4 4 ... 6.3 75 MSU-K 063 1 364 109 01 0.25
2.2 4 3 3 5.5 7.5 6.3 ... 10 120 MSU-K 10 1 364 110 01 0.25
4 7.5 7.5 7.5 10 11 10 ... 16 190 MSU-K 16 1 364 111 01 0.25
5.5 10 9 9 11 15 16 ... 20 240 MSU-K 20 1 364 112 01 0.25
5.5 11 11 11 15 18.5 20 ... 25 300 MSU-K 25 1 364 113 01 0.25
Accessories
Type P/N
Short-circuit limiter Iu = 32 A, Ve ... 415 V MSU-L 20 3 364 051 01
Electrical trip device Under- 110/120 V 50/60 Hz MSU-B 1 3 364 052 25
(1 per manual motor voltage 220/240 V 50/60 Hz MSU-B 2 3 364 052 40
controller) trip 380/440 V 50/60 Hz MSU-B 3 3 364 052 59
Other voltages on request
Open 110/120 V 50/60 Hz MSU-D 1 3 364 053 25
circuit 220/240 V 50/60 Hz MSU-D 2 3 364 053 40
trip 380/440 V 50/60 Hz MSU-D 3 3 364 053 59
Other voltages on request
Auxiliary switch blocks : side mounting 1 N/O + 1 N/C MSU-A 1 3 364 054 01
side mounting 2 N/C MSU-A 2 3 364 054 02
side mounting 1 E/M + 1 N/C MSU-A 3 3 364 054 03
side mounting 2 E/M MSU-A 5 3 364 054 05
side mounting 1 c/o contact for increased cont. reliability MSU-A 6 3 364 054 06
internal fitting 1 N/O + 1 N/C MSU-A 7 3 364 054 07
internal fitting 1 N/C alarm cont. (alarm signalling switch) MSU-A 8 3 364 054 08
internal fitting 1 N/O alarm cont. (alarm signalling switch) MSU-A 9 3 364 054 09
side mounting PE and N termination MSU-A 10 3 364 054 10
Notes
Recommendation : it is recommended that 4 A to 25 A units are spaced 10 mm apart.
Technical details and dimensions pages 1697, 1700
Selection criteria page 1695
1692
S021007 000623
Accessories
Description MSU-ST 31 MSU-G 05
MSU-L 20 MSU-ST 32
MSU-G 4
MSU-A 1
MSU-G 03 MSU-B/-D...
MSU-A
Characteristics
Type P/N
Busbar adapter, Iu 32 A, Ve 660 V, 54 mm wide, for mounting a MSU-K manual motor starter
(including accessories) on busbars with a cross section of 12 x 5 mm or 12 x 10 mm with a MSU-G 05 3 364 006 01
busbar spacing of 40 mm.
Busbar adapter, Iu 32 A, Ve 660 V, 54 mm wide, for mounting a MSU-K manual motor starter MSU-G 06 3 364 007 01
(including accessories) with Ie limiter, otherwise as above.
Busbar adapter, Iu 32 A, Ve 660 V, 54 mm wide, for MSU-K manual motor starter and MSU-LC 292 3 364 028 01
contactors up to 11 kW (2 mounting rails), otherwise as above.
Incoming supply block 80 A, Vi 660 V for connection of the supply lead when using MSU-G 4 3 364 056 01
the 3-phase busbar system MSU-G 03
Set of links 3 pole (Contactor - Manual motor starter) MSU-VS 3 3 366 070 00
Protecting cap, 3 pole, for unused phase terminals on the 3-phase busbars MSU-DS S 3 364 057 01
(packing unit : 10 each)
Busbar support for 3 copper busbars, 12 or 15 mm wide and 5 mm thick; MSU-ST 31 3 364 010 01
the busbar spacing can be 40 or 50 mm, as required (dynamic short-circuit rating
50 kA with 50 mm busbars and 500 mm support spacing).
Packing unit : 1 set = 2 complete busbar supports including captive fixing screws.
Busbar support as above, but for 60 mm busbar spacing, copper busbars MSU-ST 32 3 364 029 01
12...30/5 mm
Notes
Typical applications page 1701
1693
S021008 000623
Accessories
Description
MSU-SL ... MSU-C ...
MSU-V 1
MSU-P
MSU-N 1
MSU-K 1
Characteristics
Molded enclosure Surface mounting type (RAL 7032) IP 41 MSU-C 1 3 364 058 01
with ground protection Surface mounting type (RAL 7032) IP 55 MSU-CE 1 3 364 058 02
Flush mounting type (RAL 7032) IP 41 MSU-P 1 3 364 059 01
Position lock for molded enclosure with 3 padlocks in the off position
Interlocking device for 3 padlocks with 8 mm shackle dia IP 55 MSU-V 1 3 364 015 01
Emergency stop button, stayput, red on yellow surface, IP 41 MSU-K 1 3 364 061 01
resetting by pulling
Emergency stop button, spring return, red on yellow surface MSU-K 3 3 364 073 01
Indicator lights with fixed connection lead red MSU-SL-1 3 364 063 01
and neon lamp 110 V .... 120 V AC/DC white MSU-SL-2 3 364 063 07
green MSU-SL-3 3 364 063 02
N or PE termination
for fitting into MSU-C+P enclosures (1additional pc.) MSU-N 1 3 364 066 01
Notes
* Follow special mounting instructions when fitting into molded enclosure !
1694
S021010 000623
0.4...0.63 65 65 o 65 65 o 65 65 o 65 65 o 42 42 o
0.63...1 65 65 o 65 65 o 65 65 o 65 65 o 1 1 20
1...1.6 65 65 o 65 65 o 65 65 o 65 65 o 1 1 20
Short-circuit limiting
To increase the Icu/Ics, the MSU-K can be combined with the short-circuit limiter MSU-L20.
For this combination there are the following values for rated service short-circuit breaking capacity :
Notes
1)
Icu = Rated maximum short-circuit breaking capacity
2)
Ics = Rated service short-circuit breaking capacity
1695
S021009 000623
min
x Current value
The "characteristic curve" of the thermal overcurrent trip device shows tripping for all setting ranges as a function of the multiple of the set current value, and
represents the mean value of the scatter bands in the cold condition.
When switchgear is at operating temperature, the trip time of the thermal overcurrent trip device is reduced to approx. 25 % of the values shown.
Terminal capacities
Type Conductor Number of Conductor cross section, mm2
type conductors 1 1,5 2 2,5 4 6 10 16 or 25
MSU-K solid 1 ✘ ✘ ✘ ✘ ✘ ✘ - -
(manual 2 ✘ ✘ ✘ ✘ ✘ ✘ - -
motor flexible with 1 ✘ ✘ ✘ ✘ ✘ - - -
starter) wire end ferrule 2 ✘ ✘ ✘ ✘ ✘ - - -
MSU solid 1 ✘ ✘ ✘ ✘ ✘ ✘ ✘ ✘
(short 2 ✘ ✘ ✘ ✘ ✘ ✘ ✘ -
circuit flexible with 1 ✘ ✘ ✘ ✘ ✘ ✘ ✘ -
limiter) wire end ferrule 2 ✘ ✘ ✘ ✘ ✘ ✘ ✘ ✘
MSU-A solid 1 ✘ ✘ ✘ ✘ - - - -
(auxiliary 2 ✘ ✘ ✘ ✘ - - - -
switch) flexible with 1 ✘ ✘ ✘ ✘ - - - -
wire end ferrule 2 ✘ ✘ - - - - - -
MSU solid 1 ✘ ✘ ✘ ✘ ✘ ✘ ✘ ✘
(incoming 2 ✘ ✘ ✘ ✘ ✘ ✘ ✘ -
supply flexible with 1 ✘ ✘ ✘ ✘ ✘ ✘ ✘ ✘ (16)
block) wire end ferrule 2 ✘ ✘ ✘ ✘ ✘ ✘ - -
1696
S021011 000623
Climatic-proof Damp heat, constant, to DIN IEC 68 Part 2 Test 3, damp heat, cyclic,
to DIN IEC 68 Part 2 Test 30
Rated operational voltage Ve up to 690 V AC, (up to 600 V AC to CSA and UL) up to 220 V DC
Max. breaking capacity Icn according to IEC 157-1 (P-1) : o-t-co VDE 0660/T 101
see table page 1695
Trip curve T II
Undervoltage trip Pick up : 0.85 to 1.1 Uc, drop out : 0.7 to 0.35 Uc, 2,2 VA, 1 W, voltage should be continuously
applied (100 % duty)
Open circuit shunt release Pick-up at 0.7 to 1.2 x Vc, 50 % duty, power consumption 3.4 VA, 1.6 W
Auxiliary switch :
Thermal currrent I 6A
Rated operational current Ie side AC 11 : 230 V, 3.5 A / 400 V, internal AC 11 : 230 V, 2 A / 400 V, 1A /
mounted : 2 A / 500 V, 1 A; fitting : 500 V, 0.5 A
DC 11 : 60 V, 1.5 A / 110 V, DC 11 : 60 V, 0,7 A / 110 V,
1 A / 220 V, 0.5 A 0.55 A / 220 V, 0.25 A
1697
S021013 000623
Special features MSU-K manual motor starters have a high breaking capacity up to 6.3 A : ∞ up to 10 A; 6 kA, up to
High breaking capacity 25 A : 4 kA at 400 V. This is made possible by a modern design, by which very short break times are
achieved. Because of this, the circuit breakers have become limiters. The advantages are :
- Back-up fuses are only necessary at rated equipment currents > 2,5 A and 400 V.
- The dynamic and thermal loading of electrical installation components at short-circuit is reduced.
Short-circuit limiter By the use of the short-circuit current limiter, the short-circuit breaking capacity of the MSU circuit
breakers of ≥ 6.3 A-25 A rated current at 380/415 V is increased to 50 kA. Fuses can largely be
eliminated.
Temperature compensation To achieve high tripping accuracy over a large ambient temperature range, MSU-K manual motor
starters are temperature compensated from -5°C ... +55°C
Integrable shunt release Undervoltage or open-circuit tripping devices, as well as alarm contacts, can be integrated in the
and alarm contacts equipment. Contour and dimensions of the equipment remain unchanged.
Operating safety in accordance The equipment cap covers the terminal screws. This meets the safety requirements of VDE 0106
with VBG 4 Part 100 and VBG 4.
Simple mounting The manual motor starter is easily clipped on to a mounting rail (DIN EN 50 022) by an integral snap-
on mount.
Convenient and rapid connection Captive terminal screws supplied in the "open" position allow time-saving and simple connection :
insert the wire, tighten screws, done. Time and effort for unscrewing of the terminal is eliminated and
terminal parts can no longer go astray.
Easy auxiliary switch mounting Auxiliary switches are necessary for signalling or for interlocking circuitry. ENTRELEC-SCHIELE has
selected modular construction to avoid mistakes during assembly. Simple adaptation to requirements
is possible and stocking reduced.
Modular construction The equipment is designed such that its shape is identical with that of automatic circuit breakers.
Because of this, it can easily be installed in flush-mounted distribution systems. When an auxiliary
switch is attached, the manual motor starter has the same overall width as a 3-pole automatic circuit
breaker.
Accessories To ensure optimum protection against dust and water in all applications, the range includes three
Protective casing types of enclosures, of impact-resistant insulation material and of protection types IP 41 and IP 55.
The protection level can be increased to IP 55 by an additional kit. The circuit breaker can be clipped
into all types of casing. The sizes of enclosures are such that even switchgear with an auxiliary switch
attached to it can easily be fitted and the terminal compartment for cable connection is ample in size.
Auxiliary switches for side mounting, Five different auxiliary switch blocks can be supplied. After removing the front cover, the block can
on right and left hand side be snapped in without tools.
Auxiliary switch for internal fitting Remove the front cover and snap in the auxiliary switch block.
Three-phase busbars Our three-phase busbars for 4 connections are suitable for parallel connection of any number of
for Vu = 660 V, Iu = 80 A manual motor starters with auxiliary switch blocks fitted provided the Ith of 63 A is not exceeded. The
first busbar is used - in combination with the incoming supply block MSU-G 4 - for supplying the
system and for parallel connection of the first manual motor starter. Manual motor starters can be
connected additionally to each additional busbar in parallel, as required, and without cutting the bar
to length. The incoming supply can also be connected at the center or on both sides. The gives good
load distribution.
Typical applications page 1701.
Additional covering is not necessary, because both switchgear and busbars are safe to touch (satisfy
VDE 0106 Part 100) in the basic versions. Unused outlets have a shock protection cover.
1698
S021012 000623
Short-circuit limiter Iu = 32 A By attaching the short-circuit limiter to the manual motor starter, back-up fuses can be dispensed with
for all non-intrinsically safe equipment ≥ 2,5 A - 25 A at 400 V. The rated breaking capacity Icn (of the
combination of manual motor starter and short-circuit limiter) is increased as a result of heavy current
limitation and short break time (see page 1695). With this, it is possible to use the switchgear combination
in the power system where the prospective short-circuit current exceeds the "normal" switching capacity
of the manual motor starter. The short-circuit limiter can be used - taking into account the continuous
current Iu - as individual or group protection for several MSU-K ... manual motor starters.
Typical applications page 1701.
Shunt release Undervoltage trip MSU..B for protection from hazardous re-starting of machines after power failure.
Open circuit shunt release Open circuit shunt release MSU-D.. for control and interlocking purposes are inserted under the
switchgear cover.
Mounting of the shunt release and After removing the cover, these can be clipped in with a "handle" and the connections on the knock-
alarm contact out of the cover are turned outwards. The above assembly procedure also applies to alarm contacts.
Emergency stop button When manual motor starters are to be used as emergency stop devices, this can be done with
emergency stop button sets
- MSU-K 3 (spring return)
- MSU-K 2 (stay put, released by key)
- MSU-K 1 (stay put, released by pulling)
Fixing is with 4 screws from the inside of the cover.
Interlocking devices When used as a main switch, the manual motor starter must be lockable in the off position in accordance
with VDE 0113. This requirement can be fulfilled using the interlocking device MSU-V 1. It is fixed
with 4 screws from the inside of the casing (only with MSU-C and MSU-P) and is located such that
by-passing of the interlock - e.g. by removing the casing cover - is impossible.
Indicator light For visual indication of the switch position (enclosed equipment), the indicator light MSU-SL can be
supplied. After breaking out a knock-out on the casing cover, the light is pushed through from the
front and fastened with screws from the rear and is then electrically connected.
Alarm contact The alarm contact MSU-A has alarm signaling function. Ist N/O or N/C contact is actuated when
thermal or electromagnetic release - fault - takes place. It does not respond to manual actuation of
the MSU-K.
1699
S021014 000623
Circuit diagrams
Manual motor starter Current limiter Undervoltage trip Open circuit trip Alarm contact
MSU-K MSU-L20 MSU-B.. MSU-D.. MSU-A 8 (1 N/C)
MSU-A 9 (1 N/O)
Dimensions
Manual motor starter MSU-K Manual motor starter MSU-K Mounting positions
with short-circuit limiter
Auxiliary switch
a = 208
Molded enclosure, surface mounting types MSU-C 1, MSU-CE 1 Molded enclosure, flush mounting type MSU-P 1 cut-out 118 x 72 mm
1700
S021015 000623
Busbar adapter
Typical applications
Types of protection
Busbar spacing :
40 mm 60 mm
*1. Copper busbars 12-30/5 mm *1. Copper busbars 12-30/5 mm 8. Manual motor starter MSU-K ... 1. 3-phase busbar MSU-G 03
2. Busbar adapter MSU-G 05 2. Busbar adapter MSU-LC 291 9. Contactor DL ... 11 kW 2. Manual motor starter MSU-K ...
3. Manual motor starter MSU-K ... 3. Manual motor starter MSU-K ... 10. Busbar support MSU-ST 32 3. Manual motor starter MSU-K ...
or or 4. Manual motor starter MSU-K ...
4. Busbar adapter MSU-G 06 4. Busbar adapter MSU-LC 291 Supply via terminal block MSU-G 4
5. Current limiter MSU-L 20 5. Current limiter MSU-L 20
6. Manual motor starter MSU-K 6. Manual motor starter MSU-K ...
7. Busbar support MSU-ST 31 or
7. Busbar support MSU-LC 292
1701
NOTES