Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Standby 500 kW
Prime 455 kW
60 Hz 1800 rpm 480V
Specifications
Standby Prime Speed
Frequency Voltage
kW (kVA) kW (kVA) rpm
480V 60 Hz Rating
60 Hz 480/277V 500 (625) 455 (568) 1800
60 Hz 240/139V 500 (625) 455 (568) 1800
60 Hz 208/120V 500 (625) 455 (568) 1800
600V 60 Hz Rating
60 Hz 600V 500 (625) 455 (568) 1800
60 Hz 480V 400 (500) 365 (456) 1800
LEHX0028-01 Page 1 of 9
Cat® XQ570 Rental Generator Set
LEHX0028-01 Page 2 of 9
Cat® XQ570 Rental Generator Set
LEHX0028-01 Page 3 of 9
Cat® XQ570 Rental Generator Set
LEHX0028-01 Page 4 of 9
Cat® XQ570 Rental Generator Set
Technical Data
Cat Generator
Frame Size LC6134G
Pitch 0.6667
No. of poles 4
Excitation Static regulated brushless PM excited
Number of bearings Single bearing, close coupled
Insulation Class H
Enclosure Drip proof IP23
Alignment Pilot shaft
Overspeed capability – % of rated 125% of rated
Voltage regulator 3-phase sensing with volts-per-hertz
Voltage regulation (adjustable to compensate for
Less than ± 1⁄2% voltage gain
engine speed droop and line loss)
Wave form deviation 3%
Telephone Influence Factor (TIF) Less than 50
Harmonic Distortion (THD) Less than 5%
LEHX0028-01 Page 5 of 9
Cat® XQ570 Rental Generator Set
XQ570 — Weight
Weight— kg (lb)
Lube Oil & Coolant – Empty Fuel DEF Tank 14,400 (31,900)
Chassis Weight Addition 3,379 (7,450)
Standard Features
EMCP 4.4 Local Control Panel • Shutdowns with common indicating light for
• Generator-mounted EMCP 4.4 provides power - Low oil pressure - Overspeed
metering, protective relaying, and engine and - High coolant temp - High oil temp
generator control and monitoring. - Failure to start (overcrank) - Emergency stop
• NEMA 12, IP44 dust-proof enclosure - Low coolant level
• UL508A listed • Emergency stop pushbutton
• Convenient service access for Cat service tools • Panel illuminating lights
(service tools not included) • Display navigation keys including two shortcut
• Integration with the Cat IVR provides enhanced keys for engine parameters or generator
system monitoring parameters
• Ability to view and reset diagnostics of all • Fuel level monitoring and control
controls networked on primary CAN data link
EMCP 4.4 Generator Protective Relaying
eliminates need for separate service tools for
• Generator protective features provided by
troubleshooting.
EMCP 4.4
• True RMS AC metering, 3 phase
- Phase over/under voltage (device 27/59)
EMCP 4.4 Engine Operator Interface - Over/under frequency (device 81 O/U)
• Controls - Reverse power (device 32/32RV)
- Run/auto/stop - Emergency stop - Current balance (46)
- Speed adjust - Cycle crank - Overcurrent (device 50/51) (GCB trip unit)
- Voltage adjust - Cool-down timer - Loss of excitation (device 40) (Cat DVR)
• Engine monitoring - Generator phase sequence
- rpm - DC volts
Container
- Operating hours - Oil pressure
• 20' ISO standard cube container
- Coolant temperature - Oil temperature
• Painted standard Cat power module white
• Generator monitoring
• Sound attenuated air intake louvers
- L-L volts, L-N volts, phase amps
• Floor insulated with acoustic glass and covered
- Average volts, amps, frequency
by galvanized steel
- ekW, kVA, kVAR, kW-hr, %kW
• Two lockable personnel doors with panic
- Power factor (average, phase)
release
- kW-hr, kVA-hr (total)
• External drain access to standard fluids
LEHX0028-01 Page 6 of 9
Cat® XQ570 Rental Generator Set
LEHX0028-01 Page 7 of 9
Cat® XQ570 Rental Generator Set
Modes of Operation
• Provides for single unit standalone operation, b. A run request is sent to the PM generator
island mode paralleling and load sharing with plant
other power modules, and single unit-to-utility c. The first PM generator to reach rated
mode paralleling for base load control (with to voltage and frequency is closed to
open transition between paralleling modes) the bus
• Island mode paralleling features: d. In multi-unit island mode, the remaining
- Lead unit select control allows single unit to PM generators are paralleled to the bus as
connect to a dead bus or Hard Wired Dead they reach rated voltage and frequency.
Bus Arbitration (HWDBA) to allow first unit This function is performed via the lead
up to voltage and speed to be first unit to unit select jumper and interconnect wiring
connect to a dead bus connected between the power modules.
- Auto synchronization (voltage and phase e. Plant load is transferred to the power
matching) modules, which share load equally via load
- Load sharing (kW) analog signal (like units share lines.
and legacy compatible)
Single Unit Base Load Operation
- Load sharing (kVAR) analog signal (like
• Utility mode (normal)
units only)
- The utility is providing power for the plant
• Utility mode paralleling features:
loads
- Auto synchronization (voltage and phase
- The PM is in auto mode and the generator
matching)
breaker is open
- Base-load control (programmable set-point or
- The PM is interconnected to the utility
potentiometer adjust)
breaker aux contact, lead unit jumper is
- Soft load/unload (programmable, shared
not installed and load share lines are not
set-point)
connected
- Power factor control (programmable set-point)
- The paralleling controls automatically detect
Single Unit Standalone and Multi-unit utility parallel mode when the utility aux
Island Operation contact is closed
• Utility standby mode (normal) • Base load mode
- The utility is providing power for the plant - Unit receives remote run request and starts
loads - Unit reaches rated voltage and frequency
- The PM generator breaker is open - UMR performs sync-check to permit generator
- The PM is in automatic standby mode to breaker to close
respond to a utility failure - Unit ramps to base-load set point at
• Emergency mode (emergency) programmed ramp time
- Utility failure - Unit continues to run until remote run
a. The customer protective relaying senses a request is removed or unit is stopped at
utility abnormal condition control panel
LEHX0028-01 Page 8 of 9
Cat® XQ570 Rental Generator Set
www.Cat.com/rentalpower
©2016 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, ACERT, MEUI, ADEM, “Caterpillar Yellow”,
the “Power Edge” trade dress as well as corporate and product identity used
LEHX0028-01 (1-16) herein, are trademarks of Caterpillar and may not be used without permission.