Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Lecture-10
Introduction to Earthquake
Resistant Analysis & Design
of RC Structures (Part II)
By: Prof Dr. Qaisar Ali
Civil Engineering Department
UET Peshawar
www.drqaisarali.com
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Topics Addressed
Load Combinations
Miscellaneous Considerations
Design Example
References
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 2
1
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 3
Load Combinations
E = ρEh + Eν
E = Eh + Eν
E = Eh + 0.5CaID
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 4
2
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 5
Load Combinations
Soil type: SD
For seismic zone 2B and soil type SD, Seismic coefficient Ca = 0.28
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 6
3
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 7
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 8
4
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
1.4D
1.4D+1.7L
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 9
Load Combinations
1.2D+1.6L
0.9D ± 1.0E
BCP SP-2007
BCP has same combinations as UBC-97.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 10
5
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
ACI 318-14 using load combinations and strength reduction factors of UBC-
97.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 11
Load Combinations
Load effects obtained for each load case are multiplied with amplification
factors and combined as per code load combination requirements.
With this approach, the structure has to be analyzed only for each load case.
After analysis, any load combinations can be performed with load cases.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 12
6
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
BAY
15 ft
15 ft
15 ft
20 ft 20 ft 20 ft 20 ft
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 13
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 14
7
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 15
Example 1 E E
26 22 22
9
-1.4
-43 -43 -0.5 -17 -17 -39 -22 -37 39 -22 37
44 40 43 39
4.5 -37 -37 -39 -35 44 -37
1.4D + 1.7L 1.474D + 0.55L + 1.1E 1.14D + 1.1E Envelop
1.166D + 0.55L − 1.1E 0.84D − 1.1E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 16
8
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
SDL = 40 psf
LL = 60 psf Portion of frame
considered
15 ft
15 ft
15 ft
20 ft 20 ft 20 ft 20 ft
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 17
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 18
9
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Bent left (+) Bent right (−)
Case Study 1
26 22 Bent down (+) Bent up (−)
BM Sign convention for beam
-1.4 -39 -37
-43 -43 -22
2.0 37 33
1.0D 1.0E
9 22
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 19
Load Combinations
-2.8 -2.5
-89 -89 -79 -79
4.5 4.0
Load combination 1
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 20
10
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
41 39 37 35
-35 -47
-84 -91
-38 -33 -34 -30
1.166D + 0.55L − 1.1E (UBC-97) Load combination 2 & 3 1.2D + 1.0L − 1.0E (ACI-318-14)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 21
Load Combinations
42 39 38 36
-12 -17
-60 -61
-39 -35 -35 -31
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 22
11
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Note that in each case, strength reduction factors are different. Therefore,
there will be difference in reinforcement as well.
Caution about use of load combination in SAP2000: Before designing in SAP2000,
make sure that combinations used are the same as used in the relevant code.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 23
Load Combinations
SDL = 40 psf
LL = 60 psf
15 ft
15 ft
15 ft
20 ft 20 ft 20 ft 20 ft
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 24
12
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
h=10.5 ft
F2 =15.5 kips
h=10.5 ft
F1 = 7.74 kips
h=10.5 ft
Load Combinations
Column
Moments
Beam
Moments
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 26
13
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Column
Moments
Beam
Moments
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 27
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 28
14
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 29
Load Combinations
Column
Moments
Beam
Moments
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 30
15
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Column
Moments
Beam
Moments
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 31
Load Combinations
Column
Moments
Beam
Moments
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 32
16
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
Column
Moments
Beam
Moments
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 33
Load Combinations
Column
Moments
Beam
Moments
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 34
17
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Load Combinations
74 52 31 52 74 54 22 21 22 54
Column
55 62 52 62 55 56 42 37 42 56
Moments
91 133 123 133 91 85 81 77 81 85
78 58 58 78 84 36 36 84
-74 -109 -88 -88 -88 -88 -109 -74 -38 -60 -80 -71 -71 -80 -60 -38
10 78 2 58 2 2 58 2 78 10 6 50 37 37 50 6
-100 -135 -114 -114 -114 -114 -135 -100 -72 -93 -86 -85 -85 -86 -93 -72
Beam
Moments 56 78 37 48 58 48 48 58 48 37 78 56 46 54 10 3 37 10 10 37 3 10 54 46
-146 -181 -160 -160 -160 -160 -181 -146 -97 -123 -109 -105 -105 -109 -123 -97
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 35
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 36
18
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 37
44
51 37
-38
34
-50 -80 -75 -73
54 36
-36
-38 -85 -79 -71 -2
1.2D+1.6L
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 38
19
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
-19 35 25 -12 27 25
11 4
-21 -65 -41 -59 -10 -48 -25 -44
54 31
-16 -8 32 17
-5 -95 -51 -80 -35 9 -61 -19 -52 -32
1.2D+1.0L+1.0E 0.9D+1.0E
36 27
-31 31 25 -23 21 18
34 27 -44
-46 -43 -60 -39 -36 -27 -24
41 33 22 19
-32 -25
-60 -51 -86 -42 32 -45 -18 -55 -15 32
1.2D+1.0L−1.0E 0.9D−1.0E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 39
1.2D+1.0L+1.0E 0.9D+1.0E
51 33
-43 40 33 -28 21 19
50 37
-66 -49 -81 -45 -46 -18 -52 -16
-46 41 37 -32 23 22
1.2D+1.0L−1.0E 0.9D−1.0E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 40
20
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
-19 50 33 -4 30 19
2 -11
-13 -94 -42 -85 6 -63 -13 -56
63 33 46 20
-12 -2
-31 -123 -21 -105 -77 -90 3 -77 -80
1.2D+1.0L+1.0E 0.9D+1.0E
54 37
-45 40 34 -30 22 20
56 42
-72 -44 -86 -40 -53 -12 -57 -12
41 38 -36 24 24
-50
-97 -22 -109 -18 81 -82 10 -78 9 80
1.2D+1.0L−1.0E 0.9D−1.0E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 41
53 33 32
-16 0 20
-5 -18
-4 -101 -36 -91 14 -70 -7 -63
70 36 49 23
-6 7
49 -138 -15 -117 -100 64 -105 15 -89 -101
1.2D+1.0L+1.0E 0.9D+1.0E
59 42
-49 39 36 -34 22 21
64 50
-81 -37 -92 -34 -61 -5 -63 -5
-56 42 40 -31 26 28
1.2D+1.0L−1.0E 0.9D−1.0E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 42
21
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
54 33 35 20
-11 2
-13 3 -26 23
-108 -29 -98 -77 0 -69
78 37 58 21
-1 12
68 -152 -4 -130 -122 83 -119 26 -102 -123
1.2D+1.0L+1.0E 0.9D+1.0E
64 46
-53 40 35 -38 23 22
71 58
-89 -29 -97 -27 -70 1 -69 0
42 44 29 34
-61 -47
-134 6 -132 6 127 -119 39 -101 34 126
1.2D+1.0L−1.0E 0.9D−1.0E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 43
B
Story 2
A
(A) (B)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 44
22
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
B
A Story 1
(A) (B)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 45
Story 2
C F
(C) (F)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 46
23
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Story 1
C F
(C) (F)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 47
E
Story 2
(E)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 48
24
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
E
Story 1
(E)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 49
Top moment
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 50
25
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 51
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 52
26
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
3. Goto Define → Special Seismic Load Effects and select from two
options based
Vertical on requirement:
component of earthquake loads can also be neglected
1. After(i)completing
Include Special
Vertical Seismic
theDefine
modeling,
component
Goto of Design
goto
earthquake
if Load Data
loadsDesign
Add Default
acceptable. can be
(ii) Do
Option Not
→ Include
Preferences
Click
Goto
included Define
from
Combos Special
Modify→
this
Select →LoadSeismic
Concrete
Button
option.
toConcrete
Generate to
load
Frame Design
Frame
detailsto
Combinations
Design Data
Design
seecombinations
of
to see the
Option (i) is normally selected.
load
Load
generated
generate combinations
Combination
load combinations details
Load combinations
for concrete
Select UBC-97 so that
Load UBC load including
combination combinations
verticalcan be generated
(Without inclusion
material of vertical
component
component of earthquake
of earthquakeload
load)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 54
27
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Option 21
In a second option, To perform analysis and design as per BCP, manually define all load
combinations as per UBC-97 in Define Load Combination section.
Then go to design Concrete Frame Design View/ Revise Preferences and change design code
to ACI 318-05.
Change the strength Go reduction
to Design factors
Concrete as Frame
per UBC Design
i.e., ΦView/
for shear
Revise
andPreferences
torsion = 0.85 instead
of 0.75. After tocompleting
select code for thedesign.
structural model, go to Define Load cases
SometimesDefined Load load
the desired patterns
combinations might not match the required code
and Go required
all to Define load
load Combinations
patterns. to generate Load
Note: UBC 97 used for earthquake load definition.
combinations, therefore all combinations should be checked before final design.
combinations
To generate load aspattern
per UBC-97
combinations select the code. As UBC isdiscussed
used for in
AfterEarthquake
this, the model load
is ready should
for analysis bedesign
and defined
as perasUBC-97.
earthquake
previous definition therefore select UBC.
lecture
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
Structural systems designed for high and moderate seismic risk are
referred to as Special and Intermediate respectively.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 56
28
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 57
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 58
29
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 59
(Seismic Hook)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 60
30
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
i. they carry the horizontal shear forces induced by earthquakes, and thereby
resist diagonal shear cracks,
ii. they hold together the vertical bar and prevent them from excessively
bending outwards (in technical terms, this bending phenomenon is called
buckling), and
iii. they contain the concrete in the column. The ends of the ties must be bent
at 135° hooks. Such hook ends prevent opening of hoops and
consequently buckling of concrete and buckling of vertical bars.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 61
Note: These provisions generally apply to beams because axial load on beams
is generally less than Agfc′/10.
However they are also applicable to columns subjected to axial load less
than Agfc′/10.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 62
31
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
e.g., for width (b) = 12″ and depth (h) = 18″, b/h = 12/18 = 0.67 > 0.3, O.K.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 63
32
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
s d/2
≥ 2h ≥ 2h
Column
Column
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 65
≥ 2h ≥ 2h
33
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 67
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 68
34
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 69
1. Size
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 70
35
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Clear span, hc
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 71
Larger of h1 or h2
lo Clear span/6
6 long. bar dia.
18” s
6”
72
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures
36
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
hx
Alternate hx
90-deg hooks
hx hx hx
4” ≤ so = 4 + [(14 – hx)/3] ≤ 6”
hx = max. value of hx on all column faces
hx 14”
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 73
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 74
37
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 75
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 76
38
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
M+nb,r
M-nc,b M+nc,b
M+nc,b + M-nc,t 6(M+nb,l + M-nb,r)/5 M-nc,b + M+nc,t 6(M-nb,l + M+nb,r)/5
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 77
20db
Column
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 78
39
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
The ACI 318-14 does not give complete details for the design
and detailing of joints of SMRF. For details see ACI 352-02
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 79
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 80
40
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Asl− Asr−
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 82
41
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
so/2
lo h2
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 83
Miscellaneous Considerations
Unlike regions of high seismic risk, two way slab system without
beams are allowed in regions of moderate seismic risk.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 84
42
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
Detail the selected frame of E-W interior frame of the given
structure as per SMRF requirements. The structure is already
designed for the following seismic zone data.
Seismic zone: 4
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 85
Design Example
Slab-Beam
Given 3D structure: Frame
Structure
Beams: 15″ × 24″
fc′ = 3 ksi Columns: 15″ square
fy = 40 ksi
SDL = 40 psf
LL = 60 psf
15 ft
10.5 ft Zone = 4
15 ft Ca = 0.44
20 ft 20 ft 20 ft 20 ft
Cv = 0.64
I=1
W = 2002
V = 259 kip
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 86
43
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
Load Combinations
ACI 318-14 load combinations have been used.
1.2D+ 1.6L
0.9D + 1.0E
0.9D − 1.0E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 87
Design Example
Analysis
Analysis has been done using SAP2000. SAP2000 develops
envelop of maximum bending moments automatically for the
given load combinations.
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 88
44
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
Analysis
Analysis results for shown portion of E-W interior frame is
shown next.
10.5 ft
15 ft
15 ft
10.5 ft
15 ft
20 ft 20 ft 20 ft 20 ft
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 89
E E
26 -38.7 38.7
11
-1.4
-37 -37 -0.5 -13.6 -13.6 -72
-38.7 -68 72 -38.7 68
42 23
49 42 +4 23 +4 +4 +49 +4
-80 -80 -74 -19.3 -96.7 -70 -73 -82 -82 -69 -74 -96.7 -96.7 -70
-2.5 70 -96.7 - 67 70 68
19.
70 3 64 69 63
4 -64 -58 -65 -59 70 64
1.2D + 1.6L 1.2D + 1.0L + 1.0E 0.9D + 1.0E Envelop
1.2D + 1.0L − 1.0E 0.9D − 1.0E
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 90
45
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
Selected portion of E-W interior Frame:
Bending Moment Envelop
As the software checks SMRF moment capacity requirements and ACI
minimum moment capacity requirements at critical sections. Therefore
final shape of the bending moment envelop of the beam is as shown:
According to SMRF requirements the +ve As at the beam ends = ½ -ve As at beam ends. Therefore value of 4 has been changed to 48.3.
Mid span bending moment value of 49 has been changed to 95.3 due to the requirement of minimum reinforcement at critical regions.
70 64
Analysis Envelop
20 ft 20 ft 20 ft 20 ft
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 91
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 92
46
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
20 ft 20 ft 20 ft 20 ft
Column reinforcement:
2.25/ 0.31 = 7.25 (take 8 bars for even
distribution of bars at all faces of column)
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 93
Design Example
SMRF Requirements Checklist
Provisions for Beams
Sizes
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 94
47
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
SMRF Requirements Checklist
Provisions for Beams
Flexural Reinforcement
Asl− = 6 #5 Asr− = 6 #5
As+ (at joints) ≥ ½ As− (at joints) As (at all critical sections) ≥ Asmin
4 #5 bars ≥ ½ (6 #5 bars) OK As Asmin = 6 #5 bars OK
Provide at least 6 bars at critical sections)
As (any section) ≥ ¼ Max. As at joints
As (at any section) ≤ Asmax
2 #5 bars ≥ ¼ (6 #5 bars) OK Asmax = 0.025bd = 25 #5 bars OK
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 95
Design Example
SMRF Requirements Checklist
Provisions for Beams
Flexural Reinforcement
Asl− = 6 #5 Asr− = 6 #5
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 96
48
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
SMRF Requirements Checklist
Provisions for Beams
Transverse Reinforcement
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 97
Design Example
SMRF Requirements Checklist
Provisions for Beams
Lap Splice: If required then,
Not to be provided within joints. Not to be provided within 2h region from face of
the support.
2h=48″ 2h=48″
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 98
49
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
SMRF Requirements Checklist
Provisions for Columns
Size: All columns are 15″ square, which is more than least required for
SMRF (i.e., 12″).
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 99
Design Example
SMRF Requirements
Checklist
Provision for Columns
lo
Transverse Reinforcement:
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 100
50
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
SMRF Requirements Checklist
Provisions for Columns
Lap Splice:
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 101
Design Example
SMRF Requirements Checklist
Provision for Joints
To prevent beam column joint cracking, ACI Code 18.8.2.3 requires that
the column dimension parallel to the beam reinforcement must be at
least 20 times the diameter of the largest longitudinal bar.
20 × 5/8 = 12.5″
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 102
51
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
SMRF Requirements Checklist
Provision for Joints
6 #5 bars
2″
6 #5 bars
Beam
Joint Column
Interior joint
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 103
Design Example
SMRF Requirements Checklist
Provision for Joints
For exterior columns, the column dimension parallel to beam longitudinal
bar must be greater than the development length of beam bars in
columns with 90° hooks is not to be less than largest of:
The development length of beam bars in columns with 90° hooks is not
to be less than largest of:
8db = 8 × 5/8 = 5″
6″
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 104
52
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design Example
SMRF Requirements Checklist
Provision for Joints
Development of beam
reinforcement in column
= 13″ > ldh = 7″
Development of beam
reinforcement in column
= 22″ > ldh = 7″
2″
Beam
Joint Column
Exterior Joint
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 105
References
ACI 318-14
UBC-97
BCP
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 106
53
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
The End
Prof. Dr. Qaisar Ali CE 5115 Advance Design of Reinforced Concrete Structures 107
54