Hilti PROFIS Engineering 3.0.

61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200-R + HAS-U A4 M12
Return period (service life in years): 50
Item number: 2223845 HAS-U A4 M12x180 (element) / 2045036
HIT-HY 200-R (adhesive)
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 140.0 mm (hef,limit = - mm)
Material: A4
Evaluation Service Report: ETA 12/0084
Issued I Valid: 8/28/2019 | -
Proof: SOFA design method + fib (07/2011) - after ETAG BOND testing
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm

Anchor plate :
R lx x ly x t = 350.0 mm x 235.0 mm x 12.0 mm; (Recommended plate thickness: 10.0 mm)

Profile: Double flat bar, ; (L x W x T) = 72.0 mm x 35.0 mm x 5.0 mm


Base material: 2
cracked concrete, C40/50, fc,cyl = 40.00 N/mm ; h = 230.0 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

Application also possible with HVU2 + HAS-U A4 M12_hef1 under the selected boundary conditions.
More information in section Alternative fastening data of this report.

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -0.800; Vx = 0.000; Vy = 4.300; no no 83
Mx = -0.600; My = 0.000; Mz = 0.000;

2 Combination 2 N = -0.800; Vx = 0.000; Vy = -4.300; no no 83


Mx = 0.600; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces


Controlling load case: 1 Combination 1
y

Anchor reactions [kN]


Tension force: (+Tension, -Compression) Compression
Anchor Tension force Shear force Shear force x Shear force y x
1 2.285 11.288 0.000 -11.288
2 2.450 15.588 0.000 15.588
1 2
max. concrete compressive strain: 0.06 [‰] Tension
max. concrete compressive stress: 1.71 [N/mm ]
2

resulting tension force in (x/y)=(-98.6/-67.5): 4.735 [kN]


resulting compression force in (x/y)=(-62.7/61.8): 5.535 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

3 Tension load SOFA (fib (07/2011), section 16.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 2.450 31.551 8 OK
Combined pullout-concrete cone failure** 4.735 32.084 15 OK
Concrete Breakout Failure** 4.735 47.701 10 OK
Splitting failure** 4.735 54.496 9 OK

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

NRk,s [kN] gM,s NRd,s [kN] NSd [kN]


59.000 1.870 31.551 2.450

3.2 Combined pullout-concrete cone failure


0 2
Ap,N [mm ]
2
Ap,N [mm ] y A,Np t Rk,ucr,25 [N/mm ]
2
scr,Np [mm] ccr,Np [mm] cmin [mm]
129,894 115,200 1.128 15.00 339.4 169.7 140.0
0
yc t Rk,cr [N/mm ]
2
max t Rk,cr [N/mm ]
2
y g,Np y g,Np
1.079 7.55 15.28 1.270 1.139

ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np


1.4 0.992 0.0 1.000 0.947 1.000
0
NRk,p [kN] NRk,p [kN] gM,p NRd,p [kN] NSd [kN]
39.872 48.125 1.500 32.084 4.735

Group anchor ID
1, 2

3.3 Concrete Breakout Failure


0 2
Ac,N [mm ]
2
Ac,N [mm ] y A,N ccr,N [mm] scr,N [mm]
175,000 176,400 0.992 210.0 420.0

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


1.4 0.993 0.0 1.000 0.900 1.000
0
k1 NRk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.700 80.670 1.500 47.701 4.735

Group anchor ID
1, 2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

3.4 Splitting failure


0 2
Ac,N [mm ]
2
Ac,N [mm ] y A,N ccr,sp [mm] scr,sp [mm] y h,sp
199,800 211,600 0.944 230.0 460.0 1.223

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1


1.4 0.994 0.0 1.000 0.883 1.000 7.700
0
NRk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
80.670 1.500 54.496 4.735

Group anchor ID
1, 2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

4 Shear load SOFA (fib (07/2011), section 16.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 15.588 18.910 83 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength* 15.588 48.018 55 OK
Concrete edge failure in direction y+** 15.588 20.597 76 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

VRk,s [kN] gM,s VRd,s [kN] VSd [kN]


29.500 1.560 18.910 15.588

4.2 Pryout Strength (Bond Strength controls)


0 2
Ap,N [mm ]
2
Ap,N [mm ] y A,Np t Rk,ucr,25 [N/mm ]
2
ccr,Np [mm] scr,Np [mm] cmin [mm]
64,947 115,200 0.496 15.00 169.7 339.4 140.0
0
yc t Rk,cr [N/mm ]
2
max t Rk,cr [N/mm ]
2
k4 y g,Np y g,Np
1.079 7.55 15.28 2.000 0.000 1.000

ec1,V [mm] y ec1,Np ec2,V [mm] y ec2,Np y s,Np y re,Np


0.0 1.000 0.0 1.000 0.947 1.000
0
NRk,p [kN] NRk,p [kN] gM,c,p VRd,cp [kN] VSd [kN]
39.872 21.299 1.500 48.018 15.588

Group anchor ID
1, 2

4.3 Concrete edge failure in direction y+

lf [mm] dnom [mm] kV a b


140.0 12.00 1.700 0.100 0.061
0 2
c1 [mm] Ac,V [mm ]
2
Ac,V [mm ] y A,V
140.0 105,000 88,200 1.190

y s,V y h,V y a,V ec,V [mm] y ec,V y re,V y 90°,V


1.000 1.000 1.000 40.0 0.840 1.000 2.000
0
VRk,c [kN] gM,c VRd,c [kN] VSd [kN]
30.895 1.500 20.597 15.588

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
bN bV a Utilization bN,V [%] Status
steel 0.078 0.824 2.000 69 OK
concrete 0.148 0.757 1.500 72 OK

a a
bN + bV <= 1

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 1.815 [kN] dN = 0.0344 [mm]


VSk = 11.546 [kN] dV = 0.5773 [mm]
dNV = 0.5783 [mm]
Long term loading:

NSk = 1.815 [kN] dN = 0.0757 [mm]


VSk = 11.546 [kN] dV = 0.9237 [mm]
dNV = 0.9268 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Bore hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• The anchor plate overlaps the concrete plate edges. A local concrete spalling due to compression has to be checked separately!
• Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

8 Anchor plate stress check


Scope: For the loads / load combinations applied on the anchor plate, an anchor plate stress check is performed (based on the results of a
FE calculation). This stress check contains normal stresses resulting from bending moments in two directions. The user is responsible to
select an anchor plate thickness that meets the requirement per guideline for a rigid anchor plate (to ensure that the assumed load distribution
(1)
is correct). A detailed description can be found in Mallée.

(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999

8.1 Base material properties

Steel type: S 275


2
Yield stress: fy = 275.00 [N/mm ]
Partial safety factor: gm,s = 1.000
2
Ultimate strength: fu = 430.00 [N/mm ]
2
Young's modulus: Es = 210,000.00 [N/mm ]
Poisson ratio: n = 0.3

8.2 Results

Relevant load combination: LC 01

Stress distribution s 11
2
182.02 [N/mm ]

2
-81.65 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

Stress distribution s 22
2
61.89 [N/mm ]

2
-222.06 [N/mm ]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

Deformations (z-direction)
2.3 [mm]

-0.6 [mm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

9 Installation data
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm
2 2 Anchor type and diameter: HIT-HY 200-R + HAS-U A4
M12
Profile: Double flat bar, ; (L x W x T) = 72.0 mm x 35.0 mm x 5.0 mm Item number: 2223845 HAS-U A4 M12x180 (element) /
2045036 HIT-HY 200-R (adhesive)
Hole diameter in the fixture: df = 14.0 mm Installation torque: 40 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 14.0 mm
Recommended plate thickness: 10.0 mm Hole depth in the base material: 140.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 170.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

Hilti HAS-U threaded rod with HIT-HY 200 injection mortar with 140 mm embedment h_ef, M12, Stainless steel, SAFEset Auto cleaning
Hammer drilled installation per ETA 12/0084, with annular gaps filled with Hilti Filling set or any suitable gap solutions

9.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Filling set
the hole • Torque wrench
• Proper diameter wire brush

150.0
y
175.0 175.0
117.5
77.0

185.0

x
117.5

1 2
50.0

35.0 80.0 235.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -140.0 -67.5 - - - 140.0
2 -60.0 -67.5 - - - 140.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

10 Alternative fastening
10.1 Alternative fastening data

Anchor type and diameter: HVU2 + HAS-U A4 M12_hef1


Return period (service life in years): 50
Item number: 2223844 HAS-U A4 M12x160 (element) / 2164507
HVU2 M12x110 (capsule)
Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 110.0 mm, hnom = 110.0 mm
Material: A4
Evaluation Service Report: ETA-16/0515
Issued I Valid: 11/13/2019 | -
Proof: SOFA design method + fib (07/2011) - after ETAG BOND testing
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm

Anchor plate :
R lx x ly x t = 350.0 mm x 235.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)

Profile: Double flat bar, ; (L x W x T) = 72.0 mm x 35.0 mm x 5.0 mm


Base material: 2
cracked concrete, C40/50, fc,cyl = 40.00 N/mm ; h = 230.0 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

Max. Utilization with HVU2 + HAS-U A4 M12_hef1: 83 %


Fastening meets the design criteria!

10.2 Installation data


2 2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm Anchor type and diameter: HVU2 + HAS-U A4 M12_hef1
Profile: Double flat bar, ; (L x W x T) = 72.0 mm x 35.0 mm x 5.0 mm Item number: 2223844 HAS-U A4 M12x160 (element) /
2164507 HVU2 M12x110 (capsule)
Hole diameter in the fixture: df = 14.0 mm Installation torque: 40 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 14.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 110.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 140.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

Hilti HAS-U threaded rod with HVU2 capsule mortar with 110 mm embedment h_ef, M12_hef1, Stainless steel, SAFEset Auto cleaning
Hammer drilled installation per ETA-16/0515, with annular gaps filled with Hilti Filling set or any suitable gap solutions

10.2.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • HVA square drive shafts
• Properly sized drill bit accessories to blow from the bottom of • Filling set
the hole • Torque wrench
• Proper diameter wire brush

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.0.61

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/middle-east.html
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: bkt N6 Date: 6/18/2020
Fastening point:

11 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan