YORK ® VARIABLE REFRIGERANT FLOW

System Product Catalog


Commercial VRF HVAC Systems
Water Cooled

Standard Efficiency Cooling Only Modular & Mini VRF


YORK® Variable Refrigerant Flow System

Efficiency and comfort for your customers.


New growth opportunities for your business.

Building climate control is about comfort and efficiency – delivering


just the right heating and cooling to every space using no more energy 2 WHY VRF?
than necessary. YORK® variable refrigerant flow (VRF) technology lets
Introducing YORK® VRF 2-4
you do that for customers in innovative ways that present new growth What is VRF? 5
opportunities for your business. Why Partner with
Johnson Controls? 7-9
VRF technology gives building owners, architects, consulting engineers, Summary of Features
and Benefits 10-11
and mechanical contractors an innovative solution to address the
common challenge of reducing operating costs in buildings with varied
loads and occupancy rates while delivering comfort to all areas. The 12 INDOOR UNITS
systems can offer:
Overview 13-15
• Exceptional efficiency, delivering energy savings for some applications Ductless Units 16-21
Ducted Units 22-24
compared to conventional HVAC systems.

• Flexibility to specify a customized modular system to the exacting


35 OUTDOOR UNITS
requirements of each project, with options that include heat pump
and a host of fan coil options. Overview 36-37

• Freedom for designers to choose ducted systems with short or


long runs, or ductless systems that allow for much lower clearance 38 OPTIONAL PARTS
between building floors and therefore lower overall construction costs. & ACCESSORIES
Optional Parts
• Impressively quiet comfort, with control to deliver precisely the & Accessories 39
correct amount of heating or cooling to each zone.

40 CONTROLS

Control Systems 41
Interface 42
Central Station 43

The information contained in this catalog is for illustration purposes only and is subject to change at the sole discretion
of Johnson Controls. Statements, figures, calculations, plans, images and representations are only examples. Johnson
Controls encourages you, as the purchaser, to analyze your HVAC requirements and to work with Johnson Controls to
determine the exact VRF System to fulfill your needs.

2 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 1
Introducing YORK® VRF from Johnson Controls

YORK® VRF systems are modular and controlled Gain control flexibility
solutions that include models with capability to Users can deploy from three basic control options.
heat or cool different zones.
• Indoor fan coil units come with a selection of thermostats, from simple
The technology brings an array of advantages over conventional units with on/off, setpoint, load and speed settings, to programmable
systems. units that enable scheduling. Wireless units are available to provide
remote control of zone space conditions.
• Save on energy. Systems essentially eliminate duct losses. In addition,
variable-speed compressors in outdoor units provide extremely high • Central station controllers for larger projects provide remote control
part-load efficiency. and scheduling of the entire system from one or more control points.

• Keep people comfortable. Users can set individual temperature • Adapters (gateways) enable control of large buildings or campuses
set points for multiple zones. Variable-speed compressors with through building automation systems such as Metasys®.
wide capacity and precise modulation help maintain each zone’s
temperature within a narrow range. Indoor units also operate quietly. Choose multiple applications

• Go green. VRF technology can help users attain LEED® certification YORK® VRF systems suit a wide range of buildings in new construction
points for resource efficiency. and retrofits. Prime candidates include:
• Buildings with multiple zones that have different comfort needs –
Enjoy design freedom such as hotels, schools, medical office buildings, commercial office
A variety of standard modular components let you customize and buildings and others.
size equipment to meet specific project requirements. Because • Historical building renovations in which ducted HVAC options are
ductwork is generally needed only for ventilation, ducts can be smaller, severely limited and the basic building structure must not be disturbed.
reducing capital cost. Systems can easily be adapted as space is
• Buildings in climate zones favorable for heat pump technology.
reconfigured. Unlike conventional HVAC systems, VRF systems allow
addition of capacity to accommodate expansion simply by adding
modular units (capacities 10-39 HP). There is no need to remove and
replace the original unit or reconfigure ductwork.

Install with ease


YORK® VRF systems are designed for quick and simple installation,
since piping from the outdoor units can be connected from the front,
back, or underneath. Indoor units are small and light and easy to
transport and handle; outdoor units can be brought into a building
for installation on a rooftop via a service elevator – no crane or other
heavy equipment is needed. Service is simple, too: Systems need little
maintenance beyond changing filters and cleaning coils.

2 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 3
Advanced compressor technology yields the highest efficiency How VRF works
ratings resulting in energy savings
A VRF system typically consists of one or more outdoor condensing
units from which refrigerant is piped to a series of indoor fan coil units
Rated highest for energy efficiency
serving individual zones within building spaces. The system conditions
The YORK® VRF Systems boast YORK® systems rank impressively high in the ratings that matter most the spaces by delivering to the indoor fan coil units only the volume
for VRF technology. The traditional measure of HVAC equipment, energy of refrigerant required to meet the heating or cooling needs of each
efficiencies up to:
efficiency ratio (EER), measures system efficiency at full load. While this zone (see Figure 1).
• 4.65 EER may be appropriate for equipment that operates in a traditional cycle (fully
The basic types of YORK® VRF Water Cooled systems, ranging
on or fully off), it is not appropriate for properly sized VRF systems, which
from 10-30 HP capacity:
spend the vast majority of time at part load, reaching full load only on the
hottest or coldest days. YORK® VRF systems excel against truer measures • Heat pump VRF systems are two-pipe systems
of efficiency:

Exclusive Hitachi compressor


results in high efficiency ratings

The core technology of YORK® VRF systems is the exclusive Hitachi- Heat pump VRF systems are two-pipe systems that
designed high-efficiency scroll compressor. Hitachi invented the first air enable design for ductless or ducted applications. Precise
conditioning scroll compressor in 1983 and in 2008 applied a cutting- heating or cooling is delivered to multiple zones.
edge large-capacity scroll compressor to VRF technology. Its advantages
include a high compression ratio, excellent reliability and efficiency, and
lower compressor noise level.

Profit from quality and innovation


The YORK® VRF line includes a wide selection of products and
control options. Numerous innovative features enhance performance,
energy efficiency, quiet operation and service life. Quality is built in,
from design through manufacturing in state-of-the-art, ISO-certified
facilities.

Figure 1

4 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 5
Get expert advice at every step: select, design, specify, install Get the tools that give you an edge

Your Johnson Controls account team supports you as no one else Right-size systems with intuitive selection software
can, at every step of every project. Effective training, intuitive design YORK ® VARIABLE REFRIGERANT FLOW

and specification software, advanced logistics and delivery, and easily


The YORK® VRF selection software intuitively guides you step by System Product Catalog
Commercial VRF HVAC Systems
step through equipment selection, so you can quickly and accurately
accessible documentation form a powerful support package that adds Water Cooled
choose an appropriate and cost-effective equipment package for
substantial value to YORK® VRF systems.
each project.
Get your team up to speed fast.
Efficient performance, quality installations. PC-based program

The PC-based program gives you mobility and flexibility. The software
Comprehensive training programs provide knowledge and skills
helps you:
necessary to effectively and efficiently deploy YORK® VRF
technology. Our world-class VRF training center offers a multitude of • Design accurate final system drawings including piping and wiring
classes with specialized modules and topics that help: diagrams in an easy, quick, step-by-step process.

• Salespeople submit competitive bids and close deals. • Accurately select systems using a System Sizing Analysis. The process
starts with the indoor fan coil units, so that outdoor units are optimally
• Designers select and configure the right equipment easily
sized. Proprietary algorithms figure the system size using data input
and accurately.
on the indoor units, load, and measurements, so your system does
• Installers learn the proper procedures and complete jobs not include capacity that will go unutilized.
accurately, on time and on budget. • Use intuitively designed features and functionality that make the
• Service technicians maintain, troubleshoot and repair systems design process easy, fast, and accurate. You can select options and
efficiently. accessories without referring to additional information or performing
additional calculations.
The training center includes a dedicated VRF laboratory to provide
• Gain an edge by confidently designing VRF systems that are right-
hands-on experience with the various systems, components and
sized, and include the right equipment for each project.
controls. YORK® VRF training programs help deliver peace of mind that
your staff is prepared to support your business with the knowledge to
compete in a growing industry.

6 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 7
Get winning advice to make the best decisions
Consistent delivery: YORK® VRF systems bring exciting new possibilities in building space
Get the right equipment to the jobsite on time conditioning, enabling you to satisfy customers, win more business,
and enhance your reputation. When you work with Johnson Controls
Ample inventory and advanced order management and logistics
as your partner, our experts can guide you through a thorough analysis
systems can help you complete installations in a timely manner.
to select the system that best delivers exceptional energy efficiency,
Consistent service and predictable deliveries help you prevent delays
increased occupant comfort, and a lower life-cycle cost. You can choose
waiting for essential components and enable you to set a project timeline
from a wide portfolio of HVAC solutions including:
and schedule labor efficiently. Fast and accurate parts delivery from our
• YORK® VRF systems
main distribution center.
• YORK® chillers
• YORK® rooftop units YORK® VRF systems
Let’s go to work – together • YORK® custom built-up air handlers
• Metasys® building automation systems
YORK® VRF systems can be configured to meet your project
requirements and deliver exceptional performance. Select heat Our analysis will provide data that helps you appropriately compare all
pump or cooling only outdoor units with DC inverter-driven compressors options, so you can make the best-informed decision on every project.
offering energy savings and the ability to scale to size. Multiple
ventilation options help make sure your systems introduce the right
volume of outside air. A host of options and accessories help ensure a
custom fit for your project. And users benefit from our variety of control
technology options. YORK® Chillers

Let’s explore the many advantages of VRF systems together so you


can put them to work for your customers. On these pages, you can
explore detailed information on the full range of YORK® VRF systems.

YORK® Rooftop Units

YORK® custom built-up air handlers

8 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 9
YORK® VRF Systems: Summary of Features and Benefits

FEATURES ADVANTAGES BENEFITS FEATURES ADVANTAGES BENEFITS


Flexible pipe line length: meets • Compatible with almost all types of • In multiple-unit applications at partial load, outdoor • Optimizes efficiency
various projects and can reach • Allows design freedom Rotational operation units operate alternately so that operating hours are • Extends service life
120 meters • projects with long or short pipe line length
shared equally • Increases reliability
ARCHITECT / SYSTEM DESIGNER

• Requires less indoor space than conventional


Reduced installation area • Expands options for positioning outdoor units • Allows one outdoor unit to be taken off-line for • Avoids system downtime
systems Backup operation function
maintenance while remaining units keep operating • Protects occupant comfort

System
• Provides flexibility to customize systems to each • Simplify projects
Modular System Efficiency optimized for
project’s needs • Allows easier adaptation and expansion of the installation • Lower energy consumption with partial loads • Saves energy
part-load operation
• Provides better installation flexibility • Reduces system costs
Ductless systems • Extremely quiet (sound ratings as low as 27
• Greater free area between floor and ceiling • Ideal for historic renovations
dBA for indoor units)
Noise reduction preference • Lets users choose from three settings
• Accommodates retrofits by making use of mode for a “not to exceed” sound level • Ideal where outdoor units are positioned on
existing duct infrastructure side of building or in locations where there are
Ducted systems • Reduces overall construction costs noise restrictions
• Suits unique buildings that include ducted and
ductless areas
DC inverter-driven scroll • Engineered to deliver the optimum efficiency

Compressor
Heat pump VRF systems • Precisely heats or cools multiple zones • Provides extreme system design flexibility • Among industry’s most efficient VRF systems
compressor at normal load conditions
Comprehensive training • Specific training to YORK VRF Selection System • Enables effective equipment selection and specification

• Fast, easy and intuitive selection of the • Allows equipment selection and system pipe line Compressor modulation • Smoothly delivers only the exact amount of • Allows fine control for optimum comfort
System selection software
in 1 Hz increments refrigerant needed for the load

BUILDING OWNER
equipment dimensioning. • Saves energy

• Users can select from a wide variety of power • Limits electric demand charges

Outdoor Units
Demand control settings from 100% to 60% and program “not to • Limits electric consumption
exceed” a given power level • Reduces noise
• Pipe line can be connected to the outdoor unit • Reduces installation time and cost
CONTRACTOR / INSTALLER

from front and lateral side.


Installation simplicity
• Small and light indoor units are easy to handle • Allows demand control programming to act at time • Saves energy
without heavy equipment Demand control with timer
interval of 10 to 20 minutes • Limits demand charges
MECHANICAL

• Specific training to installation and operation of • Provides an installation with higher speed and quality
Comprehensive training
the York VRF System

Indoor Units
As high as .74 WG static • Offers adjustable speeds to match the static pressure • Flexibility to accommodate long or short
• Enhances installation efficiency pressure in ducted systems requirement ductwork runs
Consistent, reliable product • Ensures correct components are delivered to
delivery job sites on time • Allows efficient labor scheduling

Optional motion and • Sets back temperature when space is unoccupied, • Saves energy
• All components accessible via removal of one • Speeds up time spent on maintenance, repair, radiant sensors increasing efficiency even further • Protects occupant comfort
Easy maintenance access and troubleshooting
panel
• Controls multiple indoor and outdoor units from one • Maximizes indoor comfort
control point
H-Link II Protocol • Saves energy
• Adds versatility to connect various central control
options • Improves system management

Controls
• Auto-adjusts for daylight saving time
• Adjusts in 1 degree F increments
Temperature control • Provides options to satisfy multiple projects/
• Adjustable fan speeds
buildings

• Enables control of VRF systems by way of a building • Optimizes comfort


H-LINK II BACnet adapter
management system (e.g. Metasys®) for almost • Saves energy
for integration into BMS
unlimited control in a building of campus enterprise. • Unified interface for all HVAC systems

10 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 11
YORK® VRF INDOOR UNITS

Indoor Units Overview

Choose the style and size from the wide selection of indoor units
to meet your requirements for layout and design.

DUCTLESS INDOOR UNIT MODEL NUMBERS

4-Way Cassette 2-Way Cassette Wall Mount


JTKF028H0PS0AQ JTKF071H0PS0AQ JTKT022H0PS0AS JTKT080H0PS0AS JTHW022H0NB0AQ
JTKF036H0PS0AQ JTKF084H0PS0AQ JTKT028H0PS0AS JTKT112H0PS0AS JTHW028H0NB0AQ
JTKF043H0PS0AQ JTKF090H0PS0AQ JTKT040H0PS0AS JTKT140H0PS0AS JTHW036H0NB0AQ
JTKF050H0PS0AQ JTKF112H0PS0AQ JTKT056H0PS0AS JTKT160H0PS0AS JTHW040H0NB0AQ
JTKF056H0PS0AQ JTKF142H0PS0AQ JTKT071H0PS0AS JTHW050H0NB0AQ
JTKF063H0PS0AQ JTKF160H0PS0AQ JTHW056H0NB0AQ
JTHW063H0NB0AQ

Floor Concealed Floor Exposed


JTFC028H0NB0AQ JTFE028H0NB0AE
JTFC043H0NB0AQ JTFE040H0NB0AE
JTFC056H0NB0AQ
JTFC071H0NB0AQ

DUCTED INDOOR UNIT MODEL NUMBERS

Indoor Units
YORK® VRF indoor units operate quietly 4-Way Cassette
and are easy to install, service and 2-Way Cassette High Static and Medium Ducted Ducted Low Static Ducted Slim
Wall Mounted JTDM022H0NB0AQ JTDH084H0NB0AQ JTDL022H0NB0AQ JTDL071H0NB0AQ JTDN022H0PB0AQ JTDN063H0PB0AQ
maintain. A wide variety of ductless and JTDM028H0NB0AQ JTDH090H0NB0AQ JTDL028H0NB0AQ JTDL084H0NB0AQ JTDN028H0PB0AQ JTDN071H0PB0AQ
Floor Concealed JTDM036H0NB0AQ JTDH112H0NB0AQ JTDL036H0NB0AQ JTDL090H0NB0AQ JTDN036H0PB0AQ JTDS022H0PB0AQ
ducted units are available in styles and JTDM043H0NB0AQ JTDH142H0NB0AQ JTDL043H0NB0AQ JTDL112H0NB0AQ JTDN043H0PB0AQ JTDS028H0PB0AQ
Floor Exposed
JTDM050H0NB0AQ JTDH160H0NB0AQ JTDL050H0NB0AQ JTDL142H0NB0AQ JTDN050H0PB0AQ JTDS036H0PB0AQ
capacities to fit multiple applications. Units High Static and Medium Ducted JTDM056H0NB0AQ JTDH224H0NF0AQ JTDL056H0NB0AQ JTDL160H0NB0AQ JTDN056H0PB0AQ JTDS043H0PB0AQ
JTDM063H0NB0AQ JTDH280H0NF0AQ JTDL063H0NB0AQ
operate quietly with sound ratings as low as Ducted Low Static JTDM071H0NB0AQ
JTDM224H0NF0AQ
27 dBA. Ducted Slim JTDM280H0NF0AQ

12 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 13
YORK® VRF INDOOR UNITS

Indoor Unit Selection

kW 2.2 2.8 3.6 4.5 5 5.6 6.3 7.1 8 9 11.2 14 16 22.4 28

4-Way
Cassette

2-Way
Cassette

Wall
Mount

Ducted
High and
Medium Static

Ducted
Low
Static

Ducted
Slim
4-Way Cassette Indoor Unit
Floor Ceiling mounted 4-way cassettes measuring 33 x 33 inch (84 x
Concealed 84 cm) are offered with standard decorative panels. Compact,
thin and lightweight, they are easy to install even in tight spaces.
Floor
Exposed Key Features

• Optional motion and radiant heat sensors for shutoff and activation in
response to room occupancy. Capacities: 2.8 to 16kW

• Multiple fan speed settings


• Optional fresh air kit available
• Four air volume settings including Ultra Hi for higher ceilings
• 4-way airflow standard but can be configured for 2-way or 3-way
• Integrated condensate pumps included in all units.
• Uniform panel sizing
• Optional lift mechanism allows panel to be lowered for convenient service
access

14 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 15
YORK® VRF INDOOR UNITS

4-Way Cassette Indoor Unit 4-Way Cassette Indoor Unit (continued)


Indoor Unit Type 4-Way Cassette Type Indoor Unit Type 4-Way Cassette Type

Model JTKF028H0PS0AQ JTKF036H0PS0AQ JTKF043H0PS0AQ JTKF050H0PS0AQ Model JTKF056H0PS0AQ JTKF063H0PS0AQ JTKF071H0PS0AQ JTKF080H0PS0AQ

Indoor Unit Power Supply AC 1Φ,220-240V/50Hz AC 1Φ,220V/60Hz Indoor Unit Power Supply AC 1Φ,220-240V/50Hz AC 1Φ,220V/60Hz

kW 2.9 3.8 4.4 5.2 kW 5.8 6.5 7.3 8.7

4,500 Nominal Cooling Capacity*1) kcal/h 5,000 5,600 6,300 7,500


Nominal Cooling Capacity*1) kcal/h 2,500 3,300 3,800
9,900 13,000 15,000 17,700 Btu/h 19,800 22,200 25,000 29,700
Btu/h
2.8 3.6 4.3 5.0 kW 5.6 6.3 7.1 8.4
kW
4,300 Nominal Cooling Capacity*2) kcal/h 4,800 5,400 6,100 7,200
Nominal Cooling Capacity*2) kcal/h 2,400 3,100 3,700
14,700 17,000 Btu/h 19,100 21,500 24,200 28,700
Btu/h 9,500 12,300
3.3 4.2 4.9 5.6 kW 6.5 7.5 8.5 9.6
kW
2,800 3,600 4,200 4,800 Nominal Heating Capacity kcal/h 5,600 6,500 7,300 8,300
Nominal Heating Capacity kcal/h
11,100 14,300 16,700 19,100 Btu/h 22,200 25,600 29,000 32,800
Btu/h
Sound Pressure Level (High/Medium/Low) dB (A) 32-30-28 32-30-28 32-30-28 32-30-28 Sound Pressure Level (High/Medium/Low) dB (A) 32-30-28 32-30-28 32-30-28 32-30-28

248 248 248 248 248 248 248 298


Height mm (in.) Height mm (in.)
(9-3/4) (9-3/4) (9-3/4) (9-3/4) (9-3/4) (9-3/4) (9-3/4) (11-3/4)

840 840 840 840 840 840 840 840


Outer Dimensions Width mm (in.) Outer Dimensions Width mm (in.)
(33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16)

840 840 840 840 840 840 840 840


Depth mm (in.) Depth mm (in.)
(33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16) (33-1/16)

23 23 23 24 24 24 24 26
Net Weight kg (Ibs.) Net Weight kg (Ibs.)
(51) (51) (51) (53) (53) (53) (53) (57)

Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance) Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)

Indoor Fan m3/min. Indoor Fan m3/min. 16/14/12 19/17/14 20/17/15 26/23/20
13/12/11 15/13.5/12 15/13.5/12 16/14/12
Air Flow Rate (Hi/Me/Lo) Air Flow Rate (Hi/Me/Lo) (cfm) (565/494/424) (671/600/494) (706/600/530) (918/812/706)
(cfm) (459/424/388) (530/477/424) (530/477/424) (565/494/424)
Motor W 56 56 56 56 Motor W 56 56 56 56

Flare-Nut Connection (with Flare Nuts) Connections Flare-Nut Connection (with Flare Nuts)
Connections mm
mm Refrigerant Piping
Refrigerant Piping Φ6.35 Φ9.53 Φ9.53 Φ9.53
Φ6.35 Φ6.35 Φ6.35 Φ6.35 (in.)
(in.) Liquid Line
Liquid Line (1/4) (3/8) (3/8) (3/8)
(1/4) (1/4) (1/4) (1/4)
mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
mm Φ12.7 Φ12.7 Φ12.7 Φ15.88 Gas Line
Gas Line (in.) (5/8) (5/8) (5/8) (5/8)
(in.) (1/2) (1/2) (1/2) (5/8)
Condensate Drain VP25 VP25 VP25 VP25
Condensate Drain VP25 VP25 VP25 VP25
Approximate Packing Measurement m 3
0.22 0.22 0.22 0.26
Approximate Packing Measurement m3 0.22 0.22 0.22 0.22
Adaptable Panel Model JP-N23NAQ JP-N23NAQ JP-N23NAQ JP-N23NAQ
Adaptable Panel Model JP-N23NAQ JP-N23NAQ JP-N23NAQ JP-N23NAQ
Color Neutral White
Color Neutral White
37 37 37 37
37 37 37 37 Height mm (in.)
Height mm (in.) (1-7/16) (1-7/16) (1-7/16) (1-7/16)
(1-7/16) (1-7/16) (1-7/16) (1-7/16)
950 950 950 950
950 950 950 950 Outer Dimensions Width mm (in.)
Outer Dimensions Width mm (in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
(37-3/8) (37-3/8) (37-3/8) (37-3/8)
950 950 950 950
950 950 950 950 Depth mm (in.)
Depth mm (in.) (37-3/8) (37-3/8) (37-3/8) (37-3/8)
(37-3/8) (37-3/8) (37-3/8) (37-3/8)
6 6 6 6
6 6 6 6 Net Weight kg (lbs.)
Net Weight kg (lbs.) (13) (13) (13) (13)
(13) (13) (13) (13)
Approximate Packing Measurement m3 0.08 0.08 0.08 0.08
Approximate Packing Measurement m3 0.08 0.08 0.08 0.08

NOTES:
NOTES:
1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616.
1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27°C DB (80°F DB)
Indoor Air Inlet Temperature: 27°C DB (80°F DB)
*1) 19.5°C WB (67°F WB)
*1) 19.5°C WB (67°F WB)
*2) 19.0°C WB (66.2°F WB)
*2) 19.0°C WB (66.2°F WB)
Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Heating Operation Conditions
Heating Operation Conditions
Indoor Air Inlet Temperature: 20°C DB (68°F DB)
Indoor Air Inlet Temperature: 20°C DB (68°F DB)
Outdoor Air Inlet Temperature: 7°C DB (45°F DB)
Outdoor Air Inlet Temperature: 7°C DB (45°F DB)
6°C WB (43°F WB)
6°C WB (43°F WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
1.5 Meter Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.
The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

16 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 17
YORK® VRF INDOOR UNITS

4-Way Cassette Indoor Unit (continued)


Indoor Unit Type 4-Way Cassette Type

Model JTKF090H0PS0AQ JTKF112H0PS0AQ JTKF142H0PS0AQ JTKF160H0PS0AQ

Indoor Unit Power Supply AC 1Φ,,220V/50Hz AC 1Φ,,220V/60Hz


kW 9.3 11.6 14.5 16.5
Nominal Cooling Capacity*1) kcal/h 8,000 10,000 12,500 14,200
Btu/h 31,700 39,700 49,500 56,300
kW 9.0 11.2 14.2 16.0
Nominal Cooling Capacity*2) kcal/h 7,700 9,600 12,200 13,800
Btu/h 30,700 38,000 48,400 54,600
kW 10.0 13.0 16.3 18.0
Nominal Heating Capacity kcal/h 8,600 11,200 14,000 15,500
Btu/h 34,100 44,400 55,500 61,400
Sound Pressure Level (High/Medium/Low) dB (A) 34-32-30
298
41-36-33
298
43-38-35
298
44-40-36
298
Two-Way Cassette Key Features
Height mm (in.)
(11-3/4) (11-3/4) (11-3/4) (11-3/4) · Slim and stylish design
Ceiling-mounted one-way cassettes offer compact designs and a choice
840 840 840 840
Outer Dimensions Width mm (in.) of corner-mounted, one-way discharge or two-way discharge (from · Automatic swing louver distributes airflow
(33-1/16) (33-1/16) (33-1/16) (33-1/16)
840 840 840 840 the front and downward). evenly for uniform temperature
Depth mm (in.)
(33-1/16) (33-1/16) (33-1/16) (33-1/16)
26 29 29 29 lndoor 2-Way Cassette Type
Net Weight kg (Ibs.)
(57) (64) (64) (64)
Model JTKT022H0PS0AS JTKT028H0PS0AS JTKT040H0PS0AS JTKT056H0PS0AS
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Power Supply AC1Φ,220-240V/50Hz AC1Φ,220V/60Hz
Indoor Fan m3/min. 26/23/20 32/28/24 34/29/25 37/32/27 kW 2.3 2.9 4.1 5.8
Air Flow Rate (Hi/Me/Lo) (cfm) (918/812/706) (1,130/989/847) (1,201/1,024/883) (1,307/1,130/954)
Nominal Cooling Capacity*1 kcal/h 2,000 2,500 3,550 5,000
Motor W 56 108 108 108
Btu/h 7,900 9,900 14,100 19,800
Connections Flare-Nut Connection (with Flare Nuts)
mm kW 2.2 2.8 4.0 5.6
Refrigerant Piping Φ9.53 Φ9.53 Φ9.53 Φ9.53
(in.) Nominal Cooling Capacity*2 kcal/h 1,900 2,400 3,400 4,800
Liquid Line (3/8) (3/8) (3/8) (3/8)
Btu/h 7,500 9,600 13,600 19,100
mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
Gas Line kW 2.5 3.2 4.8 6.3
(in.) (5/8) (5/8) (5/8) (5/8)
Nominal Heating Capacity kcal/h 2,100 2,800 4,100 5,400
Condensate Drain VP25 VP25 VP25 VP25
Btu/h 8,500 10,900 16,400 21,500
Approximate Packing Measurement m 3
0.26 0.26 0.26 0.26
Sound Pressure Level
Adaptable Panel Model JP-N23NAQ JP-N23NAQ JP-N23NAQ JP-N23NAQ dB (A) 30/29/28/27 31/29/28/27 37/34/31/30 39/36/33/30
(High2/High/Medium/Low)
Color Neutral White Dimensions H x W x D mm 298 x 860 x 630
37 37 37 37 Net Weight kg 23 25
Height mm (in.)
(1-7/16) (1-7/16) (1-7/16) (1-7/16) Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
950 950 950 950 m3/min 10/9/7.5/6.5 11/9.5/8.5/7 15/13/11.5/10 16.5/14.5/12.5/10.5
Outer Dimensions Width mm (in.) Air Flow Rate
(37-3/8) (37-3/8) (37-3/8) (37-3/8)
Hi2/Hi/Me/Lo (cfm) (353/318/265/230) (388/335/300/247) (530/459/406/353) (583/512/441/371)
950 950 950 950
Depth mm (in.) Motor w 57
(37-3/8) (37-3/8) (37-3/8) (37-3/8)
Connections Flare-Nut Connection (With Flare Nuts)
6 6 6 6
Net Weight kg (lbs.) Liquid / Gas mm Φ6.35/Φ12.7
(13) (13) (13) (13)
Condensate Drain VP25
Approximate Packing Measurement m3 0.08 0.08 0.08 0.08
Approximate Packing
m3 0.24
NOTES: Measurement
1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions Adaptable Panel Model JP-AP90DNA (without Monitor Sensor)
Indoor Air Inlet Temperature: 27°C DB (80°F DB)
*1) 19.5°C WB (67°F WB) Color Neutral White
*2) 19.0°C WB (66.2°F WB)
Dimensions H x W x D mm 30 x 1,100 x 710
Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Heating Operation Conditions Net Weight kg 7.5
Indoor Air Inlet Temperature: 20°C DB (68°F DB)
Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Approximate Packing
6°C WB (43°F WB) m3 0.13
Piping Length: 7.5 Meters Piping Lift: 0 Meter Measurement
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

18 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 19
YORK® VRF INDOOR UNITS

Capacities: 2.2 to 16 kW

Two-Way Cassette (continued)


lndoor 2-Way Cassette Type

Model JTKT071H0PS0AS JTKT080H0PS0AS JTKT112H0PS0AS JTKT140H0PS0AS JTKT160H0PS0AS

Wall Indoor Unit


Power Supply AC1Φ,220-240V/50Hz AC1Φ,220V/60Hz
kW 7.3 8.3 11.6 14.5 16.5
Nominal Cooling Capacity*1 kcal/h 6,300 7,100 10,000 12,500 14,200
Wall-mount units include lndoor Wall Type
Btu/h 25,000 28,200 39,700 49,600 56,300
wide-angle louvers that dis- Model JTHW022H0NB0AQ JTHW028H0NB0AQ JTHW036H0NB0AQ
kW 7.1 8.0 11.2 14.0 16.0
tribute airflow comfortably. An Power Supply AC1Φ,.220V/60HZ
Nominal Cooling Capacity*2 kcal/h 6,100 6,900 9,600 12,000 13,800
kW 2.3 2.9 3.8
Btu/h 24,200 27,200 38,200 47,800 54,600
auto-swing function ensures
Nominal Cooling Capacity*1 kcal/h 2,000 2,500 3,300
kW 8.5 9.0 12.5 16.0 18.0 efficient air distribution and
Btu/h 7,800 9,900 13,000
Nominal Heating Capacity kcal/h 7,300 7,700 10,700 13,800 15,500 uniform temperature through-
kW 2.2 2.8 3.6
Btu/h 29,000 30,700 42,600 54,600 61,400 out the conditioned space. Nominal Cooling Capacity*2 kcal/h 1,900 2,400 3,100
Sound Pressure Level Refrigerant and drain piping
dB (A) 30/29/28/27 31/29/28/27 37/34/31/30 39/36/33/30 39/36/33/30 Btu/h 7,500 9,600 12,300
(High2/High/Medium/Low)
can be connected at the right, kW 2.5 3.3 4
Dimensions H x W x D mm 298 x 860 x 630 298 x 1,420 x 630
Net Weight kg 25 39
left or rear of the unit for ease Nominal Heating Capacity kcal/h 2,150 2,800 3,450
Btu/h 8,500 11,100 13,600
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance) of installation
Sound Pressure Level
Air Flow Rate m3/min 18.5/16.5/14.5/12.5 21/18.5/16/12.5 30/26.5/23/20 16.5/14.5/12.5/10.5 37/32.5/28.5/24 dB (A) 38/36/32 38/36/32 40/36/34
(High/Medium/Low)
Hi2/Hi/Me/Lo (cfm) (353/318/265/230) (388/335/300/247) (530/459/406/353) (583/512/441/371) (583/512/441/371)
mm 280 280 280
Outer Dimensions(H)
Motor w 57 57 x 2 Key Features (ln.) 11 11 11
Connections Flare-Nut Connection (With Flare Nuts)
mm 780 780 780
Liquid / Gas mm Φ9.52/Φ15.88 • Removable front panel for Outer Dimensions(W)
(ln.) 31 31 31
Condensate Drain VP25 easy cleaning. mm 220 220 220
Approximate Packing Outer Dimensions(D)
m3 0.24 0.36 • Standard wireless controller (ln.) 9 9 9
Measurement
Adaptable Panel Model JP-AP90DNA (without Monitor Sensor) JP-AP160DNA (without Monitor Sensor) and built-in wireless sensor Net Weight
kg 10 10 10
(lbs) 22 22 22
Color Neutral White • Standard condensate pump
Refrigerant R410A (Nitrogen-charged for Corrosion-resistance)
Dimensions H x W x D mm 30 x 1,100 x 710 30 x 1,660 x 710
lndoor Fan Air Flow Rate m3/
Net Weight kg 7.5 7.5 510/450/390 510/450/390 550/450/400
(Cooling/Heating) min
Approximate Packing
m3 0.13 0.20 Motor Power w 30 30 30
Measurement
Connections Refrigerant Piping Flare-nut Connection(with Flare Nuts)

NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the 2. The sound pressure level is based on following conditions. mm Φ6.35 Φ6.35 Φ6.35
JIS standard B8616. 1.5 Meter Beneath the Unit. Liquid Line
Cooling Operation Conditions The above data was measured in an anechoic chamber so that reflected should be (ln.) (1/4) (1/4) (1/4)
Indoor Air Inlet Temperature: 27°C DB (80°F DB) taken into consideration in the field.
*1) 19.5°C WB (67°F WB) mm Φ12.7 Φ12.7 Φ12.7
*2) 19.0°C WB (66.2°F WB) Gas Line
Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
(ln.) (1/2) (1/2) (1/2)
Heating Operation Conditions Condensate Drain VP16 VP16 VP16
Indoor Air Inlet Temperature: 20°C DB (68°F DB)
Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Approximate Packing
6°C WB (43°F WB) m3 0.12 0.12 0.12
Piping Length: 7.5 Meters Piping Lift: 0 Meter Measurement

20 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 21
YORK® VRF INDOOR UNITS

Ducted Low Static Indoor Unit

Features
• High-efficiency DC fan motor
• Multiple fan speed settings
Capacities: 2.2 to 6.3 kW • Up to 30 pa static pressure
• Bottom access for easy service and troubleshooting
Wall Indoor Unit (continued) • Built-in condensate pump
Capacities: 2.2 to 28 kW

lndoor Wall Type


Model JTHW045H0NB0AQ JTHW050H0NB0AQ JTHW056H0NB0AQ JTHW063H0NB0AQ
Power Supply AC1Φ.220V/60HZ
Indoor Unit Type In-the-Ceiling Type (Low Static Pressure)
kW 4.1 5.2 5.8 6.5
Nominal Cooling Model JTDL022H0NB0AQ JTDL028H0NB0AQ JTDL036H0NB0AQ JTDL04H0NB0AQ JTDL050H0NB0AQ
kcal/h 3,550 4,500 5,000 5,600
Capacity*1
Btu/h 14,100 17,700 19,800 22,200
Indoor Unit Power Supply AC 1Φ,220V/60Hz
kW 4 5 5.6 6.3
Nominal Cooling kW 2.3 2.9 3.8 4.4 5.2
kcal/h 3,450 4,300 4,800 5,400
Capacity*2
Nominal Cooling Capacity*1) kcal/h 2,000 2,500 3,300 3,800 4,500
Btu/h 13,600 17,000 19,100 21,500
Btu/h 7,800 9,900 13,000 15,100 17,700
kW 4.5 5.6 6.3 7.1
kW 2.2 2.8 3.6 4.3 5.0
Nominal Heating
kcal/h 3,900 4,800 5,400 6,100 Nominal Cooling Capacity*2) kcal/h 1,900 2,400 3,100 3,700 4,300
Capacity
Btu/h 15,300 19,100 21,500 24,200 Btu/h 7,500 9,500 12,300 14,700 17,000

Sound Pressure Level kW 2.8 3.3 4.2 4.9 5.6


dB (A) 41/38/35 41/38/35 41/38/35 44/41/38 Nominal Heating
(High/Medium/Low) kcal/h 2,400 2,800 3,600 4,200 4,800
Capacity
mm 280 290 290 290 Btu/h 9,600 11,100 14,300 16,700 19,100
Outer Dimensions(H)
(ln.) 11 12 12 12 Sound Pressure Level
dB (A) 29.5-26-24.5 29.5-26-24.5 34-32-30 34-32-30 34-32-30
(High/Medium/Low)
mm 780 1050 1050 1050
Outer Dimensions(W) mm 270 270 270 270 270
(ln.) 31 41 41 41 Height
(in.) (10-5/8) (10-5/8) (10-5/8) (10-5/8) (10-5/8)
mm 220 220 220 220 mm 650+75 650+75 650+75 650+75 650+75
Outer Dimensions(D) Outer Dimensions Width
(ln.) 9 9 9 9 (in.) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16)
kg 10 13.5 13.5 13.5 mm 720 720 720 720 720
Net Weight Depth
(in.) (28-3/8) (28-3/8) (28-3/8) (28-3/8) (28-3/8)
(lbs) 22 30 30 30
kg 26 26 26 26 35
Refrigerant R410A (Nitrogen-charged for Corrosion-resistance) Net Weight
(Ibs.) (57) (57) (57) (57) (77)
lndoor Fan Air Flow Rate
m3/min 600/510/450 720/620/520 720/620/520 820/720/620
(Cooling/Heating) Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Motor Power w 40 50 50 60
Indoor Fan
Connections Refrigerant Piping Flare-nut Connection(with Flare Nuts) m3/min. 8/7/6 8/7/6 13/11/9 13/11/9 15/13/11
Air Flow Rate
(cfm) (283/247/212) (283/247/212) (459/388/212) (459/388/212) (530/459/358)
mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 (Hi/Me/Lo)
Liquid Line
(ln.) (1/4) (1/4) (1/4) (1/4)
External Pressure *3) pa 30 30 30 30 30
mm Φ12.7 Φ15.88 Φ15.88 Φ15.88
Gas Line
(ln.) (1/2) (5/8) (5/8) (5/8) Motor W 20 20 40 40 45
Condensate Drain VP16 VP16 VP16 VP16
Connections
Flare-Nut Connection (with Flare Nuts)
Approximate Packing Refrigerant Piping
m3 0.12 0.15 0.15 0.15
Measurement
mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
Liquid Line
NOTES: 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the
2. The sound pressure level is based on following conditions.
(in.) (1/4) (1/4) (1/4) (1/4) (1/4)
JIS standard B8616. 1.5 Meter Beneath the Unit.
Cooling Operation Conditions
mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88
The above data was measured in an anechoic chamber so that reflected should be Gas Line
Indoor Air Inlet Temperature: 27°C DB (80°F DB) taken into consideration in the field. (in.) (1/2) (1/2) (1/2) (1/2) (3/8)
*1) 19.5°C WB (67°F WB)
*2) 19.0°C WB (66.2°F WB) Condensate Drain VP25 VP25 VP25 VP25 VP25
Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20°C DB (68°F DB) Approximate
Outdoor Air Inlet Temperature: 7°C DB (45°F DB) m3 0.21 0.21 0.21 0.21 0.27
6°C WB (43°F WB) Packing Measurement
Piping Length: 7.5 Meters Piping Lift: 0 Meter

22 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 23
YORK® VRF INDOOR UNITS

Ducted Low Static Indoor Unit (continued) Ducted Low Static Indoor Unit (continued)
Indoor Unit Type In-the-Ceiling Type (Low Static Pressure) Indoor Unit Type In-the-Ceiling Type (Low Static Pressure)

Model JTDL056H0NB0AQ JTDL063H0NB0AQ JTDL071H0NB0AQ JTDL084H0NB0AQ JTDL090H0NB0AQ Model JTDL112H0NB0AQ JTDL142H0NB0AQ JTDL160H0NB0AQ JTDL224H0NF0AQ JTDL280H0NF0AQ

Indoor Unit Power Supply AC 1Φ,220V/60Hz Indoor Unit Power Supply AC 1Φ,220V/60Hz AC 1Φ,220V/60Hz AC 3Φ,380-415V/60Hz

kW 5.8 6.5 7.3 8.7 9.3 kW 11.6 14.5 16.5 23.2 28.6
Nominal Cooling Capacity*1) kcal/h 5,000 5,600 6,100 7,500 8,000 Nominal Cooling Capacity*1) kcal/h 10,000 12,500 14,200 20,000 24,600
Btu/h 19,800 22,200 25,000 29,700 31,700 Btu/h 39,700 49,500 56,300 79,200 97,600

kW 5.6 6.3 7.1 8.4 9.0 kW 12.6 14.2 16.0 22.4 28.0
Nominal Cooling Capacity*2) kcal/h 4,800 5,400 6,100 7,200 7,700 Nominal Cooling Capacity*2) kcal/h 9,600 12,200 13,800 19,300 24,100
Btu/h 19,800 21,500 24,200 28,700 30,700 Btu/h 38,000 48,400 54,600 76,500 95,600

kW 6.5 7.5 8.5 9.6 10.0 kW 13.0 16.3 18.0 25.0 31.5
Nominal Heating Nominal Heating
kcal/h 5,600 6,500 7,300 8,300 8,600 kcal/h 11,200 14,000 15,500 21,500 27,100
Capacity Capacity
Btu/h 22,200 25,600 29,000 32,800 34,100 Btu/h 44,400 55,500 61,400 85,300 107,500

Sound Pressure Level Sound Pressure Level


dB (A) 34-32-30 35-33-31 35-33-31 40-37-33 40-37-33 dB (A) 41.5-39-35 42-39-35 43-39-37 50 52
(High/Medium/Low) (High/Medium/Low)

mm 270 270 270 350 350 mm 350 350 350 470 470
Height Height
(in.) (10-5/8) (10-5/8) (10-5/8) (13-3/4) (13-3/4) (in.) (13-3/4) (13-3/4) (13-3/4) (18-1/2) (18-1/2)

mm 900+75 900+75 900+75 900+75 900+75 mm 900+75 1,300+75 1,300+75 1,060 1,250
Outer Dimensions Width
Outer Dimensions Width (in.) (35-7/16+2-15/16) (51-3/16+2-15/16) (51-3/16+2-15/16) (41-3/4) (49-1/4)
(in.) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16)
mm 800 800 800 1,120 1,120
mm 720 720 720 800 800 Depth
Depth (in.) (31-1/2) (31-1/2) (31-1/2) (44-1/12) (44-1/12)
(in.) (28-3/8) (28-3/8) (28-3/8) (31-1/2) (31-1/2)
kg 46 58 58 96 106
kg 35 35 35 46 46 Net Weight
Net Weight (Ibs.) (101) (128) (128) (207) (234)
(Ibs.) (77) (77) (77) (101) (101)
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Indoor Fan
Indoor Fan m3/min. 27/23/19 37/31/25 38/35/29 58 72
m3/min. 15/13/11 16/14/12 16/14/12 25/21/17 7225/21/17 Air Flow Rate
Air Flow Rate (cfm) (954/812/671) (1,306/1,095/883) (1,341/1,236/1,024) (2048) (2542)
(cfm) (530/459/388) (565/494/424) (565/494/424) (883/741/600) (883/741/600) (Hi/Me/Lo)
(Hi/Me/Lo)
External Pressure *3) pa 60 60 60 100 100
External Pressure *3) pa 30 30 30 60 60

Motor W 100 160 180 900 1070


Motor W 45 45 45 100 100
Connections
Connections Flare-Nut Connection (with Flare Nuts)
Flare-Nut Connection (with Flare Nuts) Refrigerant Piping
Refrigerant Piping
mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53
mm Φ6.35 Φ9.53 Φ9.53 Φ9.53 Φ9.53 Liquid Line
Liquid Line (in.) (3/8) (3/8) (3/8) (3/8) (3/8)
(in.) (1/4) (3/8) (3/8) (3/8) (3/8)
mm Φ15.88 Φ15.88 Φ15.88 Φ19.05 Φ22.2
mm Φ15.88 Φ15.88 Φ15.88 Φ19.05 Φ22.2 Gas Line
Gas Line (in.) (5/8) (5/8) (3/8) (3/4) (7/8)
(in.) (5/8) (5/8) (3/8) (3/4) (7/8)
Condensate Drain VP25 VP25 VP25 VP25 VP25
Condensate Drain VP25 VP25 VP25 VP25 VP25
Approximate
Approximate m3 0.38 0.52 0.52 0.9 1.06
m3 0.27 0.27 0.27 0.38 0.38 Packing Measurement
Packing Measurement
NOTES:
1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27°C DB (80°F DB)
*1) 19.5°C WB (67°F WB)
*2) 19.0°C WB (66.2°F WB)
Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20°C DB (68°F DB)
Outdoor Air Inlet Temperature: 7°C DB (45°F DB)
6°C WB (43°F WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.
3. The data for external pressure *3) indicates” Standard Pressure Setting values when a filter is not used.

24 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 25
YORK® VRF INDOOR UNITS

Ducted High and Medium Static Indoor Unit Ducted High and Medium Static Indoor Unit (continued)

Features Indoor Unit Type In-the-Ceiling Type (High Static Pressure)

Model JTDM056H0NB0AQ JTDM063H0NB0AQ JTDM071H0NB0AQ JTDH080H0NB0AQ JTDH090H0NB0AQ


• High-efficiency DC fan motor
• Multiple fan speed settings Indoor Unit Power Supply AC 1Φ,220V/60Hz

• Up to 80 pa static pressure Nominal Cooling


kW 5.8 6.5 7.3 8.7 9.3
kcal/h 5,000 5,600 6,300 7,500 8,000
• Bottom access for easy service and troubleshooting Capacity*1)
Btu/h 19,800 22,200 25,000 29,700 31,700

• Condensate pump Capacities: 2.2 to 28 kW kW 5.6 6.3 7.1 8.4 9.0


Nominal Cooling
kcal/h 4,800 5,400 6,100 7,200 7,700
Capacity*2)
Btu/h 19,100 21,500 24,200 28,700 30,700
Indoor Unit Type In-the-Ceiling Type (High Static Pressure) 9.6 10.0
kW 6.5 7.5 8.5
Nominal Heating
kcal/h 5,600 6,500 7,300 8,300 8,600
Model JTDM022H0NB0AQ JTDM028H0NB0AQ JTDM036H0NB0AQ JTDM043H0NB0AQ JTDM050H0NB0AQ Capacity
Btu/h 22,200 25,600 29,000 32,800 34,100
Sound Pressure Level
Indoor Unit Power Supply AC 1Φ,220V/60Hz dB (A) 35-33-31 36-34-32 36-34-32 42-39-35 42-39-35
(High/Medium/Low)
kW 2.3 2.9 3.8 4.4 5.2 mm 270 270 270 350 350
Nominal Cooling Height
kcal/h 2,000 2,500 3,300 3,800 4,500 (in.) (10-5/8) (10-5/8) (10-5/8) (13-3/4) (13-3/4)
Capacity*1)
Btu/h 7,800 9,900 13,000 15,100 17,700 Outer mm 900+75 900+75 900+75 900+75 900+75
Width
kW 2.2 2.8 3.6 4.3 5.0 Dimensions (in.) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16) (35-7/16+2-15/16)
Nominal Cooling
kcal/h 1,900 2,400 3,100 3,700 4,300 mm 720 720 720 800 800
Capacity*2) Depth
Btu/h 7,500 9,500 12,300 14,700 17,000 (in.) (28-3/8) (28-3/8) (28-3/8) (31-1/2) (31-1/2)
kW 2.8 3.3 4.2 4.9 5.6 kg 35 35 35 46 46
Nominal Heating Net Weight
kcal/h 2,400 2,800 3,600 4,200 4,800 (Ibs.) (77) (77) (77) (101) (101)
Capacity
Btu/h 9,600 11,100 14,300 16,700 19,100
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Sound Pressure Level
dB (A) 35-33-31 35-33-31 35-33-31 35-33-31 35-33-31
(High/Medium/Low)
Indoor Fan
mm 270 270 270 270 270 m3/min. 15/13/11 16/14/12 16/14/12 25/21/17 25/21/17
Height Air Flow Rate
(in.) (10-5/8) (10-5/8) (10-5/8) (10-5/8) (10-5/8) (cfm) (530/459/388) (565/494/424) (565/494/424) (883/741/600) (883/741/600)
(Hi/Me/Lo)
mm 650+75 650+75 650+75 650+75 900+75 External Pressure (Option)
Outer Dimensions Width pa 50(80) 50(80) 50(80) 120(90) 120(90)
(in.) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (35-7/16+2-15/16) *3)
mm 720 720 720 720 720
Depth Motor W 75 75 75 120 120
(in.) (28-3/8) (28-3/8) (28-3/8) (28-3/8) (28-3/9)
kg 26 26 26 26 35 Connections
Net Weight Flare-Nut Connection (with Flare Nuts)
(Ibs.) (57) (57) (57) (57) (77) Refrigerant Piping
mm Φ6.35 Φ9.53 Φ9.53 Φ9.53 Φ9.53
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance) Liquid Line
(in.) (1/4) (3/8) (3/8) (3/8) (3/8)
Indoor Fan mm Φ15.88 Φ15.88 Φ15.88 Φ15.88 Φ15.88
m /min.
3
8/7/6 8/7/6 13/11/9 13/11/9 15/13/11 Gas Line
Air Flow Rate (in.) (5/8) (5/8) (5/8) (5/8) (5/8)
(cfm) (283/247/212) (283/247/212) (459/388/212) (459/388/212) (530/459/358)
(Hi/Me/Lo)
Condensate Drain VP25 VP25 VP25 VP25 VP25
External Pressure (Option)
pa 50(80) 50(80) 50(80) 50(80) 50(80)
*3) Approximate
m3 0.27 0.27 0.27 0.38 0.38
Packing Measurement
Motor W 35 35 60 60 75

Connections
Flare-Nut Connection (with Flare Nuts)
Refrigerant Piping
mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35
Liquid Line
(in.) (1/4) (1/4) (1/4) (1/4) (1/4)
mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88
Gas Line
(in.) (1/2) (1/2) (1/2) (1/2) (5/8)

Condensate Drain VP25 VP25 VP25 VP25 VP25

Approximate
m3 0.21 0.21 0.21 0.21 0.27
Packing Measurement

26 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 27
YORK® VRF INDOOR UNITS

Ducted High and Midium Static Indoor Unit (continued) Ducted Slim Narrow Indoor Unit
Indoor Unit Type In-the-Ceiling Type (High Static Pressure)
Features
Model JTDH112H0NB0AQ JTDH142H0NB0AQ JTDH160H0NB0AQ JTDH224H0NF0AQ JTDH280H0NF0AQ
• High-efficiency DC fan motor
Indoor Unit Power Supply AC 1Φ,220V/60Hz AC 1Φ,220V/60Hz AC 3Φ,380-415V/60Hz • Multiple fan speed settings

Nominal Cooling
kW 11.6 14.5 16.5 23.2 28.6 • Up to 30 pa static pressure
Capacity*1)
kcal/h 10,000 12,500 14,200 20,000 24,600 Capacities: 2.2 to 4.5 kW
Btu/h 39,700 49,500 56,300 79,800 97,600 • Bottom access for easy service and troubleshooting
kW 11.2 14.2 16.0 22.4 28.0
Nominal Cooling • Built-in condensate pump
kcal/h 9,600 12,200 13,800 19,300 24,100
Capacity*2)
Btu/h 38,000 48,400 54,600 76,500 95,600
kW 13.0 16.3 18.0 25.0 31.5
Nominal Heating
kcal/h 11,200 14,000 15,500 21,500 27,000
Capacity Indoor Unit Slim In-the Ceiling Type
Btu/h 44,400 55,500 61,400 85,300 107,000
Model JTDS022H0PB0AQ JTDS028H0PB0AQ JTDS036H0PB0AQ JTDS043H0PB0AQ
Sound Pressure Level
dB (A) 43-40-36 44-41-37 45-41-37 50 52 Power Supply AC 1Φ,220V/60Hz
(High/Medium/Low)
mm 350 350 350 470 470 KW 2.3 2.9 3.8 4.4
Height
(in.) (13-3/4) (13-3/4) (13-3/4) (18-1/2) (18-1/2) Nominal Cooling Capacity *1 kcal/h 2,000 2,500 3,300 3,800
Outer mm 900+75 1,300+75 1,300+75 1,060 1,250 Btu/h 7,800 9,900 13,000 15,000
Width
Dimensions (in.) (35-7/16+2-15/16) (51-3/16+2-15/16) (51-3/16+2-15/16) (41-3/4) (49-1/4)
kW 2.2 2.8 3.6 4.3
mm 800 800 800 1,120 1,120
Depth Nominal Cooling Capacity *2 kcal/h 1,900 2,400 3,100 3,700
(in.) (31-1/2) (31-1/2) (31-1/2) (44-1/2) (44-1/12)
Btu/h 7,500 9,500 12,300 14,700
kg 46 58 58 96 108
Net Weight kW 2.8 3.3 4.2 4.9
(Ibs.) (101) (128) (128) (211) (238)
Nominal Heating Capacity kcal/h 2,400 2,800 3,600 4,200
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Btu/h 9,600 11,100 14,300 16,700
Indoor Fan Sound Pressure Level
m3/min. 27/23/19 37/31/25 38/35/29 58 72 dB(A) 28-25-22 28-25-22 32-30-28 32-30-28
Air Flow Rate (High/Medium/Low)
(cfm) (954/812/671) (1,306/1,095/883) (1,341/1,236/1,024) (2048) (2542)
(Hi/Me/Lo) H mm 192 192 192 192
External Pressure (Option) Outer Dimensions W mm 700 700 700 700
pa 120(90) 120(90) 120(90) 180 180
*3)
D mm 902 602 602 602
Motor W 120 200 280 650 900 kg 21 21 21 21
Net Weight
(lbs) 46 46 48 48
Connections
Flare-Nut Connection (with Flare Nuts) Refrigerant R410A (Nitrogen-charged for Corrosion-resistance)
Refrigerant Piping
mm Φ9.53 Φ9.53 Φ9.53 Φ9.53 Φ9.53 Indoor Fan Air Flow Rate
Liquid Line m /min
3
8/7/6 8/7/6 10/8/7 10/8/7
(High /Medium /Low)
(in.) (3/8) (3/8) (3/8) (3/8) (3/8)
Motor Power w 50 50 60 60
mm Φ15.88 Φ15.88 Φ15.88 Φ19.05 Φ22.2
Gas Line Connections Refrigerant Piping Flare-nut Connection (with Flare Nuts)
(in.) (5/8) (5/8) (5/8) (3/4) (7/8)
mm Φ6.35 Φ6.35 Φ6.35 Φ6.35
Condensate Drain VP25 VP25 VP25 VP25 VP25 Liquid Line
(in.) (1/4) (1/4) (1/4) (1/4)
Approximate mm Φ12.7 Φ12.7 Φ12.7 Φ12.7
m 3
0.38 0.52 0.52 0.9 1.06
Packing Measurement Gas Line
(in.) (1/2) (1/2) (1/2) (1/2)
NOTES:
1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. Condensate Drain VP25
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27°C DB (80°F DB)
External Static Pressure Pa 10(30) 10(30) 10(30) 10(30)
*1) 19.5°C WB (67°F WB) Approximate Packing
*2) 19.0°C WB (66.2°F WB) m3 0.15 0.15 0.15 0.15
Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Measurement
Heating Operation Conditions
Indoor Air Inlet Temperature: 20°C DB (68°F DB) NOTES: 2. The sound pressure level is based on following conditions.
Outdoor Air Inlet Temperature: 7°C DB (45°F DB) 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS 1.5 Meter Beneath the Unit.
6°C WB (43°F WB) standard B8616. With Discharge Duct (2.0m) and Return Duct (1.0m).
Piping Length: 7.5 Meters Piping Lift: 0 Meter Cooling Operation Conditions Voltage of the power source for the indoor fan motor is 220V.
2. The sound pressure level is based on following conditions. Indoor Air Inlet Temperature: 27°C DB (80°F DB) In case of the power source of 240V, the sound pressure level increases by about 1 dB.
1.5 Meter Beneath the Unit. *1) 19.5°C WB (67°F WB) The above data was measured in an anechoic chamber so that reflected should be taken
With Discharge Duct (2.0m) and Return Duct (1.0m). *2) 19.0°C WB (66.2°F WB) into consideration in the field.
Voltage of the power source for the indoor fan motor is 220V. Outdoor Air Inlet Temperature: 35°C DB (95°F DB) 3. The data for external pressure *3) indicates” Standard Pressure Setting values when a
In case of the power source of 240V, the sound pressure level increases by about 1 dB. Heating Operation Conditions filter is not used.
The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field. Indoor Air Inlet Temperature: 20°C DB (68°F DB)
3. The data for external pressure *3) indicates” Standard Pressure Setting values when a filter is not used. Outdoor Air Inlet Temperature: 7°C DB (45°F DB)
6°C WB (43°F WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter

28 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 29
YORK® VRF INDOOR UNITS

Ducted Slim Indoor Unit Ducted Slim Indoor Unit (continued)

Features Indoor Unit Type In-the-Ceiling Type (Low Static Pressure)

Model JTDN050H0PB0AQ JTDN056H0PB0AQ JTDN063H0PB0AQ JTDN071H0PB0AQ


• High-efficiency DC fan motor
Indoor Unit Power Supply AC 1Φ,220V/60Hz
• Multiple fan speed settings kW 5.2 5.8 6.5 7.3
• Up to 30 pa static pressure Nominal Cooling Capacity*1) kcal/h 4,500 5,000 5,600 6,300
Capacities: 2.2 to 7.1 kW Btu/h 17,700 19,800 22,200 25,000
• Bottom access for easy service and troubleshooting kW 5.0 5.6 6.3 7.1
Nominal Cooling Capacity*2) kcal/h 4,300 4,800 5,400 6,100
• Built-in condensate pump
Btu/h 17,100 19,100 21,500 24,200
kW 5.6 6.5 7.5 8.5
Nominal Heating Capacity kcal/h 4,800 5,600 6,500 7,300
Indoor Unit Type In-the-Ceiling Type (Low Static Pressure) Btu/h 19,100 22,200 25,600 29,000

Model JTDN022H0PB0AQ JTDN028H0PB0AQ JTDN036H0PB0AQ JTDN043H0PB0AQ Sound Pressure Level


dB (A) 34-30-28 34-30-28 35-33-30 35-33-30
(High/Medium/Low)
Indoor Unit Power Supply AC 1Φ,220V/60Hz mm 192 192 192 192
Height
kW 2.3 2.9 3.8 4.4 (in.) (7-9/16) (7-9/16) (7-9/16) (7-9/16)
Nominal Cooling Capacity*1) kcal/h 2,000 2,500 3,300 3,800 mm 1,170 1,170 1,170 1,060
Outer Dimensions Width
Btu/h 7,800 9,900 13,000 15,100 (in.) (46-1/16) (46-1/16) (46-1/16) (41-3/4)
kW 2.2 2.8 3.6 4.3 mm 447 447 447 447
Depth
Nominal Cooling Capacity*2) kcal/h 1,900 2,400 3,100 3,700 (in.) (17-19/32) (17-19/32) (17-19/32) (17-19/32)
Btu/h 7,500 9,500 12,300 14,700
27 27 27 27
Net Weight kg (Ibs.)
kW 2.8 3.3 4.2 4.9 (59) (59) (59) (59)
Nominal Heating Capacity kcal/h 2,400 2,800 3,600 4,200
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)
Btu/h 9,600 11,100 14,300 16,700
Indoor Fan Air Flow Rate m /min.
3
14.5/12.5/10.5 14.5/12.5/10.5 16/14/12 16/14/12
Sound Pressure Level
dB (A) 27-24-21 27-24-21 31-29-26 31-29-26 (Hi/Me/Lo) (cfm) (512/442/371) (512/442/371) (565/494/424) (565/494/424)
(High/Medium/Low)
mm 192 192 192 192 External Pressure (Option) *3) pa 10(30) 10(30) 10(30) 10(30)
Height
(in.) (7-9/16) (7-9/16) (7-9/16) (7-9/16)
Motor W 40 40 50 50
mm 900 900 900 900
Outer Dimensions Width Connections Refrigerant Piping Flare-Nut Connection (with Flare Nuts)
(in.) (35-7/16) (35-7/16) (35-7/16) (35-7/16)
mm Φ6.35 Φ6.35 Φ9.53 Φ9.53
mm 447 447 447 447 Liquid Line
Depth (in.) (1/4) (1/4) (3/8) (3/8)
(in.) (17-19/32) (17-19/32) (17-19/32) (17-19/32)
mm Φ15.88 Φ15.88 Φ15.88 Φ15.88
21 21 22 22 Gas Line
Net Weight kg (Ibs.) (in.) (5/8) (5/8) (5/8) (5/8)
(46) (46) (48) (48)
Condensate Drain VP25 VP25 VP25 VP25
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)

Indoor Fan Air Flow Rate m3/min. Approximate Packing Measurement m3 0.18 0.18 0.18 0.18
8/7/6 8/7/6 10/8/7 10/8/7
(Hi/Me/Lo) (cfm) (283/247/212) (283/247/212) (353/283/247) (353/283/247)
NOTES:
External Pressure (Option) *3) pa 10(30) 10(30) 10(30) 10(30) 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Motor W 16 16 25 25 Indoor Air Inlet Temperature: 27°C DB (80°F DB)
*1) 19.5°C WB (67°F WB)
Connections *2) 19.0°C WB (66.2°F WB)
Flare-Nut Connection (with Flare Nuts) Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Refrigerant Piping
Heating Operation Conditions
mm Φ6.35 Φ6.35 Φ6.35 Φ6.35 Indoor Air Inlet Temperature: 20°C DB (68°F DB)
Liquid Line Outdoor Air Inlet Temperature: 7°C DB (45°F DB)
(in.) (1/4) (1/4) (1/4) (1/4) 6°C WB (43°F WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
mm Φ12.7 Φ12.7 Φ12.7 Φ12.7 2. The sound pressure level is based on following conditions.
Ges Line
(in.) (1/2) (1/2) (1/2) (1/2) 1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Condensate Drain VP25 VP25 VP25 VP25 Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.
Approximate Packing Measurement m 3
0.15 0.15 0.15 0.15
3. The data for external pressure *3) indicates” Standard Pressure Setting values when a filter is not used.

30 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 31
YORK® VRF INDOOR UNITS

Floor Concealed (220-240/1/50) Floor Exposed


Indoor Unit Type Floor Concealed Type lndoor Floor Exposed Type
Model JTFC028H0NB0AQ JTFC043H0NB0AQ JTFC056H0NB0AQ JTFC071H0NB0AQ
Model JTFE028H0NB0AE JTFE040H0NB0AE
Indoor Unit Power Supply AC 1Φ,220V/60Hz

kW 2.9 4.4 5.8 7.3 Power Supply AC 1Φ,220V/60Hz

Nominal Cooling Capacity*1) kcal/h 2,500 3,800 5,000 6,300


kW 2.9 4.1
Btu/h 9,900 15,100 19,800 25,000
Nominal Cooling Capacity*1 kcal/h 2,500 3,500
kW 2.8 4.3 5.6 7.1

Nominal Cooling Capacity*2) kcal/h 2,400 3,700 4,800 6,100 btu/h 9,900 14,100
Btu/h 9,500 14,700 19,100 24,200
kW 2.8 4.0
kW 3.3 4.9 6.5 8.5

Nominal Heating Capacity kcal/h 2,800 4,200 5,600 7,300 Nominal Cooling Capacity*2 kcal/h 2,400 3,400

Btu/h 11,100 16,700 22,200 29,000


btu/h 9,600 13,600
Sound Pressure Level
dB (A) 35-32-29 38-35-31 39-36-32 42-38-34
(High/Medium/Low) kW 3.2 4.8
mm 620 620 620 620
Height Nominal Heating Capaciy kcal/h 2,800 4,100
in. 24.41 24.41 24.41 24.41

Outer mm 900 900 1,170 1,170 btu/h 10,900 16,400


Width
Dimensions in. 35.43 35.43 46.06 46.06 Sound Pressure Level
dB (A) 35/32/29 38/35/31
mm 202 202 202 202 (High2/High/Medium/Low)
Depth
in. 7.95 7.95 7.95 7.95 Cabinet Color Spring White
kg 25 26 31 31
Net Weight Dimensions H x W x D mm 630 x 1,045 x 220 630 x 1,170 x 220
(lbs) 55 57 68 68

Refrigerant R410A/R407C/R22 (Nitrogen-Charged for Corrosion-Resistance) Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance)

Indoor Fan Air Flow Rate (Hi/Me/Lo) m /min.


3
8/7/6 10/8/7 14.5/12.5/10.5 16/14/12 m3/min 8.5/7/6 12/10/9
Air Flow Rate
Motor W 16 25 40 50
Hi2/Hi/Me/Lo
(cfm) 300/247/212 424/353/318
Connections
Flare-Nut Connection with Flare Nuts
Refrigerant piping
Motor w 20 28
mm Φ6.35 Φ6.35 Φ6.35 Φ6.35
Liquid Line
in. 1/4 1/4 1/4 3/8 Connections Flare-Nut Connection (With Flare Nuts)
mm Φ12.7 Φ12.7 Φ15.88 Φ15.88
Gas Pipe Liquid / Gas mm Φ6.35/Φ12.7
in. (1/2) (1/2) (5/8) (5/8)
Condensate Drain VP25 Condensate Drain 18.5 OD
Approximate
m 3
0.19 0.19 0.23 0.23 Approximate Packing Measurement m3 0.26 0.29
Packing Measurement

NOTES: NOTES:
1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616. 1. The nominal cooling capacity is the combined capacity of Johnson Controls’ standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions Cooling Operation Conditions
Indoor Air Inlet Temperature: 27°C DB (80°F DB) Indoor Air Inlet Temperature: 27°C DB (80°F DB)
*1) 19.5°C WB (67°F WB) *1) 19.5°C WB (67°F WB)
*2) 19.0°C WB (66.2°F WB) *2) 19.0°C WB (66.2°F WB)
Outdoor Air Inlet Temperature: 35°C DB (95°F DB) Outdoor Air Inlet Temperature: 35°C DB (95°F DB)
Heating Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 20°C DB (68°F DB) Indoor Air Inlet Temperature: 20°C DB (68°F DB)
Outdoor Air Inlet Temperature: 7°C DB (45°F DB) Outdoor Air Inlet Temperature: 7°C DB (45°F DB)
6°C WB (43°F WB) 6°C WB (43°F WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions. 2. The sound pressure level is based on following conditions.
1 meter beneath the Unit 1 meter beneath the Unit
1 meter from inlet grille. 1 meter from inlet grille.
The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field. The above data was measured in an anechoic chamber so that reflected should be taken into consideration in the field.

32 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 33
Summary Table of Outdoor Units

Heat Pump
VRF
Capacity 10, 20, 30 HP
Maximum connectable indoor unit quantity 32

Combination capacity ratio between OD and ID 50% to 130%


Total piping length ft (m) 984 (300)
Maximum piping length between OD and ID ft (m) 394 (120)
Maximum equivalent piping length between OD and ID ft (m) 459 (140)
Maximum piping length between 1st branch and ID ft (m) 131 (40)

Maximum height difference between OD and ID (when OD is higher than ID) ft (m) 164 (50)
Maximum height difference between OD and ID (when ID is higher than OD) ft (m) 131 (40)
Maximum height difference between ID and ID ft (m) 49 (15)

Conditions of operation

Cooling Operation
Heating Operation

113 (45)
113 (45)

Water Intake Water Intake


Temperature Temperature
°F (°C) °F (°C)

Cooling Operation Heating Operation


50 (10) Area 50 (10) Area

69.8/59 89.6/73.4 59 (15) 80.6 (27)


(21/15) (32/23) Return Air Temperature
Return Air Temperature of the Indoor unit

Outdoor Units
of the Indoor unit (DBT °F (°C)
(DBT/WBT °F (°C)

Reliable, quiet YORK® VRF outdoor units are available


in capacities to fit multiple applications and operate multiple
indoor units. Cooling Only units provide flexibility to design for a
variety of building spaces and ambient conditions. Units operate
quietly with sound ratings as low as 52 dBA.

34 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 35
YORK® VRF OUTDOOR UNITS

Outdoor Units Overview Outdoor Unit 220/380V

YORK® VRF outdoor units provide maximum flexibility for modular design.
Type Single Unit Systems
10-30HP Systems
Tonnage 10HP 20HP 30HP
JTWH100NPER0AB 2x JTWH100NPER0AB 3x JTWH100NPER0AB
Model JTWH100NPEF0AB 2x JTWH100NPEF0AB 3x JTWH100NPEF0AB
ER-3ø220V / EF-3ø380V
Power Supply 220Vca / 60 Hz and 380Vca / 60 Hz
kW 28 56 84
Nominal Cooling Capacity kcal/h 24.074 48.149 72.223
BTU/h 95.563 191.126 286.689
kW 31,5 63,0 94,5
Nominal Heating Capacity kcal/h 27.084 54.167 81.251
BTU/h 107.509 215.017 322.526
Sound Pressure Level dBA 52 54 56
Chamber Color - Beige
JTWH100NPER0AB 2x JTWH100NPER0AB 3x JTWH100NPER0AB Heigh mm 1.200
External Dimensions Width mm 780 1.710 2.640
JTWH100NPEF0AB 2x JTWH100NPEF0AB 3x JTWH100NPEF0AB Depth mm 555
10HP 20HP 30HP Net Weight kg 155 310 465
Weight when in Operation kg 157 314 471
ER - 3ø220V Refrigerant - R-410A
Refrigerant
Flow Control - Expansion Valve Controlled by a Microcomputer
EF - 3ø380V Scroll Inverter Compressor Quantity - 1 2 3
Heat Exchanger Type - PHE - Brazed Plate Exchanger
Maximum Pressure of Water in the Brazed Plate Exchanger MPa 1,96
Inlet -
1” 1/4 ISO 228/1 - G (OUTER NUT)
Benefits: Water Connections Outlet -
Drain Outlet - 1/2” BSPT (INTERNAL SCREW) - Only Frontal
Refrigerant Piping of up to Liquid Line (mm) ø 9,53 - Short-Nut Connection
· Smaller amount of copper tube 120m Gas Line (mm) ø 22,22 - Flange (Supplied by the Manufacturer)
Water Flow m³ / h 5,76 5,76 x 2 5,76 x 3
· Smaller amount of refrigerant charge Refrigerant Load (INCLUDED) kg 3,2 3,2 + 3,2 3,2 + 3,2 + 3,2
Closed Bores for Electrical Electrical Network mm ø 42
cooling · Smaller loss of the effective capacity Interconnection Control Circuits mm ø 42
tower Combination of Capacities (HP)
Min 50% of Nominal Capacity
· Installation at coastal area Combination of Condenser and
Max 130% of Nominal Capacity
Minimum Capacity for Individual Operation (HP) Min 0,8
Indoor Units
· High building project Combination for Indoor Units
Min 2

2 Max 16 20 32

Remarks:
1. The cooling and heating capacities described above are the combined capacities of the Standard Split System by YORK and are based on standard JIS B8616.
Piping Length: 7.5 m and piping drop: 0 m
1 Maximum Gap
1 External Unit above Internal: 50m Cools Heats
Incoming Water Temperature 30° C 20° C
External Unit below Internal: 40m BS 27° C 20° C
5 Incoming Indoor Air Temperature
BU 19° C -
Piping maximum length from the first multi-kit until BS: Dry Bulb / BU: Wet Bulb
Water 2
piping the farther evaporator: 40m 2. The sound pressure level is based on the following conditions:
At 1 m from the surface of the servicce seal of the unit and at 1.5 m from ground level.
The information above was measured inside a wind chamber, and, on-site, the sound reflected must be taken into consideration.
Piping maximum length from multi-kit to each
3 3 In the event of nighttime operations, the noise level decreases 2 dBA.

evaporator: 30m 3. This equipment must be installed in a machine room or indoor environments protected against rains and other bad weather, with an environment temperature of 10° C to 40° C, and ventilated for the elimination of the
4 heat dissipated by the equipment.
It may not be installed in outdoor environments.
Piping maximum length from condenser until the
4 4. The condensation tower system must be selected as per the recommendations described in the User Manual.
farther evaporator:
5. The equipment is supplied with filter “Y” MESH 40 and with a flange for the gas line.

Water Piping Real 120m/Equivalent: 140m


Outdoor unit is
Refrigerant Piping close to indoor units Maximum gap between each evaporator or multi-
5
kit and evaporator: 15m

36 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 37
YORK® VRF OPTIONAL PARTS & ACCESSORIES

First Multi-kit
Outdoor Unit HP 10HP 20HP 30HP
< 80m JE-102SN JE-242SN JE-302SN

> 80m JE-162SN JE-302SN JE-302SN

Piping Connection Kit (FOR COMBINED SYSTEM)


Outdoor Unit 20HP 30HP
Equivalent lenght (m) < 80 > 80 < 80 > 80
Multi-kit 1 JM-20SNQ JM-30SNQ JM-30SNQ JM-30SNQ

Multi-kit 2 - - JM-20SNQ JM-20SNQ

First Multi-kit~Last Multi-kit


Total Indoor Unit HP Lower than 6 6 to 8.99 9 to 11.99 12 to 15.99 16 to 17.99 18 to 25.99 26 to 35.99 Over 36
Gas (Ømm) Ø15.88 Ø19.05 Ø22.2 Ø25.4 Ø28.6 Ø28.6 Ø31.75 Ø38.1

Liquid (Ømm) Ø9.53 Ø9.53 Ø9.53 Ø12.7 Ø12.7 Ø15.88 Ø19.05 Ø19.05

Multi-kit JE-102SN JE-162SN JE-242SN JE-302SN

Last Multi-kit~Indoor Unit


Pipe Size (Ømm)
Indoor Unit Max. Liquid Pipe Lenght
Gas Pipe Liquid Pipe
6.35 15 m
0.8HP~1.8HP 12.7
9.53 30 m

Optional Parts & Accessories


6.35*1 15 m
2.0HP~2.3HP 15.88
9.53 30 m

5HP~6.0HP 15.88 9.53 30 m

8HP 19.05 9.53 30 m

10HP 22.2 9.53 30 m


Selection software tool indicates
Notes:
which piping kits are needed for your design 1. When liquid pipe length of indoor unit(0.8~2.0HP) is more than 15m, please change the liquid pipe dimension from Ø6.35 into Ø9.53.

38 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 39
Control Systems
• The new large LCD display
permits users to see the operating
conditions and settings.
JCWB10NEWS
• The timer can be set at half-hour
JCRA10NEWQ
intervals up to 72 hours.
• All the functions can be selected by
remote control switches.
Remote Control Switch
Compatible with the H-LINKⅡ • The JCWA10NEWQ monitors the Wireless
operating conditions in the system Remote Control Switch
• The newly-adopted LED-backlit LCD and an alarm is issued if a problem Compatible with the H-LINKⅡ
provides enhanced legibility. Large,
occurs.
clear character display is realized by • One-touch handy operation, no wiring
Full Dot Matrix LCD. • A “self-diagnosis function” work required.
checks for problems on printed
• The newly-adopted directional key boards in indoor and outdoor • Two or more units can be operated
provides optimized operation. The simultaneously by remote control.
units.
manual operation is facilitated by
• Equipped with energy-saving * Receiver kit is required.
reducing number of switch buttons
from 13 to 9. functions such as a preset
temperature range limiting
• “Schedule Timer” provides the function for preventing excessive
timer operations for “Run/Stop” and
cooling/heating and a preset
“Temperature Setting”. The weekly
temperature automatic reset
management is available by using this JCOA111EWS
function, as well as an operation
function. In addition “Holiday Setting”
locking mechanism and the
and “Schedule ON/OFF”setting are
capability to prevent users from
available.
forgetting to turn off the system.
• 4 type of menus are offered for flexible (Function selection setting is Centralized
use as follows:
required) ON/OFF Controller
Menu: Contains “Schedule”, “Elevating Compatible with the H-LINKⅡ
Grill”, etc. for users. Up to 160 indoor units
Help Menu: Contains information Up to 16 remote control groups
provided by this remote control switch
for users such as “About Indication”, • Only performs operation/stop
“Contact Information”, etc. JCSA10NEWS control per remote control group.
Test Run Menu: This menu • By connecting to the H-LINK, up to

Controls
provides the functions 16 remote control groups and 160
installation of this remote control
Half-size indoor units can be controlled. Up
switch.
Remote Control Switch to 8 units can be connected to the
Check Menu: This menu provides the Compatible with the H-LINKⅡ H-LINK
functions for service and maintain
• The main function of this easy- • An external input terminal is
YORK® VRF systems offer a wide range Wired Controller to-use remote control system is
temperature setting. provided as standard. External
of control systems to suit multiple applications. Wireless Controller signals enable the following
• Operation modes can be switched
Systems include wired and wireless controls, central station over(when function selection setting functions: central operation/stop,
Central Station is made). emergency stop, central operation
and computerized control options, and BACnet Adapter for Computerized Controller JCWA10NEWQ • Suitable for facilities used by various output, central alarm output
people, such as hotels.
control by way of building management systems. • Can be used in combination with
BACnet Adapter • “2 remote control” or “group the Central Station.
control” (up to 16 max.) can be
Remote Control Switch
used. * Make sure to use it with a remote control switch.
Compatible with the H-LINKⅡ Indoor units cannot be used without a remote
• If a problem occurs, an alarm code control switch.
• The JCWA10NEWQ has a design that immediately shows the details of * There are restrictions on remote group registration.
matches the interior. the problem. Please contact our sales staff for more information.

40 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 41
YORK® VRF CONTROLLERS

Interface Central Station


You can select the air conditioner control interface depending on your needs to create a comfortable space. Central Station mini Specification for Management Computer
JCMA101EWS (AC 100-240V)
Communication Unit Units of Adopting for H-LINKⅡ
Connection Method to Upper System • BACnet / IP by IEEE802.3 Compliance (100BASE-TX/10BASE-T) CCM 01 (AC 24V)
Communication Line Non-Polar 2-Wire
Quantity of Connection • Up to 64 Indoor Units per BACnet® Adaptor
• RUN/STOP Wiring Length 1,000m (Total Length)
• Available / Not Available for Operation by
• Operation Mode Setting
Control Item at Upper System Remote control Switch Outdoor Unit Indoor Unit Central Controller Total Unit Number
• Temperature Setting 120
• Filter Sign Reset
• Fan Speed Setting mm Connecting
JBAA101EWS (for BACnet®) Unit Number*
H-LINKⅡ 64 160 8 200
• Indoor Suction Temperature Notification
• RUN/STOP State Notification
Connecting the • Alarm Code Notification
• Alarm Signal Notification H-LINK 16 128 8 145
JBAA101EWS to an Monitoring Item at • Communication Abnormality Notification
• Operation Mode State Notification
H-LINK (communication Upper System • Filter Sign
• Fan Speed State Notification *: Connecting unit quantity indicates the maximum unit numbers which is possible to
line between machines) • Available/Not Available for operation
• Ten parameters setting
allows control of up to 64 by remote control switch 140mm connect in the same H-LINK (Control Wiring).
indoor units.
Up to eight HC-A64BNP
can be connected to the Functions
same H-LINK. Most compact in our touch panel centralized controller.
Connection Method To Upper System • LonTalk Protocol SNVT(Standard Network Variable Type) FTT-10A Free Topology Its down-to-detail control functionalities, • Run/Stop/Abnormality • Operation Mode
• Setting Temperature • Setting Fan Speed • Setting Louver
such as Weekly Scheduling, Accumulated Work Hours, Monitor Function
JLAA101EWS (Standard) • RCS Operation Prohibited Setting • Filter Sign • Alarm Code
• Accumulated Operating Time
Number of Connection 64 Remote Controller Group etc., help you save energy.
Run/Stop Monitor Run/Stop status & malfunction Up to 32 remote-controlled groups and up to 160 indoor • Run/Stop* • Operation Mode • Temperature Setting
Simultaneous Run/Stop Operation Mode setting Control Function
Control units can be connected to the single air-conditioning • Fan Speed • Louver • RCS Operation Prohibited • Filter Sign Reset
Operation Mode setting Temperature setting
Temperature setting Thermo status
system.
*: “All Groups Run/Stop” command signal exception function for selected
JLAA101EWS (Option A)
groups is available by “Exception of Run/Stop Ope.” function.
Number of Connectable RCG 64 Remote Controller Group
Run/Stop Monitor Run/Stop status & malfunction
Simultaneous Run/Stop Indoor unit Inlet Temperature/
Operation Mode setting RC Thermo Temperature
Control
Temperature setting
Fan Speed setting
RC permitted/prohibited (all items) Central Station EZ Specification for Management Computer

JLAA101EWS (Option B) JCTA121EWS (AC 100-240V)


Communication Unit Units of Adopting for H-LINKⅡ
Number of Connectable RCG 32 Remote Controller Group CCL 01 (AC 24V)
JLAA101EWS Communication Line Non-Polar 2-Wire
Monitor Run/Stop status & malfunction
(for LONWORKS®) Run/Stop Operation Mode setting Wiring Length 1,000m (Total Length)
Simultaneous Run/Stop Temperature setting
Operation Mode setting Fan Speed setting 170 Outdoor Unit Indoor Unit Central Controller Total Unit Number
Temperature setting Louver setting mm
Control Fan Speed setting Alarm Code Connecting
H-LINKⅡ 64 160 8 200
Louver setting Indoor unit Inlet Unit Number*
RC permitted/prohibited (all items) Temperature/RC Thermo
H-LINK 16 128 8 145
Temperature
Temperature Mode Switch Indoor unit Outlet Temperature
Outdoor Temperature *: Connecting unit quantity indicates the maximum unit numbers which is possible to
250mm connect in the same H-LINK (Control Wiring).
JLAA101EWS (Option C)
Eazy control with 8.5 inch color touch panel
Number of Connectable RCG 16 Remote Controller Group
Run/Stop Monitor Run/Stop status
Its down-to-detail control functionalities, Functions
Simultaneous Run/Stop Operation Mode setting such as Weekly Scheduling, Accumulated Work Hours,
Operation Mode setting Temperature setting • Run/Stop/Abnormality • Operation Mode
Temperature setting Fan Speed setting etc., help you save energy. Monitor Function
• Setting Temperature • Setting Fan Speed • Setting Louver
Fan Speed setting Louver setting • RCS Operation Prohibited Setting • Filter Sign • Alarm Code
Louver setting Thermo status Up to 64 remote-controlled groups and up to 160 indoor • Accumulated Operating Time
RC permitted/prohibited (all items) Alarm Code
RC permitted/prohibited Indoor unit Inlet Temperature/
units can be connected to the single air-conditioning
(Run/Stop, Operation Mode RC Thermo Temperature • Run/Stop* • Operation Mode • Temperature Setting
Control system. Control Function
setting, Indoor unit Outlet Temperature • Fan Speed • Louver • RCS Operation Prohibited • Filter Sign Reset
Temperature setting) Outdoor Temperature
Filter Sign Reset RC permitted/prohibited (all items)
Outdoor unit capacity control RC permitted/prohibited *: “All Groups Run/Stop” command signal exception function for selected
Outdoor unit Operating Sound (Run/Stop, Operation Mode setting, groups is available by “Exception of Run/Stop Ope.” function.
Reduction control Temperature setting)
Temperature Mode Switch Filter Sign
Outdoor unit control mode

42 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 43
Notes

44 JOHNSON CONTROLS | YORK® VRF SYSTEMS JOHNSON CONTROLS | YORK® VRF SYSTEMS 45
Authorized Dealer