Project:______________________
Date:________________________
Document No:________________
Revision:_____________________
Mention Notes & Details
Reviewed (Yes/No/ Not
Sr. No. Check point against each point, as Remarks
Applicable)
applicable
A) Processes & Organizational requirement :
1 Reviewed the Qualification Criteria (Q-Matrix) ?
Preparer - Min. 'RS', Reviewer - Min. 'Q'
Identification of Reviewer?
[if yes, the check list shall be filled with reviewer. If no, Lead
engineer/responsible engineer shall take care on behalf of reviewer]
9
10
B) Past project learning & references:
1 Reference project drawings referred (if any)?
2 Shared lesson learnt, good practice from PIP system/past experience ?
3
4
5
C) Contractual requirements:
1 Read DCD/Client Technical Specification?
2 Any Client requirement for transformer removal arrangement?
3
Any Client requirement for power evacuation arrangement (BPI, LA, Gantry
tower, Overhead conductor arrangement etc.) ?
4 Any Client requirement for protective fencing arrangement?
5 Any Client requirement for side/top clearance ?
6
Any Client requirement for Fire wall construction (brick/concrete), thickness
& arrangement ?
7 Any Client requirement for Spare transformer location & arrangement?
8 Any Client requirement for Emergency stop push button ?
9
10
D) Input :
1 Study of Single line diagram?
2
Study of Plot Plan w.r.t. transformer yard arrangement interface with
switchyard, CW piping, road arrangement etc.?
3
8
Availability, Study & review of Suitability of Neutral formation arrangement ?
9
Availability, Study & review of Suitability of Fire protection & Oil water system
arrangement ?
10
E) Interfacing requirements
1 Interface with CW piping coordinated?
2
Interface with Switchyard (i.e. location of gantry tower, BPI/LA, OH Line)
considering skew angle of overhead line coordinated?
3
Interface with gantry tower arrangement (i.e. combined with fire wall)
coordinated?
4 Interface with Bus duct routing & support arrangement coordinated?
5 Interface with various civil drawings coordinated?
6 Interface with cable raceway coordinated?
7
Interface with Fire protection piping, DV shed & Oil water system piping
coordinated?
8
Rail elevation and Grade elevation coordinated as per transformer handling
requirement?
9
10
F) MTO related
1 Fire wall length & height optimized?
2 Bus duct(s) [IPBD/SPBD/NSPBD] length & bends optimized?
1. Distance between A row [TG bldg. first column] to center line of
transformers shall be minimized.