Sei sulla pagina 1di 15

DISEÑO DE REDES

INTERNAS DE GAS
PROYECTO
“SARAMAGO PLAZA”

MEMORIAS DE DISEÑO

Diseñó: Ing. Ernesto Calderón Carrillo


M.P. 68202-28204 STD

BUCARAMANGA, ENERO DE 2016


CONTENIDO.
1. DESCRIPCION DEL PROYECTO. ............................................................................... 3

2. PARAMETROS DE DISEÑO: ....................................................................................... 3

3. DISEÑO DE TUBERIAS POR TIPO DE APARTAMENTO: ..................................... 4

4. VENTILACION DE RECINTOS INTERIORES: ......................................................... 8

5. DISEÑO DE REGULACION PRIMERA ETAPA: ..................................................... 13

6. ESPECIFICACIONES DE EQUIPOS .......................................................................... 13

7. PLANOS: ...................................................................................................................... 15

2
DISEÑO DE REDES INTERNAS DE GAS
MEMORIAS DE DISEÑO

1. DESCRIPCION DEL PROYECTO.


TIPO DE SOLUCION: Vivienda Multifamiliar
MUNICIPIO: Bucaramanga
DISTRIBUIDOR DOMICILIARIO: Gasoriente
NUMERO DE PISOS: 9 (Nueve) Pisos
NUMERO DE APARTAMENTOS: 28 (veintiocho) Apartamentos
PROPIETARIO: INPROCA LTDA
DIRECCIÓN: Carrera 24 No. 17-29
BARRIO: Barrio San Francisco

2. PARAMETROS DE DISEÑO:

 CAIDA DE PRESION: Se acepta una caída de presión de 4 milibares en la


red interna de cada vivienda.

 Ecuación de Cálculo: Renuard


 Número de soluciones de vivienda: 28 apartamentos.
 Modelo de cargas definido:

DEMANDA MAXIMA PREVISTA (Qp)


1 Consumo de los artefactos por apartamento MCH KW
1.1 Calentador de paso 5.5 L/Min 0,94 10,50
1.2 Estufa de Cuatro quemadores 0,66 7,40
1.3 Horno 0,18 2,05
Total demanda (Qp) 1,78 19,95

Notas: MCH= metros cúbicos hora


KW = Kilowatios.
Modelo de calentador: HACEB Referencia CAL AS CPG-5.5 GN DISP BL
Modelo del Horno: HACEB Referencia ARF 60 GAS NE GN.
Modelo Estufa: HACEB CUB ASL CG 60-43 INOX GN.

3
3. DISEÑO DE TUBERIAS POR TIPO DE APARTAMENTO:
El diseño de la red para cada apartamento se tiene en cuenta desde el
centro de medición. Cada tipo de apartamento está definido en los planos
que hacen parte integral del presente diseño.

PROYECTO SARAMAGO PLAZA


DISEÑO DE REDES DE GAS A BAJA PRESION
CALCULO DE TUBERÍAS PARA LOS APARTAMENTOS TIPO I (PISOS 2 - 3 - 4 - 5 - 6 - 7 - 8)
MEMORIAS DE CALCULO

FORMULA DE DISEÑO RENUARD


PODER CALORIFICO 11,21 KWH/M3
PRESION INICIAL 21 mbar
PRESION FINAL MINIMA 17 mbar
CALCULO ERNESTO CALDERON CARRILLO

TRAMO TUBERIA DIAMETRO TIPO Caudal PERDIDA Pf VELOCIDAD


Pi (mbar)
PISO Inicio Fin LONG (m) LE (mts) (mm) Tubería (mch) (mbar) (mbar) (m/s)
MED A 16.8 20.16 16.00 PE-AL-PE 2.5 21.00 1.41 19.59 4.65
A B 0.4 0.48 15.80 GALV 2.5 19.59 0.04 19.56 4.77
2
B CALENT 3.1 3.72 15.80 GALV 0.94 19.56 0.09 19.47 1.79
B EST 3.1 3.72 15.80 GALV 0.66 19.56 0.05 19.51 1.26
MED A 19.8 23.76 16.00 PE-AL-PE 2.5 21.00 1.66 19.34 4.65
A 3.1 0.4 0.48 15.80 GALV 2.5 19.34 0.04 19.31 4.77
3
B CALENT 3.1 3.72 15.80 GALV 0.94 19.31 0.09 19.22 1.79
B EST 3.1 3.72 15.80 GALV 0.66 19.31 0.05 19.26 1.26
MED A 22.8 27.36 16.00 PE-AL-PE 2.5 21.00 1.91 19.09 4.65
A B 0.4 0.48 15.80 GALV 2.5 19.09 0.04 19.06 4.77
4
B CALENT 3.1 3.72 15.80 GALV 0.94 19.06 0.09 18.97 1.80
B EST 3.1 3.72 15.80 GALV 0.66 19.06 0.05 19.01 1.26
MED A 25.8 30.96 16.00 PE-AL-PE 2.5 21.00 2.16 18.84 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.84 0.04 18.81 4.78
5
B CALENT 3.1 3.72 15.80 GALV 0.94 18.81 0.09 18.72 1.80
B EST 3.1 3.72 15.80 GALV 0.66 18.81 0.05 18.76 1.26
MED A 28.8 34.56 16.00 PE-AL-PE 2.5 21.00 2.41 18.59 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.59 0.04 18.55 4.78
6
B CALENT 3.1 3.72 15.80 GALV 0.94 18.55 0.09 18.47 1.80
B EST 3.1 3.72 15.80 GALV 0.66 18.55 0.05 18.51 1.26
MED A 31.8 38.16 16.00 PE-AL-PE 2.5 21.00 2.66 18.34 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.34 0.04 18.30 4.78
7
B CALENT 3.1 3.72 15.80 GALV 0.94 18.30 0.09 18.22 1.80
B EST 3.1 3.72 15.80 GALV 0.66 18.30 0.05 18.26 1.26
MED A 34.8 41.76 16.00 PE-AL-PE 2.5 21.00 2.91 18.09 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.09 0.04 18.05 4.78
8
B CALENT 3.1 3.72 15.80 GALV 0.94 18.05 0.09 17.97 1.80
B EST 3.1 3.72 15.80 GALV 0.66 18.05 0.05 18.01 1.26
OBSERVACIONES:
CALENT Calentador a gas de 5.5 litros
EST Estufa de 4 quemadores

REFERENCIA DE Tubería: PE-AL-PE 16.20 (Diá.Int:16 mm)


REFERENCIA DE Tubería: PE-AL-PE 20.25 (Diá.Int:20 mm)
REFERENCIA DE Tubería PE-AL-PE 16.20 (Diá Int 16 mm)

4
PROYECTO SARAMAGO PLAZA
DISEÑO DE REDES DE GAS A BAJA PRESION
CALCULO DE TUBERÍAS PARA LOS APARTAMENTOS TIPO II (PISOS 2 - 3 - 4 - 5 - 6 - 7 - 8)
MEMORIAS DE CALCULO

FORMULA DE DISEÑO RENUARD


PODER CALORIFICO 11,21 KWH/M3
PRESION INICIAL 21 mbar
PRESION FINAL MINIMA 17 mbar
CALCULO ERNESTO CALDERON CARRILLO

TRAMO TUBERIA DIAMETRO TIPO Caudal PERDIDA Pf VELOCIDAD


Pi (mbar)
PISO Inicio Fin LONG (m) LE (mts) (mm) Tubería (mch) (mbar) (mbar) (m/s)
MED A 16.8 20.16 16.00 PE-AL-PE 2.5 21.00 1.41 19.59 4.65
A B 4.8 5.76 15.80 GALV 2.5 19.59 0.43 19.17 4.77
2
B CALENT 1.8 2.16 15.80 GALV 0.94 19.17 0.05 19.12 1.79
B EST 6.1 7.32 15.80 GALV 0.66 19.17 0.09 19.08 1.26
MED A 19.8 23.76 16.00 PE-AL-PE 2.5 21.00 1.66 19.34 4.65
A B 4.8 5.76 15.80 GALV 2.5 19.34 0.43 18.92 4.77
3
B CALENT 1.8 2.16 15.80 GALV 0.94 18.92 0.05 18.87 1.80
B EST 6.1 7.32 15.80 GALV 0.66 18.92 0.09 18.83 1.26
MED A 22.8 27.36 16.00 PE-AL-PE 2.5 21.00 1.91 19.09 4.65
A B 4.8 5.76 15.80 GALV 2.5 19.09 0.43 18.67 4.78
4
B CALENT 1.8 2.16 15.80 GALV 0.94 18.67 0.05 18.62 1.80
B EST 6.1 7.32 15.80 GALV 0.66 18.67 0.09 18.58 1.26
MED A 25.8 30.96 16.00 PE-AL-PE 2.5 21.00 2.16 18.84 4.66
A B 4.8 5.76 15.80 GALV 2.5 18.84 0.43 18.41 4.78
5
B CALENT 1.8 2.16 15.80 GALV 0.94 18.41 0.05 18.36 1.80
B EST 6.1 7.32 15.80 GALV 0.66 18.41 0.09 18.32 1.26
MED A 28.8 34.56 16.00 PE-AL-PE 2.5 21.00 2.41 18.59 4.66
A B 4.8 5.76 15.80 GALV 2.5 18.59 0.43 18.16 4.78
6
B CALENT 1.8 2.16 15.80 GALV 0.94 18.16 0.05 18.11 1.80
B EST 6.1 7.32 15.80 GALV 0.66 18.16 0.09 18.07 1.26
MED A 31.8 38.16 16.00 PE-AL-PE 2.5 21.00 2.66 18.34 4.66
A B 4.8 5.76 15.80 GALV 2.5 18.34 0.43 17.91 4.78
7
B CALENT 1.8 2.16 15.80 GALV 0.94 17.91 0.05 17.86 1.80
B EST 6.1 7.32 15.80 GALV 0.66 17.91 0.09 17.82 1.26
MED A 34.8 41.76 16.00 PE-AL-PE 2.5 21.00 2.91 18.09 4.66
A B 4.8 5.76 15.80 GALV 2.5 18.09 0.43 17.66 4.78
8
B CALENT 1.8 2.16 15.80 GALV 0.94 17.66 0.05 17.61 1.80
B EST 6.1 7.32 15.80 GALV 0.66 17.66 0.09 17.57 1.26
OBSERVACIONES:
CALENT Calentador a gas de 5.5 litros
EST Estufa de 4 quemadores

REFERENCIA DE Tubería: PE-AL-PE 16.20 (Diá.Int:16 mm)


REFERENCIA DE Tubería: PE-AL-PE 20.25 (Diá.Int:20 mm)
REFERENCIA DE Tubería PE-AL-PE 16.20 (Diá Int 16 mm)

5
PROYECTO SARAMAGO PLAZA
DISEÑO DE REDES DE GAS A BAJA PRESION
CALCULO DE TUBERÍAS PARA LOS APARTAMENTOS TIPO III (PISOS 2 - 3 - 4 - 5 - 6 - 7 - 8)
MEMORIAS DE CALCULO

FORMULA DE DISEÑO RENUARD


PODER CALORIFICO 11,21 KWH/M3
PRESION INICIAL 21 mbar
PRESION FINAL MINIMA 17 mbar
CALCULO ERNESTO CALDERON CARRILLO

TRAMO TUBERIA DIAMETRO TIPO Caudal PERDIDA Pf VELOCIDAD


Pi (mbar)
PISO Inicio Fin LONG (m) LE (mts) (mm) Tubería (mch) (mbar) (mbar) (m/s)
MED A 23.8 28.56 16.00 PE-AL-PE 2.5 21.00 1.99 19.01 4.66
A B 0.4 0.48 15.80 GALV 2.5 19.01 0.04 18.97 4.77
2
B CALENT 3.1 3.72 15.80 GALV 0.94 18.97 0.09 18.89 1.80
B EST 3.15 3.78 15.80 GALV 0.66 18.97 0.05 18.93 1.26
MED A 26.8 32.16 16.00 PE-AL-PE 2.5 21.00 2.24 18.76 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.76 0.04 18.72 4.78
3
B CALENT 3.1 3.72 15.80 GALV 0.94 18.72 0.09 18.64 1.80
B EST 3.15 3.78 15.80 GALV 0.66 18.72 0.05 18.68 1.26
MED A 29.8 35.76 16.00 PE-AL-PE 2.5 21.00 2.49 18.51 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.51 0.04 18.47 4.78
4
B CALENT 3.1 3.72 15.80 GALV 0.94 18.47 0.09 18.38 1.80
B EST 3.15 3.78 15.80 GALV 0.66 18.47 0.05 18.42 1.26
MED A 32.8 39.36 16.00 PE-AL-PE 2.5 21.00 2.74 18.26 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.26 0.04 18.22 4.78
5
B CALENT 3.1 3.72 15.80 GALV 0.94 18.22 0.09 18.13 1.80
B EST 3.15 3.78 15.80 GALV 0.66 18.22 0.05 18.17 1.26
MED A 35.8 42.96 16.00 PE-AL-PE 2.5 21.00 3.00 18.00 4.66
A B 0.4 0.48 15.80 GALV 2.5 18.00 0.04 17.97 4.78
6
B CALENT 3.1 3.72 15.80 GALV 0.94 17.97 0.09 17.88 1.80
B EST 3.15 3.78 15.80 GALV 0.66 17.97 0.05 17.92 1.26
MED A 38.8 46.56 16.00 PE-AL-PE 2.5 21.00 3.25 17.75 4.66
A B 0.4 0.48 15.80 GALV 2.5 17.75 0.04 17.72 4.78
7
B CALENT 3.1 3.72 15.80 GALV 0.94 17.72 0.09 17.63 1.80
B EST 3.15 3.78 15.80 GALV 0.66 17.72 0.05 17.67 1.26
MED A 41.8 50.16 16.00 PE-AL-PE 2.5 21.00 3.50 17.50 4.66
A B 0.4 0.48 15.80 GALV 2.5 17.50 0.04 17.47 4.78
8
B CALENT 3.1 3.72 15.80 GALV 0.94 17.47 0.09 17.38 1.80
B EST 3.15 3.78 15.80 GALV 0.66 17.47 0.05 17.42 1.26
OBSERVACIONES:
CALENT Calentador a gas de 5.5 litros
EST Estufa de 4 quemadores

REFERENCIA DE Tubería: PE-AL-PE 16.20 (Diá.Int:16 mm)


REFERENCIA DE Tubería: PE-AL-PE 20.25 (Diá.Int:20 mm)
REFERENCIA DE Tubería PE-AL-PE 16.20 (Diá Int 16 mm)

6
PROYECTO SARAMAGO PLAZA
DISEÑO DE REDES DE GAS A BAJA PRESION
CALCULO DE TUBERÍAS PARA LOS APARTAMENTOS TIPO IV (PISOS 2 - 3 - 4 - 5 - 6 - 7 - 8)
MEMORIAS DE CALCULO

FORMULA DE DISEÑO RENUARD


PODER CALORIFICO 11,21 KWH/M3
PRESION INICIAL 21 mbar
PRESION FINAL MINIMA 17 mbar
CALCULO ERNESTO CALDERON CARRILLO

TRAMO TUBERIA DIAMETRO TIPO Caudal PERDIDA Pf VELOCIDAD


Pi (mbar)
PISO Inicio Fin LONG (m) LE (mts) (mm) Tubería (mch) (mbar) (mbar) (m/s)
MED A 23.8 28.56 16.00 PE-AL-PE 2.5 21.00 1.99 19.01 4.66
A B 3.6 4.32 15.80 GALV 2.5 19.01 0.32 18.69 4.78
2
B CALENT 1.6 1.92 15.80 GALV 0.94 18.69 0.04 18.64 1.80
B EST 4.1 4.92 15.80 GALV 0.66 18.69 0.06 18.63 1.26
MED A 26.8 32.16 16.00 PE-AL-PE 2.5 21.00 2.24 18.76 4.66
A B 3.6 4.32 15.80 GALV 2.5 18.76 0.32 18.44 4.78
3
B CALENT 1.6 1.92 15.80 GALV 0.94 18.44 0.04 18.39 1.80
B EST 4.1 4.92 15.80 GALV 0.66 18.44 0.06 18.38 1.26
MED A 29.8 35.76 16.00 PE-AL-PE 2.5 21.00 2.49 18.51 4.66
A B 3.6 4.32 15.80 GALV 2.5 18.51 0.32 18.19 4.78
4
B CALENT 1.6 1.92 15.80 GALV 0.94 18.19 0.04 18.14 1.80
B EST 4.1 4.92 15.80 GALV 0.66 18.19 0.06 18.13 1.26
MED A 32.8 39.36 16.00 PE-AL-PE 2.5 21.00 2.74 18.26 4.66
A B 3.6 4.32 15.80 GALV 2.5 18.26 0.32 17.94 4.78
5
B CALENT 1.6 1.92 15.80 GALV 0.94 17.94 0.04 17.89 1.80
B EST 4.1 4.92 15.80 GALV 0.66 17.94 0.06 17.88 1.26
MED A 35.8 42.96 16.00 PE-AL-PE 2.5 21.00 3.00 18.00 4.66
A B 3.6 4.32 15.80 GALV 2.5 18.00 0.32 17.68 4.78
6
B CALENT 1.6 1.92 15.80 GALV 0.94 17.68 0.04 17.64 1.80
B EST 4.1 4.92 15.80 GALV 0.66 17.68 0.06 17.62 1.26
MED A 38.8 46.56 16.00 PE-AL-PE 2.5 21.00 3.25 17.75 4.66
A B 3.6 4.32 15.80 GALV 2.5 17.75 0.32 17.43 4.78
7
B CALENT 1.6 1.92 15.80 GALV 0.94 17.43 0.04 17.39 1.80
B EST 4.1 4.92 15.80 GALV 0.66 17.43 0.06 17.37 1.26
MED A 41.8 50.16 16.00 PE-AL-PE 2.5 21.00 3.50 17.50 4.66
A B 3.6 4.32 15.80 GALV 2.5 17.50 0.32 17.18 4.79
8
B CALENT 1.6 1.92 15.80 GALV 0.94 17.18 0.04 17.14 1.80
B EST 4.1 4.92 15.80 GALV 0.66 17.18 0.06 17.12 1.26
OBSERVACIONES:
CALENT Calentador a gas de 5.5 litros
EST Estufa de 4 quemadores

REFERENCIA DE Tubería: PE-AL-PE 16.20 (Diá.Int:16 mm)


REFERENCIA DE Tubería: PE-AL-PE 20.25 (Diá.Int:20 mm)
REFERENCIA DE Tubería PE-AL-PE 16.20 (Diá Int 16 mm)

7
PROYECTO SARAMAGO PLAZA
DISEÑO DE REDES DE GAS A BAJA PRESION
CALCULO DE TUBERÍAS PARA LA ZONA SOCIAL
MEMORIAS DE CALCULO

FORMULA DE DISEÑO RENUARD


PODER CALORIFICO 11,21 KWH/M3
PRESION INICIAL 21 mbar
PRESION FINAL MINIMA 17 mbar
CALCULO ERNESTO CALDERON CARRILLO

TRAMO TUBERIA DIAMETRO TIPO Caudal PERDIDA Pf VELOCIDAD


Pi (mbar)
PISO Inicio Fin LONG (m) LE (mts) (mm) Tubería (mch) (mbar) (mbar) (m/s)
MED A 37 44.40 20.00 PE-AL-PE 2.2 21.00 1.19 19.81 2.62
9
A TUR 26 31.20 15.80 GALV 2.2 19.81 2.60 17.21 4.21
OBSERVACIONES:
TUR Equipo de baño turco

REFERENCIA DE Tubería: PE-AL-PE 16.20 (Diá.Int:16 mm)


REFERENCIA DE Tubería: PE-AL-PE 20.25 (Diá.Int:20 mm)
REFERENCIA DE Tubería PE-AL-PE 16.20 (Diá Int 16 mm)

4. VENTILACION DE RECINTOS INTERIORES:


Para la ventilación de recintos interiores se tendrá en cuenta el volumen de
aire disponible en cada uno de los apartamentos tipo y el volumen de aire
requerido de acuerdo a los gasodomésticos instalados. Si el volumen de
aire disponible es inferior al requerido el recinto será confinado y necesitará
ventilación. En las tablas anexas se calcula por separado para cada tipo de
apartamento si es espacio confinado o no confinado.

8
ELEMENTOS DE VENTILACION EN AREAS DONDE SE USA GASODOMESTICOS
APARTAMENTOS TIPO 1
VOLUMEN DE AIRE DISPONIBLE
AREA ALT. VOLUMEN
APARTAMENTO
M2 ENTREPISO M3
COCINA 5.04 3.78
AREA ROPAS 2.08 2.50 5.20
SALACOMEDOR 17.28 43.20
VOLUMEN DE AIRE DISPONIBLE 52.18
GASODOMESTICO POT CONSUMO VOLUMEN
KW M3/KW M3
ESTUFA 4 QUEMADORES 7.40 25.16
HORNO 2.05 3.40 6.97
CALENTADOR DE 5 LITROS 10.50 35.70
VOLUMEN DE AIRE REQUERIDO 67.83
NECESITA VENTILACION

GASODOMESTICO POT AREA MIN AREA


KW CM2/KW CM2
ESTUFA 4 QUEMADORES 7.40 44.40
HORNO 2.05 6.00 12.30
CALENTADOR DE 5 LITROS 10.50 63.00
AREA DE REJILLA REQUERIDO 119.70
REJILLA DIMENSIONES AREA % AREA
CANT
SUPERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 1 40 20 800.00 60% 480.00
PLASTICA 0 20 20 400.00 60% 0.00
AREA DE REJILLA SUMINISTRADO 480.00
REJILLA DIMENSIONES AREA % AREA
CANT
INFERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 0 40 20 800.00 60% 0.00
PLASTICA 1 20 20 400.00 60% 240.00
AREA DE REJILLA SUMINISTRADO 240.00
NOTA: EN EL VOLUMEN DISPONIBLE SE HA DESCONTADO UN 30% POR EQUIPAMENTO

9
ELEMENTOS DE VENTILACION EN AREAS DONDE SE USA GASODOMESTICOS
APARTAMENTOS TIPO 2
VOLUMEN DE AIRE DISPONIBLE
AREA ALT. VOLUMEN
APARTAMENTO
M2 ENTREPISO M3
COCINA 6.24 15.60
AREA ROPAS 2.99 2.50 7.48
SALACOMEDOR 19.60 49.00
VOLUMEN DE AIRE DISPONIBLE 72.08
GASODOMESTICO POT CONSUMO VOLUMEN
KW M3/KW M3
ESTUFA 4 QUEMADORES 7.40 25.16
HORNO 2.05 3.40 6.97
CALENTADOR DE 5 LITROS 10.50 35.70
VOLUMEN DE AIRE REQUERIDO 67.83
NO SE NECESITA VENTILACION

GASODOMESTICO POT AREA MIN AREA


KW CM2/KW CM2
ESTUFA 4 QUEMADORES 7.40 44.40
HORNO 2.05 6.00 12.30
CALENTADOR DE 5 LITROS 10.50 63.00
AREA DE REJILLA REQUERIDO 119.70
REJILLA DIMENSIONES AREA % AREA
CANT
SUPERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 1 40 20 800.00 60% 480.00
PLASTICA 0 20 20 400.00 60% 0.00
AREA DE REJILLA SUMINISTRADO 480.00
REJILLA DIMENSIONES AREA % AREA
CANT
INFERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 0 40 20 800.00 60% 0.00
PLASTICA 1 20 20 400.00 60% 240.00
AREA DE REJILLA SUMINISTRADO 240.00
NOTA: EN EL VOLUMEN DISPONIBLE SE HA DESCONTADO UN 30% POR EQUIPAMENTO

10
ELEMENTOS DE VENTILACION EN AREAS DONDE SE USA GASODOMESTICOS
APARTAMENTOS TIPO 3
VOLUMEN DE AIRE DISPONIBLE
AREA ALT. VOLUMEN
APARTAMENTO
M2 ENTREPISO M3
COCINA 4.20 10.50
AREA ROPAS 0.00 2.50 0.00
SALACOMEDOR 11.78 29.45
VOLUMEN DE AIRE DISPONIBLE 39.95
GASODOMESTICO POT CONSUMO VOLUMEN
KW M3/KW M3
ESTUFA 4 QUEMADORES 7.40 25.16
HORNO 2.05 3.40 6.97
CALENTADOR DE 5 LITROS 10.50 35.70
VOLUMEN DE AIRE REQUERIDO 67.83
NECESITA VENTILACION

GASODOMESTICO POT AREA MIN AREA


KW CM2/KW CM2
ESTUFA 4 QUEMADORES 7.40 44.40
HORNO 2.05 6.00 12.30
CALENTADOR DE 5 LITROS 10.50 63.00
AREA DE REJILLA REQUERIDO 119.70
REJILLA DIMENSIONES AREA % AREA
CANT
SUPERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 1 40 20 800.00 60% 480.00
PLASTICA 0 20 20 400.00 60% 0.00
AREA DE REJILLA SUMINISTRADO 480.00
REJILLA DIMENSIONES AREA % AREA
CANT
INFERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 0 40 20 800.00 60% 0.00
PLASTICA 1 20 20 400.00 60% 240.00
AREA DE REJILLA SUMINISTRADO 240.00
NOTA: EN EL VOLUMEN DISPONIBLE SE HA DESCONTADO UN 30% POR EQUIPAMENTO

11
ELEMENTOS DE VENTILACION EN AREAS DONDE SE USA GASODOMESTICOS
APARTAMENTOS TIPO 4
VOLUMEN DE AIRE DISPONIBLE
AREA ALT. VOLUMEN
APARTAMENTO
M2 ENTREPISO M3
COCINA 4.20 10.50
AREA ROPAS 0.00 2.50 0.00
SALACOMEDOR 11.78 29.45
VOLUMEN DE AIRE DISPONIBLE 39.95
GASODOMESTICO POT CONSUMO VOLUMEN
KW M3/KW M3
ESTUFA 4 QUEMADORES 7.40 25.16
HORNO 2.05 3.40 6.97
CALENTADOR DE 5 LITROS 10.50 35.70
VOLUMEN DE AIRE REQUERIDO 67.83
NECESITA VENTILACION

GASODOMESTICO POT AREA MIN AREA


KW CM2/KW CM2
ESTUFA 4 QUEMADORES 7.40 44.40
HORNO 2.05 6.00 12.30
CALENTADOR DE 5 LITROS 10.50 63.00
AREA DE REJILLA REQUERIDO 119.70
REJILLA DIMENSIONES AREA % AREA
CANT
SUPERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 1 40 20 800.00 60% 480.00
PLASTICA 0 20 20 400.00 60% 0.00
AREA DE REJILLA SUMINISTRADO 480.00
REJILLA DIMENSIONES AREA % AREA
CANT
INFERIOR LARGO ANCHO CM2 EFECTIVIDAD CM2
CELOSIA (ALUMINIO) 0 40 20 800.00 60% 0.00
PLASTICA 1 20 20 400.00 60% 240.00
AREA DE REJILLA SUMINISTRADO 240.00
NOTA: EN EL VOLUMEN DISPONIBLE SE HA DESCONTADO UN 30% POR EQUIPAMENTO

12
5. DISEÑO DE REGULACION PRIMERA ETAPA:
El diseño de la regulación de primera etapa se hará por la ecuación de
Muller para baja presión y se presenta el cuadro correspondiente al cálculo
de la red.

DIMENSIONAMIENTO DE TUBERIAS A MEDIA PRESIÓN UNIONES SOLDADAS (FORMULA DE MULLER) CON 345 MBAR
Interior
Nominal

ACCESORIOS LONG. LONG. P1 PRESIÓN PRESIÓN PRESIÓN 2 P2 P2 PERDIDAS EN PERDIDAS EN PERD. PERD. VEL.
TUBERÍA
CAUDAL

EQUIV. TOTAL MAN*ATM ABS^2 MAN*ATM EL TRAMO EL TRAMO ACUMUL. ACUMUL. TRAMO
TRAMO

LONG.

ABSOLUTAS MANOMETRICA RESULTADOS RESULTADOS


S
Ø
Ø

mbares + mbares -
m³/hr Pul. mm m Tee Codos Válvulas m m mbar 723.6 723.6 mbar psi m/s
A-B 37.7 1.25 35.05 5.7 1 4 0 3.82 9.52 345.0 1068.6 1141906.0 1065.53 341.93 4.96 0.29% 0.89% APROBADO 0.29% 0.89% 10.20 APROBADO
B-C 27.46 1 26.64 0.7 0 4 0 1.72 2.42 346.0 1069.6 1144044.2 1067.96 344.36 4.99 0.15% 0.47% APROBADO 0.15% 0.47% 12.83 APROBADO
C-D 22.5 1 26.64 1 0 4 0 1.72 2.72 347.0 1070.6 1146184.4 1069.30 345.70 5.01 0.12% 0.38% APROBADO 0.12% 0.38% 10.50 APROBADO
NOMBRE DEL PROYECTO CONJUNTO SARAMAGO PLAZA PROYECTO : ERNESTO CALDERON CARRILLO

6. ESPECIFICACIONES DE EQUIPOS
Especificaciones técnicas del calentador propuesto. Modelo CAL AS CPG 5.5 GN

Especificaciones del horno a gas: Modelo ARF 60 GAS


13
Especificaciones de la estufa 4 quemadores: Modelo CUB ASL CG 60-43

FICHA TECNICA DE PRODUCTO CALEFACCIÓN


DESCRIPCIÓN ESPECIFICACIONES

Referencia (s) CUB ARL/ASL CG 60-43 INOX ML

Tipo de Producto Eléctrico A Gas Mixto

Tipo de Mesa INOXIDABLE Vidrio Templado Temperatura Máxima de operación (°C) 350

Encendido Electronico Si NO Con catenaria SI NO

AREZZO 2 4 57 (Platina)
Nro. De Parrillas Nro de puntos de apoyo Altura con empaque (mm)
ASSENTO 3 4 57 (Hierro Fundido)

Eléctrico A Gas

Nro. de Puestos Tubulares Plato Blindado Quem. Rápido Quem. Semirápido

N.A N.A 1 3

Tipo de Gas Gas Natural Gas Propano

Rango Presiones (mbar) 20 +5/-3 29 +6/-4

Categoría II2H3B/P II2H3B/P

Q. de mesa Semirápido Q. de mesa Rápido Potencia Total Generada


Potencia Reducida
4,14 MJ/h (1,15 kW) 4,14 MJ/h (1,15 kW) 27,36MJ/h (7,6 kW)

Especificaciones técnicas del baño turco (zona social)

14
7. PLANOS: