Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Woodward GmbH
Handwerkstr. 29
70565 Stuttgart
Germany
Email: stgt-info@woodward.com
Internet: http://www.woodward.com
Brief Overview
The easYgen-3000XT series are control units for engine-generator system management
applications.
The control units can be used in applications such as: co-generation, stand-by, AMF, peak
shaving, import/export or distributed generation.
The easYgen-3000XT series is also applicable for islanded, island parallel, mains parallel
and multiple unit mains parallel operations.
Scope of delivery
The following parts are included in the scope of delivery. Please check prior to the
installation that all parts are present.
Configuration files and Technical Manual are available on device internal memory.
Opening USB connection to the easYgen-XT offers read access to the files listed below
but with status "delivery" -- please be aware that this files are not updated. The latest
versions are available at the Woodward web site.
• Configuration
◦ msi-file (installing application files and ToolKit)
◦ eds-file (zipped)
• Technical Manual (PDF)
QR Code
To get access to the complete product documentation, scan this QR code or use the
following link: ══▷ http://wwdmanuals.com/easygen-3200xt.
A typical application mode for the control unit is the use for mains parallel operation in a
multi genset application.
• In this case, the easYgens-XT will function as an engine control with generator,
mains and engine protection.
• The control unit can open and close the generator circuit breaker (GCB) and the
mains circuit breaker (MCB).
• The easYgens-XT are well prepared for system control and management, "talking"
with other easYgens-3100XT/3200XT and easYgens-3400XT/3500XT.
For a listing of all available application modes please refer to ╚═▷ “6 Application Field”.
Table of Contents
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46█
........
3.3.5.1.1 Parameter Setting '3Ph 4W OD' (3-phase, 4-wire, Open delta) . . . . . . . . . . . . . . . . . . . . .62█
........
3.3.6.1.2 Parameter Setting 'Phase L1' 'Phase L2' 'Phase L3' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81█
.........
3.3.6.2.1 Parameter Setting 'Phase L1' 'Phase L2' 'Phase L3' . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83█
.........
4 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107█
..........
4.4.4.2.1 Control The Power Factor / Reactive Power At The Mains Interchange Point . . . . . . . . . .287█
.........
4.4.4.3.1 Mains Parallel Operation With Mains Interchange Real Power Control (Import/
Export) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312█
..........
5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .653█
..........
5.3 Restore Language Setting via HMI, Buttons and Softkeys . . . . . . . . . . . . . . . . . . . . . . . 661█
..........
6.3.7 Configuring A PWM Duty Cycle For A CAT ADEM Controller . . . . . . . . . . . . . . . . . . . . . . 708█
..........
6.3.15.2.2 Example “Emergency power unit” with internal GGB control (only easYgen
3400XT/3500XT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .737█
.........
6.5.2.6.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .797█
.........
9 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 840█
..........
9.2.6 Protocol 5014 (Based on Protocol 5003 but with enhancements) . . . . . . . . . . . . . . . . . .945█
.........
9.2.9.1 Receive Data (sent from remote control to the easYgen) . . . . . . . . . . . . . . . . . . . . . . .1036█
..........
9.2.9.2 Transmit Data (sent from easYgen to control external devices) . . . . . . . . . . . . . . . . . .1044█
..........
9.5.5.15 Wire Break Monitoring (of internal and external analog inputs) . . . . . . . . . . . . . . . . . .1156█
...........
11 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1163█
..........
1 General Information
I 2020-04 TM
NEW Software Revision Release 2.10 or higher
Corrections/Repairs
• Breaker transition mode "Closed Transition": Being in island mode with multiple
running easYgens did not allow constant power control in the single easYgens.
This is fixed now.
• Phase shift (ROCOF) - Not possible to trigger in Decoupling Test Mode. This is fixed
now.
• The disabling of the maintenance call by configure maintenance hours and days to
zero is improved. In the past one last maintenance call was executed even the
hours and days were RESET. This is fixed now.
• Improvement Modbus TCP slave handling: Changed receive of Modbus to fix
occasional blocking of TCP port in multiple Modbus setups.
• The FRT mains monitoring is further expanded. (VDE-AR-N 4110). See ╚═▷
“4.5.1.3.2 Generator Overfrequency (Level 1 & 2) ANSI# 81O”
Corrections/Repairs
• L1-N [%] and L3-N [%] are in AM with wrong percentage value when measurement
system = 1Ph3W. Percentage value is based on Un/sqrt(3). It should be based on
Un/2.
For details see ╚═▷ “The following AnalogManager operations are available:”.
• Introduction of the CAN protocol 5017 with all relevant alarms of an EG3000XT. For
details see ╚═▷ “9.2.5 Protocol 5011 (Alarm Values Visualization)”.
• Change in AnalogManager: The setpoints for W and var are reworked to kW and
kvar for better configuration handling.
• Support of Diesel Particle Filter SPNs according to Deutz EMR4 ECU. Refer to ╚═▷
“7.5.2 Supported J1939 ECUs & Remote Control Messages” for details.
• The time span of excitation the charging alternator (D+) is now configurable. For
details, see ╚═▷ “3.3.4 Charging Alternator”.
• It is now possible to fade out decimals of analog values on the HMI customer
screens. For details see ╚═▷ “4.3.2.1 Configure Customer Screens”.
• The free AnalogManager output values 1-16 are now usable in the CANopen PDO
system. For details see ╚═▷ “9.4.2.14 Group 21: CAN1 Receive”.
• J1939 MTU ECU9: The device supports from now on the function "Rapid start" and
"droop". See ╚═▷ “7.5.2 Supported J1939 ECUs & Remote Control Messages”.
Refer to MTU ECU9 documentation for more details.
• Introduction of ECU (J1939) messages regarding diesel particle filter (DPF). See
╚═▷ “7.5.2 Supported J1939 ECUs & Remote Control Messages”.
• Inverse Time Overcurrent Tp monitor:
The setting Inverse time overcurrent Time constant Tp can now configured on up
to 5 seconds (Before 1.99s)
• Introduction of a new LDSS feature: LDSS with predicted load. For details see ╚═▷
“6.3.15 LDSS with predicted load”.
• Introduction of the J1939 handling for ECU Hatz EDC 17. For details see ╚═▷ “7.5.2
Supported J1939 ECUs & Remote Control Messages”.
• General additionally J1939 SPNs implemented concerning diese particel filter
(DPF). See ╚═▷ “7.5.2 Supported J1939 ECUs & Remote Control Messages” for
details.
• Introduction of a new monitor: Easygen monitors ECU malfunction (emission) and
protection alarm on J1939. See ╚═▷ “7.5.2 Supported J1939 ECUs & Remote
Control Messages” for details.
• The device easYgen3500XT-P2 provides now a dedicated phase rotation monitor
instead a LogicsManager command variable only.╚═▷ “4.5.1.6.2.2 Generator Phase
Rotation”
• Introduction of a new monitor in the easYgen: For multiple easYgen applications a
MCB plausibility alarm can be used. See ╚═▷ “4.4.4.5.4 Derating And Uprating Of
Power ” for details.
• Now, the event logger also provides the information that the "Emergency run" is
finished.
• Special ethernet communication UDP handling included to withstand "broadcast
storm".
• In all application modes with L-MCB the Homepage and submenu "busbar/System/
LS5" indicates now Mains (LS5) instead of LS5 only.
Corrections/Repairs
• The devices are CSA certified (For details see ╚═▷ “8.1.8 Approvals”).
• The device provides now the capability to create an own Modbus address point
list, beginning with address 50,000. For this purpose WW provides a
TelegramMapper software tool to create customer specific DataTelegrams. This self
created DataTelegrams can be used with easYgen-XT revision 1.14 or higher. For
details see ╚═▷ “4.7.3 Modbus Protocol”.
• The device offers the capability to disable the password protection for the
individual interface communication channels. If the password level is disabled the
access level is set on code level 5. For details see ╚═▷ 9126, ╚═▷ 9128, and ╚═▷
9129.
• For running the Remote Panel RP-3000XT with the easYgen-XT, the user can
dynamically switch the Remote Panel into an Full mode, Annunciator mode or Off
mode.
Corrections/Repairs
Indication of red and amber alarm lamps of ADEC ECU7 in easYgen did not work
(ADEC ECU 7 is transmitting only one byte of DM1, eight are expected).
Application mode GCB/MCB together with “GCB auto unlock”: If emergency run
was active, “GCB auto unlock” could have caused simultaneous dead bus closure
of GCB and MCB if mains returned during the “GCB open pulse”. This could only
happen in parallel logic if the “GCB open time pulse” (5708) was configured higher
or same than 2 s. (This was because the mains settling time - which is shortened
to 2 s in emergency case - and the “GCB open time pulse” were mismatched.)
MCB plausibility alarm works fine now: If MCB was not enabled (12923 = FALSE)
and start without load was active and emergency run was active, the GCB no
longer will be frequently closed and opened.
• The active power setpoint can be changed now even in island mode and with load
control enabled.
• The event logger stores from now, when the engine has stopped. Until now only
the starting information was stored.
• GCB no longer opens and closes permanently if emergency and start without load
• Setpoint Ramp active power 2 is executed in island parallel operation, too
• Busbar display and voltage of busbar is correct now (HMI and ToolKit), even if
"Generator/Busbar" is configured for HOME screen, and measurement for 1 Phase
measurement is set to "Phase-Neutral".
The Busbar voltage on HOME screen is no longer always Zero (000 V) when there
is actually voltage measured.
• Description, images, and tables updated according to the new features, functions,
and corrections listed above.
• The Ethernet port is named Ethernet #1 or Ethernet A which means the same.
• Two symbols "generator Add-on/Add-off" explained (see ╚═▷ “4.1.5.4
Sequencing”).
• Load Control example updated (see ╚═▷ ⇱).
• NOTE added: Use Pin 61 or (metal housing) protective earth, see ╚═▷ “6.3.8 Wiring
Self Powered Discrete Inputs”.
• More user-friendly description of remotely changing setpoints (see ╚═▷ “6.4.1.7
Remotely Changing The Setpoint” and ╚═▷ “6.5.1.3 Remotely Changing The
Setpoint”).
• Settings proposal for J1939 communication with Cummins ECU (see ╚═▷ “7.5.2
Supported J1939 ECUs & Remote Control Messages”).
• Product label with Unom (see ╚═▷ “8.1 Technical Data”).
• Data Protocols updated:
◦ 5003, start addr. 450066, ID 10149
◦ 5003, start addr. 450120, ID 10298
◦ 5010, start addr. 450111, ID8009
◦ 5014, start addr. 450066, ID 4087
◦ 5014, start addr. 450136, ID 4090
• LogicsManager References update:
◦ 07.xx: IDs changed
◦ 09.xx: IDs changed
◦ 10.xx: IDs changed
◦ 11.xx: IDs changed
◦ 13.xx: IDs changed
◦ 15.xx: IDs changed
• Layout optimizations and typo corrections.
• A customer specific device name can be entered and will be used e.g. as device
name in Ethernet network. For more details refer to ╚═▷ “4.3.5 System
Management”.
• All monitoring functions in the device are from now on expanded with an
additional functionality:
◦ Each monitor can be individually enabled by an internal LogicsManager flag.
• Device identification via settings file: Serial number will be part of the .wset file
generated and saved via ToolKit. Device identification, file management, and
support request become much easier.
• AnalogManager became even more flexible:
◦ 16 free configurable and accessible constants enable pre-sets to be used as
AnalogManager input. For details refer to ╚═▷ “4.9.2 AnalogManager
Constants” and ╚═▷ “4.9.1 Operations”.
Corrections/Repairs
The easYgen-XT is not making a reboot procedure if a Modbus TCP write order is
executed on a password protected parameter just at that moment the password
level expires.
Technical Manual
• Description, images, and tables updated according to the new features and
functions listed above.
• Wrench button (softkey) explained. For details refer to ╚═▷ “4.1.4.3 Status/
Monitoring Screens”.
• Explained in more detail:
◦ ╚═▷ “6.5.1.3 Remotely Changing The Setpoint”
◦ ╚═▷ “6.4.1.7 Remotely Changing The Setpoint”
Corrections/Repairs
• Internal bugfixing.
Technical Manual
In future the published revision number will be reduced to less details: "X.YY" but
without "-ZZ" e.g., "1.13".
• The Wago DI/DO expansion boards are directly configurable now. Refer to ╚═▷
“4.7.4.2.1 Expansion Modules at CANopen Interface” for details.
• The idle mode will be entered into the event logger from now on.
• MPU (Speed sensor): The configuration allows now a minimum rated rpm of 100
rpm. Refer to ╚═▷ “Magnetic pickup input (MPU)” for details.
• The Period of use counter value is from now on available in the AnalogManager
(11.58).
Corrections/Repairs
• Measured frequencies:
The frequency evaluation in the device differentiates between all frequencies for
monitoring and phase-phase frequency for logic purposes.
• TEST mode:
Now in TEST mode »OFF« it is not possible anymore to trigger the TEST button
LED, neither via button nor via LogicsManager.
• Relay 7:
• Power factor setpoint sent by interface (ID508): Works with negative values, too.
• RPDOs: Work even with short negative integers.
• External DI status: Can be reset in all situations.
• Phoenix expansion boards:
When the Phoenix terminals are powered off the configuration will not be lost.
Technical Manual
The basic code entry for the password got a disguise input.
• Modbus TCP:
Corrections/Repairs
The issue with a short open command , when closing the GCB from external, is
fixed.
Refer to ╚═▷ “The following AnalogManager operations are available:” for details.
• Corrections regarding the Load share gateway indication in the HMI are made.
• Minor rework of synchroscope.
• Prevent an unintended parameter default setting if a parameter was changed and
shortly (less than 3 seconds) after the power supply was switched off.
•
Technical Manual
• Release 5.0
Technical Manual
Notes
New device features & updates in comparison to easYgen-3000 series will be found in
the transition manual #37595. Please check availability at Woodward web site
www.woodward.com.
General data tables relevant for the easYgen-XT series will additionally be found in
Excel files.
Safety instructions
Safety instructions are marked with symbols. The safety instructions are always
introduced by signal words that express the severity of the danger.
DANGER!
WARNING!
This combination of symbol and signal word indicates a possibly dangerous situation that
can cause death or severe injuries if it is not avoided.
CAUTION!
This combination of symbol and signal word indicates a possibly dangerous situation that
can cause slight injuries if it is not avoided.
NOTICE!
This combination of symbol and signal word indicates a possibly dangerous situation that
can cause property and environmental damage if it is not avoided.
Additional markings
To highlight instructions, results, lists, references, and other elements, the following
markings are used in these instructions:
Marking Explanation
Marking Explanation
Dimensions in Figures
All information and instructions in this manual have been provided under due
consideration of applicable guidelines and regulations, the current and known state of the
art, as well as our many years of in-house experience. Woodward assumes no liability for
any damages due to:
The originator is solely liable for the full extent for damages caused by such conduct. The
obligations agreed-upon in the delivery contract, the general terms and conditions, the
manufacturer’s delivery conditions, and the statutory regulations valid at the time the
contract was concluded, apply.
Copyright
This manual is protected by copyright. No part of this manual may be reproduced in any
form or incorporated into any information retrieval system without written permission of
Woodward GmbH.
Delivery of this manual to third parties, duplication in any form - including excerpts - as
well as exploitation and/or communication of the content, are not permitted without a
written declaration of release by Woodward GmbH.
Actions to the contrary will entitle us to claim compensation for damages. We expressly
reserve the right to raise any further accessory claims.
In addition, our employees are interested in any information and experiences that arise
from usage and can be valuable for the improvement of our products.
Warranty terms
Please enquire with your nearest Woodward representative about the terms of warranty.
1.4 Safety
The genset control unit has been designed and constructed solely for the intended use
described in this manual.
The easYgen-... devices are available in two different enclosures. They are designed to be
installed either on the back plate of a switch gear cabinet (e.g. easYgen-x100.../...-
x400...) or on the front plate of a switch gear panel (e.g. easYgen-x200.../...-x500...).The
terminals are always located on the inner side of the housing.
The genset control unit must be used exclusively for engine-generator system management
applications.
• Intended use requires operation of the control unit within the specifications listed in ╚═▷ “8.1 Technical
Data”.
• All permissible applications are outlined in ╚═▷ “2.2 Application Modes Overview”.
• Intended use also includes compliance with all instructions and safety notes presented in this manual.
• Any use which exceeds or differs from the intended use shall be considered improper use!
• No claims of any kind for damage will be entertained if such claims result from improper use.
NOTICE!
Improper use of the genset control unit may cause damage to the control unit as well as
connected components.
1.4.2 Personnel
WARNING!
If unqualified personnel perform work on or with the control unit hazards may arise which
can cause serious injury and substantial damage to property.
• Therefore, all work must only be carried out by appropriately qualified personnel.
This manual specifies the personnel qualifications required for the different areas of work,
listed below:
The workforce must only consist of persons who can be expected to carry out their work
reliably. Persons with impaired reactions due to, for example, the consumption of drugs,
alcohol, or medication are prohibited.
Electrical hazards
DANGER!
There is an imminent life-threatening hazard from electric shocks from live parts.
Damage to insulation or to specific components can pose a life-threatening hazard.
WARNING!
The engine, turbine, or other type of prime mover should be equipped with an overspeed
(over-temperature, or over-pressure, where applicable) shutdown device(s), that
operates totally independently of the prime mover control device(s) to protect against
runaway or damage to the engine, turbine, or other type of prime mover with possible
personal injury or loss of life should the mechanical-hydraulic governor(s) or electric
control(s), the actuator(s), fuel control(s), the driving mechanism(s), the linkage(s), or
the controlled device(s) fail.
this Woodward device has a self test check implemented. Permanently under control are:
• supply voltage.
The internal signal "self check" is aligned in series with the inverse signal »Ready for op.
OFF« parameter ╚═▷ 12580. Per default (factory settings) discrete output R01 is
energized/closed if device itself is OK.
LogicsManager (LM) equation parameter ╚═▷ 12580 allows to customize this safety relay.
You can use the result of this equation: LM command variable 99.01 .
CAUTION!
The discrete output "Ready for operation" must be wired in series with an emergency
stop function.
This means that it must be ensured that the generator circuit breaker is opened and the
engine is stopped if this discrete output is de-energized.
If the availability of the plant is important, this fault must be signaled independently from
the unit.
Modifications
WARNING!
• constitute "misuse" and/or "negligence" within the meaning of the product warranty
thereby excluding warranty coverage for any resulting damage
• invalidate product certifications or listings.
Use of batteries/alternators
NOTICE!
• Make sure the charging device is turned off before disconnecting the battery from
the system.
Unit includes a lithium backup battery for Real Time Clock. Field replacement of the
battery is not allowed.
Electrostatic discharge
ᐳ
• Protective equipment: ESD wrist band
NOTICE!
1. ▷ Avoid build-up of static electricity on your body by not wearing clothing made of
synthetic materials. Wear cotton or cotton-blend materials as much as possible because
these do not store static electric charges as easily as synthetics.
2. ▷ Before working on terminals on the control unit, ground yourself by touching
and holding a grounded metal object (pipes, cabinets, equipment, etc.) to
discharge any static electricity.
Alternatively wear an ESD wrist band connected to ground.
3. ▷ Before any maintenance work on the control unit, ground yourself by
touching and holding a grounded metal object (pipes, cabinets, equipment,
etc.) to discharge any static electricity.
Alternatively wear an ESD wrist band connected to ground.
4. ▷ Keep plastic, vinyl, and Styrofoam materials (such as plastic or Styrofoam cups,
cigarette packages, cellophane wrappers, vinyl books or folders, plastic bottles, etc.)
away from the control unit, modules and work area.
5. ▷ Opening the control cover may void the unit warranty. Do not remove the printed circuit
board (PCB) from the control cabinet unless instructed by this manual.
If instructed by this manual to remove the PCB from the control cabinet,
follow these precautions:
• "Woodward manual 82715, Guide for Handling and Protection of Electronic Controls,
Printed Circuit Boards, and Modules".
Marine usage of the easYgen genset control requires additional precautions as listed
below:
The specified marine approvals are initially only valid for metal housing units. They are
only valid for plastic housing units, if they are installed using the screw kit .
Some additional, independent safety and protection devices are necessary to meet
safety requirements of Rules and Regulations of marine Classification Societies.
• Please consider for final functional arrangements to comply with appropriate Lloyd's
Register Rules as subject of the Plan Approval process.
Protective gear
Personal protective equipment serves to protect risks to the safety and health of persons
as well as to protect delicate components during work.
Certain tasks presented in this manual require the personnel to wear protective
equipment. Specific required equipment is listed in each individual set of instructions.
The ESD (electrostatic discharge) wrist band keeps the user's body set to ground
potential. This measure protects sensitive electronic components from damage due to
electrostatic discharge.
Tools
Use of the proper tools ensures successful and safe execution of tasks presented in this
manual.
• Note the required torque range individually specified in the tasks listed in this
manual.
2 System Overview
HMI and ToolKit are aligned for the same sequence and structure of functions and
parameters.
Restrictions
For detailed information on the application modes and special applications refer to ╚═▷
“Device status”.
• AUTO
• MANUAL (MAN)
• TEST
• STOP
• ... and an internal (non) operating phase during starting the device itself
The plastic housing (HMI) version of the easYgen-3000XT enables to select an operation
mode by pressing the according button at the front panel - if current settings allow this
function.
For more information about the operation modes please see ╚═▷ “5.2 Change Operating
Modes”.
3 Installation
ᐳ
• Special tool: Torque screwdriver
1. ▷
Drill the holes according to the dimensions in ╚═▷ Fig. 4 (dimensions shown in mm).
Ensure sufficient clearance for access to the terminals (top and bottom) and
connectors located at the sides.
2. ▷ Mount the unit to the back panel and insert the screws.
3. ▷ Tighten the screws to a torque according to the quality class of the used screws.
• Don't drill holes if you want to use the clamp fasteners. If the holes are drilled into
the panel, the clamp fasteners cannot be used anymore.
• In order to enhance the protection to IP 66, fasten the unit with the screw kit instead
of the clamp fastener hardware.
Dimensions
Panel cutout
ᐳ For installation into a door panel with the fastening clamps, proceed as follows:
1. ▷ Cut out the panel according to the dimensions in ╚═▷ Fig. 6.
Don't drill the holes if you want to use the clamp fasteners. If the holes are
drilled into the panel, the clamp fasteners cannot be used anymore!
2. ▷
Loosen the wire connection terminal screws on the back of the unit and remove the wire
connection terminal strip if required.
3. ▷
Insert the four clamping screws into the clamp inserts from the shown side (╚═▷ Fig. 8;
opposite the nut insert) until they are almost flush. Do not completely insert the screws
into the clamp inserts.
4. ▷ Insert the unit into the panel cutout. Verify that the unit fits correctly in the cutout. If the
panel cutout is not big enough, enlarge it accordingly.
5. ▷
Re-install the clamp inserts by tilting the insert to a 45° angle. (╚═▷ Fig. 9/1) Insert the
nose of the insert into the slot on the side of the housing. (╚═▷ Fig. 9/2) Raise the clamp
insert so that it is parallel to the control panel.
6. ▷
Tighten the clamping screws (╚═▷ Fig. 10/1) until the control unit is secured to the
control panel (╚═▷ Fig. 10/2). Over tightening of these screws may result in the clamp
inserts or the housing breaking. Do not exceed the recommended tightening torque of
0.1 Nm.
7. ▷
Reattach the wire connection terminal strip (╚═▷ Fig. 11) and secure them with the side
screws.
The housing is equipped with 12 nut inserts (╚═▷ Fig. 12), which must all be tightened
properly to achieve the required degree of protection.
ᐳ
• Special tool: Torque screwdriver
If the thickness of the panel sheet exceeds 2.5 mm, be sure to use screws
with a length exceeding the panel sheet thickness by 4 mm.
NOTICE!
Before working with terminals please read and follow the instructions of chapter ╚═▷
“Electrostatic discharge”.
For CAN and RS485 shielded cabling, no more than 25 mm wiring exposed without shield
coverage are allowed at terminal plug side.
General notes
NOTICE!
All technical data and ratings indicated in this chapter are merely listed as examples.
Literal use of these values does not take into account all actual specifications of the
control unit as delivered.
• For definite values please refer to chapter ╚═▷ “8.1 Technical Data”.
Wire sizes
Field wiring shall be made with use of cables which have temperature rating not less
than 90 °C.
AWG mm² AWG mm² AWG mm² AWG mm² AWG mm² AWG mm²
The device terminals are allocated (similarly for all housing variants) as follows:
The max. possible conductor cross-section of the terminals used is Amax = 2.5
mm2!
LT Variant description
The temperature range is the only difference between standard plastic housing and LT
variant.
The manual is describing plastic housing and metal housing variant. Describing the
plastic housing means both standard and LT variant - if not, it is mentioned!
The Protective Earth terminal 61 is not connected on the sheet metal housing.
• Use the protective earth (PE) connector located at the bottom center of the sheet
metal housing instead.
Mains, generator, and busbar voltage measuring terminals no longer differentiate with
separate terminals for each voltage range.
General recommendations
Ensure appropriate cable cross sections following the local standards and restrictions.
The maximum cable cross section of the terminal blocks is 2.5 mm2.
For every type of signal lines like power supply, DI, DO, AI, AO, MPU:
• Rout all cables connected to terminal blocks away from back cover.
USB
terminals
USB Ethernet
Screw
Host
In Device #A
preparation
40
41
*1
Relay [R01] isolated
[R01] Busbar voltage (system1)
Fixed to ready for operation
42
*1
Relay [R02] 480 Vac
38
L1
43
[R02]
Preconfigured to Centralized alarm
Busbar voltage (system1)
Relay [R03]*1
44
[R03]
Preconfigured to Starter
Relay [R04]*1 N 480 Vac
36
45
[R04]
Preconfigured to solenoid / gas valve
Generator voltage
46
480 Vac
34
47
*1 L3
Relay [R05] isolated
[R05] Generator voltage
Preconfigured to Preglow
48
Terminals easYgen3100XT/3200X
L2 480 Vac
32
49
*1
Relay [R06] isolated
[R06] Fixed to „Command close GCB“, Generator voltage
if GCB is activated.
50
*1
Relay [R07] isolated 480 Vac
30
L1
51
480 Vac
28
53
*1
Relay [R08] isolated N
[R08] Fixed to „Command close MCB“, Mains voltage
if MCB is activated.
54
*1
Relay [R09] isolated
L3 480 Vac
26
55
*1
Relay [R10]
L2 480 Vac
24
57
*1
Relay [R11]
[R11] Preconfigured to Alarm class A or B
L1 480 Vac
22
59
20
61
Earth
Analog output [AO 02]
NC (+/−10Vdc / +/−20mA / PWM) +
19
62
[AO 02]
Voltage Biasing
Do not
+
18
63
[AO 01]
65
isolated
Engine
15
66
Emergency Stop
*1 [AI 03]
Discrete Input [D02] isolated
[D02] −
13
68
Start in Auto
Discrete Input [D03] isolated*1 Analog Input Type 1
[D03] +
12
69
Alarm acknowledgement
*1 [AI 01]
Discrete Input [D06] isolated
[D06] −
72
Enable MCB
Discrete Input [D07] isolated
[D07] s1
73
Alarm input
*1 (isolated) L2
Discrete Input [D10] isolated
[D10] 1A / 5A compatible s2
76
Alarm input
*1
[D11] Discrete Input [D11] isolated s1
77
Alarm input
L1
Discrete Input [D12] isolated*1
[D12] s2
78
+ Mains s1
79
1: RS485_A
terminals
CAN #3
terminals
1: CAN_GND 1: CAN_GND
RS485 #1 2: RS485_B
Screw
Screw
1) Configurable by LogicsManager
General notes
WARNING!
• Connect Protective Earth (PE) to the unit to avoid the risk of electric shock.
• The conductor providing the connection must have a wire larger than or equal to
2.5 mm² (14 AWG). The connection must be performed properly.
WARNING!
• Connect Protective Earth (PE) to the unit to avoid the risk of electric shock.
Use the protective earth (PE) connector located at the bottom center of the sheet
metal housing.
• The conductor providing the connection must have a wire larger than or equal to
2.5 mm² (14 AWG). The cable length should be as short as possible.
• The connection must be performed properly.
WARNING!
The maximum permissible differential voltage between terminal 64 (B-) and terminal 61
(PE) is 100 VRMS. On engines where a direct connection between battery minus and PE is
not possible, it is recommended to use an isolated external power supply if the
differential voltage between battery minus and PE exceeds 100 VRMS.
Woodward strictly recommends to use a power supply that is fulfilling the SELV
restrictions (SELV = separated or safety extra-low voltage, see IEC)
Woodward recommends to use one of the following slow-acting protective devices in the
supply line to terminal 63:
Power ON
Terminal Description
C 64 0 Vdc
Characteristics
General notes
The charging alternator D+ acts as an pre-exciting output during the engine start-up.
During regular operation, it acts as an input for monitoring the charging voltage.
Terminal Description
General notes
Woodward recommends protecting the voltage measuring inputs with slow-acting fuses
rated for 2 to 6 A.
The wide range terminals allow several voltages. The current voltage (range) of the
application must be "told" to the genset controller device. Settings are described in
chapter ╚═▷ “4.6 Configure Measurement”.
General notes
The voltage measuring inputs for 120 V and 480 V are using the same terminals 30 to
36. The current voltage range must be selected by the corresponding settings via HMI
and/or ToolKit.
Parameter ╚═▷ 1800 ("Gen. PT secondary rated volt.") must be configured to the correct
value to ensure proper measurement.
Generator voltage - L1 A 30
Generator voltage - L2 B 32
Generator voltage - L3 C 34
Generator voltage - N D 36
Generator windings
A generator system that is connected to the load through a 3-phase, 4-wire connection
but have the device wired for a 3-phase, 3-wire installation may have the L2 phase
grounded on the secondary side. In this application the device will be configured for 3-
phase, 4-wire OD for correct power measurement.
A L1 A L1 A L1
A1
A1 A2 A1 A5
A2 A5 A2 A6
A6
C2 B6
C6 B6
C1 B5
C2 B2 C5 B5
C1 B1 C2 B2
C1 B1
C B C B C B
L2 L2 C6 B2 L2
C5 B1
L3 L3 L3
Measuring inputs
Terminal assignment
Generator voltage - L1 A 30
Generator voltage - L2 B 32
Generator voltage - L3 C 34
Generator windings
A L1 A L1 A L1
A1
A1 A2 A1 A5
A2 A5 A2 A6
A6
C2 B6
N C6 N B6 N B5
C1
C2 B2 C5 B5
C1 B1 C2 B2
C1 B1
C B C B C B
L2 L2 C6 B2 L2
C5 B1
N N N
L3 L3 L3
Measuring inputs
Terminal assignment
Generator voltage - L1 A 30
Generator voltage - L2 B 32
Generator voltage - L3 C 34
Generator voltage - N D 36
Generator windings
A L1 A L1
C6 A1
C5 A2
C2 A1
C1 A2
C2 A5
C1 A6
C B C B
L2 L2
B2 B1 B6 B5 B2 B1
L3 L3
Measuring inputs
Terminal assignment
Generator voltage - L1 A 30
Generator voltage - L2 B 32
Generator voltage - L3 C 34
-/- -/- 36
Generator windings
A L1
A1 A5
A2 A6
B6
B5
N
B5 C2 B1 C6 B2
B1
B6 C1 B2 C5
C2
C1
A C
L3
A1 A2
N A5 A6
C6
C C5
N L3
L1 N
Measuring inputs
Terminal assignment
Generator voltage - L1 A 30
Generator voltage - L3 C 34
Generator voltage - N D 36
B 32
Generator windings
A
L1
A1 B6
A2 B6
A N
N
A1 A2 A5 A6
N
L1 N
Measuring inputs
Terminal assignment
Generator voltage - L1 A 30
Generator voltage - N B 32
C 34
D 36
Never configure the busbar measurement for phase-neutral, if the other systems like
mains and generator are configured as 3ph 3W or 4ph 4W without being the neutral in
the middle of the triangle.
Generator windings
A
L1
A1 B6
A2 B6
A B
L2
A1 A2 A5 A6
B
L1 L2
Measuring inputs
Terminal assignment
Generator voltage - L1 A 30
Generator voltage - L2 B 32
General notes
The voltage measuring inputs for 120 V and 480 V are using the same terminals 22 to
28. The current voltage range must be selected by the corresponding settings via HMI
and/or ToolKit.
Parameter ╚═▷ 1803 ("Mains PT secondary rated volt.") must be configured with the
correct value to ensure proper measurement.
If the easYgen is intended to be operated in parallel with the mains, the mains voltage
measuring inputs must be connected.
Mains voltage - L1 A 22
Mains voltage - L2 B 24
Mains voltage - L3 C 26
Mains voltage - N D 28
Mains windings
A L1 A L1 A L1
A1
A1 A2 A1 A5
A2 A5 A2 A6
A6
C2 B6
N C6 N B6 N B5
C1
C2 B2 C5 B5
C1 B1 C2 B2
C1 B1
C B C B C B
L2 L2 C6 B2 L2
C5 B1
N N N
L3 L3 L3
Measuring inputs
Terminal assignment
Mains voltage - L1 A 22
Mains voltage - L2 B 24
Mains voltage - L3 C 26
Mains voltage - N D 28
Mains windings
A L1 A L1
C6 A1
C5 A2
C2 A1
C1 A2
C2 A5
C1 A6
C B C B
L2 L2
B2 B1 B6 B5 B2 B1
L3 L3
Measuring inputs
Terminal assignment
Mains voltage - L1 A 22
Mains voltage - L2 B 24
Mains voltage - L3 C 26
-/- -/- 28
Mains windings
A L1
A1 A5
A2 A6
B6
B5
N
B5 C2 B1 C6 B2
B1
B6 C1 B2 C5
C2
C1
A C
L3
A1 A2
N A5 A6
C6
C C5
N L3
L1 N
Measuring inputs
Terminal assignment
Mains voltage - L1 A 22
Mains voltage - L3 C 26
Mains voltage - N B 24
D 28
Mains windings
A
L1
A1 B6
A2 B6
A N
N
A1 A2 A5 A6
N
L1 N
Measuring inputs
Terminal assignment
Mains voltage - L1 A 22
Mains voltage - N B 24
C 26
D 28
Mains windings
A
L1
A1 B6
A2 B6
A B
L2
A1 A2 A5 A6
B
L1 L2
Measuring inputs
Terminal assignment
Mains voltage - L1 A 22
Mains voltage - L2 B 24
General notes
The voltage measuring inputs for 120 V and 480 V are using the same terminals 38 to
40. The current voltage range must be selected by the corresponding settings via HMI
and/or ToolKit.
Parameter ╚═▷ 1812 ("Busb1 PT secondary rated volt.") must be configured to the
correct value to ensure proper measurement.
Busbar windings
A
L1
A1 B6
A2 B6
A N
N
A1 A2 A5 A6
N
L1 N
Measuring inputs
Terminal assignment
Busbar voltage - N B 40
Busbar windings
A
L1
A1 B6
A2 B6
A B
L2
A1 A2 A5 A6
B
L1 L2
Measuring inputs
Terminal assignment
General notes
WARNING!
• Before disconnecting the device, ensure that the current transformer (CT) is short-
circuited.
The current measuring inputs for 1 A and 5 A are using the same terminals 3 to 8. The
current range must be selected by the corresponding settings via HMI and/or ToolKit.
Generally, one line of the current transformers secondary must be grounded close to the
CT.
CAUTION!
Terminal Description
Wiring terminals
F E D C B A
L1 L2 L3
Terminal 3 4 5 6 7 8
Wiring terminals
Phase L1 and L3
Terminal 3 4 5 6 7 8
"Phase L1 and L3" applies if the generator voltage measurement is configured to 1Ph 3W
(╚═▷ “3.3.5.1 Generator Voltage”).
Fig. 51: Current measuring - generator, 'Phase L1' 'Phase L2' 'Phase L3'
Wiring terminals
F E D C B A
Phase L1
Terminal 3 4 5 6 7 8
Phase L2
Terminal 3 4 5 6 7 8
Phase L3
Terminal 3 4 5 6 7 8
General notes
WARNING!
• Before disconnecting the device, ensure that the current transformer (CT) is short-
circuited.
The current measuring inputs for 1 A and 5 A are using the same terminals 1 to 2. The
current range must be selected by the corresponding settings via HMI and/or ToolKit.
Generally, one line of the current transformers secondary must be grounded close to the
CT.
Terminal Description
Fig. 53: Current measuring - mains, 'Phase L1' 'Phase L2' 'Phase L3'
Wiring terminals
B A
Phase L1
Terminal 1 2
Phase L2
Terminal 1 2
Phase L3
Terminal 1 2
General notes
WARNING!
• Before disconnecting the device, ensure that the current transformer (CT) is short-
circuited.
The current measuring inputs for 1 A and 5 A are using the same terminals 1 to 2. The
current range must be selected by the corresponding settings via HMI and/or ToolKit.
The mains current input can be configured to measure the mains current or ground
current. The parameter 'Mains current input' determines, if this input will measure the
mains current (default) or the ground current.
Generally, one line of the current transformers secondary must be grounded close to the
CT.
Terminal Description
If the unit's current transformers are wired according to the diagram (╚═▷ Fig. 55), the
following values are displayed.
Terminal Description
B 2
C 3 5 7 Generator current
D 4 6 8
(cos φ)
(cos φ)
(cos φ)
Measuring 3PH 3W
The values of single active power, reactive power, and power factor in L1, L2 and L3 are
not displayed. This values can not be determined through this connection type.
Definition
Power Factor is defined as a ratio of the real power to apparent power. In a purely
resistive circuit, the voltage and current waveforms are instep resulting in a ratio or
power factor of 1.00 (often referred to as unity).
In an inductive circuit the current lags behind the voltage waveform resulting in usable
power (real power) and unusable power (reactive power). This results in a positive ratio or
lagging power factor (i.e. 0.85 lagging).
In a capacitive circuit the current waveform leads the voltage waveform resulting in
usable power (real power) and unusable power (reactive power). This results in a negative
ratio or a leading power factor (i.e. 0.85 leading).
Properties
Inductive Capacitive
Load type Electrical load whose current waveform lags Electrical load whose current waveform leads
the voltage waveform thus having a lagging the voltage waveform thus having a leading
power factor. Some inductive loads such as power factor. Some capacitive loads such as
electric motors have a large startup current capacitor banks or buried cable result in
requirement resulting in lagging power factors. leading power factors.
Control signal If the control unit is equipped with a power factor controller while in parallel with the utility:
A voltage lower "-" signal is output as long as A voltage raise "+" signal is output as long as
the measured value is "more inductive" than the measured value is "more capacitive" than
the reference setpoint the reference setpoint
Example: measured = i0.91; setpoint = i0.95 Example: measured = c0.91; setpoint = c0.95
Phasor diagram
U L3-E U L3-E
I L3
I L3
I L1
U L1-E U L1-E
180° 0° 180° 0°
I L1
I L2
I L2
U L2-E U L2-E
Fig. 56: Phasor diagram: capacitive load (left) and inductive load (right)
General notes
The shield of the MPU (Magnetic Pickup Unit) connection cable must be connected to a
single point ground terminal near the easYgen.
The shield must not be connected at the MPU side of the cable.
The number of teeth on the flywheel reference gear and the flywheel speed must be
configured so that the magnetic pickup input frequency does not exceed 14 kHz.
Overview
Terminal Description
Characteristic
╚═▷ Fig. 59 shows the minimal necessary input voltage depending on frequency. It is
recommended to ensure input voltage greater than minimal necessary with a margin of 2
to 3 V (especially at high ambient temperature above +50 °C).
General notes
WARNING!
Discrete input [DI 01] "Emergency Stop" is only a signaling input. This input may only be
used to signal that an external emergency stop button has been actuated.
According to EN 60204, this input is not approved to be used as the emergency stop
function.
• The emergency stop function must be implemented external to the control and
cannot rely on the control to function properly.
The discrete inputs are electrically isolated which permits the polarity of the connections
to be either positive or negative.
• All discrete inputs must use the same polarity, either positive or negative signals,
due to the common ground.
Terminal Description
A B
Operation logic
Discrete inputs may be configured to normally open (N.O.) or normally closed (N.C.)
states.
In the state N.O., no potential is present during normal operation; if an alarm is issued or
control operation is performed, the input is energized.
In the state N.C., a potential is continuously present during normal operation; if an alarm
is issued or control operation is performed, the input is de-energized.
The N.O. or N.C. contacts may be connected to the signal terminal as well as to the
ground terminal of the discrete input (╚═▷ “Schematic and terminal assignment”).#
General notes
CAUTION!
The relay output "Ready for operation" must be wired in series with an emergency stop
function. This means that it must be ensured that the generator circuit breaker is opened
and the engine is stopped if this relay output is de-energize.
• We recommend to signal this fault independently from the unit if the availability of
the plant is important.
Terminal Description
N.O. Common
A B Form A
A02
A04
A03
A04
A02
A03
A02
A03
NOTICE!
Interferences in the interaction of all components may affect the function of electronic
devices. One interference factor is disabling inductive loads, like coils of electromagnetic
switching devices.
When disabling such a device, high switch-off induced voltages may occur, which might
destroy adjacent electronic devices or result interference voltage pulses, which lead to
functional faults, by capacitive coupling mechanisms.
Connect the resistive analog input's return wires (GND) always to Engine Ground
(terminal 15) and as close to the easYgen terminals as possible.
• Table A
• Table B
• Linear
• Pt100
• Pt1000
• AB 94099
• VDO 120° C
• VDO 150° C
• VDO 10 bar
• VDO 5 bar
The 9 setpoints of the free configurable Tables A and B can be selected for Type definition
(parameters 1000, 1050, and 1100).
A catalog of all available VDO sensors is available for download at the VDO homepage
(══▷ http://www.vdo.com)
Wiring senders
Terminal Description
CAUTION!
Mixed senders
When both types resistive sender and single pole sender are connected to the device,
connection from minus (pins 9, 11, 13) should be made with short wire to the Engine
Ground (pin 15) on input connector.
It is possible to combine single- and two-pole senders but with the lower accuracy.
The easYgen offers current, voltage or PWM analog outputs for different applications.
Most commonly they are used for speed and voltage biasing.
Controller configuration can change the multifunction controller bias output signals. The
analog outputs are galvanically isolated.
CAUTION!
Connecting external power sources to the analog outputs may damage the device.
In case that higher permanent insulation voltages are required than described in the
technical data, please install isolation equipment (isolation amplifier) for proper and safe
operation.
or
V*
Voltage
or
V*
Voltage
NOTICE!
Before working with terminals please read and follow the instructions of chapter ╚═▷
“Electrostatic discharge”.
For CAN and RS485 shielded cabling, no more than 25 mm wiring exposed without shield
coverage are allowed at terminal plug side.
General notes
Pin assignment
Terminal Description .. used for FULL duplex ... used for HALF duplex Amax
mode mode
RS-485 half-duplex
Fig. 69: RS-485 - connection for half-duplex operation (120 Ohms termination resistor
at both ends)
RS-485 full-duplex
Shielding
easYgen-3000XT is prepared for shielding: Terminal 4 and the connector housing are
internally grounded via an RC element. Therefore, they may either be grounded directly
(recommended) or also via an RC element on the opposite connection.
General notes
To connect this USB 2.0 (slave) device a USB cable with USB Type A (PC/laptop side) and
Type B (Woodward device side) connectors is necessary.
The USB interface is a service port and the preferred ToolKit connection!
Connecting it to a PC/laptop will display the USB interface available and all files prepared
from Woodward manufacturing side. Read/write attributes of this service port are
restricted to read only.
Pin assignment
Topology
Please note that the CAN bus must be terminated with a resistor, which corresponds to
the impedance of the cable (e.g. 120 Ω, 1/4 W) at both ends.
For very critical EMC conditions (many noise sources with high noise levels) and for high
transmission rates we recommend to use the 'Split termination concept' as shown.
• Divide the termination resistance into 2x60 Ohms with a center tap connected to
ground via a capacitor of 10 to 100 nF.
The maximum length of the communication bus wiring is dependent on the configured
baud rate. Observe the maximum bus length.
(Source: CANopen; Holger Zeltwanger (Hrsg.); 2001 VDE VERLAG GMBH, Berlin und
Offenbach; ISBN 3-8007-2448-0).
1000 kbit/s 25 m
800 kbit/s 50 m
50 kbit/s 1000 m
20 kbit/s 2500 m
Bus shielding
All bus connections of the easYgen are internally grounded via an RC element. Therefore,
they may either be grounded directly (recommended) or also via an RC element on the
opposite bus connection.
Troubleshooting
If there is no data transmission on the CAN bus, check for the following common CAN bus
communication problems:
Woodward recommends the use of shielded, twisted-pair cables for the CAN bus (see
examples).
This Ethernet interface 10/100Base-T/-XT complies with the IEEE 802.3 specifications.
Pin assignment
4 Not connected NC NC
5 Not connected NC NC
7 Not connected NC NC
8 Not connected NC NC
Notes
Visualization
Two LEDs (green and yellow) indicate communication status as well known by the
standard.
• The green LED indicates the link activity: blinking during data transmission.
General notes
Ethernet category 5 (STP CAT 5) shielded cable is required with shielded plug RJ45. The
chosen switch shall support a transmission speed of 10/100 Mb/s with a network segment
expansion capability of 100 m.
Flexibility
The Ethernet port has auto MDI/MDI-X functionality what allows to connect straight-
through or crossover Ethernet cable.
The Ethernet port is named Ethernet #1 or Ethernet A which means the same.
The maximum length from connection to connection is 100 m. Some third party suppliers
offer technology to expand the connection.
Topology
Remote Control
The Woodward Remote Control is able to visualize the display of the remotely controlled
device and to make front button and soft key related functionality available.
Access via Remote Panel PR-3000XT is described in chapter ╚═▷ “4.3.6 Configure Remote
Panel Mode” and the Technical Manual »37593 RP-3000XT«.
Fig. 77: Application Example: Multiple Generator operation with a ToolKit access point
(A)
Fig. 78: Application Example: Multiple Generator operation with a ToolKit access point
(B)
Troubleshooting
Check the IP addressed of the single devices. See chapter ╚═▷ “4.7.5 Ethernet Interfaces”
for details.
4 Configuration
Parameter Numbers
This device is working with variables and values in FLOAT format. This allows to handle
values by number and exponent.
There is a need to convert FLOAT to INTEGER (32 bit) for common Data Protocols,
communication with some PLCs, and for some display restrictions.
Rounding error
Numbers higher than 8388608 come with an rounding error of 0.005% of the number
itself.
Some parameters have a separate definition of value and unit. This flexibility comes with
the need to take additional care for factorized units like "k..., M..., m..., µ..." multiplying or
dividing the number of the value.
Device and software offer a very flexible handling of values with well defined selectable
rules. It is on customers responsibility to combine what fits.
From device side it is neither restricted nor controlled to use values in a wrong way.
Exceptions
• The well introduced HMI/display softbutton »Next Page« is continued but in ToolKit
named »STATUS MENU«.
• Some monitoring parameters in HMI/display are in ToolKit placed directly with it's
settings e.g.: find 10341 »Freq. dep. derating of power« at
The following drawing shows the first three (major) levels of the easYgen-3100XT-
P1/3200XT-P1 menu structure:
The following chapters only apply to model with front panel and display.
Buttons can be disabled by ToolKit with parameter ╚═▷ 12978 »Lock keypad«.
Main screen
After power-up the control unit displays the main screen / HOME screen (╚═▷ Fig. 80).
The main screen can be divided into the following basic sections:
Fig. 80: Main screen (shown with default settings for screen configuration)
1 Values
2 Status Messages
3 Alarm Messages
Values »1«
The "values" section (╚═▷ Fig. 80/1) of the screen illustrates all measured power related
information including voltages, currents, frequencies, power, and power factor values.
If the mains data display is disabled, the main screen will only show generator data with
bigger digits.
For information on specialized menu screens refer to ╚═▷ “4.1.5 Specialized Menu
Screens”
The "status message" section (╚═▷ Fig. 80/2) of the screen shows the actual operating
information.
For a list of all operation states refer to ╚═▷ “9.5.1 Status messages”.
The "alarm message" section (╚═▷ Fig. 80/3) of the screen shows the last alarm message
that is occurred and not yet acknowledged.
For a list of all alarm messages refer to ╚═▷ “9.5.5 Alarm Messages”.
The single line diagram (╚═▷ Fig. 80/4) shows the current status of the engine and power
circuit breakers.
Softkeys »5«
The softkeys (╚═▷ Fig. 80/5) permit navigation between screens, levels and functions as
well as configuration and operation.
Display Display Mode Next step to display all measured (delta/wye) voltages one
after the other.
Code req. Request a blink code for one error message from the ECU.
Status symbols
Main Screen Voltage Display Mode The index of the symbol indicates whether delta or wye
voltage is displayed and which phases are displayed.
Single Line Rotating Field CW Generator, mains or busbar rotating field moves clockwise.
Diagram
Rotating Field CCW Generator, mains or busbar rotating field moves counter-
clockwise.
Monitoring Enabled Indicates that the engine delayed monitoring has expired
and the monitoring functions are enabled.
Alarm List Alarm Condition Present Indicates that corresponding alarm condition is still present.
Alarm class A/B/C/D/E/F Symbol with "!" indicates that an alarm of class A/B/C/D/E/F
present is present.
Alarm class A/B/C/D/E/F not Symbol without "!" indicates that an alarm of class
present A/B/C/D/E/F is not present.
Synchroscope Phase Angle Indicates the actual phase angle between busbar and
mains or busbar and generator.
The following chapters list notes related to the specific menu screens.
For information on standard softkeys and status symbols refer to ╚═▷ “4.1.1 Basic
Navigation”.
General notes
• The “Home” button is a one-click way back to the overview starting point: the HOME
page / HOME screen
• The “Home Screen” offers display alternatives via parameter ╚═▷ 4103» Home
screen data«
◦ Generator
◦ Generator/Mains
◦ Generator/Busbar
◦ Generator/Engine
• To display the single line diagram with/without mains is selectable via parameter
╚═▷ 4129 »Oneline diagram with mains«
• Two display brightness levels can be switched by LogicsManager. Can be used for
e.g.:
◦ Saving energy
Display alternatives
The HOME screen allows a number of pre-selectable and softbutton controlled display
variants.
• Generator
◦ Power
◦ Power Factor PF
◦ Frequency
• Generator/Mains
◦ Voltage
◦ Frequency
◦ Current
◦ Power
◦ Power factor
• Generator/Busbar
◦ Voltage
◦ Power
◦ Frequency
• Generator/Engines
Available at HOME page, two softbuttons give one-click access to customer specific
(monitoring) screens.
Full functionality available via ToolKit. HMI allows access to the AnalogManager but not to
the text fields »Description« and »Unit«.
Notes
Value AM 7690, 7695, 7700, ..., 7775 AnalogManager to select parameter for
display. Additionally available via , too.
The following chapters list standard menu screens, where all user input is handled
similarly.
For information on standard softkeys and status symbols refer to ╚═▷ “4.1.1 Basic
Navigation”.
For information on all other menu screens refer to ╚═▷ “4.1.5 Specialized Menu Screens”.
Navigation screens offer access to sub-menu screens via the displayed softkey.
Sub-menu entries are only displayed if the code level needed to access
them is the same/or higher than the displayed code level in the center of the
navigation screen.
1. ▷ Use the following softkeys in a value setting screen to select, change and confirm a
setting.
Softkey Description
Generator Which values are shown in the display and whether they are correct
depends on the measurement type.
Busbar/System Which values are shown in the display and whether they are correct
depends on the measurement type.
Mains Which values are shown in the display and whether they are correct
depends on the measurement type.
Analog inputs/outputs The analog outputs are displayed as a percentage of the selected
hardware range, i.e. 50% of a 0 to 20 mA output refer to 10 mA or
alternatively as absolute values (depending on selected parameters).
Discrete inputs/outputs The configured logic for the discrete input "N.O./N.C." will determine
how the easYgen reacts to the state of the discrete input.
Counters and service For additional information on setting/resetting counters refer to ╚═▷
“4.10 Configure Counters”.
Engine —
Engine (J1939) —
J1939 Status —
Version —
Load diagnostic —
If a softkey appears with a wrench symbol it is possible to reset the peak hold
value(s).
The softkey »Display mode« on the main screen "HOME" changes the type of voltage
display.
The amount of information available from the system depends on how the measuring is
configured in the control unit.
The following tables illustrate what values are available depending on the configured
measurement type:
All alarm messages, which have not been acknowledged and cleared, are displayed. Each
alarm is displayed with the alarm message and the date and time of the alarm occurred
in the format yy-mon-dd hh:mm:ss.ss.
Self-acknowledging alarm messages get a new timestamp when initializing the unit
(switching on).
Symbol/Softkey Description
Symbol without "!" indicates that an alarm of class A/B/C/D/E/F is not present.
Acknowledgment is only possible, if the alarm condition is no longer present. If the Alarm
LED is still flashing (an alarm is present, which has not yet been acknowledged as
'Seen'), this softkey resets the horn and acknowledges the alarm as 'Seen'.
This screen displays system events. A date/time stamp is added to each entry!
Symbol/Softkey Description
4.1.5.4 Sequencing
The sequencing screen shows all gensets participating in load sharing. The operation
mode of each genset as well as the state of its GCB is shown on this screen.
Symbol Description
Sequence is running with respect to the settings e.g., the sequencing timing - see table below:
The remaining time is displayed on the upper right side on the grey bar "Sequencing ...",
see table below:
Sequencing Add-on delay ... s Shows the remaining time until the own Add-on delay:
generator is add-on
IOP ╚═▷ 5764
Sequencing Minimum run Shows the remaining time the own Minimum run time, ╚═▷ 5759
time ... s generator is running at minimum
Sequencing Add-off delay ...s Shows the remaining time until the own Add-off delay:
generator is add-off
The bottom field displays the actual load sharing values. If this device is not participating
in load sharing, "LD start stop Off" is displayed here.
The states of the easYgen devices are displayed. The operation mode of each genset as
well as the state of its GCB is shown on this screen.
Symbol/Softkey Description
Segment number
This screen displays easYgen devices configured differently than the LDSS setting of your
current device.
Symbol Description
This screen displays the diagnostic status (the current communication state of the load
share and system bus) of the accepted easYgen devices. Refer to ╚═▷ “6.2.2.2 Diagnostic
Screens” for details.
The setpoint is displayed on the left and the actual value is displayed on the right half of
the screen.
The source, which is used for setpoint 1 or setpoint 2, is displayed with the respective
AnalogManager function number.
The setpoints may only be adjusted if the respective controller is enabled. Frequency and
voltage may be adjusted within the configured operating limits.
Active power may be adjusted between 0 and the configured load control setpoint
maximum. The power factor may be adjusted between 0.71 leading and 0.71 lagging.
Symbol/Softkey Description
Symbol/Softkey Description
Manual mode and Auto mode do have separate setpoints. The Manual mode setpoints are
temporary and can be set via front panel softkeys only.
Setpoint for ... ... in AUTO mode ... in MANUAL mode ... in TEST mode
Menu path for visualization: [Next page / Setpoints / Setpoints PID 1-3]
The needle indicates the actual phase angle between busbar and generator or mains.
Please take care for compensation settings with parameters ╚═▷ 8825 »Phase angle
compensation GCB« and ╚═▷ 8824 »Phase angle GCB«.
If phase angle compensation ╚═▷ 8825 is active the compensated values are taken for
synchroscope display (and synchronization)!
WARNING!
The 12 o'clock position on the top means 0° and the 6 o'clock position on the bottom
means 180°.
The actual phase angle is indicated on the bottom of the screen. The maximum positive
and negative phase angles are indicated 'green'. The length of the green part changes
according to the parameters.
The frequency and voltage differences are indicated on top of the bargraphs.
Symbol/Softkey Description
This screen displays the conditions of all LogicsManager command variables, which are
located in their respective groups.
Symbol Description
Select the highlighted command variable group and display the state of the
command variables in this group.
Variable is TRUE.
Variable is FALSE.
4.1.5.12 LogicsManager
1. ▷ Configure a logical operation using various command variables, signs, logical operators,
and delay times to achieve the desired logical output.
Symbol/Softkey Description
Help screen
Symbol/Softkey Description
Starts a special TEST mode which allows mains decoupling test independent
from breaker status (even if not mains parallel; GCB open, no rotation of prime
mover/generator).
Stops the TEST mode so mains decoupling is possible if system is mains parallel
only.
Notes:
or
Restricted Access
The function Mains Decoupling Test is available on Code level CL3. Code levels CL0 to
CL2 are intentionally not supported. Refer to ╚═▷ “4.3.4 Enter Password” for details.
The Mains decoupling test opens the selected breaker for mains decoupling (parameter
╚═▷ 3110).
CAUTION!
This function is independent from the breaker status and is active for 1 sec.
As long as the decoupling function is executed the »Execute« button and the warning text
are faded out.
Symbol Description
State is TRUE
State is false
Section Description
Section Assignment
Missing Receive-PDO number: active {x} RPDO {x} is not received at the moment
Missing Receive-PDO number: latched {x} RPDO {x} has not been received
Notes
Symbol Description
State is TRUE
State is false
Section Description
RPDO has incorrect mapping parameters / (The mapping is done automatically by the parameter ╚═▷ 15320
“Select external terminals”)
TPDO has more than 8 bytes
Text “4IKD_1.1_27347.seq” This example indicates the name of the current selected file for
the external terminals inclusive version.
Notes
Text “CANopen sequencer file error” 0000000 If the value indicated here is not equal “0000000” there is
something wrong with the file indicated above.
Section Assignment
Missing Node-ID number: active {x} Node {x} is not received at the moment
Missing Node-ID number: latched {x} Node {x} has not been received
Notes
J1939 state
Section Description
Text “J1939 sequencer file error” 0000000 If the value indicated here is not equal “0000000” there is
something wrong with the file indicated below.
Text “Standard_1.1_27347.ecu” This example indicates the name of the current selected file for
ECU inclusive version.
Notes
Current Ethernet state is displayed. Setting can be found under [Next Page / Diagnostic /
Interfaces / Ethernet].
• »Ethernet A«
• »SNTP«
• »Servlink«
• »Modbus TCP/IP«
4.1.5.18 USB
Current USB state is displayed. Setting can be found under [Next Page / Diagnostic /
Interfaces / USB].
4.1.5.19 RS-485
Current RS-485 interface state is displayed. Setting can be found under [Next Page /
Diagnostic / Interfaces / RS485].
The status of the configured J1939 ECU error messages is displayed here if the unit is
configured accordingly. Some ECUs have a special screen for proprietary features. ╚═▷
Chapter 4.1.5.20 shows the special screen for Scania S6.
The following softkeys are only visible if parameter ╚═▷ 15127 is configured to "ON".
Symbol/Softkey Description
Request a blink code for one error message from the ECU.
Scania S6: Reset the blink code. To do this, disable the ignition (terminal U15),
press this softkey, and enable the ignition again within 2 seconds.
SPN Description
1081: Eng. wait to start Engine Wait to Start Lamp: Lamp signal which indicates that the engine is too
lamp cold to start and the operator should wait until the signal becomes inactive
(turns off).
Values:
• Off
• On
• Missing
3697: DPF Lamp Diesel Particulate Filter Lamp Command: Command to control the diesel
particulate filter lamp.
Values:
• Off
• On solid
• On fast blink
• Missing
3698: Exh. Gas Command to control the exhaust system high temperature lamp: This lamp
temp.lamp indicates that the exhaust system temperature is high.
SPN Description
Values:
• Off
• On solid
• Missing
3699: DPF Passive Diesel Particulate Filter Passive Regeneration Status: Indicates the state of diesel
regen. state particulate filter passive regeneration.
Values:
• Not active
• Active
• Missing
3700: DPF Active regen. Diesel Particulate Filter Active Regeneration Status: Indicates the state of diesel
status particulate filter active regeneration.
Values:
• Not active
• Active
• Missing
3701: DPF Regeneration Diesel Particulate Filter Status: Indicates the state of the diesel particulate filter
needed regeneration need and urgency.
Values:
• No (not needed)
• Lowest level
• Moderate level
• Highest level
• Missing
3702: DPF Diesel Particulate Filter Active Regeneration Inhibited Status: Indicates the state
Act.regen.inhibit of diesel particulate filter active regeneration inhibition.
Values:
• Not inhibited
• Inhibited
• Missing
This screen element (on main screen) displays time indications according to the operating
condition of the easYgen device. The time indications of the events indicated in the table
below are shown in the display. The counter starts with the setting value of the related
event and counts down to zero. After that, the status change of another event is shown.
The sequence of the events is related on the configuration of the device.
Event Description
Crank protect Refer to parameter ╚═▷ 3326 for details (only half of the configured time is
used).
NOTICE!
wset file properties changed. easYgen-XT wset files are different from wset files of
easYgen Series.
• wset Settings files created with easYgen must be converted before use with
easYgen-XT!
• NEW ... .wset files are NOT BACKWARD COMPATIBLE!
• Please ask your Woodward sales support contact for conversion/update instruction
to use files created with easYgen.
• Configure language/clock
• Password
• Configure HMI
◦ Configure display
◦ Screen configuration
General notes
The following parameters are used to set the unit language, the current date and time,
and the daylight saving time feature.
If a custom language is configured, the enumeration text in Toolkit displays "Reserve 1".
In the easYgen HMI, the enumeration text is the name of the current custom language.
If the language is set to "Reserve1" without a loaded custom language, the language of
the HMI will be set to English.
Update Clock
• HMI/displays the actual value and enables direct change of each parameter
• ToolKit displays the »Actual values« (ID 1690 to 1695) beside and the time values
and date values can be prepared each as a set before transfer
[Default]
1700 Language 0 selectable languages The desired language for the unit
display text is configured here.
(Set language) [English]
Available languages are: English,
German, Dutch, Spanish, French,
Italian, Portugese, Japanese,
Chinese, Russian, Turkish, Polish,
Slovakian, Finnish, Swedish,
Reserve 1.
»Values to be set«
Example
[Default]
1698 Transfer time to clock 2 Yes Yes transfers the time values to
the clock.
[No]
Notes
• 0 = Year 2000
• 99 = Year 2099
1699 Transfer data to clock 2 Yes Yes transfers the date values to
the clock.
[No]
Notes
[Default]
Notes
Example
Notes
4598 DST begin weekday 2 Sunday to Saturday The weekday for the DST begin
date is configured here
[Sunday]
Notes
[Default]
Notes
4593 DST begin month 2 1 to 12 The month for the DST begin date
is configured here.
[1]
Example
Notes
4597 DST end time 2 0 to 23 The real-time clock will fall back
by one hour when this time is
[0] reached on the DST end date
Example
Notes
[Default]
4599 DST end weekday 2 Sunday to Saturday The weekday for the DST end date
is configured here
[Sunday]
Notes
Notes
4596 DST end month 2 1 to 12 The month for the DST begin date
is configured here.
[1]
Example
Notes
Example
If daylight saving time starts at 2:00 am on the 2nd Sunday in March and ends at 2:00 am
on the 1st Sunday in November, the unit has to be configured like shown in ╚═▷ Tab. 38
to enable an automatic change to daylight saving time and back to standard time.
ID Parameter Setting
Year DST Begins 2 a.m. DST Ends 2 a.m. DST Begins 1 a.m. DST Ends 1 a.m.
(Second Sunday in (First Sunday in UTC=GMT (Last UTC=GMT (Last
March) November) Sunday in March) Sunday in October)
2008 March 9, 2008 November 2, 2008 March 30, 2008 October 26, 2008
2009 March 8, 2009 November 1, 2009 March 29, 2009 October 25, 2009
2010 March 14, 2010 November 7, 2008 March 28, 2010 October 31, 2010
easYgen-3000XT comes with two fully customizable screens - just one click (one
level) from home screen. Softbutton text and displayed name, values, and units can be
defined/selected. The new full-featured AnalogManager 1:1 parameter monitoring but
even math. function computing.
The (configurable) names of the customer screens are displayed at home page as
softbutton text. Pressing one of this softbuttons opens the screen with the configured
Names, Values, and Units.
Numbering convention
[Default]
[Unit] Notes
Notes
7690 AM Customer screen 2 Determined by AnalogManager For details see ╚═▷ Fig. 199.
1.1 90.01
[Default]
Setting range
ID Parameter CL Description
[Default]
Display Configuration
[Default]
4557 Key activation time 2 1 to 999 min If no soft key has been pressed for
the time configured here, the 2nd
[120 min] display brightness will be used.
Notes
[Default]
7794 Enable 2nd display 2 Determined by LogicsManager Once the conditions of the
brightness 86.33 LogicsManager have been fulfilled,
the brightness level of the display
[(04.64 NOT& 1) & 1] switches to the 2nd brightness
level defined by parameter ╚═▷
= 11971 7796.
7799 Enable front (panel) 2 Determined by LogicsManager If this parameter is TRUE and
heater 86.34 ambient temperature goes below
-10° C, the display (front panel)
[(1 & 1) & 1] will be heated for seven minutes
(and wait further 3minutes).
= 11972
For information on the
LogicsManager and its default
settings see ╚═▷ “4.8 Configure
LogicsManager”╚═▷ “9.3.1
LogicsManager Overview”.
Notes
12978 Lock keypad 2 Determined by LogicsManager Key pad can be locked remotely.
86.30
This parameter is intentionally not
[(0 & 1) & 1] available via HMI/display.
= 11924
For information on the
LogicsManager and its default
settings see ╚═▷ “4.8 Configure
LogicsManager”╚═▷ “9.3.1
LogicsManager Overview”.
Screen Configuration
[Default]
Notes
General notes
The home screen data configuration "Generator/Engine" offers an engine value indication.
With the following AnalogManagers the according sources can be configured and scaled.
[Default]
8897 AM Engine fuel level 2 Determined by AnalogManager With this AnalogManager the
81.27 according fuel level source can be
configured and scaled. The
[A1 = 06.03 Analog input 3] indication is displayed in the
format 000.0% .
All lights on the controller may be tested for correct operation with this function.
Lamp test is available via HMI/display, ToolKit, and parameter 10773 with logical
command variable 04.61.
General notes
Password protection covers direct and remote access through all methods and interfaces
of interconnectivity of the device.
Personal security
Configure password security before handing over the device to the customer!
Note your password on a secure location. The next higher password level (2 and 4)
allows to reset the password of the level below (1 and 3).
To restore the according User Name Account needs support from Woodward (authorized
partner).
The following table and drawing provide an overview about the possible access channels
to the easYgen-XT.
Remote Panel with the Woodward screen share concept connected over Ethernet (HMI ③=①
simulation)
3rd party Remote Panel (i.e. Proface, Sütron, ...) running Modbus TCP ④
Netbiter® Easy Connect gateway running Servlink TCP (ToolKit via internet) ⑤
The according password handling for each of this access is defined afterwards.
Two login procedures cover all access channel variants: The ...
The currently selected entry number is visible only - all other numbers are hidden and a
"*" asterisk is displayed instead.
The Basic Code Entry asks for four numbers to open the related password level. It starts
with the default value of parameter ╚═▷ 10416 »Random number for password«.
The User Account Entry comes with more security as requested for internet access. It
asks for »Username:« and »Password:« ("Alphanumeric Password"). To open the related
password level, both rows entries need the correct alphanumeric strings.
The already existing User names cannot be changed. They are fixed for the desired code
level, which shall be entered.
View hidden password entry by pushing the symbol on the right side of
the »Password:« box.
A code level always belongs to an access channel. Each access channel has its own
password level. This password level can be different to others (other channels) at the
same time.
The access related code level is available and visible beside the access related interface
settings.
Please check: LogicsManager 86.30 Parameter ╚═▷ 12978 "Lock keypad 1" = TRUE?
Access Channels
Maximum Security
Each of these channels have their own independent access level. That has the advantage
that e.g. a HMI channel password level opens not automatically the access rights for the
other channels.
Maximum Flexibility
The device offers the capability to disable the password protection for the individual
interface communication channels RS485, Ethernet and CAN 1. If the password level is
disabled the access level is set on code level 5.
CAN1 CANopen
CAN2
This chapter defines the properties of the single password code levels. The device
differentiates several password levels. Generally with a higher reached password level the
access rights increases.
Code Level 0
The Level 0 means there are no access rights enabled. All configurations are blocked.
• General:
This level releases the access to a limited number of parameters and configurations
In this and higher levels the password for the Basic Code Level CL01 can be changed
This level is selected with the User Name CL01 and the according password can only
be changed being in code level CL01.
Being in code level AC02 or higher the password of the Basic Level CL01 can be
reset to its default by the Yes/No parameter ╚═▷ 10434.
• General:
The access is dismissed automatically (see ╚═▷ “Automatic Logout from Password
level (Fall into level 0)”).
In this and higher Levels, the password for the Basic Code Level CL01 can be
changed.
This level is selected with the User Name AC02 and the according algorithm for the
password can only be changed being in the Commissioning code level CL03.
Being in code level AC02 or higher the password of the Basic Level CL01 can be
reset to its default by the Yes/No parameter ╚═▷ 10434.
(fix)
The operator connects ToolKit with the The operator navigates on the
device and closes the upcoming easYgen-XT HMI or on RP-3000XT to
security login window without the screen[Parameter / Password /
entering username and password Password display].
(Code level 0). The operator navigates
with ToolKit to the page [Parameter / The operator reads the indicated
Configure system management]. random number. He tells it to a higher
instance.
The operator reads on that page ╚═▷
10416 »Random number for The higher instance calculates:
password«. He tells it to a higher (10414 »Code temp.
instance. commissioning« + 10416 »Random
Number«) x 3.
The higher instance calculates:
(10414 »Code temp. The higher instance takes the lower
commissioning« + 10416 »Random four digits of the result and tells it the
Number«) x 3. operator. The operator enters the
result as password into the control.
The higher instance takes the lower
four digits of the result and puts the
according algorithm string
10437 »Alphanumeric code temp.
comm.« as prefix in front.
• General:
In this Level, the operator has access to all parameters and configurations, which are
usually needed on a commissioning level
In this and higher levels the password for the Commissioning Level CL03 can be
changed
This level is selected with the User name CL03 and the according password can only
be changed being in the Commissioning Level CL03
Being in code level AC04 or higher the password of the Commissioning Level CL03
can be reset to its default by the Yes/No parameter ID ╚═▷ 10435
• General:
This Level allows temporary access to nearly all parameters and configurations,
except calibration and super user items.
In this and higher levels the passwords for the Commissioning Level CL04 can be
changed
This level is selected with the User name AC03 and the according algorithm for the
password can only be changed being in the Super Commissioning Level CL05
Being in code level AC04 or higher the password of the Commissioning Level CL03
can be reset to its default by the Yes/No parameter ID ╚═▷ 10435
• General:
In this Level, the operator has access to nearly all parameters and configurations,
except calibration items
In this and higher Levels the password fro the Super Commissioning Level CL05 can
be changed
This level is selected with the User name CL05 and the according password can only
be changed being in the Super Commissioning Level CL05
Being in a higher level as CL05 the password of the Super Commissioning Level CL05
can be reset to its default by the Yes/No parameter ID ╚═▷ 10436
If you have forgotten your password for the Super Commissioning Level, please contact
Woodward or a representative for help.
What forces the Logout from Password levels (Fall into level 0)
All basic code entry channels with »0« as password or a wrong password
• The maximum length of the alpha numeric prefix (ID ╚═▷ 10437; ╚═▷ 10438) is 6
characters
Each time a password is entered, the random number is calculated at new. This
guarantees max. security.
The easYgen HMI password level shall be visible in the parameter menu screens.
A dynamic key symbol is visible and displays the currently entered code level number
inside:
In case of a password level time out during configuration over HMI, the HMI display
switches back to the main screen.
The ToolKit supports the User Account entry and in case of CANopen connection the Basic
Code entry.
Ethernet Connection: The ToolKit password level is visible in the menu [STATUS MENU /
Diagnostic / Interfaces / Ethernet / Servlink]. Refer to your IP-address (PC).
USB Connection: The ToolKit password level is visible in the menu [STATUS MENU /
Diagnostic / Interfaces / USB].
CAN Connection: The ToolKit password level is visible in the menu [STATUS MENU /
Diagnostic / Interfaces / CAN / CANx].
The easYgen must be a member of an Ethernet network and both user name and
password have to be transferred (from PLC) to the device.
The easYgen must be a member of a RS-485 network and the password has to be
transferred (from PLC) to the device.
With factory settings the password is expected to be "500" for code level 5.
The easYgen must be a member of a CANopen network and the password has to be
transferred (from PLC) to the device.
The easYgen provides several CAN ports and therefore each port has his own password
level. The password is written by a SDO Communication Channel.
With factory settings the password is expected to be "500" for code level 5.
The following table shows exemplary send data for the device on the CANopen bus.
Identifier Description Data (hex)
The following table shows exemplary send data for the device on the CANopen bus.
Identifier Description Data (hex)
The current code level is indicated by the lock symbol in the configuration menu screens.
The lock symbol indicates the number of the code level and appears as "locked" (in code
level CL00) or "unlocked" (in higher code levels).
Symbol Status
Locked
[Default]
10400 Password display 0 0000 to 9999 The password for configuring the
control via the front panel must be
[random number] entered here.
10405 Code level display 0 (display only) This value displays the code level
which is currently enabled for
[0] access via the front panel display
or the Woodward Remote Panel
with screen share mode.
The password and/or User name for access via interface cannot be entered via HMI.
[Default]
10402 Password for CAN 0 0000 to 9999 The password for configuring the
interface 1 control via the CAN interface #1
[random number] must be entered here.
10407 Code level CAN 0 [0] This value displays the code level
interface 1 which is currently enabled for
access via the CAN interface #1.
10432 Password for CAN 0 0000 to 9999 The password for configuring the
interface 2 control via the CAN interface #2
[random number] must be entered here.
10422 Code level CAN 0 [0] This value displays the code level,
interface 2 which is currently enabled for
access via the CAN interface #2.
7486 Code level for USB 0 [0] This value displays the code level,
which is currently enabled for
access via the USB interface.
10430 Password for serial 0 0000 to 9999 The password for configuring the
interface control via the RS485 interface
[random number] must be entered here.
10420 Code level for RS485 0 [0] This value displays the code level,
which is currently enabled for
access via the RS485 interface.
7490 User name Modbus 0 The user name for configuring the
TCP control via the Modbus TCP/IP
interface must be entered here.
7491 Password Modbus 0 0000 to 9999 The password for configuring the
TCP/IP control via the Modbus TCP/IP
[random number] interface must be entered here.
10427 Code level Modbus 0 [0] This value displays the code level,
TCP/IP which is currently enabled for
access via the Modbus TCP/IP
interface.
7824 Code level Servlink 0 [0] This value displays the code level,
Master 1 which is currently enabled for
access as Servlink Master 1.
7825 Code level Servlink 0 [0] This value displays the code level,
Master 2 which is currently enabled for
access as Servlink Master 2.
7826 Code level Servlink 0 [0] This value displays the code level,
Master 3 which is currently enabled for
access as Servlink Master 3.
7827 Code level Servlink 0 [0] This value displays the code level,
Master 4 which is currently enabled for
access as Servlink Master 4.
7828 Code level Servlink 0 [0] This value displays the code level,
Master 5 which is currently enabled for
access as Servlink Master 5.
7829 Code level Servlink 0 [0] This value displays the code level,
Master 6 which is currently enabled for
access as Servlink Master 6.
7830 Code level Servlink 0 [0] This value displays the code level,
Master 7 which is currently enabled for
access as Servlink Master 7.
7831 Code level Servlink 0 [0] This value displays the code level,
Master 8 which is currently enabled for
access as Servlink Master 8.
General notes
Each individual password can be used to access the appropriate configuration level
through multiple access methods and communication protocols (via the front panel, via
serial RS-485 interface, and via the CAN bus).
[Default]
10415 Password Basic 1 1 to 9999 The password for the code level
"Basic" is defined in this
[-] parameter.
10412 Code temp. super 5 1 to 9999 The algorithm for calculating the
commissioning password for the code level
[400] "Temporary Super commissioning"
is defined in this parameter.
10411 Password super 5 1 to 9999 The password for the code level
commissioning "Super commissioning" is defined
[500] in this parameter.
10438 Alphan. code temp. 5 (up tp 6 characters) Alphanumeric code for temporary
super comm. super commissioning level
[xk38]
This is the alphanumeric algorithm
value for the formula to reach the
temporary commissioning code
level (Level 04), entered as string
here.
[Default]
10416 Random number for [(random four letters Random number generated by the
password number)] easYgen-XT device. Needed to get
an alphanumeric password by
Woodward support.
[Default]
10439 Old password basic level 1 ((empty)) Enter here your old alphanumeric
password to release the password
change for the basic code level
(CL01)
10440 New password basic 1 ((empty)) Enter here your new alphanumeric
level password string for the basic code
level (CL01)
Notes
10434 Reset password basic 2 Yes The control resets the password of
level the basic level to "CL0001".
[No]
10444 Old password commiss. 3 ((empty)) Enter here your old alphanumeric
level password to release the password
change for the commissioning
code level (CL03)
10445 New password commiss. 3 ((empty)) Enter here your new alphanumeric
level password string for the
commissioning code level (CL03)
Notes
[Default]
[No]
10449 Old passw. super comm. 5 ((empty)) Enter here your old alphanumeric
level password to release the password
change for the super comm. code
level (CL05)
10450 New passw. super 5 ((empty)) Enter here your new alphanumeric
comm. level password string for the super
comm. code level (CL05)
Notes
10436 Reset passw. super 11 Yes The control resets the password of
comm. level the commissioning level to
"CL0005" e.g., if you forgot your
password.
Notes
[Default]
[No]
CAUTION!
Don't initiate »Set factory default settings« during controlling a genset! This
causes easYgen rebooting.
Parameter ╚═▷ 1701 »Set factory default values« causes a reboot of the control. During
this time the genset system is not controlled by the easYgen! An uncontrolled operation
can lead into life-threatening hazard or damage.
After settings changed: Please wait 30 seconds to be sure changes are saved before
power cycling the device.
[Default]
Notes
Notes
up to 38 characters but
varies on font
Note
1701 Set factory default 4 Yes All parameters, with the exception
values of customer defined passwords,
will be restored to factory default
values. If the default setting is
initiated the alarm LED starts
twinkling with a higher rate (ca. 5
Hz).
Notes
Notes
The reboot of the device can be initiated by operating a Yes/No switch in ToolKit. This is
beneficial because some parameters, like
Please be careful with this setting because the device goes off and reboots at new with
all its consequences. It's the same like power off/on cycle.
• Modbus protocol
• CANOpen
• J1939
General notes
If the remote panel interacts with an easYgen, different use cases could be desired. So
the remote panel runs usually without any restrictions, if it is connected with an
easYgen-3100XT or easYgen-3400XT. This mode is called Full Access Mode.
But if the remote panel runs with an easYgen-3200XT or easYgen-3500XT, it is not always
allowed that both HMI have full control access rights to the genset. Here it is desired to
either restrict the control rights for the remote panel (Annunciator Mode) or for the local
HMI (Local Keylock). And finally it will be desired to switch off the remote panel
completely.
To maintain the different operating modes in the remote panel the easYgen has to
determine with LogicsManagers in which operation mode the Remote Panel RP-3000XT
shall run. If no LogicsManager is true, full mode with password suppression is active.
Following operation modes are defined (in order of the LogicsManager priority):
Fig. 128: Remote Panel with display (plastic housing) variant of easYgen-XT
The password suppressed Full Mode becomes active, if there is no mode selected via
LogicsManager.
• Button BACK on the upper right is still active (leave password screen)
Fig. 130: Remote Panel with non-display (metal housing) variant of easYgen-XT
AND
AND
The RP-3000XT shows measurement, condition, and alarm data of the easYgen-3000XT.
Data in regards to configuration and parameter are faded out and a "disabled" screen
(crossed out ╚═▷ Fig. 133) is displayed instead.
• All Operating Mode buttons are not visible, but the current operation is indicated
• The MAN Start/Stop buttons and the breaker soft key buttons are not indicated
• The Configuration capability is deactivated (according soft key buttons are not
indicated or not active)
• All configuration screens of the easYgen are suppressed in the RP-3000XT (disabled
screen)
AND
Priority of RP Modes
»RP Off mode« higher than »RP Annunciator« higher than »RP Full mode«.
[Default]
= 11994
= 11995
[Default]
= 11996
[Default]
Stop sequence
Start/stop diagram
Stop sequence
Start/stop diagram
CAUTION
It is imperative to connect an
emergency stop circuit to discrete
input DI 1 to be able to perform an
emergency stop by disabling the
ignition in case the gas valve fails
to close.
Notes
Notes
Notes
Notes
3310 Ignition delay [tID] 2 0 to 9999 s With gas engines often a purging
operation is desired before
(Gas Engine only) [5 s] starting.
3311 Gas valve delay [tGD] 2 1 to 999 s By energizing the ignition relay
the gas valve delay is started
(Gas Engine only) [5 s] ("Ignition" is displayed).
3312 Minimum speed for 2 10 to 1,800 rpm After expiration of the ignition
ignition delay the number of revolutions
[100 rpm] set here must be reached, so the
(Gas Engine only) "Ignition" relay will be energized.
Speed States
Firing speed and the speed detection is now managed by LogicsManager equations
named “Firing speed detection” and “Speed detection”. The default setting of them is
backward compatible!
The possibility to arrange different sources to determine speed and firing speed comes
with more flexibility. Woodward recommends to spend some time to understand the
parameters and dependencies listed below or on ToolKit page [Parameter / Configuration /
Configure application / Configure engine / Configure start/stop].
The “Firing Speed” detection is a basic function of the easYgen genset controls. This
information influences a lot of functions and therefore is to configure very carefully!
With the firing speed detection the device recognizes e.g. the engine as successfully
started, removes the starter immediately and triggers the timer »Monitoring delay
time« for engine speed relevant monitoring. The firing speed can be detected out of
different sources.
In comparison to the easYgen-3000 first generation, the firing speed is generated through
a LogicsManager equation always and allows all speed source combinations. By default
this LogicsManager is configured backward compatible: easYgen-XT behaves like the first
generation easYgen-3000.
Speed detection
With the “Speed” detection the device recognizes e.g. the engine as turning or as
successful stopped. The speed can be detected out of different sources.
The easYgen provides two LogicsManager command variables (LMCV) for detecting
speed:
The rpm measurement allows lower firing speed limits. With a speed sensor the firing
speed can be configured down to 5 Hz.
Configuration A)
• Firing speed: 5 Hz
• Rated speed: 1800 rpm
Rated frequency: 60 Hz
Calculation
• Firing speed [rpm] = (Firing speed [Hz] * Rated speed [rpm]) / Rated frequency [Hz]
• Firing speed [rpm] = 5 Hz * 1800 rpm / 60 Hz = 150 rpm
Configuration B
• Firing speed: 5 Hz
• Rated speed: 1500 rpm
Rated frequency:50 Hz
Calculation
• Firing speed [rpm] = (Firing speed [Hz] * Rated speed [rpm]) / Rated frequency [Hz]
• Firing speed [rpm] = 5 Hz * 1500 rpm / 50 Hz = 150 rpm
Usually both command variables 02.34 and 02.35 are entered in the LogicsManager
equation for detecting firing speed.
The result of the LM »Firing speed detection« goes directly into the start / stop logic and
other functions of the easYgen. Through the LogicsManager approach other sources can
be taken into account.
The rpm measurement allows lower speed limits. With a speed sensor the speed can be
configured down to 5 Hz.
Usually both command variables 02.36 and 02.37 are entered in the LogicsManager
equation for detecting speed.
The result of the LM »Speed detection« goes directly into the start / stop logic and other
functions of the easYgen. Through the LogicsManager approach other sources can be
taken into account.
When the firing speed is reached, the starter is disengaged under one of the following
conditions:
Auxiliary operations
The auxiliary operations start, as soon as the engine is to be started or a running engine
is detected.
At the same time, the discrete output for the auxiliary services (LogicsManager 03.01) will
be enabled. This discrete output remains enabled as long as speed is detected or if the
controller is in the MANUAL mode.
[Default]
3307 Start pause time [tSP] 2 1 to 99 s This is the delay time between the
individual starting attempts.
[7 s]
This time is also used to protect
the starter relay. The message
"Start - Pause" is displayed.
Notes
Notes
Notes
Notes
CAUTION
3301 Auxiliary services 2 0 to 9999 s After each engine stop (the engine
postrun [tPOST] stop timer has expired), the
[0 s] discrete output for the auxiliary
(Coasting auxiliary services postrun (LogicsManager
operation (post 03.31) remains energized for an
operation)) adjustable time (i.e. operate a
cooling pump).
= 11458
Notes
12970 MAN engine start 2 Determined by LogicsManager With the rising edge of this
87.50 LogicsManager equation an
engine start command in
[(0 & 1) &1] operating mode MANUAL is
initiated. The state TRUE of this
= 11439 LM inhibits the start command in
MANUAL.
12971 MAN engine stop 2 Determined by LogicsManager With the rising edge of this
87.59 LogicsManager equation an
engine stop command in
[(0 & 1) &1] operating mode MANUAL is
initiated. The state TRUE of this
=11448 LM inhibits the start command in
MANUAL.
= 11459
This LogicsManager equation (ID = 12999 with logical command variable 11459) enables
or blocks all monitoring functions, which are speed related by enabled setting: “Delayed
by engine speed”:
• Under/Over frequency
• Under speed
• Under voltage
• ...
In the default setting of the easYgen the engine start/stop is executed by the easYgen
directly. So the engine monitoring is released, if the control energizes the solenoid valve
(Start/Gas 11657) and the firing speed is reached. In the moment the easYgen removes
the solenoid valve the monitoring is disabled. This avoids wrong alarms during the engine
stopping procedure.
In cases the start/stop of the drive is executed from outside, the command variable 03.28
Start/Gas (11657) is replaced by a command from outside i.e. any discrete input (09.XX).
With starting the drive the operator gives the command for monitoring. With stopping the
drive the command has to be removed to avoid wrong alarms during the engine stopping
procedure.
The delayed engine monitoring can be seen with the upcoming “Eye” symbol in the
single line diagram.
To configure the MPU input, the number of teeth on the flywheel detected by the
magnetic pick up (MPU) or the number of pickup pulses per revolution of the engine must
be configured.
The table below shows the speed measuring range for various flywheel teeth numbers
(parameter ╚═▷ 1602) and rated speeds (parameter ╚═▷ 1601) for a minimum signal
voltage of 2 Vrms.
Fly wheel teeth Rated speed [rpm] Speed measuring range [rpm]
Fly wheel teeth Rated speed [rpm] Speed measuring range [rpm]
Fly wheel teeth Rated speed [rpm] Speed measuring range [rpm]
[Default]
15155 Engine speed source 2 [Internal] The internal MPU input is used as
engine speed source.
General notes
This function allows for a controlled operation of an engine without alarm messages at a
lower speed (below the configured underspeed monitoring values) for e.g. a warm-up
operation with low emission.
The frequency controller output does not control the idle speed; it will remain in initial
state position. The GCB cannot be closed in idle mode.
A message may be output to a relay here using the LogicsManager (Idle mode is active,
command variable 04.15), e.g. as a signal for a speed controller. The display indicates
"Idle run active" during idle mode.
The idle mode can be only used if the function is supported by the ECU or the frequency
controller.
The normal operation monitoring limits will be enabled again, if one of the following
conditions is fulfilled:
• Idle mode has ended and generator frequency has reached rated frequency -1 Hz.
(e.g. 49 Hz at 50 Hz rated)
• Idle mode has ended and engine delayed monitoring (parameter ╚═▷ 3315) has
expired.
The flexible limits 33 through 40 are disabled during idle mode operation (╚═▷ “4.5.5
Flexible Limits”).
[Default]
12570 Auto idle mode 2 Determined by LogicsManager Once the conditions of the
86.20 LogicsManager have been fulfilled
the engine will be operated in idle
[(0 & 1) ≥1 0] mode automatically for the
configured time during start-up.
= 15719 Monitoring is limited as described
above.
Notes
12550 Constant idle run 2 Determined by LogicsManager As long as the conditions of the
86.14 LogicsManager have been fulfilled
(Continuous idle mode) the engine will be continuously
[(0 & 1) & 0] operated in idle mode. Monitoring
is limited as described above. A
= 10713 key switch via a DI may be
configured here for example.
Notes
3328 Automatic idle time 2 1 to 9999 s The automatic idle mode is active
for the time configured here.
(Time for automatic idle [30 s] Monitoring is limited as described
mode) above during this time.
• Programmable
◦ The discrete input has been assigned a default function using either the
LogicsManager or preconfigured alarms such as "emergency stop".
• Fixed
◦ The discrete input has a specific function that cannot be changed depending
upon the configured application mode.
Discrete input [DI Programmable This discrete input is configured as alarm class F and is
01] not delayed by the engine speed.
Preconfigured to "Emergency STOP"
• Energized
• De-energized
Discrete input [DI Programmable This discrete input is configured as alarm class B and is
03] delayed by the engine speed.
Preconfigured to "Low oil pressure"
Discrete input [DI Programmable This discrete input is configured as alarm class B and is
04] not delayed by the engine speed.
Discrete input [DI Programmable This discrete input is used as a remote acknowledgment
05] for alarms. The input is normally de-energized. When an
Preconfigured to "External alarm is to be acknowledged the input is energized. The
acknowledgment" first time an alarm in acknowledged, the centralized
alarm/horn is silenced. When the input is energized a
second time, all alarms, which are no longer active, will
be acknowledged.
Discrete input [DI Programmable Only applicable for application mode A04
06]
Preconfigured to "Release MCB" This discrete input is configured as a Control input in the
alarm class and is not delayed by the engine speed.
• Energized
• De-energized
Discrete input [DI Fixed to "MCB open reply" Only applicable for application mode A04
07]
This input implements negative function logic.
Discrete input [DI Fixed to "GCB open reply" Only applicable for application modes A03 and A04
08]
This input implements negative function logic.
Discrete input [DI Programmable Can be set-up with description, delay, operation, alarm
09] class, self acknowledgment, and enable.
"Discrete Input 9
The genset control usually decides whether it performs voltage and frequency (V/f)
control or power and power factor (P/PF) control using the reply of the circuit breakers,
i.e. the discrete inputs DI 7 and DI 8.
Alarm inputs
All discrete inputs, which are not assigned to a function, can be used as alarm or control
inputs. These discrete inputs can be freely configured as such (╚═▷ “4.4.2.2 Discrete
Inputs”).
• Programmable
◦ The discrete output has been assigned a default function using the
LogicsManager.
◦ The following text describes how these functions are assigned using the
LogicsManager.
• Fixed
◦ The discrete output has a specific function that cannot be changed depending
upon the configured application mode.
For information on the function of the discrete outputs depending on the configured
application mode refer to ╚═▷ “4.4.2.3 Discrete Outputs (LogicsManager)”.
CAUTION!
The discrete output "Ready for operation" must be wired in series with an emergency
stop function.
This means that it must be ensured that the generator circuit breaker is opened and the
engine is stopped if this discrete output is de-energized.
If the availability of the plant is important, this fault must be signaled independently from
the unit.
CAUTION!
The circuit breaker commands must be checked before every commissioning because the
relays can be used for different applications and can be assigned to various functions.
Relay output [R Programmable This discrete output is used to ensure that the internal
01] functions of the controller are operating properly.
Fixed to "Ready for operation"
It is possible to configure additional events, which cause
CAUTION! Only relay [R 01] has an the contacts of this discrete output to open, using the
inverse logic. The relay opens (all LogicsManager.
other relays close), if the logical
output of the LogicsManager becomes
TRUE.
Relay output [R Programmable When a centralized alarm is issued, this discrete output is
02] enabled.
Preconfigured to "Centralized alarm
(horn)" A horn or a buzzer maybe activated via this discrete output.
Pressing the button with the "✔" symbol will acknowledge
the centralized alarm and disable this discrete output.
Relay output [R Programmable The generator starting circuit is engaged when this discrete
03] output is enabled.
Preconfigured to "Starter"
This discrete output will enable depending on the start
sequence (refer to the start sequence description in ╚═▷
“4.4.1.1 Configure Engine (general)”) to energize the
starter for the configured starter time (parameter ╚═▷
3306).
Gas valve
The gas valve for the engine is energized when this discrete
output is enabled. If the engine is given a stop command or
engine speed drops below the configured firing speed, this
discrete output is disabled immediately.
Ignition
Notes
Relay output [R Fixed to "Command: close GCB" Only applicable for application modes A03 and A04 .
06]
The "Command: close GCB" output issues the signal for the
GCB to close. This relay may be configured as an impulse or
steady output signal depending on parameter ╚═▷ 3414.
Impulse
Steady
Relay output [R Fixed to "Command: open GCB" Not applicable for application mode A01
07]
The parameter ╚═▷ 3403 defines how this relay functions.
Relay output [R Fixed to "Command: close MCB" Only applicable for application mode A04 .
08]
The discrete output "Command: close MCB" is an impulse
output signal.
Relay output [R Fixed to "Command: open MCB" Only applicable for application mode A04 .
09]
The controller enables this discrete output when the MCB is
to be opened for switching operations.
Relay output [R Programmable The auxiliary services output (LogicsManager 03.01) will be
10] enabled with the start command (prior to the engine start
Preconfigured to "Auxiliary services" because of the prerun time) and remains enabled as long
as the engine is running.
Relay output [R Programmable This discrete output is enabled when a warning alarm (class
11] A or B alarm) is issued (╚═▷ “9.5.4 Alarm Classes”).
Preconfigured to "Warning alarm"
After all warning alarms have been acknowledged, this
discrete output will disable.
Relay output [R Programmable This discrete output is enabled when a shutdown alarm
12] (class C or higher alarm; refer to ╚═▷ “9.5.4 Alarm Classes”
Preconfigured to "Shutdown alarm" for more information) is issued.
General notes
Discrete inputs may be configured to normally open (N.O.) or normally closed (N.C.)
states.
Fig. 146: Discrete inputs - alarm/control inputs - operation logic (state N.O.)
Fig. 147: Discrete inputs - alarm/control inputs - operation logic (state N.C.)
Alarm inputs may also be configured as control inputs and then be used as command
variables in the LogicsManager.
The discrete inputs 1 to 6 are pre-configured to various functions and differ in their
default values. However, they may still be configured freely.
The discrete inputs 7 & 8 are always used for the circuit breaker replies and cannot be
configured.
If a discrete input has been configured with a shut-down alarm that has been enabled to
self-acknowledge, and has been configured as engine delayed the following scenario may
happen:
• The discrete input shuts down the engine because of its alarm class.
• Due to the engine stopping, all engine delayed alarms are ignored.
• The alarm class is acknowledged automatically.
• The alarm will self-acknowledge and clear the fault message that shut the engine
down.
Parameter IDs
The following parameters are used to configure the discrete inputs 1 through 12. The
parameter IDs refer to discrete input 1.
• Refer to ╚═▷ Tab. 45 for the parameter IDs of the parameters DI 2 through
DI 12(23).
DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 DI 9 DI 10 DI 11 DI 12
MCB GCB
open open
only only
Des‐ 1400 1410 1420 1430 1440 1450 1460 1480 1488 1496 1504
crip‐
tion
DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 DI 9 DI 10 DI 11 DI 12
MCB GCB
open open
only only
Delay 1200 1220 1240 1260 1280 1300 1320 1360 1380 1205 1225
Oper‐ 1201 1221 1241 1261 1281 1301 1321 1361 1381 1206 1226
ation
Alarm 1202 1222 1242 1262 1282 1302 1322 1362 1382 1207 1227
class
Self 1204 1224 1244 1264 1284 1304 1324 1364 1384 1209 1229
ack‐
now‐
ledg‐
ed
Enabled 1203 1223 1243 1263 1283 1303 1323 1363 1383 1208 1228
[Default]
Notes
Notes
For information on the LogicsManager and its default settings see ╚═▷ “9.3.1
LogicsManager Overview”.
Some outputs are assigned a function according to the application mode (see following
table).
No. Terminal None A01 GCB open A02 GCB A03 GCB/MCB A04
CAUTION! Only relay [R 01] has an inverse logic. The relay opens (all other relays close), if
the logical output of the LogicsManager becomes TRUE.
[R 04] 45/46 LogicsManager; pre-assigned with 'Diesel: Fuel solenoid, Gas: Gas valve'
No. Terminal None A01 GCB open A02 GCB A03 GCB/MCB A04
CAUTION!
The discrete output "Ready for operation" must be wired in series with an emergency
stop function.
This means that it must be ensured that the generator circuit breaker is opened and the
engine is stopped if this discrete output is de-energized.
If the availability of the plant is important, this fault must be signaled independently from
the unit.
[Default]
12580 Ready for op. Off 2 Determined by LogicsManager The "Ready for operation" relay is
99.01 energized by default if the power
(Ready for operation supply exceeds 8 V.
OFF) [(0 & 0) & 1]
Once the conditions of the Logics‐
= 11870 Manager have been fulfilled, the
relay will be de-energized. This
LogicsManager output may be
configured with additional
conditions, which may signal a
PLC an "out of operation"
condition by de-energizing the
relay on terminals 41/42, like
"shutdown alarm" or no "AUTO
mode" present.
Notes
12110 Relay {x} 2 Determined by LogicsManager Once the conditions of the Logics‐
99.02 Manager have been fulfilled, the
(See ID For (pre-defined) relay will be energized.
table function see assignment [(03.05 Horn & 1) & 1]
below) table above) Notes
= 11871
For information on the Logics‐
Manager and its default settings
see ╚═▷ “9.3.1 LogicsManager
Overview”.
Parameter IDs
• Refer to ╚═▷ Tab. 47 for the parameter IDs of the parameters for relay 3 to relay 12.
R1 R2 R3 R4 R5 R6 R7 R8 R9 R 10 R 11 R 12
Parameter ID 12580 12110 12310 12320 12130 12140 12150 12160 12170 12180 12560 12590
The conversions described below are only active for parameters »Unit« of
and
For example:
• Temperature works with the exact string»°C« only but not with »°c« or »degC« or »°
C« ...
• Pressure needs the exact string »bar« only but don't work with »Bar« or »BAR« ... !
AI {x} 1034, 1084, ...; external AI{x} 16208, 16218, ...; PID {x} setpoint 7494, 7495, ...;
customer screens {x.y} 7692, 7697, ...
[Default]
General notes
The characteristic curves of "Table A" and "Table B" (freely configurable over 9 defined
points) are independently configurable and can be used among other predefined curves
for each of the analog inputs. Each point may be scaled to related values measured from
the analog input (0 to 250/500/2500 Ohms, 0 to 10 V, or 0 to 20 mA), so that the actual
display and monitoring reflects the corresponding values (e.g. 200 to 600 kW).
The created characteristic curves can be used for scaling the analog inputs.
The X and Y junction may be moved within the range of values and the space between
setpoints can be nonuniform.
When configuring the X coordinates, ensure the coordinates always increase in scale
continuously.
In the following example the first set of x/y coordinates is correct and the second set of
x/y coordinates is wrong:
(correct)
X-coordinate 0 10 20 40 50 60 80 90 100
wrong:
X-coordinate 0 10 20 60 20 30 80 40 100
If the first X coordinate is >0, all values smaller than the first X value will be output with
the first Y value.
If the last Y value is <100, all higher values will be output with the value of Y9.
All parameters used to configure the characteristic curve follow the samples listed below.
• Refer to ╚═▷ “Parameter IDs and default values for all scaling points” for the
parameter IDs of the individual parameters for all scaling points of tables 'A' and 'B'.
[Default]
3560 to Table {A/B} X-value 2 -900000.000 to 900000.000 The analog input is assigned to a
3568 {1..9} curve. This parameter defines the
[0, ...] actual value assigned to each of
or the nine points along the X-axis of
the total range of the selected
3610 to hardware for analog input.
3618
Example
If a 0 to 20 mA input is configured
and the X1-coordinate = 0, then
the value configured for Y1 is
output for an input of 0 mA.
3550 to Table {A/B} Y-value 2 -21000000.00 to 21000000.00 This parameter defines the Y-
3558 {1..9} coordinate (the displayed and
[0, ...] monitored value) at the
or corresponding X-coordinate.
3600 to Example
3608
If a 0 to 20 mA input is configured
and the X2-coordinate = 10, then
the value configured for the Y2-
coordinate is output for an input
of 10 mA.
Table A - X value 3560 3561 3562 3563 3564 3565 3566 3567 3568
Table A - Y value 3550 3551 3552 3553 3554 3555 3556 3557 3558
Table B - X value 3610 3611 3612 3613 3614 3615 3616 3617 3618
Table B - Y value 3600 3601 3602 3603 3604 3605 3606 3607 3608
General notes
[Default]
1025 Analog input {x}: 2 user-defined (up to 39 characters) The event history will store this
Description text message and it is also
1075 [Analog inp. {x}] displayed on the visualization
screen.
1125
If the programmed limit value of
the analog input has been
reached or exceeded this text is
displayed in the control unit
screen.
Notes
[Default]
Notes
1001 User defined min. 2 -21000000.00 to 21000000.00 The value (y-axis) to be displayed
display value for the minimum of the input
1051 [0] range must be entered here.
(User defined minimum
1101 display value) Notes
1002 User defined max. 2 -21000000.00 to 21000000.00 The value (y-axis) to be displayed
display value for the maximum of the input
1052 [2000] range must be entered here.
(User defined maximum
1102 display value) Notes
[Default]
Example
Notes
Example
Notes
[Default]
Notes
1046 Offset 2 -20.0 to 20.0 Ohms The resistive input (the "0 to 2000
Ohms" analog input) may be
1096 [0.0 Ohm] calculated with a permanent
offset to adjust for inaccuracies.
1146
If the offset feature is utilized, the
value configured in this parameter
[Default]
Notes
Exponent is 3:
1033 Analog input {X} (displayed only) Current scaled value of the AI {X}
Notes
[Default]
• 0 to 20 mA:
Minimum value 2 mA
Undershooting
• 0 to 2000 Ohms:
• 0 to 1 V:
Notes
[Default]
Notes
10113 Filter time constant 2 Off, 1 to 5 A low pass filter may be used to
for reduce the fluctuation of an
10114 analog input reading.
0/4 to 20 mA and 0 to
10116 1V The cut-off-frequency is defined as
usual with 63% (e-1).
[Default]
3632 Bargraph minimum 2 -21000000.00 to 21000000.00 The start value for the bar graph
display of the analog input is
3634 [0] defined here. The value must be
entered according to the display
3636 format, which refers to the analog
input type (parameter ╚═▷ 1000).
3633 Bargraph maximum 2 -21000000.00 to 21000000.00 The end value for the bar graph
display of the analog input is
3635 [2000] defined here. The value must be
entered according to the display
3637 format, which refers to the analog
input type (parameter ╚═▷ 1000).
The analog outputs AO 1 and AO 2 may either be configured as analog or PWM outputs.
The analog outputs are prepared for speed and voltage biasing signal for a speed
controller and voltage regulator.
• The following table shows two configuration examples with parameters and default
values for the analog outputs 1 and 2.
☼ Configuration examples
Source value at maximum level 5206 220 (kW) 5220 100 (%)
AM Data source AO1 5200 Type: Pass through 5214 Type: Pass through
A1 = 01.74 Gen. A1 = 11.03 Speed
act. power [W] bias [%]
☼ Settings/setup example
The following drawing shows the relation between the value of the AO signal selected
and its corresponding values at the terminal pin. For settings see table below the
drawing.
Example 3 with AO 1
Parameter / AnalogManager
ID
[Default]
5200 AM Data source ... 2 Determined by AnalogManager The data source may be selected
93.01, 93.02 from the available data sources.
5214
AO1: [A1 = 11.03 Speed bias Notes
(%)]
Refer to ╚═▷ “9.4.2 Data Sources
AO2: [A1 = 11.02 Voltage bias AM” for a list of all data sources.
(%)]
[mA] Notes
Example
Notes
Example
Notes
5210 PWM output level 2 0.00 to 10.00 V If PWM has been enabled in
parameter ╚═▷ 5203/╚═▷ 5217, is
5224 [10.00 V] defined in %, and the level of the
PWM signal (amplitude) may be
adjusted here.
5204 Source value at 2 -21000000.00 to 21000000.00 The value from the data source
minimum level must exceed the value configured
5218 [0] here to raise the output signal
above minimum hardware level.
Negative percentage values may
be used to change the sign, e.g.
for power.
5206 Source value at 2 -21000000.00 to 21000000.00 If the value from the data source
maximum level reaches the value configured here,
5220 [10000] the output signal will reach
maximum hardware level.
Negative percentage values may
be used to change the sign, e.g.
for power.
5203 Filter time constant 2 Off, 1 to 7 A filter time constant may be used
to reduce the fluctuation of an
5217 analog output value.
Notes
General notes
Configuration of these external analog inputs is performed similarly to the internal analog
inputs.
• Refer to ╚═▷ Tab. for the parameter IDs of the parameters for external analog inputs
1 through 16.
Please note that the available options for the parameters "Type" and "Sender type" differ
from the internal analog inputs.
The parameters "Offset" and "Monitoring wire break" are not available for the external
analog inputs.
A wire break or sender failure is indicated by a dedicated value sent via the CAN bus
(╚═▷ “4.7.4.1 CAN Interface 1”).
For an example for the configuration of external analog inputs refer to ╚═▷ “6.3.10 Setup
Expansion Modules at CAN 2”.
Parameter AI 1 AI 2 AI 3 AI 4 AI 5 AI 6 AI 7 AI 8
external
Parameter AI 1 AI 2 AI 3 AI 4 AI 5 AI 6 AI 7 AI 8
external
display
min.
Filter time 5863 5876 5889 5902 5915 5928 5941 5954
constant
Wire break 5854 5867 5880 5893 5906 5919 5932 5945
alarm
class
Parameter AI 9 AI 10 AI 11 AI 12 AI 13 AI 14 AI 15 AI 16
external
Parameter AI 9 AI 10 AI 11 AI 12 AI 13 AI 14 AI 15 AI 16
external
Filter time 5967 5980 5993 6942 6955 6968 6981 6994
constant
Wire break 5958 5971 5984 6933 6946 6959 6972 6985
alarm
class
Please make sure that the selected settings you are using are supported by your external
devices.
Available "Type"s
TC Type K Ni DIN(R0)
TC Type J Ni SAMA(R0)
TC Type E Cu10
TC Type R Cu50
TC Type S Cu53
TC Type T Ni 1000(Landis)
TC Type B Ni 500(Viessm.)
TC Type U KTY 84
TC Type L
TC Type C
TC Type W
TC Type HK
0 - 10 V R0=100
±10 V R0=10
0 - 20 mA R0=20
±20 mA R0=30
4 - 20 mA R0=50
Thermocouple R0=200
R0=240
R0=300
R0=400
R0=500
R0=1000
R0=1500
R0=2000
R0=3000
Two wire
Three wire
If an external expansion board (e.g. from Phoenix Contact or WAGO) is connected to the
easYgen via the CAN bus, it is possible to use 4 additional analog outputs.
The configuration of these external analog outputs is performed similarly to the internal
analog outputs.
Refer to ╚═▷ Tab. 51 for the parameter IDs of the parameters for external analog outputs
1 through 4.
Please note that the available options for the Selected hardware type are limited. Refer
to the Parameter List for details.
(displayed in
ToolKit only: ON/
OFF)
Notes:
Refer to ╚═▷ Chapter 4.4.2.7 for details and definition of the parameters.
[Default]
10237 Data source ... 2 Determined by AnalogManager The data source may be selected
93.21 .. 93.24 from the available data sources.
10247
AO1 to AO 4: [A1 = 11.03 Speed Notes
10257 bias (%)]
Refer to ╚═▷ “9.4.2 Data Sources
10267 AM” for a list of all data sources.
[mA]
Example
Example
10240 Source value at 2 -21000000.00 to 21000000.00 The value from the data source
minimum level must exceed the value configured
10250 [0] here to raise the output signal
above minimum hardware level.
10260 Negative percentage values may
be used to change the sign, e.g.
10270 for power.
10241 Source value at 2 -21000000.00 to 21000000.00 If the value from the data source
maximum level reaches the value configured here,
10251 [10000] the output signal will reach
maximum hardware level.
10261 Negative percentage values may
be used to change the sign, e.g.
10271 for power.
10239 Filter time constant 2 Off, 1 to 7 A filter time constant may be used
to reduce the fluctuation of an
10249 analog output value.
Notes
If a Woodward IKD 1 or other external expansion board (e.g. Phoenix Contact or WAGO) is
connected to the easYgen via the CAN bus, it is possible to use 32 additional discrete
inputs.
• The configuration of these external DIs is performed similarly to the internal DIs
(╚═▷ “4.4.2.2 Discrete Inputs”).
• Refer to ╚═▷ Tab. 52 for the parameter IDs of the parameters for external DIs 1
through 32.
External DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8
Alarm class 16002 16012 16022 16032 16042 16052 16062 16072
Self acknowledge 16004 16014 16024 16034 16044 16054 16064 16074
External DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16
Alarm class 16082 16092 16102 16112 16122 16132 16142 16152
Self acknowledge 16084 16094 16104 16114 16124 16134 16144 16154
External DI 17 DI 18 DI 19 DI 20 DI 21 DI 22 DI 23 DI 24
External DI 17 DI 18 DI 19 DI 20 DI 21 DI 22 DI 23 DI 24
Alarm class 16007 16017 16027 16037 16047 16057 16067 16077
Self acknowledge 16009 16019 16029 16039 16049 16059 16069 16079
External DI 25 DI 26 DI 27 DI 28 DI 29 DI 30 DI 31 DI 32
Alarm class 16087 16097 16107 16117 16127 16137 16147 16157
Self acknowledge 16089 16099 16109 16119 16129 16139 16149 16159
If a Woodward IKD 1 or other external expansion board (e.g. Phoenix Contact or WAGO) is
connected to the easYgen via the CAN bus, it is possible to use 32 additional discrete
outputs.
The configuration of the external DOs is performed in a similar way like for the internal
DOs.
Refer to ╚═▷ Tab. 56 for the parameter IDs of the parameters for external discrete
outputs 1 through 32.
External DO 1 DO 2 DO 3 DO 4 DO 5 DO 6 DO 7 DO 8
External DO 9 DO 10 DO 11 DO 12 DO 13 DO 14 DO 15 DO 16
External DO 17 DO 18 DO 19 DO 20 DO 21 DO 22 DO 23 DO 24
External DO 25 DO 26 DO 27 DO 28 DO 29 DO 30 DO 31 DO 32
General notes
The assignment of the defined relays to defined functions occurs by selection of the
application mode (i.e. function "Command: Close GCB" on relay [R 6], this relay can no
longer be operated via the LogicsManager).
The same way some relays are designated to specific functions, others may be assigned
to different functions. These are listed as "programmed" relays. If a relay is
"programmable" the function may be assigned to other relays via the LogicsManager by
configuration.
If the easYgen is intended to be operated in parallel with the mains, the mains voltage
measuring inputs must be connected. If an external mains decoupling is performed,
jumpers between busbar and mains voltage measuring inputs may be installed.
Changing the application mode will not change other configured values in the
parameters. The application mode parameter is the only one.
The configuration of pulse switching takes place in the following screen and has the
described effect on the signal sequence (the MCB cannot be controlled by the continuous
pulse for security reasons, because otherwise, the MCB would be opened in case of a
failure/exchange of the easYgen).
The parameter "Enable MCB" allows/prevents the closing of the MCB. A closed MCB will
not be opened.
If the parameter "Auto unlock" is configured to YES, an open pulse will be issued prior to
each close pulse.
In operation mode AUTO the easYgen operates its breakers automatically according to
the configured application and transition modes. Actually the breaker transition mode
“external” would only allow the breaker closure from external. On the other hand the
easYgen allows in special cases the closure of breaker from external, when the following
configurations and modes are fulfilled:
External Breaker Synchronizat‐ Dead Bus Condition for the closure acceptance
Handling ion Mode Closure
The unit closes the GCB without synchronization, if the following conditions are met. The
display indicates "GCB dead bus close".
Automatic operation
• The engine delayed monitoring (parameter ╚═▷ 3315) as well as the generator
stable time (parameter ╚═▷ 3415) have been expired or the LogicsManager function
"Undelay close GCB" (parameter ╚═▷ 12210) is enabled
• The generator voltage and frequency are within the configured operating range (╚═▷
“4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”)
• The MCB has been opened for at least the time configured in "Transfer time
GCB↔MCB" (parameter ╚═▷ 3400)
• The function "Start without load" (parameter ╚═▷ 12540) has been disabled through
the LogicsManager
• Only in critical mode: the parameter "Close GCB in override" (parameter ╚═▷ 4100)
is configured to "Yes"
• The busbar voltage is below the dead bus detection limit (parameter ╚═▷ 5820)
• There is no other device with a smaller device ID willing to close its GCB too (Dead
busbar closure negotiation)
Manual operation
• The engine delayed monitoring (parameter ╚═▷ 3315) as well as the generator
stable time (parameter ╚═▷ 3415) have been expired.
• The generator voltage and frequency are within the configured operating range (╚═▷
“4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”).
• The MCB has been open for at least the time configured in "Transfer time GCB↔MCB"
(parameter ╚═▷ 3400).
• The busbar voltage is below the dead bus detection limit (parameter ╚═▷ 5820).
• There is no other device with a smaller device ID willing to close its GCB too (Dead
busbar closure negotiation).
Each easYgen, who intends to close its GCB on a dead busbar publishes a “Dead busbar
closure request” flag over CANbus and reads back whether there is any other easYgen
publishing the same intension:
If not, the unit waits an estimated time for security and then closes its breaker.
If yes, the unit compares its own device number with the smallest device number of all
others who also intend to close. If the own device number is smaller than the rest, the
unit will close its breaker - otherwise it blocks its own closure.
The easYgen removes its wish to close its GCB on a dead busbar, if the GCB closure
failure occurs in a multiple generator application. So the next easYgen with the higher
device number gets the permission for closure.
The load sharing messages are monitored. In case of a “missing member” alarm on the
load share bus, the single dead bus closures are delayed depending on the own
Generator number to avoid simultaneous closure. The delay time is Generator Number
multiplied with 500 ms.
The GCB dead busbar closure is realized faster, if LogicsManager "Undelayed close GCB"
ID 12210 is set to TRUE.
Automatic operation
• The mains voltage is available and within the configured operating range (╚═▷
“4.5.3.3 Mains Operating Ranges”)
• The generator and busbar voltage are available and within the configured operating
range (╚═▷ “4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”)
◦ The GCB is closed (or at least one GCB is closed in a multiple genset
application)
◦ The "Enable MCB" (parameter ╚═▷ 12923) signal is present, for example
discrete input 6 is energized if configured as DI 6
◦ Engine delayed monitoring (parameter ╚═▷ 3315) and generator stable time
(parameter ╚═▷ 3415) have expired or "Undelay close GCB" (parameter ╚═▷
12210) is enabled
Manual operation
• The generator and busbar voltage are available and within the configured operating
range (╚═▷ “4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”)
◦ The GCB is closed (or at least one GCB is closed in a multiple genset
application)
◦ The "Enable MCB" (parameter ╚═▷ 12923) signal is present, for example
discrete input 6 is energized if configured as DI 6
◦ Engine delayed monitoring (parameter ╚═▷ 3315) and generator stable time
(parameter ╚═▷ 3415) have expired or "Undelay close GCB" (parameter ╚═▷
12210) is enabled
The unit closes the MCB, if the following conditions are met simultaneously.
Automatic operation
• The parameter "Dead busbar closure MCB" (parameter ╚═▷ 3431) is configured On
• The mains voltage is available and within the configured operating range (╚═▷
“4.5.3.3 Mains Operating Ranges”)
• The GCB is open or has been opened for at least the "Transfer time GCB↔MCB"
(parameter ╚═▷ 3400) (open transition mode only)
• The "Enable MCB" (parameter ╚═▷ 12923) signal is present, for example discrete
input 6 is energized if configured as DI 6
• The busbar voltage is below the dead bus detection limit (parameter ╚═▷ 5820)
Manual operation
• The parameter "Dead busbar closure MCB" (parameter ╚═▷ 3431) is configured "On"
• The mains voltage is available and within the configured operating range (╚═▷
“4.5.3.3 Mains Operating Ranges”)
• The GCB is open or has been opened for at least the "Transfer time GCB↔MCB"
(parameter ╚═▷ 3400) (open transition mode only)
• The "Enable MCB" (parameter ╚═▷ 12923) signal is present, for example discrete
input 6 is energized if configured so
• The busbar voltage is below the dead bus detection limit (parameter ╚═▷ 5820)
The GCB will be opened when the "Command GCB open" is issued. The behavior of the
GCB open relay depends on the setting of parameter ╚═▷ 3403.
If this parameter is configured as "N.O.", the relay energizes to open the GCB, if it is
configured as "N.C.", the relay de-energizes to open the GCB.
• By pressing the "GCB" or "MCB" softkey (depending on the CB logic which has been
set) in MANUAL operating mode
• In the event of an automatic stopping in the AUTOMATIC operating mode (the start
request has been terminated or a stop request has been initiated)
• If "Start without load" has been enabled through the LogicsManager and the breaker
was closed
• By pressing the "MCB" softkey (depending on the CB logic which has been set) in
MANUAL operating mode
The conditions above are only valid if the GCB is closed, whereas the following conditions
are valid regardless of the GCB is open or closed.
• Prior to the MCB closing onto the dead busbar (depending on the CB logic which has
been set)
The MCB will be opened when the relay "Command: MCB open" is energized.
The MCB will be opened under the following conditions if the MCB is closed:
• Prior to the closure of the GCB (depending on the CB logic which has been set)
• Upon pressing the "MCB" or "GCB" softkey (dependent upon the configured CB logic)
in MANUAL operating mode
Parallel breaker logic must be selected for the following operation modes:
• islanded operation
• Mains parallel operation
• The generator assumes load and the adjusted real power or reactive power setpoints
are controlled
• The generator sheds load until real power has reached the "Unload limit"
(parameter ╚═▷ 3125)
• The engine is shut down following the configured cool down period
When a stop command is issued to the engine, soft loading (power reduction) is carried
out before opening the GCB, except an alarm of class D or F is present.
For this breaker logic to function correctly, the mains power measurement must be
connected properly.
In the event of a start request, a change is made from mains to generator supply.
• The generator assumes load until the imported mains interchange real power has
reached 5 % of the "Generator rated active power" (parameter ╚═▷ 1752)
When a stop request has been issued, a change is made from generator to mains supply.
• The generator sheds load until real power has reached the "Unload limit"
(parameter ╚═▷ 3125)
The limit for opening the MCB during softloading (Unloading mains) is +/- 5% active
generator rated power without any delay. In multiple generator applications the 5% limit
is calculated out of the current nominal generator power in the system.
• One engine is running with 1000kW rated, the +/-5% limit is a power window at the
interchange point from 50kW import up to 50kW export.
• One engine is running with 500kW rated and another with 300kW rated, the +/-5%
limit is a power window at the interchange point from 40kW import up to 40kW
export.
Hint: The generator rated power is taken into account to find a good compromise
between bumpless power transfer and being not too long mains parallel.
In the event of an engine start request, a change is made from mains to generator supply.
After the engine stop request has been issued, a change is made from generator to mains
supply.
For the application modes A04 , A06 and A12 , the breaker closed transition time matches
the duration time <100 ms.
The maximum time between the reply from the CB and the CB open command is 100 ms.
In the event of an engine start request, a change is made from mains to generator supply.
• The GCB is closed after the time configured in "Transfer time GCB<->MCB"
(parameter ╚═▷ 3400) has expired.
• The MCB is closed after the time configured in "Transfer time GCB<->MCB"
(parameter ╚═▷ 3400) has expired
External breaker logic is enabled via configuration of parameter ╚═▷ 3411 to "EXTERNAL".
All breaker control (especially the CB closing instructions) must be carried out via master
controller (e.g. a PLC).
The easYgen controller always issues additionally the breaker open command under fault
conditions and in the breaker unloading states (Unloading GCB) if the stop request is
active.
In a mains parallel operation, decoupling from the mains is carried out via the MCB or the GCB in the event of a mains
failure. The breakers will not automatically close in emergency power operation. Emergency power operation in
accordance with European Community Specification DIN VDE 0108 is not possible in this power circuit breaker logic.
The GCB is opened. The MCB and the GCB may be The GCB is opened if the genset is
manually opened. The circuit breakers stopped or if decoupling from the
are opened for decoupling from the mains, but will not close if the engine
mains. is started. The MCB is opened only if
decoupling from the mains, and is
never closed.
The MCB and GCB are synchronized to permit continuous mains parallel operation in this breaker logic mode.
The GCB is opened; the MCB is Mains parallel operation can be The GCB is synchronized via an add-on
operated depending on the setting of initiated by pressing the "GCB On" or request and a mains parallel operation
"Enable MCB" (parameter ╚═▷ 12923). "MCB On" push-button. is performed. When a shed-off request
is issued, the generator sheds load
and opens the GCB and the engine is
shut down following the configured
cool down period.
The MCB and GCB are never synchronized in this breaker logic mode.
The GCB is opened; the MCB is A change can be made to either A change is made to generator
operated depending on the setting of generator or mains operation by operation through an add-on request.
"Enable MCB" (parameter ╚═▷ 12923). pressing either the "GCB On" or "MCB Once the add-on request is
On" push-button. The "STOP" push- terminated, the system changes back
button opens the GCB and to mains operation. The MCB is closed
simultaneously stops the engine. when the busbar is dead, even if there
has not been an add-on request.
Emergency power operations are
terminated following the expiration of
the mains settling timer. The GCB
opens and the MCB closes,
transferring all loads to the mains.
The MCB and the GCB are synchronized, in order to avoid a dead busbar in this breaker logic mode. Immediately after the
synchronization of one breaker, the other is opened. Continuous mains parallel operation is not possible.
The GCB is opened; the MCB is Synchronization of either the The GCB is synchronized via an add-on
operated depending on the setting of generator or the mains can be request. After the GCB closes the MCB
"Enable MCB" (parameter ╚═▷ 12923). initiated by pressing the "GCB On" or is opened. Following the shed-off
"MCB On" push-button. request being issued, the MCB is
synchronized and closed. After the
MCB has closed the GCB is opened.
The MCB and the GCB are synchronized, in order to avoid a dead busbar in this breaker logic mode. The operation of a
breaker under load is avoided by utilizing the ability to soft load. Continuous mains parallel operation is not possible with
this breaker logic.
Following the shed-off request, the MCB synchronizes and closes, the generator soft unloads to the mains and the GCB
opens. After the GCB is open the engine is stopped following the expiration of the configured cool down period.
The GCB is opened; the MCB is Synchronization of either the Via an engine request, the GCB is
operated depending on the setting of generator or the mains can be synchronized and the generator power
"Enable MCB" (parameter ╚═▷ 12923). initiated by pressing the "GCB On" or is increased. The MCB is then opened.
"MCB On" push-button. Following the disabling of the engine
request, the MCB is reverse
synchronized and the GCB is then
opened.
This operation mode may be used both in the case of an islanded system, an islanded parallel system, and a system that
is operated in mains parallel.
The GCB is opened. Mains parallel operation can be The GCB is synchronized via an add-on
performed via the "GCB On" push- request and mains parallel operation
button. is performed.
[Default]
External
Open Transition
Closed Transit.
Interchange
[Parallel]
Notes
External
Open Transition
Closed Transit.
Interchange
[Parallel]
Notes
Notes
External
Open Transition
Closed Transit.
Interchange
[Parallel]
Notes
Notes
Notes
General notes
[Default]
Notes
3414 GCB close command 2 Impulse The relay "Command: GCB close"
issues an add-on pulse. If the
relay is configured in this manner
a holding coil and sealing contacts
must be installed externally to the
control unit. The DI "Reply GCB" is
used to identify closed contacts.
Notes
3416 GCB time pulse 2 0.10 to 1.00 s The time of the pulse output may
be adjusted to the breaker being
[0.50 s] utilized.
Notes
Notes
Notes
Regardless of breaker control, the values of 5700, 5701, 5702, 5703, 5704, 8824, and 8825 are important to
the sync-check relay function.
Notes
Notes
Notes
Notes
Notes
5707 Phase matching GCB 2 0.0 to 60.0 s This is the minimum time that the
dwell time generator voltage, frequency, and
[3.0 s] phase angle must be within the
configured limits before the
breaker will be closed.
Notes
compensated according to an
installed power transformer
between generator and busbar.
Notes
Notes
8824 Phase angle GCB 2 -180 to 180° The phase angle compensation
corrects the degree between
[0°] generator voltage and busbar
voltage. The configured degree is
added to the real measured phase
angle.
Notes
3432 Dead bus closure GCB 2 [On] A dead busbar closure is allowed if
the required conditions are met.
Notes
15161 Inhibit dead bus 2 Determined by LogicsManager If active the dead bus closure of
closure GCB 87.74 the GCB can be inhibited.
Unnecessary CB switching
operations and voltage
interruptions should be avoided by
utilizing this parameter.
Notes
12210 Undelay close GCB 2 Determined by LogicsManager Once the conditions of the
86.12 LogicsManager have been fulfilled
the GCB will be closed
[(04.09 Emergency mode & 1) immediately (without waiting for
& 1] engine speed delay and generator
stable timer to expire).
= 10711
When using the standard setting,
the GCB will be closed without
delay in emergency power
operation.
Notes
12976 GCB open in MAN 2 Determined by LogicsManager With the rising edge of this
87.46 LogicsManager equation a GCB
open command in operating mode
[(0 & 1) & 1] MANUAL is initiated. The state
TRUE of this LM inhibits the GCB
= 11435 close command in MANUAL.
Notes
12977 GCB close in MAN 2 Determined by LogicsManager With the rising edge of this
87.47 LogicsManager equation a GCB
close command in operating mode
[(0 & 1) & 1] MANUAL is initiated.Precondition:
deactivated "GCB open in MAN"
= 11436
Notes
5705 Closing time GCB 2 40 to 300 ms The inherent closing time of the
GCB corresponds to the lead-time
[80 ms] of the close command.
Notes
Notes
5708 GCB open time pulse 2 1.00 to 10.00 s This time defines the length of the
GCB open time pulse, if the
[1.00 s] automatic switch unblocking GCB
is activated.
Notes
General notes
The following parameters are only applicable for application mode A04 .
[Default]
3417 MCB time pulse 2 0.10 to 0.50 s Breaker pulse duration to close
the MCB
[0.50 s]
The time of the pulse output may
be adjusted to the breaker being
utilized.
Notes
5713 Max positive phase 2 0.0 to 60.0° The prerequisite for a connect
angle MCB command being issued for the
[7.0°] MCB is that the leading phase
(Maximum permissible angle between busbar and mains
positive phase angle is below the configured maximum
MCB) permissible angle.
Notes
5714 Max negative phase 2 -60.0 to 0.0° The prerequisite for a connect
angle MCB command being issued for the
[-7.0°] MCB is that the lagging phase
(Maximum permissible angle between busbar and mains
negative phase angle is below the configured maximum
MCB) permissible angle.
Notes
Notes
5711 Pos. freq. differential 2 0.00 to 0.49 Hz The prerequisite for a connect
MCB command being issued for the
[0.18 Hz] MCB is that the differential
(Positive frequency frequency is below the configured
differential MCB) differential frequency.
5712 Neg. freq. differential 2 -0.49 to 0.00 Hz The prerequisite for a connect
MCB command being issued for the
[-0.10 Hz] MCB is that the differential
(Negative frequency frequency is above the configured
differential MCB) differential frequency.
Notes
Notes
5647 MCB slip freq. 2 -0.50 ... 0...50 Hz Individual frequency offset for the
setpoint offset MCB and LS5 synchronization. This
[-0.10 Hz] value can be a positive or
negative offset. The value is valid
as long as the parameter 'MCB
synchronization with separate slip'
On/Off' (parameter ╚═▷ 5709) is
set to 'On' .
Notes
Notes
8842 Phase angle MCB 2 -180 to 180° The phase angle compensation
corrects the degree between
[0°] busbar voltage and mains voltage.
The configured degree is added to
the real measured phase angle.
Notes
5717 Phase matching MCB 2 0.0 to 60.0 s This is the minimum time that the
dwell time generator/busbar voltage,
[3.0 s] frequency, and phase angle must
be within the configured limits
before the breaker will be closed.
Notes
5715 Closing time MCB 2 40 to 300 ms The inherent closing time of the
MCB corresponds to the lead-time
[80 ms] of the close command.
5718 MCB open time pulse 2 0.10 to 9.90 s This time defines the length of the
MCB open time pulse, if the
[1.00 s] automatic switch unblocking MCB
is activated.
12974 MCB open in MAN 2 Determined by LogicsManager With the rising edge of this
87.48 LogicsManager equation a MCB
open command in operating mode
[(0 & 1) & 1] MANUAL is initiated. The state
TRUE of this LM inhibits the MCB
= 11437 close command in MANUAL.
Notes
12975 MCB close in MAN 2 Determined by LogicsManager With the rising edge of this
87.49 LogicsManager equation a MCB
close command in operating mode
[(0 & 1) & 1] MANUAL is initiated.Precondition:
deactivated "MCB open in MAN"
= 11438
Notes
General notes
The following parameters are only applicable for application modes A03 A04 .
[Default]
• 1. PERMISSIVE
• 2. CHECK
• 3. RUN
Notes
12907 Syn. mode PERMIS. 2 Determined by LogicsManager Once the conditions of the
86.39 LogicsManager have been fulfilled
(Synchronization mode the PERMISSIVE synchronization
PERMISSIVE) [(0 & 1) & 1] mode will be enabled.
= 11618 Notes
12906 Syn. mode CHECK 2 Determined by LogicsManager Once the conditions of the
86.38 LogicsManager have been fulfilled
(Synchronization mode the CHECK synchronization mode
CHECK) [(0 & 1) & 1] will be enabled.
= 11617
Notes
12908 Syn. mode RUN 2 Determined by LogicsManager Once the conditions of the
86.40 LogicsManager have been fulfilled
(Synchronization mode the RUN synchronization mode will
RUN) [(0 & 1) & 1] be enabled.
= 11619 Notes
General notes
The device provides two independent "Sync Check" functions for the voltage comparisons
generator to busbar and busbar to mains. The criteria are the same like for the according
internal self-executed synchronization.
The easYgen provides two command variables available for the LogicsManager input:
WARNING!
The Sync. Check functionality is available in every application mode. The command
variables are independently calculated and depending on the same configurations, like
the self-executed GCB and MCB close commands. The sync. Check function has no
influence on any frequency or voltage biasing. There is no relationship to the Sync. Check
mode for the internal self-executed synchronization.
• Voltage
• Frequency
and
• Phase angle
• Voltage
• Frequency
and
• Phase angle
General Notes
The Neutral Interlocking feature controls a Neutral Contactor (NC) of each generator. The
rule is that only one neutral contactor of all running generators are closed. The Logic
ensures that with changing of generators the neutral link is passed over to another
running generator. Refer to ╚═▷ “6.3.14 Neutral Interlocking” for more information.
[Default]
Notes
To make use of the Close neutral interlocking contactor status, configure a discrete
output relay DO x to react for 03.39.
WARNING!
The following parameters dictate how the easYgen controls voltage, frequency, load and
power factor.
Failure to do so may lead to incorrect measurements and failures within the control unit
resulting in damage to or destruction of the generator and/or personal injury or death.
• Always ensure that the correct settings are entered in these parameters.
The Real load, reactive load, and process control all utilize PID controllers. The response
of each control loop can be adjusted for optimum response, however it is important to
understand what a PID controller is and the effect of each controller adjustment has on
the controller response.
Proportional gain, integral gain (stability) and DR (speed derivative ratio) are the
adjustable and interacting parameters used to match the response of the control loop
with the response of the system.
They correspond to the P (proportional), I (integral), and D (derivative) terms, and are
displayed in the easYgen as follows:
Proportional control
• Analogy: Setting hand throttle to keep constant speed on straight and level road.
Proportional control (using the same analogy) results in a certain speed as long as the car
is not subjected to any load change such as a hill. If a throttle is set to any particular
setting, the speed of the car will remain constant as long as the car remains straight and
level. If the car goes up a hill it will slow down. Of course, going down a hill the car would
gain speed.
Integral control
Integral, sometimes called reset, provides additional action to the original proportional
response as long as the process variable remains away from the setpoint. Integral is a
function of the magnitude and duration of the deviation. In this analogy the reset
response would keep the car speed constant regardless of the terrain.
Derivative
Derivative provides a temporary over-correction to compensate for long transfer lags and
reduce stabilization time on process upsets (momentary disturbances). The behavior of
the derivative parameter is shown in ╚═▷ Fig. 153.
Merging into high speed traffic of a freeway from an "on" ramp is no easy task and
requires accelerated correction (temporary overcorrection) in both increasing and
decreasing directions. The application of brakes to fall behind the car in the first
continuous lane or passing gear to get ahead of the car in the first continuous lane is a
derivative action.
If the system is unstable, make sure the governor is the cause. This can be checked by
closing the valve limiter until it has control of the actuator output. If the governor is
causing the oscillation, time the oscillation cycle time. A rule-of- thumb is, if the system’s
oscillation cycle time is less than 1 second, reduce the Proportional gain term. A rule-of-
thumb is, if the system’s oscillation cycle time is greater than 1 second, reduce the
Integral gain term (proportional gain may need to be increased also).
On an initial startup with the easYgen, all PID dynamic gain terms will require adjustment
to match the respective PID’s response to that of its control loop. There are multiple
dynamic tuning methods available that can be used with the easYgen’s PIDs to assist in
determining the gain terms that provide optimum control loop response times.
ᐳ The following method can be used to achieve PID gain values that are close to optimum:
1. ▷ Increase Derivative Ratio (DR) to 100.
2. ▷ Reduce integral gain to 0.01.
3. ▷ Increase proportional gain until system just starts to oscillate.
The optimum gain for this step is when the system just starts to oscillate
and maintains a self-sustaining oscillation that does not increase or decrease
in magnitude.
4. ▷ Record the control gain (Kc) and oscillation period (T) in seconds.
5. ▷ Set the dynamics as follows:
▶ This method of tuning will get the gain settings close, they can be fine-tuned from this
point.
AnalogManagers to define input signal of voltage setpoint (1, 2) are available in ToolKit
by
[Default]
5608 Voltage control initial 2 0.0 to 100.0% The value entered for this
state parameter is the start reference
[50.0%] point for the analog output to the
voltage controller.
Notes
5611 Integral gain 2 0.01 to 100.00 The integral gain identifies the I
part of the PID controller. The
[1.00] integral gain corrects for any
offset (between setpoint and
process variable) automatically
over time by shifting the
proportioning band. Reset
automatically changes the output
requirements until the process
variable and the setpoint are the
same. This parameter permits the
user to adjust how quickly the
reset attempts to correct for any
offset. The integral gain constant
must be greater than the
derivative time constant. If the
integral gain constant is too large,
the engine will continually
oscillate. If the integral gain
constant is too small, the engine
will take too long to settle at a
steady state.
Notes
5612 Derivative ratio 2 0.01 to 100.00 The derivative ratio identifies the
D part of the PID controller. By
[0.01] increasing this parameter, the
stability of the system is
increased.
Notes
Synchronization
Notes
5651 Time pulse minimum 1 0.01 to 2.00 s A minimum pulse on time must be
configured here. The shortest
[0.05 s] possible pulse time should be
configured to limit overshoot of
the desired voltage reference
point.
Notes
5652 Gain factor 1 0.1 to 10.0 The gain factor Kp influences the
operating time of the relays. By
[5.0] increasing the number configured
in this parameter, the operating
time of the relay will be in-creased
in response to a deviation from
the voltage reference.
Notes
5659 Cycle time factor 1 1.0 to 20.0 The cycle time factor adjusts the
time between the pulses (pause
[1.0] time).
Notes
Notes
Notes
5618 AM Voltage SP1 [V] 2 Determined by AnalogManager The voltage setpoint 1 source may
81.09 be selected from the available
data sources.
[A1 = 05.57 Internal v setp1
[V]] The internal voltage setpoint
05.57 can be changed manually at
the setpoint screen of the display.
Notes
5619 AM Voltage SP2 [V] 2 Determined by AnalogManager The voltage setpoint 2 source may
81.10 be selected from the available
data sources.
[A1 = 05.58 Internal v setp2
[V]] The internal voltage setpoint
05.58 can be changed manually at
the setpoint screen of the display.
Notes
Notes
Notes
5603 Voltage control 2 1.00 to 300.00 %/s The different setpoint values are
setpoint ramp supplied to the controller via this
[5.00 %/s] ramp. The slope of the ramp is
used to alter the rate at which the
controller modifies the setpoint
value. The faster the change in
the setpoint is to be carried out,
the greater the value entered here
must be.
Notes
Notes
• Controller type can be selected for an analog PID or a three-step controller (see
chapter ╚═▷ “4.4.4.2.2 Configure Power Factor / kvar Control”)
• PF(P) characteristic is available (see chapter ╚═▷ “4.4.4.2 Power Factor Control”)
• Beside PF(P) characteristic, Q(V) characteristic is available too (see chapter ╚═▷
“4.4.4.2 Power Factor Control”).
• Reactive power control at the interchange point offers another opportunity of power
factor control (see chapter ╚═▷ “4.4.4.2.1 Control The Power Factor / Reactive Power
At The Mains Interchange Point”).
4.4.4.2.1 Control The Power Factor / Reactive Power At The Mains Interchange Point
General notes
Being parallel to the utility, it is desired in some application to control either the power
factor or the amount of imported/exported inductive reactive power in kvar at the mains
interchange point. Similar to an import/export active power setpoint, all easYgens can be
programmed to the same setpoint and will share between each other the reactive power
to reach this setpoint.
The easYgen can work as reactive power control at the interchange point. In this mode
the gensets are monitored and restricted in reactive power flow (outcome and income;
respectively leading and lagging).
A reactive power control (kvar or power factor) can cause an overload or damage of the
generator. To avoid this the easYgen provides a 2-step protection:
1. ▷ The own absolute generator current is monitored with an percentage setting related to
rated current input (ID ╚═▷ 1754). The easYgen limits or controls down the excitation
that this given level (ID ╚═▷ 5791) is not exceeded.
2. ▷ The inductive reactive power outcome of the own generator is limited according to the
configuration of ID ╚═▷ 5792.
Or:
The inductive reactive power income of the own generator is limited according to the
configuration of ID ╚═▷ 5793.
An active Limitation is
• driving the LogicsManager command variable 05.18 Gen excitation lim. from FALSE
to TRUE
[Default]
5625 Power factor Control 2 [PID analog] The power factor is controlled
using an analog PID controller.
Notes
5614 Integral gain 2 0.001 to 100.00 The integral gain identifies the I
part of the PID controller. The
[1.000] integral gain corrects for any
offset (between setpoint and
process variable) automatically
over time by shifting the
proportioning band.
Notes
5615 Derivative ratio 2 0.01 to 100.00 The derivative ratio identifies the
D part of the PID controller. By
[0.01] increasing this parameter, the
stability of the system is
increased.
Notes
Notes
5661 Time pulse minimum 1 0.01 to 2.00 s A minimum pulse on time must be
configured here.
5662 Gain factor 1 0.1 to 10.0 The gain factor Kp influences the
operating time of the relays.
[5.0]
By increasing the number
configured in this parameter, the
operating time of the relay will be
in-creased in response to a
deviation from the power factor
reference.
Notes
5667 Cycle time factor 1 1.0 to 20.0 The cycle time factor adjusts the
time between the pulses (pause
[1.0] time).
Notes
Notes
Notes
5638 AM PF/kvar SP1[-/ 2 Determined by AnalogManager The power factor / reactive power
kvar] 81.11 setpoint 1 source can be selected
from the available data sources.
[A1 = 05.10 Intern. PF setp1
[%]] The internal PF/var setpoint 05.10
can be changed manually at the
setpoint screen of the display.
5639 AM PF/kvar SP2[-/ 2 Determined by AnalogManager The power factor / reactive power
kvar] 81.05 setpoint 2 source can be selected
from the available data sources.
[A1 = 05.11 Intern. PF setp2
[%]] The internal PF/var setpoint 05.11
can be changed manually at the
setpoint screen of the display.
5745 Int. kvar setpoint 1 -99999.9 to +99999.9 This setpoint is active only if PF/
kvar setpoint 1 is set to Mns.
[0.0] Export kvar or Mns. Import kvar.
5621 Int. power factor 2 -0.999 to +1.000 The desired power factor may be
setpoint 2 configured here so that the
[+1.000] reactive power is regulated in the
system.
5746 Int. kvar setpoint 2 -0.999 to +99999.9 This setpoint is active only if PF/
kvar setpoint 2 is set to Mns.
[0.0] Export kvar or Mns. Import kvar.
Notes
5622 React. pwr. ctrl 2 0.01 to 100.00 %/s The different setpoint values are
setpoint ramp supplied to the controller via this
[3.00 %/s] ramp.
Notes
1884 Gen. PF setpoint 2 0.0 to 99.9 s The PT1-filter for the Gen PF or
filter Gen kvar setpoint mode can be
configured here. The parameter
Notes
General notes
This feature is related to the former BDEW grid code. For the VDE-AR-N 4110 / 4105 grid
code please refer the reactive power characteristics
The Power Factor Characteristic function is adapting the reactive power flow between
generator and mains to support a dynamic stabilization of the mains. Some network
provider prefer therefore a power factor control over real power PF(P) (see chapter╚═▷
“4.4.4.2.3.1 Power factor characteristic PF(P) ” for more details).
Other provider prefer power factor control over mains voltage Q(V) as described in
chapter ╚═▷ “4.4.4.2.3.2 Power factor characteristic Q(V) ”. Both methods are
configurable alternatively.
Both power factor characteristic curves now offer four point settings.
A method to support the mains is to feed different reactive power values into the grid in
relation to the own active power value. The reactive power is defined through a power
factor setpoint for the generator. This can be defined in characteristic curve.
The characteristic is defined by four points (① .. ④). The power factor corresponding to
this characteristic is available as data source 05.29 in the AnalogManager.
To use this function, the source (05.29) must be applied as source to one of the setpoints
e.g., "Power factor setpoint 1" (parameter ╚═▷ 5638).
[Default]
5787 Point 1 power 2 0.0 to 150% The value entered into "Point 1
power" defines the cos phi (P)
[0%] characteristic.
5788 Point 1 cos phi 2 -0.999 to 1.000 The desired "Point 1 cos phi" may
be configured here which defines
[-0.950] the cos phi (P) characteristic.
5789 Point 2 power 2 0.0 to 150% The value entered into "Point 2
power" defines the cos phi (P)
[100%] characteristic.
5790 Point 2 cos phi 2 -0.999 to 1.000 The desired "Point 2 cos phi" may
be configured here which defines
[0.950] the cos phi (P) characteristic.
5028 Point 3 power 2 0.0 to 150% The value entered into "Point 3
power" defines the cos phi (P)
[100%] characteristic.
5029 Point 3 cos phi 2 -0.999 to 1.000 The desired "Point 3 cos phi" may
be configured here which defines
[0.950] the cos phi (P) characteristic.
5030 Point 4 power 2 0.0 to 150% The value entered into "Point 4
power" defines the cos phi (P)
[100%] characteristic.
5031 Point 4 cos phi 2 -0.999 to 1.000 The desired "Point 4 cos phi" may
be configured here which defines
[0.950] the cos phi (P) characteristic.
Another method to support the mains is to feed different reactive power values into the
grid in relation to the mains voltage [parameter ╚═▷ 5786 = Q(V)]. The reactive power is
defined through the value Q/S rated over voltage. This can be defined in a characteristic
curve. The resulting outcome for the reactive power control is then a power factor
setpoint.
Fig. 156: Power factor characteristic according to the relation Q/S rated over rated
voltage
The characteristic is defined by four points (① .. ④). The power factor corresponding to
this characteristic is available as data source 05.29 in the AnalogManager.
To use this function, the source (05.29) must be applied as source to one of the setpoints
e.g., "Power factor setpoint 1" (parameter ╚═▷ 5638).
[Default]
5778 Point 1 voltage 45.0 to 150.0% The value entered into "Point 1
Voltage" defines the x-coordinate
[98.0%] of point 1
5779 Point 1 Q/S rated -0.99 to +0.99 The value entered into "Point 1
Reactive power" defines the y-
[-0.31] coordinate of point 1
5797 Point 2 voltage 45.0 to 150.0% The value entered into "Point 2
Voltage" defines the x-coordinate
[106.0%] of point 2
5798 Point 2 Q/S rated -0.99 to +0.99 The value entered into "Point 2
Reactive power" defines the y-
[+0.31] coordinate of point 2
5032 Point 3 voltage 0.0 to 150.0% The value entered into "Point 3
Voltage" defines the x-coordinate
[106.0%] of point 3
5033 Point 3 Q/S rated -0.99 to +0.99 The value entered into "Point 3
Reactive power" defines the y-
[+0.31] coordinate of point 3
5034 Point 4 voltage 0.0 to 150.0% The value entered into "Point 4
Voltage" defines the x-coordinate
[106.0%] of point 4
5035 Point 4 Q/S rated -0.99 to +0.99 The value entered into "Point 4
Reactive power" defines the y-
[+0.31] coordinate of point 4
5799 Q(V) response time 001 to 999 s The response with a new reactive
power setpoint acting on the
[10 s] analog command variable 05.29
PF characteristic can be delayed.
Q(V) response time is used to
calculate the power factor
characteristic Q(V), parameter
╚═▷ 5786.
Notes
Introduction
The FNN VDE-AR-N 4105 / 4110 requests a reactive power control with a setpoint which is
leaded over a PT1-element. The PT1-element shall be adjustable with a 3 tau setting. The
3 tau setting defines at what time shall be reached 95% of the original setpoint change.
This 3 tau value is configurable.
Function
The reactive power controller PID is always receiving a reactive power setpoint even the
setpoint is entered as power factor or as power factor setpoint. The PT1 filter behavior is
always included (Refer to drawing) but the filter can configured so that it has no
influence.
Fig. 157: Setpoint Jump (standardized with height 1) and the resulting PT1 setpoint
Four reactive power setpoint filters are placed in the easYgen in regards to:
Fig. 158: The allocation of reactive power setpoints and their filters
Configuration
[Default]
1884 Gen. PF setpoint filter 0 to 99.9s The PT1-filter for the Gen PF
setpoint mode can be configured
[0.0s] here. The parameter stands for
the 3 times tau value of a PT1
element. (see drawing). That
means the configured time
defines when 95% of the original
setpoint jump is reached.
1897 Q(V) setpoint filter 0 to 99.9s The PT1-filter for the reactive
power characteristic Q(V) can be
[10.0s] configured here. The parameter
stands for the 3 times tau value of
a PT1 element. (see drawing).
That means the configured time
defines when 95% of the original
setpoint jump is reached.
1898 Q(P) setpoint filter 0 to 99.9s The PT1-filter for the reactive
power characteristic Q(P) can be
[10.0s] configured here. The parameter
stands for the 3 times tau value of
1899 Q(V) limit setpoint filter 0 to 99.9s The PT1-filter for the reactive
power characteristic Q(V) limit can
[10.0s] be configured here. The
parameter stands for the 3 times
tau value of a PT1 element. (see
drawing). That means the
configured time defines when 95%
of the original setpoint jump is
reached.
General notes
This feature is related to the VDE-AR-N 4110 / 4105 grid code. For BDEW related grid
code please refer to ╚═▷ “4.4.4.2 Power Factor Control”.
The FNN VDE-AR-N 4105 / 4110 requests different methods for reactive power control
during mains faults to stabilize the mains.
This method determines a reactive power setpoint deviation based on the mains voltage
deviation from a rated mains voltage value.
The formula contains a factor which can shift the curve on the voltage axis. The shift itself
can be determined through an analog value “VQ0”. This gives the network provider the
capability to change the reactive power influence remotely.
Function
This procedure of running different reactive power values over the voltage is based on
two points:
Point 1 is defined as the reference voltage on which the reactive power shall be zero.
Point 2 is defined through the value pair (Vmax/VC ; Qmax/Pinst.). This point defines
finally the maximal reactive power, which is allowed to run for the generator. It is valid for
leading and lagging reactive power (Under-excitation/Over-excitation).
So if mains voltage exceeds the Vmax/VC point inductive power is absorbed and with
surpassed Vmax/VC inductive reactive power is delivered to mains.
Furthermore the function provides the capability to shift point 1 on the x-axis from
outside. Through this it can be determined afterwards at what mains voltage level the
reactive power flow begins to work.
Through a dead band incorporation into the function the operator can determine to stay
on a last calculated reactive power. So as long the mains voltage deviates not again
around a dead band width the last setpoint is kept.
And finally through a test function the function gives the operator the opportunity to
simulate different mains voltages to observe whether the reactive power flow is
maintained properly.
[Default]
Binary result of
AnalogManager81.31 AM
Reference VQ0
5827 Q(V) voltage dead band 0 to 10.00% The dead band for the mains
voltage relates to the calculation
[0%] of a new reactive power reference.
If the mains voltage is higher/
lower as the previous mains
voltage +/- hysteresis the “new
value” will be used for the
reactive power calculation.
1897 Q(V) setpoint filter 0 to 99.9s The PT1-filter for the reactive
power characteristic Q(V) can be
[10.0s] configured here. The parameter
stands for the 3 times tau value of
a PT1 element. (see drawing).
That means the configured time
defines when 95% of the original
setpoint jump is reached.
This can be picked up with the AnalogManager variable “05.46 VQ0 reference”
For test purposes it is possible to configure a "Test mains voltage" which is passed to the
Q(V) characteristic instead of the real mains voltage measurement.
[Default]
5828 Enable mains test voltage On For test purposes, use the mains
test voltage instead of the
[Off] measured mains voltage. This
function is temporarily enabled.
5829 Mains test voltage 50 to 150% The Q(V) function uses the mains
test voltage for the calculation of
[100%] the reactive power reference.
General notes
The FNN VDE-AR-N 4105 / 4110 requests different methods for reactive power control
during mains faults to stabilize the mains. This method determines a reactive power
based on the actual power output of the generator. The reactive power is controlled in
relation to the actual active power. Maximal 10 reference points define the curve. The
space between the points are linear interpolated. The tolerance band for the configured
curve is +/- 2%
Function
[Default]
1898 Q(P) setpoint filter 0 to 99.9s The PT1-filter for the reactive
power characteristic Q(P) can be
[10.0s] configured here. The parameter
stands for the 3 times tau value of
a PT1 element. (see drawing).
That means the configured time
defines when 95% of the original
setpoint jump is reached.
Introduction
The FNN VDE-AR-N 4105 / 4110 requests different methods for reactive power control
during mains faults to stabilize the mains.
This method determines a reactive power setpoint deviation based on the mains voltage.
The curve here is defined with four points. The value pairs of point 2 and point 3 can be
influenced through an offset value remotely.
This is a way to shift the dead band into a reactive power flow zone. The network provider
can influence the basic reactive power flow remotely.
Function
This procedure of running different reactive power values over the voltage is based on
four point:
• Point 1 is defined as the reference voltage on which the lagging reactive power flow
shall be limited (max. over-excitation). Example in drawing [V/VC 0.94 ; Q/Pbinst
-0.33]
• Point 2 is defined as the lowest reference voltage at which the reactive power flow is
zero. Example in drawing [V/VC 0.96 ; Q/Pbinst 0.00]
• Point 3 is defined as the highest reference voltage at which the reactive power flow
is zero. Example in drawing [V/VC 1.04 ; Q/Pbinst 0.00]
• Point 4 is defined as the reference voltage on which the leading reactive power flow
shall be limited (max. under-excitation). Example in drawing [V/VC 1.06 ; Q/Pbinst
0.33]
Furthermore the function provides the capability to shift point 2 and point 3 so that the
dead band is shifted into a reactive power flow zone. With this setting the network
provider can relative simple shift the reactive power flow (leading or lagging) in the usual
voltage range. This helps to compensate any local situations from remote.
Finally, through a test function, the function gives the operator the chance to simulate
different mains voltages to observe if the reactive power flow is being maintained
properly.
[Default]
Format 00.00
1899 Q(V) limit setpoint filter 0 to 99.9s The PT1-filter for the reactive
power characteristic Q(V) limit can
[10.0s] be configured here. The
parameter stands for the 3 times
tau value of a PT1 element. (see
drawing). That means the
configured time defines when 95%
of the original setpoint jump is
reached.
81.32
For test purposes it is possible to configure a "Test mains voltage" which is passed to the
Q(V) limit characteristic instead the real mains voltage measurement.
The parameter Ids are the same like for the Q(V) reactive power characteristic.
CAUTION!
For correct load share communication all load sharing gensets in the system must
actively use the same load share communication interface (and network)!
Load share communication is defined by parameter »Load share interface « ╚═▷ 9924
(CAN or Ethernet) and others.
The easYgen performs proportional load and/or var sharing. This means each generator
will share the load at the same percentage level of the generator rated power when
paralleled against the mains, in an islanded operation with multiple generators paralleled,
or when re-synchronizing the common bus to the mains.
Also in islanded operation the load ramp rate parameters ╚═▷ 5522 and ╚═▷ 5622 are
used to ramp a new generator onto the other.
If not enough nominal power on the busbar is available, from now on the ramping of an
engine onto others will be interrupted but the load sharing will be executed immediately.
This is to avoid overloading of already online generators.
Proportional load/var sharing will not be performed when the easYgen has the GCB
closed and is in the constant power/base load mode.
A system can consist out of 32 gensets which are controlled by a single easYgen.
4.4.4.3.1 Mains Parallel Operation With Mains Interchange Real Power Control (Import/Export)
The easYgen controllers maintain the real load level on the individually controlled
generators at a level so that the real power setpoint at the mains interchange remains at
the configured setpoint. The real power setpoint for the mains interchange must be
configured identically for each easYgen.
The easYgen controller communicates with other controls in the system via a CAN bus.
This enables the controllers to adjust the real power generated by the generator while
remaining within the rated power of the generator. A smaller generator will contribute
less real power as compared to a large generator, but they will both be utilized to the
same capacity factor. An example of this would be a 100 kW generator with a configured
1000 kW generator and a mains interchange of 825 kW. The 100 kW generator would
contribute 75 kW and the 1000 kW generator would contribute 750 kW or both
generators would be at 75% of their rated capacity.
How the reactive power handling is executed depends the PF/kvar setpoint mode. Two
setpoints (╚═▷ 5743 and ╚═▷ 5744) are available. Each setpoint allows the modes:
• Gen PF
• Mains PF
In PF modes the reactive load sharing is not performed when operating in parallel with
the mains. Reactive power control will be defined by the configured power factor
setpoints (╚═▷ 5620 or ╚═▷ 5621) of the individual controllers. If the power factor
controller setpoint is configured as +0.950, the easYgen will proportionally share the real
load with all generators in parallel with the mains while controlling the reactive power at
a 0.95 inductive (lagging) power factor regardless of the what power factor the mains is
operating at.
The parameter "Active power Load share gain" (parameter ╚═▷ 4522) can be used to
define the priority of the reference variable for real power sharing (real power at
interchange). A higher configured value influences the control more towards maintaining
the real power setpoint for the interchange. A lower configured value influences the
control more towards maintaining real power sharing between units.
The parameter "React. power Load share gain" (parameter ╚═▷ 4543) has no influence
here.
In kvar modes the reactive load sharing is performed when operating in parallel with the
mains. Mains import/export kvar control at the interchange point will be determined by
the configured int. kvar setpoints (╚═▷ 5745 or ╚═▷ 5746) of the individual controllers.
The easYgen controllers maintain the voltage and frequency of the individually controlled
generators at a constant level. This makes it imperative that the voltage and frequency
setpoints are configured identically for each easYgen.
The easYgen controller communicates with other controls in the system via a CAN bus.
This enables the controllers to adjust the real power generated by the generator while
remaining within the rated power of the generator. A smaller generator will contribute
less real power as compared to a large generator, but they will both be utilized to the
same capacity factor.
☼ Example
The reactive power will be shared proportionally among all generators involved.
The parameter "Active power Load share gain" (parameter ╚═▷ 4522) can be used to
define the priority of the reference variable for real power sharing. A higher configured
value influences the control more towards frequency control. A lower configured value
influences the control more towards real power sharing.
The parameter "Active power Load share gain" (parameter ╚═▷ 4522) can be used to
define the priority of the reference variable for real power sharing. A higher configured
value influences the control more towards frequency control. A lower configured value
influences the control more towards real power sharing.
The bus frequency reference point is dictated by the measured mains frequency and the
configured frequency differential (+ slip frequency setpoint offset (parameter ╚═▷ 5502).
☼ Example
If + slip frequency setpoint offset = 0.2 Hz, the easYgen will calculate the bus frequency
reference point as:
The differential voltage is configured as a window. The monitored voltage from the
potential transformers secondary for the mains and the bus must be within the configured
voltage differential limit in relation to the rated voltage configuration.
This means that the voltage window dV [%] is in relation to the rated voltage
configuration [%].
When the monitored bus frequency and voltage are within the configured differential
limits, the "Command: close MCB" relay will enable, closing the MCB, and the system will
be paralleled to the mains.
4.4.4.3.4 Prerequisites
All easYgen controllers connected to the system must have rated system frequencies and
breaker logic configured identically and the parameter "Active power load share"
(parameter ╚═▷ 5531) or "Reactive power load share" (parameter ╚═▷ 5631) must be
enabled.
The easYgen utilizes a peer relationship between units to control the system. This permits
for parallel applications of up to 32 generators.
The current load-share interface is selected by parameters ╚═▷ 9924 and ╚═▷ 11986 LM
86.13.
For set-up of the load-share communication refer to ╚═▷ “3.4.5 Ethernet Interface (incl.
Remote Panel)” for information about the CAN bus connection or to ╚═▷ “4.7.5 Ethernet
Interfaces” for Ethernet
The "Active/Reactive power load share" together with the "Active/Reactive power load
share gains" determine if and how a generator performs real power or frequency control
when paralleled with other generators in an islanded operation.
In the illustrated control system, it must be noted that each control calculates the mean
utilization factor of all controls from the data transmitted via the selected bus and then
compares this with its own utilization factor. The utilization factor is compared with the
reference variable and results in a new reference variable setpoint. Frequency and real
power control are carried out simultaneously in these controls (corresponding to the
reference variable).
Frequency control is carried out via the measured voltage/frequency of the voltage
system. The MPU is used merely for monitoring functions, or is available as a control
value to the secondary controller.
4.4.4.3.7 Parameters
[Default]
4522 Active power load 2 0.01 to 9.99 This parameter defines the impact
share gain of the active power load sharing
[1.25] error signal on the frequency/load
controller setpoint. The active
power load share gain can be
adjusted between 0.01 to 9.99.
Notes
4543 React. power load 2 0.01 to 9.99 This parameter defines the impact
share gain of the reactive power load sharing
[1.25] error signal on the voltage/
reactive load controller setpoint.
The reactive power load share
gain can be adjusted between
0.01 to 9.99.
Notes
High data volume on communication ports can cause low HMI display operation dynamic.
Recommendation:
Reduce data transfer volume on CAN bus. This can be done with parameter ╚═▷
9921 »Transfer rate LS fast message«.
A general action to reduce data volume on CAN1 is disabling the TPDO1 data protocol if it
is not used. Therefore navigate to parameter ╚═▷ 9600 »COB-ID« and enter "80000000"
via front panel or "2147483648" via ToolKit.
For more information how to reduce bus load see ╚═▷ “4.4.4.3.6 Load Sharing”.
This ... gain parameter replaces the former existing (%) ... factor of non-XT easYgen. The
table below shows the relation between the old and new values.
Weighting % LS Gain
10 2.25
Weighting % LS Gain
20 2
30 1.75
40 1.5
50 1.25
60 1
70 0.75
80 0.5
90 0.25
98 0.05
Load sharing with several gensets is possible for a supply of several split busbars. Each of
this individual groups is called a segment.
General
A group breaker splits the busbar in a way that some gensets supply one busbar and
some supply another one. However, it is necessary to group the gensets, which supply
the same busbar.
The designer of a busbar system gives all individual bus bars an own number: The
Segment Number for the easYgen is defined with ID 1723. Each easYgen is connected
with its GCB on one of these segments.
The configured segment number can be changed to one of three alternative segment
numbers by three LogicsManager equations. These LogicsManager equations stand for
the segment numbers 2, 3, or 4. They are usually controlled by circuit breaker reply
auxiliary contacts. This is finally the segment number the easYgens interacts with.
☼ Example
Six gensets (G1 through G6) supply a system with two group breakers (A, B) as shown
in . All gensets have the same segment number configured #1 (parameter ╚═▷ 1723)
Case I Group breakers A and B are closed and G1 through G6 supply the same
busbar. The same segment number is configured to each genset since
all gensets supply the same busbar.
Case II Group breaker A is closed and group breaker B is open (G1 through G4
supply a different busbar than G5 and G6). A different segment number
must be selected for G5 and G6 by enabling the LogicsManager
function "Segment no.2 act" (parameter ╚═▷ 12929320) in order to
change the segment number of G5 and G6 to #2.
Case III Group breakers A and B are open (G1 and G2, G3 and G4, as well as G5
and G6 supply different busbars).
A different segment number must be selected for G3 and G4
(LogicsManager function "Segment no.2 act" (parameter ╚═▷
12929320)) as well as to G5 and G6 (LogicsManager function "Segment
no.3 act" (parameter ╚═▷ 12928320)).
With this, the segment number of G3 and G4 is changed to #2 and the
segment number of G5 and G6 is changed to #3.
[Default]
12929 Segment no.2 act 2 Determined by LogicsManager Once the conditions of the
86.87 LogicsManager have been fulfilled,
this genset is assigned load share
segment number 2 (this
parameter has priority over
parameters ╚═▷ 12928 and ╚═▷
12927).
12928 Segment no.3 act 2 Determined by LogicsManager Once the conditions of the
86.88 LogicsManager have been fulfilled,
this genset is assigned load share
segment number 3 (this
parameter has priority over
parameters ╚═▷ 12927).
12927 Segment no. 4 act 2 Determined by LogicsManager Once the conditions of the
86.89 LogicsManager have been fulfilled,
this genset is assigned load share
segment number 4.
5568 Mode ext. load share 2 The operation mode for the
gateway external Woodward Load Share
Gateway (LSG) is configured here.
[0] Off
1 Woodward EGCP-2
RS-485 (P & Q)
2 Woodward SPM-D
R = 4.99k | P: 0 − 4 V (0 to 100%)
| Q: 0 − 5 V (-85% to +85%)
Woodward MFR 15
R = 4.99k | P: 0 − 4 V (0 to 100%)
3 Woodward 2301 A
R = 54.90k | P: 0 − 3 V (0 to
100%)
4 Caterpillar LSM
R = 25.00k | P: 0 − 3 V (0 to
100%)
6 POW-R-CON
R = 20.67k | P: 0 − 5 V (0 to
100%)
7 Prepared
R = 25.00k | P: -5 − +5 V (0 to
100%)
8 Prepared
R = 25.00k | P: 0 − 7 V (0 to
100%)
9 Woodward GCP/MFR
10 to 16 Not defined
Notes
R: Internal resistance
4.4.4.3.9 Droop
The isochronous running frequency or voltage controllers keep the desired frequency or
voltage set point independent on the real or reactive power of the generator.
The frequency controller with activated droop behavior (LogicsManager ID╚═▷ 12904)
reduces the desired frequency setpoint dependent on the active power of the generator
(ID╚═▷ 1752). In case of a full loaded engine the frequency setpoint will be reduced with
the percentage value (ID╚═▷ 5504) related to rated frequency.
freal
{
Frated
Droop
0.98 x Frated
P
0 Prated Prated
2
Fig. 164: Frequency controller - behavior with and without droop, diagram
The resulting frequency setpoint is calculated as follows: F'Set = FSet - (Preal * (Frated *
droop factor) / Prated)
The voltage controller with activated droop behavior (LogicsManager ID╚═▷ 12905)
reduces the desired voltage setpoint dependent on the reactive power of the generator
(ID╚═▷ 1758). In case of a full reactive loaded generator the voltage will be reduced with
the percentage value (ID╚═▷ 5604) of the rated frequency.
Vreal
{
Vrated
Droop
0.98 x Vrated
Q
0 Qrated Qrated
2
Fig. 165: Voltage controller - behavior with and without droop, diagram
The resulting voltage setpoint is calculated as follows: V'Set = VSet - (Qreal * (Vrated *
droop factor) / Qrated)
The droop tracking for frequency/voltage control is implemented such that when the
control is switched to frequency/voltage control with droop the frequency/voltage real
value does not change at the current active/reactive load. This is provided by pre-
calculating a setpoint offset, which is needed to hold rated frequency/voltage at present
load.
This is a feature in applications where for example the load sharing over communication
interface gets lost and the number of generators remains the same.
The easYgen allows disabling the droop tracking for frequency and voltage generally. This
makes sense in applications where the number of generators can vary during running in
droop mode.
Multiple easYgens are load sharing under each other, if they run islanded from mains or
they control export/import power at a common interchange point. For dynamic reasons it
makes sense to disable the load sharing, when the easYgens running in droop or can fall
into droop mode (Missing member case).
[Default]
5747 Droop tracking 2 [On] The frequency and voltage setpoint offset is pre-
calculated to hold the frequency and voltage, when
control is switched into droop.
5748 Load sharing in 2 [On] As long the load sharing function is enabled, it is
droop mode done in droop mode too.
Frequency control provides a kick impulse function, which issues a pulse if the frequency
control deadband (parameter ╚═▷ 5550) is not exceeded and no synchronization could be
performed for 20 seconds. The function is enabled, if a synchronization is carried out.
• If the phase angle is between 0° and 180°, a "frequency lower" signal is issued.
• If the phase angle is between 180° and 360°, a "frequency raise" signal is issued.
The pulse duration is 100ms. If the synchronization still fails, another pulse will be issued
after 10 seconds.
The following conditions are required for the kick impulse function:
Analog Managers to define input signal of frequency setpoint (1, 2) are available in
ToolKit by
[Default]
5092 Derivative ratio 2 2 0.01 to 100.00 This parameter defines the D part
of the 2nd PID controller. By
[0.01] increasing this parameter, the
stability of the system is
increased. The controller will
attempt to slow down the action
of the actuator in an attempt to
prevent excessive overshoot or
undershoot. Essentially this is the
brake for the process. This portion
of the PID loop operates anywhere
within the range of the process
unlike reset.
5508 Freq. control initial 2 0.0 to 100.0% The value entered for this
state parameter is the start reference
[50.0%] point for the analog output to the
(Frequency control speed controller.
initial state)
Notes
Notes
5511 Integral gain 2 0.01 to 100.00 The integral gain identifies the I
part of the PID controller.
[1.00]
Notes
5512 Derivative ratio 2 0.01 to 100.00 The derivative ratio identifies the
D part of the PID controller.
[0.01]
By increasing this parameter, the
stability of the system is
increased. The controller will
attempt to slow down the action
of the actuator in an attempt to
prevent excessive overshoot or
undershoot. Essentially this is the
brake for the process.
Notes
Example
Synchronization
Notes
5551 Time pulse minimum 1 0.01 to 2.00 s A minimum pulse on time must be
configured here.
[0.05 s]
The shortest possible pulse time
should be configured to limit
overshoot of the desired speed
reference point.
Notes
5552 Gain factor 1 0.1 to 10.0 The gain factor Kp influences the
operating time of the relays.
[5.0]
By increasing the number
configured in this parameter, the
operating time of the relay will be
in-creased in response to a
deviation from the frequency
reference.
Notes
5636 Cycle time factor 1 1.0 to 20.0 The cycle time factor adjusts the
time between the pulses (pause
[1.0] time).
Notes
Notes
Notes
Notes
5500 Int. freq. control 2 15.00 to 85.00 Hz The internal generator frequency
setpoint 1 setpoint 1 is defined in this
[50.00 Hz] screen.
(Internal frequency
control setpoint 1) This value is the reference for the
frequency controller when
performing islanded and/or no-
load operations.
Generally 50 Hz or 60 Hz will be
the values entered into this
parameter. It is possible to enter a
different value here.
Notes
5501 Int. freq. control 2 15.00 to 85.00 Hz The internal generator frequency
setpoint 2 setpoint 2 is defined in this
[50.00 Hz] screen.
(Internal frequency
control setpoint 2) This value is the reference for the
frequency controller when
performing islanded and/or no-
load operations.
Generally 50 Hz or 60 Hz will be
the values entered into this
parameter. It is possible to enter a
different value here.
5502 Slip frequency 2 0.00 to 0.50 Hz This value is the offset for the
setpoint offset synchronization to the busbar/
[0.10 Hz] utility.
Example
Notes
5506 Phase matching df- 2 0.02 to 0.25 Hz Phase matching will only be
start enabled if the frequency
[0.05 Hz] difference between the systems to
be synchronized is below the
configured value.
Notes
5503 Freq. control setpoint 2 0.10 to 60.00 Hz/s The different setpoint values are
ramp supplied to the controller via this
[2.50 Hz/s] ramp.
(Frequency control
setpoint ramp) The slope of the ramp is used to
alter the rate at which the
controller modifies the setpoint
value.
Notes
Example
Notes
12990 2nd Frequency PIDl 2 [02.01 False And 02.01 True This LogicsManager is used to
And 02.01 True] activate the 2nd Frequency PID
controller parameter set. If the
LogicsManager output is false the
1st Frequency PID controller
parameter set is taken.
Notes
A 2nd ramp is implemented to meet both BDEW and VDE AR-N 4105 decoupling
requirements
Additionally to the »Load control setpoint ramp« parameter ╚═▷ 5522 there is an
alternative (2nd) »Load control ramp decoupling« parameter ╚═▷ 5014 available for
ramping slower. So it is possible to follow the BDEW/VDE requirements
and
Default ramping is backward compatible because parameter ╚═▷ 5015 per default comes
with zero.
With LogicsManager ╚═▷ 12853 It is possible to activate the fastest load ramp e.g., for
test.
Analog Managers to define input signal of load setpoint (1, 2, 3, 4) are available in ToolKit
by
[Default]
Notes
5514 Integral gain 2 0.01 to 100.00 The integral gain identifies the I
part of the PID controller.
[1.00]
The integral gain corrects for any
offset (between setpoint and
process variable) automatically
over time by shifting the
proportioning band.
Notes
5515 Derivative ratio 2 0.01 to 100.00 The derivative ratio identifies the
D part of the PID controller.
[0.01]
By increasing this parameter, the
stability of the system is
Notes
Notes
5561 Time pulse minimum 1 0.01 to 2.00 s A minimum pulse on time must be
configured here.
[0.05 s]
The shortest possible pulse time
should be configured to limit
overshoot of the desired speed
reference point.
Notes
5562 Gain factor 1 0.1 to 10.0 The gain factor Kp influences the
operating time of the relays.
[5.0]
By increasing the number
configured in this parameter, the
operating time of the relay will be
in-creased in response to a
Notes
5637 Cycle time factor 1 1.0 to 20.0 The cycle time factor adjusts the
time between the pulses (pause
[1.0] time).
Notes
Notes
Notes
5522 Load control setpoint 2 0.10 to 100.0%/s The different setpoint values are
ramp 1 supplied to the controller via this
ramp. The slope of the ramp is
5014 Load control setpoint 2 0.01 to 100.0%/s The different setpoint values are
ramp 2 supplied to the controller via this
[0.15%/s] ramp. The slope of the ramp is
used to alter the rate at which the
controller modifies the setpoint
value. The faster the change in
the setpoint is to be carried out,
the greater the value entered here
must be.
Notes
11978 2nd load control 2 Determined by LogicsManager The LogicsManager can be used to
setpoint ramp 87.77 switch from load ramp 1 to load
ramp 2 settings.
[(0 & 02.02) & 02.02]
If this LogicsManager condition is
TRUE and load ramp will be
performed, »Load control setpoint
ramp 2« will be used.
5015 Time until setpoint 2 0 to 9999 s The mains decoupling ramp (2nd
ramp reset load ramp) will be disabled after
[0 s] that time delay.
Notes
5016 Load control setpoint 2 0.10 to 100.00 %/s The different setpoint values are
ramp 3 supplied to the controller via this
[3.00%/s] ramp. The slope of the ramp is
used to alter the rate at which the
controller modifies the setpoint
value. The faster the change in
the setpoint is to be carried out,
the greater the value entered here
must be.
Notes
11998 3rd load control 2 Determined by LogicsManger The LogicsManager can be used to
setpoint ramp 87.79 switch from load ramp 1 or load
ramp 2 to load ramp 3 settings. If
[(02.02 & 02.02) & 02.02] this LogicsManager condition is
TRUE and load ramp will be
performed, [Load control setpoint
ramp 3] will be used. (3rd load
control setpoint ramp has the
highest priority.)
12853 Disable load setpoint 2 Determined by LogicsManager The LogicsManager can be used to
ramp 87.76 perform fastest possible load
ramp independent from load ramp
[(02.01& 1) & 1] settings.
5569 Load control 2 0.10 to 100.00 [%/sec] The ramp rate is used for the
unloading ramp unloading in parallel operation or
3.00 [%/sec] islanded operation.
3465 Min. Generator power 1 0 to 100% This is the minimum active power
setpoint. Any lower other active
[0%] power setpoint will be ignored!
Notes
and
Analog Managers to define input signal of load setpoint (1, 2, 3, 4) are available in ToolKit
by
[Default]
5526 Load setpoint 1 2 Import The value entered for the import
level shall always be supplied by
the utility. All load swings are
absorbed by the generator(s)
provided the load rating for the
generator(s) is not exceeded. The
generator will always start when
an import power operation is
enabled.
5520 Int. load control 2 0.0 to 99999.9 kW The load setpoint 1 is defined in
setpoint 1 this screen. This value is the
[100.0 kW] reference for the load controller
(Internal load control when performing parallel
setpoint 1) operations.
5539 AM ActPower SP1 2 Determined by AnalogManager The load setpoint 1 source may be
[kW] 81.05 selected from the available data
sources.
[A1 = 05.54 Internal P setp1
[kW]] The internal load setpoint 05.54
can be changed manually at the
setpoint screen of the display.
Notes
5527 Load setpoint 2 2 Import The value entered for the import
level shall always be supplied by
the utility. All load swings are
absorbed by the generator(s)
provided the load rating for the
generator(s) is not exceeded. The
generator will always start when
an import power operation is
enabled.
5521 Int. load control 2 0.0 to 99999.9 kW The load setpoint 2 is defined in
setpoint 2 this screen. This value is the
[200.0 kW] reference for the load controller
(Internal load control when performing parallel
setpoint 2) operations.
5540 AM ActPower SP2 2 Determined by AnalogManager The load setpoint 2 source may be
[kW] 81.06 selected from the available data
sources.
[A1 = 05.55 Internal P setp2
[kW]] The internal load setpoint 05.55
can be changed manually at the
setpoint screen of the display.
Notes
Notes
5796 Load setpoint 3 2 Import The value entered for the import
level shall always be supplied by
the utility. All load swings are
absorbed by the generator(s)
provided the load rating for the
generator(s) is not exceeded. The
generator will always start when
an import power operation is
enabled.
5795 Int. load control 2 0.0 to 99999.9 kW The load setpoint 3 is defined in
setpoint 3 this screen. This value is the
[150.0 kW] reference for the load controller
(Internal load control when performing parallel
setpoint 2) operations.
5606 AM ActPower SP3 2 Determined by AnalogManager The load setpoint 3 source may be
[kW] 81.07 selected from the available data
sources.
[A1 = 05.80 Internal P setp3
[kW]] The internal load setpoint 05.80
can be changed manually at the
setpoint screen of the display.
Notes
Notes
5999 Load setpoint 4 2 Import The value entered for the import
level shall always be supplied by
the utility. All load swings are
absorbed by the generator(s)
provided the load rating for the
generator(s) is not exceeded. The
generator will always start when
an import power operation is
enabled.
5998 Int. load control 2 0.0 to 99999.9 kW The load setpoint 4 is defined in
setpoint 4 this screen. This value is the
[50.0 kW] reference for the load controller
(Internal load control when performing parallel
setpoint 4) operations.
5609 AM ActPower SP4 2 Determined by AnalogManager The load setpoint 4 source may be
[kW] 81.08 selected from the available data
sources.
[A1 = 05.84 Internal P setp4
[kW]] The internal load setpoint 05.84
can be changed manually at the
setpoint screen of the display.
Notes
Notes
[Default]
Notes
5533 Warm-up mode 2 Analog val contr The maximum load is limited to
the value configured in parameter
╚═▷ 5532 until the temperature
measured according to the setting
in parameter ╚═▷ 5538 has
exceeded the threshold configured
in parameter ╚═▷ 5546.
Notes
General notes
The current active power setpoint can be derated to a defined value according to the
application.
To ensure high flexibility the easYgen-XT offer the following derating functions:
• Direct derating
(Derating driven by ECU to prevent knocking of the engine. Refer to ╚═▷ “6.3.16.3
J1939 (ECU) Derating”.)
Application fields
Derating examples:
Uprating example:
• A single engine shall run with a higher load than the others e.g. for load test.
Block Diagram
This diagram shows the different paths of the selected derating sources:
Derating priority
If more than one derating function is configured the one which calculates the lowest
setpoint becomes effective.
Derating Parameters
[Default]
15149 Direct derating on/off 2 On Only the analog source is used for
the up-/derating. The parameters
15143, 15144, and 15145 are not
visible neither in the HMI nor in
ToolKit.
15145 Max. power deviation 2 1.0 to 100.0% This parameter defines the
maximal power deviation of the
[100.0%] derating function. That means it
determines also the minimal
power while derating is active.
15147 AM Derating source 2 Determined by AnalogManager This parameter defines the analog
81.21 source »Analog input 1« which
controls the derating function.
Indication of derating
As LM command variable 05.16 for derating If derating is active “Derating active” is shown in the
status message and command variable 05.16
becomes active.
The value of derating is shown under [Status menu / Next page / Setpoints / Derating]. In
case of derating this value has positive in case of uprating has negative sign.
Introduction
The FNN VDE-AR-N 4105 / 4110 requests an active power control to stabilize the grid
during mains faults. To maintain this the easYgen can be configured to:
• both.
The reference for the uprating or derating power can be calculated out of the actual
power or the rated power. This is differently treated in grid codes 4105 and 4110.
Function
Derating:
If the mains frequency exceeds the f start value ID 5782 the device calculates a power
reduction in relation to the configured rate.
If the mains frequency exceeds the f stop value ID 5095 the calculation will be disabled
and the active power controller regulates its original active power setpoint. Should the
active power setpoint be changed meanwhile the mains failure power ramp will be
activated.
Uprating
If the mains frequency underruns the f start value ID 5094 the device calculates a power
increase in relation to the configured rate. If the mains frequency exceeds the f stop value
ID 5095 the calculation will be disabled and the active power controller regulates its
original active power setpoint. Should the active power setpoint be changed meanwhile
the mains failure power ramp will be activated.
According to the VDE-AR-N 4110 a 200ms moving average mains frequency value is used.
The frequency can be picked up under ID 236 or is usable via the AnalogManager variable
“02.90 Mains freq.200ms [Hz]”.
[Default]
5807 Up/derating based on Rated power The reference for the active power
derating/uprating is adjustable with this
[Actual power] parameter.
Parameter Derating
[Default]
5782 f start value 15 to 85Hz If the mains frequency is higher than the
start value the frequency depending
[50.20Hz] derating function is enabled.
Parameter Uprating
[Default]
5094 f start value 15 to 85Hz If the mains frequency is lower than the
start value the frequency depending
[49.8Hz] uprating function is enabled.
For test purposes it is possible to configure a "Mains voltage test frequency" which is
passed to the uprating and derating characteristics.
[Default]
Start conditions
The power derating function becomes active, if the following conditions are true:
• Mains parallel operation active (MCB and GCB are closed) AND
Stop conditions
The power derating function becomes inactive and will be reset, if at least one of the
following conditions is true:
• Mains parallel operation not active (MCB and GCB are open ) OR
AnalogManager sources:
These analog variables indicate the derating respectively uprating percent value:
Visualization
Values which indicate the actual active power stored when the derating respectively
uprating function has started:
If the frequency increases the value FStart (Parameter ╚═▷ 5782), the momentary power
of the generator will be memorized by the controller as an internal value PM. (P
measured) and indicated at “4613 f dep. Derating P reference” [%]. Now, the power will
be derated with a gradient R [%/Hz](parameter ╚═▷ 5784).
• Prated = 200 kW
• PM = 130 kW
• FMains = 50.50 Hz
Example 1: Power derating with “5807 Up/derating based on" Actual power
◦ “10341 Freq. dep. derating of power” and “05.28 P derating(f) [%]” indicates
7.8 %
The derating becomes inactive, if the frequency becomes lower than FStop (Parameter
╚═▷ 5783) ). (If the frequency becomes too high, the frequency monitoring function trips.)
Example 2: Power derating with “5807 Up/derating based on" Rated power
• The power derating ΔP may be calculated using the following formulas: The power
derating ΔPkW is calculated as follows:
◦ “10341 Freq. dep. derating of power” and “05.28 P derating(f) [%]” indicates 12
%
The derating becomes inactive, if the frequency becomes lower than FStop (Parameter
╚═▷ 5783). (If the frequency becomes too high, the frequency monitoring function trips.)
If the frequency decreases, while the derating is still active, the behavior depends on
parameter “Hold max.derating” (parameter ╚═▷ 5785)
The derating ΔP decreases to 15.6 kW according to the gradient 40 %/Hz the power
is increasing to 114.4 kW.
The derating still remains at 26 kW the power remains at 104 kW. During an active
derating process, the power will never increase again. The power can only increase
again if the derating becomes inactive, that means that the measured frequency has
reached FStop.
General notes
The easYgen offers a function to reduce the power output of photovoltaic inverter (PV
Inverter). This could be important in cases where Gensets running side by side with PV
inverter. Mainly in island applications where the consumer load can be so low that a fixed
PV power drives the Gensets into reverse power. But even in cases where a minimal
generator load output is underrun over longer time it is beneficial to reduce the PV power.
To maintain this, the easYgen offers a PV load reduction respectively a PV load setpoint to
send to the PV inverter.
The PV load reference function contains a monitor of generator reverse power. It can
be used e.g. to open the PV inverter breaker when the reverse power becomes critical.
(Refer to ╚═▷ “4.5.6.15 Monitoring PV load reference”).
Function
With knowing the system load the easYgen3000XT regulates the PV power so that a given
generator load level is kept.
• The AM variable 10.39 PV load ref. [%] (PV set-point value 0% - 100%, can be
transferred to the PV inverter over an analog output)
• LM command variables (in applications using discrete load steps these LMs can be
transferred to the PV inverter over several digital outputs):
In addition, the variable ”10.39 PV load ref. [%]“ (ID 9766) can be sent to the PV inverter
via MODBUS TCP using the MODBUS MASTER (╚═▷ “6.5.5 Modbus master”)function of the
easYgen3000XT. It is indicated also in ToolKit with a gauge.
• If the Function is disabled (by parameter ╚═▷ 8911), the output 10.39 PV load ref.
[%] is 0%.
To provide a proper function the PV reduction must be tracked slowly. Reverse power of
the generator must lead to an instant cut of the PV load.
Photovoltaic
Load Reduction
P PV load
EG3000XT 1(3) ph voltage
AC
measurement
3 Digital outputs
DI/DO
Breaker feedback
GCB
0%...100% power
Com Modbus TCP
PID Modbus
Regulation Master
HMI
G
Fig. 168: Overview PV load reduction regulated mode
Parameter
[Default]
Notes
8918 Integral gain 2 0.01 to 10.00 The integral gain identifies the I
part of the PID controller.
[1.00]
The integral gain corrects for any
offset (between setpoint and
process variable) automatically
over time by shifting the
proportioning band.
Notes
8919 Derivative ratio 2 0.01 to 10.00 The derivative ratio identifies the
D part of the PID controller.
[1.00]
By increasing this parameter, the
stability of the system is
increased. The controller will
attempt to slow down the action
of the actuator in an attempt to
prevent excessive overshoot or
undershoot. Essentially this is the
brake for the process.
8920 Sampling time 2 0.1 to 99s This is the time between two
consecutive samples.
[0.5s]
8930 Setpoint ramp 1 0.1 to 10.0%/s This is the setpoint ramp for the
actual generator minimal load if
[1.0%/s] the regulation is enabled.
8921 Delay load increase 1 0.1 to 999.0s In applications using discrete load
step steps the next increasing step can
[10.0s] be delayed here.
8922 Delay load decrease 1 0.1 to 999.0s In applications using discrete load
step steps the next decreasing step
[5.0s] can be delayed here.
8912 Int.setpoint gen.min 1 1.0 to 100.0% This is the generator load level
load which shall be preferably not
[30.0%] underrun by PV power. The value
configured here is available as
analog variable ”15.01 Int.SP
gen.load [%]“.
General notes
The easYgen provides three additional freely configurable PID controllers. These
controllers are intended and optimized for slow processes, like temperature control for
heating systems (CHPO applications). The controller can either operate as a PID analog
controller or a three-position controller.
[Default]
16348
Notes
5670
= 11406/11407/11408
Notes
5573 Integral gain 2 0.010 to 10.000 The integral gain identifies the I
part of the PID controller. The
5586 [0.100] integral gain corrects for any
offset (between setpoint and
5672 process variable) automatically
over time by shifting the
proportioning band.
5574 Derivative ratio 2 0.001 to 10.000 The derivative ratio identifies the
D part of the PID controller. By
5587 [0.001] increasing this parameter, the
stability of the system is
5673 increased. The controller will
attempt to slow down the action
of the actuator in an attempt to
prevent excessive overshoot or
undershoot. Essentially this is the
brake for the process.
5575 Time pulse minimum 1 0.01 to 2.00 s A minimum pulse on time must be
configured here. The shortest
5588 [0.05 s] possible pulse time should be
configured, but the actuator
5674 should still react safe, to limit
overshoot of the desired value
reference point. (Only three-
position controller)
5578 PID{x} control actual 2 Determined by AnalogManager The PID {x} control actual value
value may be selected from the
5591 81.14, 81.16, 81.18: [A1 = 10.01 available analog data sources. It is
ZERO] possible to select all data sources
5677 (╚═▷ “9.4.2 Data Sources AM”).
5577 PID{x} control 2 Determined by AnalogManager The PID {x} control setpoint
setpoint source may be selected from the
5590 81.13, 81.15, 81.17: [A1 = available analog data sources. It is
05.75/76/77 Int. PID{x} possible to select all data sources
5676 setpoint] (╚═▷ “9.4.2 Data Sources AM”).
5579 Int. PID{x} control 1 -32000 to 32000 The internal setpoint is defined in
setpoint this screen. This value is the
5592 [0] reference for the PID {x}
controller.
5678
5581 PID{x} control initial 2 0 to 100% The value entered for this
state parameter is the start reference
5594 [50%] point for the analog output to the
controller as long as the
5680 LogicsManager is false. If the PID
controller has been disabled (e.g.
Parameter ╚═▷ 5571), the bias
output will change to 0 %.
5692 Actuator run time 2 0.1 to 999.0 s The actuator run time is
configured here. This is the time
5693 [30.0 s] the actuator needs to move from
fully closed to fully open. This
5694 information is necessary because
the controller does not receive a
feedback of the actuator position
and needs this value to calculate
the desired actuator position.
General notes
The frequency / load and voltage / reactive power setpoints may be raised and lowered
using the LogicsManager functionality, i.e. it is possible to use LogicsManager command
variables to raise and lower these setpoints. In this case the discrete raise/lower function
always starts with the rated value (frequency / load and voltage / reactive power).
Most commonly a button may be used to energize a discrete input on the control, which is
used again as a LogicsManager command variable to enable the respective
LogicsManager function to change the setpoint.
Frequency and voltage may be adjusted within the configured operating limits (╚═▷
“4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”). Active power may
be adjusted between 0 and the configured load control setpoint maximum
(parameter ╚═▷ 5523). The power factor may be adjusted between 0.71 leading and 0.71
lagging.
[Default]
Notes
Notes
Notes
Notes
5024 Discrete ramp f +/- 2 000.01 ... 100.00 %/s Configurable ramp rate for
frequency setpoint raise and lower
[000.07 %/s] commands.
5025 Discrete ramp V +/- 2 000.01 ... 100.00 %/s Configurable ramp rate for voltage
setpoint raise and lower
[000.70 %/s] commands.
5026 Discrete ramp P +/- 2 000.01 ... 100.00 %/s Configurable ramp rate for active
power setpoint raise and lower
[003.00 %/s] commands.
5027 Discrete ramp Power 2 000.01 ... 100.00 %/s Configurable ramp rate for Power
Factor +/- Factor (PF) setpoint raise and
[007.50 %/s] lower commands.
The priority of operation modes is well defined from highest to lowest priority:
[Default]
Notes
• 1. STOP
• 2. MANUAL
• 3. AUTOMATIC
• 4. TEST
Notes
= 10715 Notes
12520 Operat. mode MAN 2 Determined by LogicsManager Once the conditions of the
86.17 LogicsManager have been fulfilled
(Activate operating the unit will change into operating
mode MANUAL) [(0 & 1) & 1] mode MANUAL.
Notes
12530 Operat. mode STOP 2 Determined by LogicsManager Once the conditions of the
86.18 LogicsManager have been fulfilled
(Activate operating the unit will change into operating
mode STOP) [(0 & 1) & 1] mode STOP.
Notes
12271 Operat. mode TEST 2 Determined by LogicsManager Once the conditions of the
86.29 LogicsManager have been fulfilled
(Activate operating the unit will change into operating
mode TEST) [(0 & 1) & 1] mode TEST.
Notes
General notes
The start of the engine can be performed via the following different logical conditions.
• A discrete input
• A temperature level
• A timer
If this logical output becomes TRUE in AUTOMATIC operating mode, the generator starts
and the GCB will be closed. The simultaneous activation of other LogicsManager outputs
(e.g. Stop req. in Auto) may affect this function.
The breaker handling depends on the configured application mode and breaker logic.
Refer to ╚═▷ Fig. 169 and ╚═▷ “9.3.4 Logical Outputs” for the priority of the logical
outputs in case that more than one logical output is TRUE.
[Default]
12120 Start req. in AUTO 2 Determined by LogicsManager Once the conditions of the
86.09 LogicsManager have been fulfilled,
(Start request in the control issues a start request
operation mode [(09.02 Discrete input OR 0) in AUTOMATIC mode.
AUTOMATIC) OR 04.13 Remote request]
Notes
= 10708
For information on the
LogicsManager and its default
settings see ╚═▷ “9.3.1
LogicsManager Overview”.
12190 Stop req. in AUTO 2 Determined by LogicsManager If this logical output becomes
86.10 TRUE, it inhibits all other start
(Stop request in processes (e.g. Start req. in Auto,
operation mode [(0 & 1) & 1] emergency power, etc.). Stopping
AUTOMATIC) of the engine can be initiated
= 10709 externally via a discrete input or
any logical combination.
Notes
It is possible to interrupt an
already activated emergency run.
Notes
Operation mode TEST gives the opportunity to test the genset. It can be activated via HMI
button »TEST« or parameter 4672 »Test run mode«.
In TEST mode the breakers are operated like in the application mode configured. The
handling in the setpoint screen is be the same like in the AUTOMATIC mode.
Emergency run (AMF) and sprinkler run -- if configured -- both are fully supported.
[Default]
4672 TEST run mode 2 [No load w/o time] With enabling the operation mode
TEST, the engine starts
[Default]
Notes
4679 TEST mode time 2 [60 s] This is the time duration for the
restriction time restricted TEST mode.
0..9999 s
[Default]
Parallel
• The MCB is not active
• With the GCB button the load test can be started and
interrupted
• If the GCB trips the load test is interrupted
Interchange
• With the GCB button and the MCB button the load test can be
started and interrupted
• The load transfer is similar to the AUTOMATIC mode
• If the GCB trips the load test is interrupted and the MCB will
be closed if the condition matches:
◦ Release MCB
◦ Mains okay
External
• The MCB button isn't active
• With the GCB button the load test can be started and
interrupted
• Only the GCB open logic is active similar to AUTOMATIC mode
• If the GCB trips the load test is interrupted
The critical mode may be used to operate a fire engine pump or any other critical
operation which does not allow a shutdown of the genset under any alarm conditions.
The LogicsManager is used to define the conditions that will enable the critical mode like
a discrete input (for conditions and explanation of programming refer to ╚═▷ “9.3.1
LogicsManager Overview”).
Alarm classes
When critical mode is enabled the alarm classes are reclassified as follows:
Alarm classes
Normal operation A B C D E F
Critical mode A B B B B B
During the postrun time all shutdown alarms become active again.
A critical mode will be initiated/started once the critical mode operation LogicsManager
output becomes TRUE (logic "1"). The "Critical mode" message is displayed on the display
screen. If the engine is not already running, the controller will attempt to start the engine
as configured (parameter ╚═▷ 4102). All shutdown alarms become warning messages
(see above).
If the operation mode changes to STOP, the postrun time will still be performed.
Refer to ╚═▷ “9.3.4 Logical Outputs” for more information about the priorities of the
logical outputs.
The fire engine pump mentioned before or other critical operation is connected to the
busbar, i.e. it requires a closed GCB to be supplied by the generator during critical
operation.
Parameter ╚═▷ 4100 (Close GCB in critical mode) should be configured to "Yes" and an
external provision for load reduction should be provided. This ensures the pump operation
of a sprinkler system.
The GCB will not be closed if the load is supplied by the mains until the mains fail and the
MCB remains closed because emergency run (parameter ╚═▷ 2802) is disabled.
If critical mode is enabled during mains supply (MCB is closed), the generator will be
started (if not already running) and the GCB will be closed.
• The "Critical mode" message is displayed on the display screen. All shutdown alarms
become warning messages.
• If critical mode is disabled again, all shutdown alarms become active again.
If the genset was not running before critical mode has been enabled, it will be stopped
after the critical mode postrun time (parameter ╚═▷ 4102) has expired. MCB operation
will be performed according to the configured transition mode.
If there is a mains failure during critical mode, the "Emerg/Critical" message is displayed
on the display screen after the mains fail delay time (parameter ╚═▷ 2800) has expired.
◦ The emergency power operation will be continued and all shutdown alarms
become active again.
◦ If the mains returns, the unit transfers the load from generator supply to mains
supply after the mains settling delay expires.
• Emergency power operation ends before the end of the critical mode:
◦ The critical mode is maintained and the load is transferred from generator
supply to mains supply after the mains settling delay expires.
◦ If open transition mode is configured, the GCB will not be opened to prevent a
dead busbar.
◦ The engine remains running until the conditions for the critical mode are no
longer existent.
◦ If the genset was not running before critical mode has been enabled, it will be
stopped after cool down time (parameter ╚═▷ 3316) has expired.
◦ The GCB will take the same state as it had before the critical mode has been
enabled.
An emergency power operation is active (load is supplied by the generator, GCB is closed,
MCB is open). If critical mode is enabled now, the GCB remains closed and the "Emerg/
Critical" message is displayed on the display screen. All shutdown alarms become
warning messages.
◦ The emergency power operation will be continued and all shutdown alarms
become active again.
◦ If the mains return, the unit transfers the load from generator supply to mains
supply after the mains settling delay expires, if Enable MCB (parameter ╚═▷
12923) has been enabled.
• Emergency power operation ends before the end of the critical mode:
◦ The critical mode is maintained and the load is transferred from generator
supply to mains supply after the mains settling delay expires.
◦ The engine remains running until the conditions for the critical mode are no
longer existent.
◦ If the genset was not running before critical mode has been enabled, it will be
stopped after cool down time (parameter ╚═▷ 3316) has expired.
◦ The GCB will take the same state as it had before the critical mode has been
enabled.
The critical mode operation has a higher priority than the remote request (Start/Stop
request in AUTO). Therefore, the remote request cannot start or stop the engine and has
no effect on the breaker positions. The "Critical mode" message is displayed on the
display screen and all shutdown alarms become warning alarms.
◦ The engine continues running. All shutdown alarms will become active again.
◦ By resetting the start request the GCB will be opened and the engine will be
stopped.
◦ The engine keeps running until the conditions for the critical mode are no
longer fulfilled and all shutdown alarms will become active again.
◦ If the genset was not running before critical mode has been enabled, it will be
stopped after cool down time (parameter ╚═▷ 3316) has expired.
◦ The GCB will take the same state as it had before the critical mode has been
enabled.
The fire engine pump mentioned before or other critical operation is connected to the
generator, i.e. it does not require a closed GCB to be supplied by the generator during
critical operation.
Parameter ╚═▷ 4100 (Close GCB in critical mode) should be configured to "No". This
ensures an open GCB during critical mode. A closed GCB is possible in case of an
emergency operation.
If critical mode is enabled during mains supply (MCB is closed), the generator will be
started (if not already running) and operated with open GCB. The "Critical mode"
message is displayed on the display screen. All shutdown alarms become warning
messages.
If critical mode is disabled again, all shutdown alarms become active again. If the genset
was not running before critical mode has been enabled, it will be stopped after the critical
mode postrun time (parameter ╚═▷ 4102) has expired.
If there is a mains failure during critical mode, the MCB will be opened after the mains fail
delay time (parameter ╚═▷ 2800) has expired and the GCB will be closed. It is not
necessary to configure parameter ╚═▷ 4101 (Break emerg. in critical mode) because the
critical operation is already supplied. The "Emerg/Critical" message is displayed on the
display screen and all shutdown alarms become warning messages.
◦ The emergency power operation will be continued and all shutdown alarms
become active again.
◦ If the mains returns, the unit transfers the load from generator supply to mains
supply after the mains settling delay expires.
• Emergency power operation ends before the end of the critical mode:
◦ The critical mode is maintained and the load is transferred from generator
supply to mains supply after the mains settling delay expires.
◦ If the genset was not running before critical mode has been enabled, it will be
stopped after cool down time (parameter ╚═▷ 3316) has expired.
An emergency power operation is active (load is supplied by the generator, GCB is closed,
MCB is open). If critical mode is enabled now, the GCB will be opened dependent on the
setting of the parameter ╚═▷ 4101 (Break emerg. in critical mode) and a closure of the
GCB is prevented for this time. The "Emerg/Critical" message is displayed on the display
screen and all shutdown alarms become warning messages.
◦ The emergency power operation will be continued and all shutdown alarms
become active again.
◦ If the mains return, the unit transfers the load from generator supply to mains
supply after the mains settling delay expires.
• Emergency power operation ends before the end of the critical mode:
◦ The critical mode is maintained and the load is transferred from generator
supply to mains supply after the mains settling delay expires.
◦ If the genset was not running before critical mode has been enabled, it will be
stopped after cool down time (parameter ╚═▷ 3316) has expired.
The critical mode operation has a higher priority than the remote request (Start/Stop
request in AUTO). Therefore, the remote request cannot start or stop the engine and has
no effect on the breaker positions. The "Critical mode" message is displayed on the
display screen and all shutdown alarms become warning alarms.
◦ The critical mode operation is continued. The engine keeps running until the
conditions for the critical mode are no longer fulfilled and all shutdown alarms
will become active again.
◦ If the genset was not running before critical mode has been enabled, it will be
stopped after cool down time (parameter ╚═▷ 3316) has expired.
◦ The GCB will take on the same state as it has before the critical mode has been
enabled.
The generator supplies the load and the GCB is closed. If critical mode is enabled, the
MCB will be operated according to the configured transition mode (parameter ╚═▷ 3411).
The GCB will be opened without unloading (transition mode interchange or parallel). The
"Critical mode" message is displayed on the display screen and all shutdown alarms
become warning alarms.
◦ The engine keeps running until the conditions for the critical mode are no
longer fulfilled and all shutdown alarms will become active again.
◦ If the genset was not running before critical mode has been enabled, it will be
stopped after cool down time (parameter ╚═▷ 3316) has expired.
The busbar is supplied by the generator and emergency run (parameter ╚═▷ 2802) is
disabled. If the critical mode is enabled, the GCB will be opened although the MCB is not
enabled. This will cause a dead busbar.
4.4.5.4.3 Parameters
[Default]
Notes
4105 Critical mode alarm 2 Yes The critical mode alarm classes
class MAN will override the normal operation
alarm classes when in MANUAL
(Critical mode alarm operation mode so alarm classes
classes active in become restricted to WARNING
MANUAL operating level - NO engine shut down.
mode ) LogicsManager output ╚═▷ 12220
becomes TRUE.
General notes
Refer to ╚═▷ “9.6.2 Load Dependent Start Stop (LDSS) Formulas” for all formulas related
to the LDSS function.
If the "Start stop mode" (parameter ╚═▷ 5752) is configured to »Generator load«, load-
dependent start stop is performed in a way that the next genset will be started if all
gensets in operation reach the maximum generator load (parameter ╚═▷ 5762 or ╚═▷
5770 "IOP/MOP Max. generator load"), a configured percentage (e.g. 80%) of the rated
power. In order to stop one generator, the load of all gensets in operation must fall below
the minimum generator load (parameter ╚═▷ 5763 or ╚═▷ 5771 "IOP/MOP Min. generator
load"), a configured percentage (e.g. 30%) of the rated power. There are different
setpoints for islanded and mains parallel operation.
The LDSS algorithm acting on »Generator load« offers different dynamic levels:
• With higher dynamic the efficiency can be increased, but the change of generators
becomes more frequent.
• With lower dynamic the efficiency can be lower for the first couple of engines, but
overall the change of generators becomes less frequent.
High:
• After removing of generator rated power the new generator load level shall not lay
higher than 75% within the Add-on / Add-off band.
Moderate:
• After removing of generator rated power the new generator load level shall not lay
over 50% within the Add-on / Add-off band.
Low:
• After removing of generator rated power the new generator load level shall not lay
over 25% within the Add-on / Add-off band
An additional dynamic parameter (parameter ╚═▷ 5757 or ╚═▷ 5758 "IOP/MOP Dynamic")
with levels "Low", Moderate", and "High" prevents the gensets from being started and
stopped continuously if only a few gensets are in operation.
This function provides an easy calculation for the start of the next genset.
5770 MOP Max. generator load only for mains parallel operation
If the configured maximum generator capacity utilization is exceeded, another genset will
be added.
If the configured minimum generator capacity utilization has been fallen below, a genset
will be stopped depending on the dynamic setting (parameter ╚═▷ 5757).
If the required generator load setpoint for the control at the mains interchange point
exceeds the MOP minimum load threshold (parameter ╚═▷ 5767), the first genset will be
added.
If at least one genset is supplying the load in parallel with the mains and the total
generator load exceeds the MOP maximum generator load threshold (parameter ╚═▷
5770), another genset will be added.
If at least two gensets are supplying the load in parallel with the mains and the
configured minimum generator capacity utilization has been fallen below, a genset will be
stopped depending on the dynamic setting (parameter ╚═▷ 5758)
If one genset is supplying the load in parallel with the mains and the generator load
exceeds the MOP minimum load threshold (parameter ╚═▷ 5767) minus the hysteresis
(parameter ╚═▷ 5769), the genset will be stopped.
The hysteresis is intended to prevent frequent starting and stopping of gensets in case of
small load variations.
• PMNsetpoint – PMNreal + PGN real active < PMOP minimum – Physteresis MOP
If the "Start stop mode" (parameter ╚═▷ 5752) is configured to "Reserve power", load-
dependent start stop is performed in a way that a configured minimum reserve power is
maintained in the system. This means that there is always enough reserve power for load
swings on the busbar regardless of the generator load. The actual reserve power in the
system is the total rated power of all gensets on the busbar minus the actual total
generator real power.
This functionality provides high system reliability and is intended for applications that
require a dedicated reserve power on the busbar, independent of the number of gensets
on the busbar.
Note:
It is also possible to change the effective reserve power via interface. Refer to:
If the reserve power falls below the IOP reserve power threshold (parameter ╚═▷ 5760),
another genset will be added.
If the reserve power exceeds the IOP reserve power threshold (parameter ╚═▷ 5760) plus
the hysteresis (parameter ╚═▷ 5761) plus the rated load of the genset, the genset will be
stopped.
The hysteresis is intended to prevent frequent starting and stopping of gensets in case of
small load variations.
If the required generator load setpoint for the control at the mains interchange point
exceeds the MOP minimum load threshold (parameter ╚═▷ 5767), the first genset will be
added.
If at least one genset is supplying the load in parallel with the mains and the reserve
power falls below the reserve power threshold (parameter ╚═▷ 5768), another genset will
be added.
If at least two gensets are supplying the load in parallel with the mains and the reserve
power exceeds the MOP reserve power threshold (parameter ╚═▷ 5768) plus the
hysteresis (parameter ╚═▷ 5769) plus the rated load of the genset, the genset will be
stopped.
The hysteresis is intended to prevent frequent starting and stopping of gensets in case of
small load variations.
If one genset is supplying the load in parallel with the mains and the generator load
exceeds the MOP minimum load threshold (parameter ╚═▷ 5767) minus the hysteresis
(parameter ╚═▷ 5769), the genset will be stopped.
The hysteresis is intended to prevent frequent starting and stopping of gensets in case of
small load variations.
• PMN setpoint – PMN real + PGN real active < PMOP minimum – Physteresis MOP
General notes
If a genset is to be started, the genset with the highest priority configured will be started.
If a genset is to be stopped, the genset with the lowest priority configured will be
stopped.
If all gensets have the same priority, the next genset is selected according to the size of
engine, i.e. the genset combination, which allows an optimum efficiency will be used.
If all gensets have the same rated load or this parameter is disabled, the remaining hours
until the next maintenance are considered. If these are also the same, the genset with
the lowest generator number will be started first or stopped last.
Priority order:
The load-dependent start/stop function requires the following conditions have been met:
• All LDSS parameters are configured identically for all members at the load share line
(╚═▷ “4.5.6.16 Multi-Unit Parameter Alignment”)
• The mains interchange load control (import/export power) has been enabled or the
gensets are in islanded operation
[Default]
= 11915 Notes
Notes
Notes
Notes
Notes
Notes
Example 1
• "Changes of engines" is
configured to "All 64h"
• Generator 1 has 262
maintenance hours
remaining
• Generator 2 has 298
maintenance hours
remaining
• The time group for generator
1 is calculated as: 262h/64h
= 4.09 = Time group 4
• The time group for generator
2 is calculated as: 298h/64h
= 4.66 = Time group 4
Example 2
• "Changes of engines" is
configured to "All 64h"
• Generator 1 has 262
maintenance hours
remaining
• Generator 2 has 345
maintenance hours
remaining
• Generator 3 has 298
maintenance hours
remaining
• The time group for generator
1 is calculated as: 262h/64h
= 4.09 = Time group 4
• The time group for generator
2 is calculated as: 345h/64h
= 5.39 = Time group 5
• The time group for generator
3 is calculated as: 298h/64h
= 4.66 = Time group 4
• Generators 1 and 3 are in
time group 4.
• Time group 4 consists of any
generator that the time
group calculation total
ranges from 4.00 through
4.99.
• Generator 2 is in time group
5.
• Time group 5 consists of any
generator that the time
group calculation total
ranges from 5.00 through
5.99.
Notes
Notes
General notes
In case of an islanded parallel operation (MCB open), the first genset will be connected to
the de-energized busbar.
There are dedicated LDSS parameters for islanded parallel operation because the supply
of the load is important here.
[Default]
5760 IOP Reserve power 2 1 to 999999 kW The value configured for the
reserve power determines when
an additional generator will be
= Reserve power
Notes
5648 IOP Reserve power 2 2 1 to 999999 kW The value configured for the
reserve power determines when
[200 kW] an additional generator will be
started. The reserve power is the
desired spinning reserve of a
generator or generators. The
reserve power is usually
estimated as the largest load
swing that a power plant may
encounter during the time it takes
to bring an additional generator
online.
= Reserve power
Notes
12604 IOP Reserve power 2 2 Determined by LogicsManager Once the conditions of the
86.41 LogicsManager have been fulfilled,
the 'IOP Reseve power 2'
[(0 & 1) & 1] (parameter ╚═▷ 5648) is used
instead of the 'IOP Reseve power'
= 11975 (parameter ╚═▷ 5760).
Notes
Notes
5762 IOP Max. generator 2 0 to 100% If the generator load exceeds the
load threshold configured here, the
[70%] load-dependent start/stop function
will start another genset.
Notes
5763 IOP Min. generator 2 0 to 100% If the generator load falls below
load the threshold configured here, the
[30%] load-dependent start/stop function
will stop a genset. If only a few
gensets are operating in a multi-
Notes
Starting genset
Stopping genset
Stopping genset
Stopping genset
Stopping genset
Notes
• Low:
• Moderate:
• High:
5764 IOP Add on delay 2 0 to 32000 s Load swings may exceed the
threshold momentarily. In order to
[10 s] prevent the engine from starting
due to short-term load swings, a
delay time may be configured.
5765 IOP Add on delay at 2 0 to 32000 s The command to start the next
rated load genset in case a genset exceeds
[3 s] rated load will be issued after the
delay configured here has expired.
Notes
5766 IOP Add off delay 2 0 to 32000 s Load swings may fall below the
threshold momentarily. In order to
[60 s] prevent the engine from stopping
due to short-term load swings, a
delay time may be configured.
General notes
In case of a mains parallel operation (MCB closed), load-dependent start stop is only
enabled, if the gensets participates in load sharing at the interchange point (all
participating gensets must be configured to the same setpoint).
A minimum load threshold must be exceeded to start the first genset, i.e. a genset will
only be started if a minimum load would be demanded from the generator.
[Default]
Example
Notes
Notes
Notes
12605 MOP Reserve power 2 2 Determined by LogicsManager Once the conditions of the
86.42 LogicsManager have been fulfilled,
the 'MOP Reseve power 2'
[(0 & 1) & 1] (parameter ╚═▷ 5649) is used
instead of the 'MOP Reseve power'
= 11976 (parameter ╚═▷ 5768).
Notes
5770 MOP Max. generator 2 0 to 100% If the generator load exceeds the
load threshold configured here, the
[70%] load-dependent start/stop function
will start another genset.
Notes
5771 MOP Min. generator 2 0 to 100% If the generator load falls below
load the threshold configured here, the
[30%] load-dependent start/stop function
will stop a genset.
Notes
Starting genset
Stopping genset
Stopping genset
Stopping genset
Stopping genset
Notes
5772 MOP Add on delay 2 0 to 32000 s Load swings may exceed the
threshold momentarily. In order to
[20 s] prevent the engine from starting
due to short-term load swings, a
delay time may be configured.
5773 MOP Add on delay at 2 0 to 32000 s The command to start the next
rated load genset in case a genset exceeds
[3 s] rated load will be issued after the
delay configured here has expired.
Notes
5774 MOP Add off delay 2 0 to 32000 s Load swings may fall below the
threshold momentarily. In order to
[60 s] prevent the engine from stopping
due to short-term load swings, a
delay time may be configured.
For further information, please refer to application examples to ╚═▷ “6.3.15 LDSS with
predicted load”.
Introduction
In case of a mains failure, the usual LDSS function of the easYgen starts either one or all
generators. This is done so because during the mains failure the consumer load
information is lost. The LDSS with predicted load (LDSS PL) can start the correct amount
of generators based on the last mains power measurements (5-minutes average value).
The LDSS PL takes the 5-minutes average value as mains load into account and passes it
to the LDSS function as consumer load. The LDSS function can thereby start the correct
amount of gensets according to that predicted load. A prerequisite for this function is the
availability of a group breaker (GGB) in the application. The GGB allows to switch the
correct amount of generators onto the load.
• The LDSS PL differentiates two source modes as base for the predicted consumer
load calculation:
◦ 1. Internal source mode: The mains power and breaker handling is provided by
the easYgenXT.
◦ 2. External source mode: The mains power, the MCB and GGB control is
provided by an external device (e.g. ATS), connected via CANopen with
easYgen.
General
To the time the engines are not started and the mains is feeding the load the LDSS PL
calculates a mains load with a 5-minute average value. This load value is passed to the
LDSS function as consumer load. So the LDSS can determine the correct amount of
engines which must be started if a start command becomes active. See ╚═▷ “General”:
Switches are in “Pos.1” and “Pos. A”.
In the moment the start request becomes active the average load calculation is frozen.
See ╚═▷ “General”: switches are in “Pos.2” and “Pos. A”.
If all requested engines are successful started and have closed their GCBs the LDSS PL
gives the release for closing the GGB. From this time on the 5-minute average load
calculation will be fed with the easYgen calculated generator load. See ╚═▷ “General”:
switches are in “Pos.3”; “Pos. B”
The LDSS function now does not differ anymore to the original function. There will be
started and stopped the correct generators according to the common LDSS parameters.
The external source mode is dedicated for external installed ATS controls which measure
the mains power. The system allows up to 5 ATS controls at the Interchange point.
In this mode, external ATS controls send information via CANopen RPDO messages. The
easYgen provides information going to the ATS control.
The internal source mode is dedicated to use the own mains power measurement
assigned via Analogmanager .
The external ATS control sends information in CANopen RPDO messages. The easYgen
provides information going to the ATS control.
[Default]
9066 Predicted load source 2 internal Internal: LDSS with predicted load
is using internal data. (LM 86.09
[external] “Start req. in AUTO” and AM 81.30
“Consumer load [kW]”)
General notes
The emergency power operation is possible only in application mode A04 (2 power circuit
breakers).
If the LogicsManager outputs 'Stop request in AUTO' or 'Inhibit emergency run' are TRUE,
an emergency power operation may be prevented or interrupted from an external
source.
Prerequisites
• The emergency power function can only be activated for synchronous generators
with parameter ╚═▷ 2802.
• Emergency power is carried out in operating mode AUTOMATIC regardless of the
status of the LogicsManager output 'Start request in AUTO' (LogicsManager).
• The GCB can be closed regardless of the engine delay time if the generator
frequency and voltage are within the configured operating limits (╚═▷ “4.5.1.1
Generator Operating Ranges: Voltage / Frequency / Busbar”) if the parameter
"Undelay close GCB" (parameter ╚═▷ 12210) has been set accordingly (default
setting).
• If the mains return during an emergency power operation (GCB is closed), the mains
settling time (parameter ╚═▷ 2801) must expire before the load is transferred from
the generator to mains operation.
If the mains are not within the configured frequency and voltage operating limits (╚═▷
“4.5.3.3 Mains Operating Ranges”) for at least the time configured in the parameter
"Mains fail delay time" (parameter ╚═▷ 2800), an emergency power operation is
activated.
MCB malfunction
An emergency power operation will be performed, if the control is not able to close or
recluse the MCB and the alarm "Fail to close MCB" occurs.
If the mains returns after a mains failure with a reversed rotation direction the generator
remains in emergency power operation until the mains rotation matches the rotation of
the generator set.
The generator will not start upon a mains rotation field alarm, but it will keep on running
if it has already started.
[Default]
2800 Mains fail delay time 2 0.00 to 99.99 To start the engine and to carry
out an emergency operation the
(Mains failure start [3.00 s] monitored mains must be failed
delay) continuously for the minimum
period of time set with this
parameter.
Notes
Notes
= 10710 Notes
It is possible to interrupt an
already activated emergency run.
Formerly (non-XT easYgen) several monitoring functions could be delayed each by use of
parameter "Delayed by engine speed". Exchanging it by the new parameter "Enabled"
introduces the one-change-switch of all monitoring functions by LogicsManager 11459
LM 87.70 Release Engine Monitoring.
With software revision 1.13 or higher each monitoring LogicsManager can be enabled
alternatively by one of 32 Flags.
Factory settings ensure same behavior of each affected monitoring function as of non-XT
easYgen series before.
The operating voltage/frequency/busbar parameters are used to check if the values are
in range when performing a dead bus closure and synchronization of the generator.
Busbar 1 must be within this ranges to synchronize the generator to the busbar.
[Default]
[Default]
Busbar monitoring
Busbar monitoring compares the actual voltage and frequency of the busbar with the
configured generator operating ranges. The voltage operating range is configured with
the "Upper voltage Limit" and "Lower voltage limit" parameter. The frequency operating
range is configured with the "Upper frequency limit" and "Lower frequency limit"
parameter. If the measured busbar voltage or frequency deviates from the operating
range for a time exceeding the configurable delay, an alarm will be issued.
[Default]
5119 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
[Default]
Notes
General notes
If this protective function is triggered, the display indicates "Gen. overvoltage 1" or
"Gen. overvoltage 2" and the logical command variable "06.05" or "06.06" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function. The diagrams listed there show a frequency trend and the associated
pickup times and length of the alarms.
The parameter limits listed below have identical setting ranges. Each parameter may be
configured with different settings to create unique trip characteristics for specific
thresholds.
[Default]
Notes
2001 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2007 2001: [B] specifies what action should be
taken when the limit is surpassed.
2007: [F]
Notes
General notes
If this protective function is triggered, the display indicates "Gen. undervoltage 1" or
"Gen. undervoltage 2" and the logical command variable "06.07" or "06.08" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function. The diagrams listed there show a frequency trend and the associated
pickup times and length of the alarms.
The parameter limits listed below have identical setting ranges. Each parameter may be
configured with different settings to create unique trip characteristics for specific
thresholds.
This monitoring function is disabled when the idle mode (╚═▷ “4.4.1.4 Idle Mode”) is
active.
[Default]
Notes
Notes
2051 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2057 2051: [B] specifies what action should be
taken when the limit is surpassed.
2057: [F]
Notes
General notes
The voltage asymmetry monitors absolute value of all three phase-phase voltage
difference: dV1=|V12- V23|, dV2=|V23- V31| and dV3=|V31- V12|. If one of measured dV1,
dV2 or dV3 exceeds a configured permissible asymmetrical limit, an alarm is issued.
The percentage of permissible asymmetrical limit refers to the generator rated voltage.
If this protective function is triggered, the display indicates "Gen. volt. asymmetry" and
the logical command variable "06.18" will be enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
This monitoring function is only enabled if Generator voltage measuring (parameter ╚═▷
1851) is configured to "3Ph 4W" or "3Ph 3W".
[Default]
(Hysteresis: 0.5%)
Notes
Notes
3901 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[F] specifies what action should be
taken when the limit is surpassed.
Notes
General Notes
The easYgen-3000XT detects the frequency out of up to six voltages (L1-N, L2-N, L3-N,
L1-L2, L2-L3 and L3-L1). The frequency measurement (of all three systems) additionally
checks the values on plausibility. With this monitoring the easYgen can detect wrong
wiring issues.
It might occur that for example a generator frequency is measured even if the generator
is not running. This can happen e.g. if PE (terminal 61) is not connected, the generator
neutral connection is broken, and mains is energized with 1Ph2W connection. In this case
a potential shift occurs which could lead to "ghostly" voltages at the generator (or
busbar, or mains) phase-neutral system. This voltages lead to a frequency measurement
even if no voltage is detected in the generator phase-phase system.
This »Plausibility AC wiring « monitoring function is only active if the wiring can provide
"Phase-Phase" and "Phase-Neutral" values.
The plausibility monitoring offers one setting for all three measurement systems. The
Monitor is placed under: [Parameter / Configure: Monitoring / Miscellaneous: Other
monitoring] .The alarm indications are called Gen. .../Busbar .../Mains AC wiring (see ╚═▷
“9.5.5 Alarm Messages”).
[Default]
[Default]
General notes
This controller provides the user with two alarm levels for generator overfrequency. Both
alarms are definite time alarms.
If this protective function is triggered, the display indicates "Gen. overfrequency 1" or
"Gen. overfrequency 2" and the logical command variable "06.01" or "06.02" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function. The diagrams listed there show a frequency trend and the associated
pickup times and length of the alarms.
The parameter limits listed below have identical setting ranges. Each parameter may be
configured with different settings to create unique trip characteristics for specific
thresholds.
[Default]
Notes
Notes
1901 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
1907 1901: [B] specifies what action should be
taken when the limit is surpassed.
1907: [F]
Notes
output "External
acknowledgment" (via a discrete
input or via an interface).
General notes
This controller provides the user with two alarm levels for generator underfrequency. Both
alarms are definite time alarms.
If this protective function is triggered, the display indicates "Gen. underfrequency 1" or
"Gen. underfrequency 2" and the logical command variable "06.01" or "06.02" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function. The diagrams listed there show a frequency trend and the associated
pickup times and length of the alarms.
The parameter limits listed below have identical setting ranges. Each parameter may be
configured with different settings to create unique trip characteristics for specific
thresholds.
[Default]
Notes
1951 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
1957 1951: [B] specifies what action should be
taken when the limit is surpassed.
1957: [F]
Notes
General notes
Monitoring of the maximum phase current is performed in three steps. Every step can be
provided with a delay time independent of the other steps.
If this protective function is triggered, the display indicates "Gen. overcurrent 1",
"Gen. overcurrent 2", or "Gen. overcurrent 3" and the logical command variable "06.09",
"06.10.", or "06.11" will be enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
2201 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2207 2201: [E] specifies what action should be
taken when the limit is surpassed.
2213 2207: [F]
Notes
2213: [F]
For additional information refer to
╚═▷ “9.5.4 Alarm Classes”
2215
87.70 LM:Eng.mon Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
General notes
The tripping time is faster as the measured current increases in magnitude according to a
defined curve. According to IEC 255 three different characteristics are available.
If this protective function is triggered, the display indicates "Inv. time overcurr." and the
logical command variable "06.22" will be enabled.
t = 80 / (I/IP)2 - 1) * tP[s]
Variables:
• t =tripping time
• for Istart:
• for IP the smaller IP is, the steeper is the slope of the tripping curve
The maximum tripping time is 327 s. If a tripping time greater than 327 s is configured,
an overcurrent fault condition will not be recognized.
Characteristics
[Default]
4037 Inv time overcurr. 2 100.0 to 300.0% Lower tripping value for inverse
Istart = time-overcurrent protection. If the
[115.0%] monitored current is less than
Istart, the inverse time-overcurrent
(Hysteresis: 1%) protection does not trip. If Istart is
less than IP, IP is used as the lower
(Reset Delay: 1 s)
tripping value.
4031 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[F] specifies what action should be
taken when the limit is surpassed.
Notes
General Notes
This function is an add-on to the over current monitoring and decreases the activation
limit dependent on the amount of voltage dip. Especially in near to generator located
over currents it can lead to situations, where the failure current remains under the
generator rated current. In this case a normal over current monitoring does not trip. The
voltage restraint over current monitoring considers this and decreases the configured
over current limit according to a modification factor, that it comes to a trip.
The considered voltages are either the single phase-phase or phase-neutral voltages.
(Refer to "Generator voltage monitoring" ╚═▷ 1770). The monitor takes always the lowest
considered voltage into account for calculating the modification factor.
Voltage restraint over current monitoring can be activated individually for “Generator
over current (limit 1-3)” and Generator inverse time over current, if the according
parameter 2227 “Voltage restraint monitoring” is switched to “Yes”.
The modification factor depends on the measured voltage in percent of rated voltage. It is
defined by a characteristic which is defined by three parameters (ID 2230, 2231, 2232 cf.
figure). This characteristic is taken into account for all over current monitoring functions,
if enabled.
Beginning at a voltage dip of 95% rated voltage (configured by 2231), the modification
factor will be linearly reduced (cf. figure 86). If the voltage reaches 25% or less
(configured by 2230) the modification factor will remain at 25% (configured by 2232).
Supposed the configured limit of an over current monitor is 110% and the measured
voltage is 25%:
The V (voltage) start value configuration must be entered higher as the V stop value
configuration. Otherwise the function does not work properly!
[Default]
2231 V start current 2 5.0 ... 100.0% Voltage for starting current limitation reduction
lim. reduction
[95.0%]
2230 V stop current 2 5.0 ... 100.0% Voltage for stopping current limitation reduction
lim. reduction
[25.0%]
[Default]
2232 Min. factor 2 5.0 ... 100.0% Minimum factor limit for current limitation reduction
limit
overcurrent [25.0%]
General notes
The power produced by the generator is calculated from the voltage and current values
measured in accordance with how parameters "Generator voltage measuring" (parameter
╚═▷ 1851) and "Generator current measuring" (parameter ╚═▷ 1850) are configured. The
controller monitors if the system is in a mains parallel or an islanded operation.
When the controller detects that the system is operating islanded from the mains, the
Generator Overload MOP (refer to ╚═▷ “4.5.1.5.2 Generator Overload MOP (Level 1 & 2)
ANSI# 32”) monitoring is disabled. If the measured generator real power during an
islanded operation is above the configured limit an alarm will be issued.
If this protective function is triggered, the display indicates "Gen. Overload IOP 1" or
"Gen. Overload IOP 2" and the logical command variable "06.14" or "06.15" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
Notes
2301 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2307 2301: [B] specifies what action should be
taken when the limit is surpassed.
2307: [D]
Notes
96.{xx} Example:
General notes
The power produced by the generator is calculated from the voltage and current values
measured in accordance with how parameters "Generator voltage measuring"
(parameter ╚═▷ 1851) and "Generator current measuring" (parameter ╚═▷ 1850) are
configured.
The controller monitors if the system is in a mains parallel or an islanded operation. When
the controller detects that the system is operating parallel with the mains, the Generator
Overload IOP (refer to ╚═▷ “4.5.1.5.1 Generator Overload IOP (Level 1 & 2) ANSI# 32”)
monitoring is disabled. If the measured generator real power during a mains parallel
operation is above the configured limit an alarm will be issued.
If this protective function is triggered, the display indicates "Gen. Overload MOP 1" or
"Gen. Overload MOP 2" and the logical command variable "06.23" or "06.24" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
Notes
2351 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2357 2351: [B] specifies what action should be
taken when the limit is surpassed.
2357: [D]
Notes
General notes
The power produced by the generator is calculated from the voltage and current values
measured in accordance with how parameters "Generator voltage measuring"
(parameter ╚═▷ 1851) and "Generator current measuring" (parameter ╚═▷ 1850) are
configured.
The generator power limits may be configured for reduced power and/or reverse power
depending on the threshold values entered. The note below explains how a reduced or
reverse power limit is configured.
If the single-phase or three-phase measured real power is below the configured limit of
the reduced load or below the configured value of the reverse power, an alarm will be
issued.
If this protective function is triggered, the display indicates "Gen. rev./red. pwr.1" or
"Gen. rev./red. pwr.2" and the logical command variable "06.12" or "06.13" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
Definition
• Reduced power Fault initiated if the monitored real power falls below the configured
(positive) limit.
• Reverse power Fault initiated if the direction of the monitored real power reverses
and the configured (negative) limit is exceeded.
Configuration examples
The values for reverse /reduced power monitoring can be configured as follows:
☼ Example
☼ Example
☼ Example
[Default]
Notes
2251 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2257 2251: [B] specifies what action should be
taken when the limit is surpassed.
2257: [F]
Notes
General notes
If this protective function is triggered, the display indicates "Unbalanced load 1" or
"Unbalanced load 2" and the logical command variable "06.16" or "06.17" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
Formulas
Exceeding IL1 ≥ (3 * IN * PA + IL2 + IL3) / 2 IL2 ≥ (3 * IN * PA + IL1 + IL3) / 2 IL3 ≥ (3 * IN * PA + IL1 + IL2) / 2
Falling below IL1 ≤ (IL2 + IL3- 3 * IN * PA) / 2 IL2 ≤ (IL1 + IL3- 3 * IN * PA) / 2 IL3 ≤ (IL1 + IL2- 3 * IN * PA) / 2
Examples
[Default]
Notes
2401 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2407 2401: [B] specifies what action should be
taken when the limit is surpassed.
2407: [E]
Notes
[Default]
Notes
Notes
[Default]
5101 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
[Default]
[Default]
Notes
Notes
5107 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
[Default]
General notes
If enabled, this monitoring function becomes only active if generator power control is
enabled (refer to ╚═▷ “4.4.4.5 Load Control”). If the measured generator power deviates
from the power setpoint by a value exceeding the limit configured in parameter ╚═▷ 2925
for a time exceeding the delay configured in parameter ╚═▷ 2923, an alarm will be
issued.
If this protective function is triggered, the display indicates "Gen act.pwr mismatch" and
the logical command variable "06.29" will be enabled.
[Default]
Notes
Notes
2921 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
This monitoring function is always enabled and becomes active when a stop command is
issued. Following a stop command, the controller tries to reduce the power before
opening the GCB. If the power falls below the unload limit (parameter ╚═▷ 3125) before
the delay (parameter ╚═▷ 3123) expires, a "GCB open" command will be issued. If the
controller fails to reduce the power to fall below the unload limit (parameter ╚═▷ 3125)
before the delay (parameter ╚═▷ 3123) expires, a "GCB open" command will be issued
together with an alarm.
If this protective function is triggered, the display indicates "Gen. unloading fault" and
the logical command variable "06.30" will be enabled.
[Default]
Notes
3121 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
The power factor is monitored for becoming more lagging (i.e. inductive) than an
adjustable limit. This limit may be a lagging or leading power factor limit. There are two
lagging power factor alarm levels available in the control. This monitoring function may
be used for monitoring an overexcitation with a warning and a shutdown alarm level. Both
alarms are definite time alarms.
• is activated,
• is blocked,
╚═▷ Fig. 179 shows an example of a leading and a lagging power factor limit and the
power factor range, for which the lagging power factor monitoring issues an alarm.
If this protective function is triggered, the display indicates "Gen. PF lagging 1" or
"Gen. PF lagging 2" and the logical command variable "06.25" or "06.26" will be enabled.
Power Factor
-0.40 +0.85
-0.50 -0.75 1.00 +0.75 +0.50
[Default]
(Hysteresis: 0.02%)
Notes
2326 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2332 2326: [B] specifies what action should be
taken when the limit is surpassed.
2332: [B]
Notes
General notes
The power factor is monitored for becoming more leading (i.e. capacitive) than an
adjustable limit. This limit may be a leading or lagging power factor limit. There are two
leading power factor alarm levels available in the control. This monitoring function may
be used for monitoring an under excitation with a warning and a shutdown alarm level.
Both alarms are definite time alarms.
Refer to ╚═▷ “6.3.1 Generator Excitation Protection” for a detailed description of this
monitoring function.
• is activated,
• is blocked,
╚═▷ Fig. 180 shows an example of a leading and a lagging power factor limit and the
power factor range, for which the leading power factor monitoring issues an alarm.
If this protective function is triggered, the display indicates "Gen. PF leading 1" or
"Gen. PF leading 2" and the logical command variable "06.27" or "06.28" will be enabled.
[Default]
Notes
2376 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2382 2376: [B] specifies what action should be
taken when the limit is surpassed.
2382: [B]
Notes
4.5.1.6.2 Miscellaneous
General notes
If this protective function is triggered, the display indicates "Ground fault 1" or "Ground
fault 2" and the logical command variable "06.19" or "06.20" will be enabled.
The ground fault protection zone is determined by the location where the generator
current transformer are physically installed.
⚙ Test
1. ▷ Short-circuit one of the three generator current transformers while the generator is at
full load.
▶ The measured current should read 100% of rated on the two phases that do not have
their current transformers short-circuited.
The ground current calculation does not take current on the neutral conductor into
consideration. In order for the controller to be able to perform calculated ground fault
current protection accurately, the neutral conductor must not conduct current.
The fault threshold value is configured as a percentage. This percentage threshold refers
to the generator rated current (parameter ╚═▷ 1754). Due to unavoidable load
asymmetries, the minimum value for this parameter should be 10% or greater.
Calculation
1 No ground fault
The pointer between the neutral point and the point of the shifted pointer IL2' results is
the sum current IS as shown in (╚═▷ Fig. 182/2).
In order to be able to add the pointers vectorially, these must be divided into their X- and
Y-coordinates (IL2X, IL2Y, IL3X and IL3Y).
The ground fault current may be calculated using the following formula:
Ground fault current is actively measured when the mains current input is configured to
monitor for ground current. The ground fault threshold is configured as a percentage of
the value entered for parameter "Generator rated current" (parameter ╚═▷ 1754).
The ground fault protection zone is determined by the physical installation location of the
generator current transformer.
[Default]
Notes
3251 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
3257 3251: [B] specifies what action should be
taken when the limit is surpassed.
3257: [F]
Notes
General notes
NOTICE!
• Ensure that the control unit is properly connected to phase voltages on both sides of
the circuit breaker(s) during installation.
Failure to do so may result in damage to the control unit and/or generation equipment
due to the breaker closing asynchronously or with mismatched phase rotations. Also
ensure that phase rotation monitoring is enabled at all connected components (engine,
generator, breakers, cable, busbars, etc.).
This function will block a connection of systems with mismatched phases only under the
following conditions:
• The voltages being measured are wired correctly with respect to the phase rotation
at the measuring points (i.e. the potential transformers in on both sides of the
circuit breaker)
• The voltages being measured are wired so that angular phase shifts or any
interruptions from the measuring point to the control unit do not exist
• The voltages being measured are wired to the correct terminals of the control unit
(i.e. L1 phase of the generator is connected with the terminal of the control unit
which is intended for the generator L1 phase)
• The configured alarm class is of class C, D, E, or F (shutdown alarm).
Correct phase rotation of the phase voltages ensures that damage will not occur during a
breaker closure to either the mains or the generator. The voltage phase rotation alarm
checks the phase rotation of the measured voltages and the configured phase rotation to
ensure they are identical.
The directions of rotation are differentiated as "clockwise" and "counter clockwise". With
a clockwise field the direction of rotation is "L1-L2-L3"; with a counter clockwise field the
direction of rotation is "L1-L3-L2". If the control is configured for a clockwise rotation and
the measured voltages are monitored as counterclockwise, the alarm will be initiated.
The direction of configured rotation being monitored by the control unit is displayed on
the screen.
If this protective function is triggered, the display indicates "Gen.ph.rot. mismatch" and
the logical command variable "06.21" will be enabled.
This monitoring function is only enabled if Generator voltage measuring (parameter ╚═▷
1851) is configured to "3Ph 4W", "3Ph 3W", or "3Ph 4W OD" and the measured voltage
exceeds 50 % of the rated voltage (parameter ╚═▷ 1766) or if Generator voltage
measuring (parameter ╚═▷ 1851) is configured to "1Ph 2W" (in this case, the phase
rotation is not evaluated, but defined by the 1Ph2W phase rotation (parameter ╚═▷
1859)).
[Default]
Notes
3951 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[F] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
There are different circumstances possible to bring a synchronous generator into a pole
slip situation. This monitor here is established for pole slip cases, when the genset is
running parallel to grid. Because in mains instability situations in conjunction with being
longer parallel to grid (VDE-AR-N 4105/4110) it can lead to situations that the
synchronous generator goes through pole-slips. These pole slips stress the genset
mechanically very hard and must be monitored. Finally the generator is to decouple from
mains, if the pole-slip rate reaches a scale which damages the genset.
Function
A pole slip situation is detected through observing the power output of the generator in a
special moment (refer to release pole slip). In this moment when the power changes from
positive to negative and back to positive one pole slip event is detected.
• The mains parallel operation is detected (GCB closed, MCB closed and “GGB closed”)
• The Generator active power is higher than a configurable “Min. active power
threshold”
• The difference between active power and active power set point is higher than the
threshold. If the active power controller is not active (external active power control),
the threshold must be set to 0%.
• The active power has changed from positive to negative and back to positive.
If during released pole slip monitoring no pole slip event is encountered anymore for a
configurable time the event counter is reset.
If, during released pole slip monitoring, no pole slip event is encountered anymore for a
configurable time, the event counter is reset.
[Default]
2417 Min. active power 2 0 to 150% With reaching once this minimum
active power in parallel operation
[10%] the pole slip monitoring is
released. The entry is related to
generator rated power.
2420 Reset time pole slip 2 10 to 999s During released pole slip
events monitoring and with a pole slip
[60s] counter which is not increased
anymore for this time, the pole
slip counter will be reset.
2421 Alarm class 2 Class A-F/Control Pole slip alarm class Default alarm
class D opens the GCB and stops
[Class D] the engine after cooldown timer.
[No]
Alarm
The device indicates and stores the text "Pole slip" (ID2425).
Visualization
LogicsManager
The device provides the LM command variable "LM 06.36 Gen pole slip" (10674).
AnalogManager
The device provides the AM variable "AM 01.86 Number pole slip" (9765).
General notes
The speed measured by the magnetic pickup unit (MPU) is monitored for overspeed. If the
MPU is disabled, the speed may only be monitored using the generator overfrequency
monitoring. If the MPU speed exceeds the overspeed limits the configured alarms will be
initiated.
If this protective function is triggered, the display indicates "Overspeed 1" or "Overspeed
2" and the logical command variable "05.01" or "05.02" will be enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
2101 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2107 2101: [B] specifies what action should be
taken when the limit is surpassed.
2107: [F]
Notes
General notes
The speed measured by the magnetic pickup unit (MPU) is monitored for underspeed. If
the MPU is disabled or not available, the speed may only be monitored using the
generator underfrequency monitoring. If the MPU speed falls below the underspeed limits
the configured alarms will be initiated.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
2151 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2157 2151: [B] specifies what action should be
taken when the limit is surpassed.
2157: [F]
Notes
General notes
Speed detection checks if the generator voltage frequency f (determined from the
measured generator voltage) differs from the measured engine speed n (determined from
the Pickup signal or the speed measured via ECU/J1939) and determines a difference (Δf-
n).
If the two frequencies are not identical (Δf-n ≠ 0) and the monitored frequency mismatch
reaches or exceeds the threshold, an alarm is output. Additionally the LogicsManager
output "Firing speed" is checked upon its logical status with respect to the measuring
values "generator frequency" and "Pickup speed".
If this protective function is triggered, the display indicates "Speed/freq. mismatch" and
the logical command variable "05.07" will be enabled.
1. A MPU is connected to the control and parameter "Speed pickup" (parameter ╚═▷
1600), is configured On.
Mismatch monitoring is carried out using the engine speed from the Pickup and the
generator frequency. If the speed/frequency mismatch or the LogicsManager is enabled
and the frequency is outside of the configured limit, an alarm will be issued.
Mismatch monitoring is carried out using the generator frequency and the
LogicsManager. If the LogicsManager output is enabled and the frequency is outside of
the configured limit, an alarm will be issued.
[Default]
Notes
Notes
2451 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[E] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
If it is not possible to start the engine within a configured number of start attempts (refer
to ╚═▷ “4.4.1.2 Engine Start/Stop”), an alarm will be initiated.
If this protective function is triggered, the display indicates "Start fail" and the logical
command variable "05.08" will be enabled.
[Default]
3304 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[F] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
If it is not possible to stop the engine within a configured time, an alarm will be initiated.
If this protective function is triggered, the display indicates "Eng. stop malfunct." and the
logical command variable "05.06" will be enabled.
[Default]
Notes
2501 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[F] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
If an engine stop has been detected without a stop command being issued, an alarm will
be initiated.
If this protective function is triggered, the display indicates "Unintended stop" and the
logical command variable "05.05" will be enabled.
[Default]
2651 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[F] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
The charge alternator monitoring issues an alarm if the voltage measured at the auxiliary
excitation input D+ (terminal 65) falls below a fix limit.
The fix limit depends on the power supply voltage. If a power supply voltage exceeding
15 V is detected, the unit assumes a 24 V system and uses a limit of 20 V. If a power
supply voltage below 15 V is detected, the unit assumes a 12 V system and uses a limit of
9 V.
If this protective function is triggered, the display indicates "Charge alt. low volt" and the
logical command variable "05.11" will be enabled.
[Default]
Notes
General Notes
Up to 20 temperatures monitored!
Gas engines needs to be monitored for equal exhaust or cylinder head temperatures. If
one cylinder temperature deviates too much from the others, something must be wrong.
This could be for example a failed spark plug or a too hot combustion.
The easYgen-3000XT series provides a monitor which supervises the deviation of a single
temperature to the average temperature of a group. Whereby either one average
temperature exists (inline engine) or two average temperatures are available (V-engine
with two banks).
• overrun,
• underrun
• or both.
The temperatures could be provided by either CAN J1939 (SPN 1137 - 1156, 20 ports) for
example Axiomatic Thermocouple Scanner or by External Analog Inputs (AI1 - AI16, 16
ports) for example Phoenix Temperature Module.
Monitoring Function
The monitor compares the single temperature deviations from the average temperature
of the according bank. An inline engine has only one group (one bank), so all
temperatures are usually allocated to bank 1. A V-engine has two groups (two banks), so
the single temperatures are distributed to bank 1 and bank 2. The monitoring mode is
valid for all temperatures. The monitoring mode can be 'Off', 'Overrun', 'Underrun' or
'Overrun and Underrun'. The mode is valid for all banks.
A cylinder with sensor defect is removed from the average temperature calculation and
trips an independent alarm!
• Wire break
Command Variables
Analog Variables
Alarm Screen
• The square contains a '!' exclamation point sign, if the sensor is missing (wire break)
or error was detected
• If an alarm occurs and the monitor is still active, the new alarm is linked by logic 'OR'
to the others
• The monitor ignores values of cylinders with wire break or sensor defect
• The alarm trip displaying is removed, if the alarm of the according level was
successful acknowledged
• The wire break trip has a higher priority as the limit monitoring. That means: with
up-coming wire break only the according trip bits are RESET. Other cylinders not
touched.
General monitoring
[Default]
= 11460
Notes
Level 1
[Default]
8878 Minimum generator 2 000.0 ... 150.0% When the generator power
power exceeds this value the level 1
[30.0%] monitoring is activated.
[100° C]
8880 Delay 2 0000 ... 9999 s Time between *** exceeds limits
and *** is activated.
[60 s]
8881 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned to an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Level 2
[Default]
8883 Minimum generator 2 000.0 ... 150.0% When the generator power
power exceeds this value the level 2
[30.0%] monitoring is activated.
[150° C]
8886 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned to an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
[Default]
8885 Delay 2 0000 ... 9999 s Time between *** exceeds limits
and *** is activated.
[60 s]
[Default]
8890 Delay 2 0000 ... 9999 s Time between *** exceeds limits
and *** is activated.
[2 s]
8888 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned to an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Temperature X Bank
[Default]
8856 Bank selct cylinder 2 [Off] The temperature does not exist.
{x}
to Bank 1 The temperature exists and is
located in cylinder bank 1.
8875
Bank 2 The temperature exists and is
located in cylinder bank 2.
Cylinder status
Each cylinder is represented by a 2-bit combination that has the following meanings:
• 00 - OK
• 01 - Overrun
• 10 - Underrun
• 11 - Error/missing
These two bits are carried by parameters ID 3352 ..3354 for the cylinders of bank 1 and
ID 3355..3357 for the cylinders of bank 2:
2 2..3 2 2..3
8 14..15 8 14..15
10 2..3 10 2..3
16 14..15 16 14..15
18 2..3 18 2..3
19 4..5 19 4..5
20 6..7 20 6..7
4.5.3 Mains
[Default]
Notes
General notes
The operator can deactivate the mains monitoring features and the decoupling function.
A dedicated LogicsManager is installed to disable all mains monitoring and the decoupling
function.
Already latched alarms (self acknowledge = No) are not removed from the alarm list by
this function.
• Mains decoupling
• Mains df/dt
[Default]
General notes
The mains operating voltage/frequency parameters are used to trigger mains failure
conditions and activate an emergency run.
The mains values must be within this ranges to synchronize the mains circuit breaker. It
is recommended to configure the operating limits within the monitoring limits.
Example
If the mains rated voltage is 400 V, the upper voltage limit is 110 % (of the mains rated
voltage, i.e. 440 V), and the hysteresis for the upper voltage limit is 5 % (of the mains
rated voltage, i.e. 20 V), the mains voltage will be considered as being out of the
operating limits as soon as it exceeds 440 V and will be considered as being within the
operating limits again as soon as it falls below 420 V (440 V – 20 V).
If the rated system frequency is 50 Hz, the lower frequency limit is 90 % (of the rated
system frequency, i.e. 45 Hz), and the hysteresis for the lower frequency limit is 5 % (of
the rated system frequency, i.e. 2.5 Hz), the mains frequency will be considered as being
out of the operating limits as soon as it falls below 45 Hz and will be considered as being
within the operating limits again as soon as it exceeds 47.5 Hz (45 Hz + 2.5 Hz).
[Default]
Notes
Notes
Introduction
After mains decoupling from the power generation device, with under-/over frequency or
under-/over voltage, the automatic reconnection to the grid after the mains settling time
is only possible, if the mains is within the following operation ranges.
The operation ranges for mains reconnecting uses the voltages according to the
configured mains voltage monitoring (ID 1771 Mains voltage monitoring, phase-phase/
phase-neutral/All). Only if all considered voltages are back in band the synchronization to
mains will be executed.
[Default]
General notes
The mains decoupling function is intended for use in a mains parallel operation and
monitors a series of subordinate mains protection thresholds. If a threshold is exceeded,
the genset control initiates a breaker opening and separates the generator(s) from the
mains at the defined breaker.
• Overvoltage level 2 (╚═▷ “4.5.1.2.1 Generator Overvoltage (Level 1 & 2) ANSI# 59”)
If one of these protective functions is triggered, the display indicates "Mains decoupling"
(the logical command variable "07.25" will be enabled) and the active level 2 alarm.
The mains decoupling function is optimized on the both relay outputs "GCB open" and
"MCB open". In case of using a free relay output in conjunction with the command
variable 07.25 an additional delay time of up to 20 ms is to consider.
When the mains decoupling function detects a breaker open failure, the according
breaker alarm will be triggered as long the monitoring function is activated. Additionally
in cases where the decoupling mode has to change over to the other breaker,
(GCB®MCB, MCB®GCB), the alarm text “Decoupling GCB«MCB“ is indicated. The breaker
open alarm already occurs after the mains decoupling feedback delay (refer to ID ╚═▷
3113).
[Default]
12922 Ext. mns. decoupl. 2 Determined by LogicsManager The unit may be configured to
86.27 decouple from the mains when
(External mains commanded by an external
decoupling) [(0 & 1) & 1] device.
Notes
3113 Mains decoupling 2 0.2 to 99.9 s If the open signal from the
feedback delay respective circuit breaker cannot
[0.4 s] be detected within the time
configured here, the mains
decoupling function performs the
action as configured in
parameter ╚═▷ 3110.
3111 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
Notes
It is recommended to configure
the operating limits (parameter
╚═▷ 5810 to ╚═▷ 5817) within the
monitoring limits.
Notes
It is recommended to configure
the operating limits (parameter
╚═▷ 5810 to ╚═▷ 5817) within the
monitoring limits.
Notes
It is recommended to configure
the operating limits (parameter
╚═▷ 5810 to ╚═▷ 5817) within the
monitoring limits.
Notes
It is recommended to configure
the operating limits (parameter
╚═▷ 5810 to ╚═▷ 5817) within the
monitoring limits.
Notes
General notes
The German Grid Code VDE-AR-N 4105 instructs the handling of electrical energy sources
running parallel to the low voltage grid. This rule has an impact with some items on the
genset control. A more detailed description relating to that VDE rule is done through the
separated application note “easYgen-3000_VDE-AR-N 4105” on the manual CD of this
product.
Here are some functions which have to be covered according to the 4105 rule:
◦ Phase shift OR
◦ df/dt
The VDE-AR-N 4105 demands a Single-failure-proof of the mains decoupling function. That
means that the decoupling of the generator from the mains must be always ensured,
even if a single element in the system fails. So the system must contain two circuit
breakers with two independent monitoring functions acting individually on each breaker.
From the perspective of the network provider that rule pursuits the mains protection but
not the availability of the electrical source, so in case of doubt the generator should be
decoupled from mains.
Woodward solves this requirement with the use of a minimum of two units acting as a
system (for example two easYgens or an easYgen and an LS-5 with 4105 functionality).
The system allows incorporating more units, so that the availability of the generator can
still be increased.
The demanded two breakers in series are realized through the use of a GCB and a MCB. If
only a GCB is available, the customer must install another circuit breaker in addition.
Using Ethernet?
Monitoring according VDE AR-N 4105 per default is [Off]. It can be enabled via ToolKit
[Configure Monitoring / Mains: Other monitoring / Setup VDE-AR-N 4105] or via Menu (see
screen ╚═▷ Fig. 186).
[Default]
Notes
[Default]
Notes
2860 Limit
2861 Delay
2910 Limit
2911 Delay
2960 Limit
2961 Delay
3010 Limit
3011 Delay
8807 Limit
[Default]
Notes
[Default]
output "External
acknowledgment" (via a discrete
input or via an interface).
[Default]
Notes
The BDEW Grid Code instructs the handling of electrical energy sources running parallel
to the medium voltage grid. This rule has an impact with some items on the genset
control. A more detailed description relating to that BDEW technical guideline can be
ordered directly by the BDEW Germany. With easYgen-3000... genset control series
functions which have to be covered according to this BDEW rule are supported.
• Q(V) Monitoring
The Change of frequency monitors (vector/phase shift or df/dt) is not directly required by
BDEW. These monitors are depending on the according network providers.
◦ Power Factor Control. Refer to ╚═▷ “4.4.4.2 Power Factor Control” for details.
◦ Power Factor Characteristic. Refer to ╚═▷ “4.4.4.2 Power Factor Control” for
details.
General notes
There are two overfrequency alarm levels available in the control. Both alarms are
definite time alarms and are illustrated in the figure below. The figure diagrams a
frequency trend and the associated pickup times and length of the alarms. Monitoring of
the frequency is accomplished in two steps.
If this protective function is triggered, the display indicates "Mains overfreq. 1" or
"Mains overfreq. 2" and the logical command variable "07.06" or "07.07" will be enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
Notes
Notes
Notes
2851 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2857 2851: [A] specifies what action should be
taken when the limit is surpassed.
2857: [B]
Notes
General notes
There are two underfrequency alarm levels available in the control. Both alarms are
definite time alarms and are illustrated in the figure below. The figure diagrams a
frequency trend and the associated pickup times and length of the alarms. Monitoring of
the frequency is performed in two steps.
If this protective function is triggered, the display indicates "Mains underfreq. 1" or
"Mains underfreq. 2" and the logical command variable "07.08" or "07.09" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
Notes
Notes
Notes
2901 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2907 2901: [A] specifies what action should be
taken when the limit is surpassed.
2907: [B]
Notes
General notes
If this protective function is triggered, the display indicates "Mains overvoltage 1" or
"Mains overvoltage 2" and the logical command variable "07.10" or "07.11" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
Notes
Notes
2951 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2957 2951: [A] specifies what action should be
taken when the limit is surpassed.
2957: [B]
Notes
Notes
It is recommended to configure
the operating limits (parameter
╚═▷ 5810 to ╚═▷ 5817) within the
monitoring limits.
General notes
If this protective function is triggered, the display indicates "Mains undervoltage 1" or
"Mains undervoltage 2" and the logical command variable "07.12" or "07.13" will be
enabled.
Refer ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
Notes
Notes
3001 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
3007 3001: [A] specifies what action should be
taken when the limit is surpassed.
3007: [B]
Notes
Notes
It is recommended to configure
the operating limits (parameter
╚═▷ 5810 to ╚═▷ 5817) within the
monitoring limits.
General notes
If this protective function is triggered, the display indicates "Mains volt. increase". The
alarm can be incorporated into the mains decoupling function.
The average is set to "Mains rated voltage" (parameter ╚═▷ 1768) if:
• The 10 minute average value is smaller than the defined limit AND
• The actual measured value is inside the operating range AND
• The mains settling time is over
Please be aware that if "Mains voltage monitoring" (parameter ╚═▷ 1771) is configured
to "All" and the mains voltage increase monitoring (parameter ╚═▷ 8806) is used, that
this function only monitors "Phase - neutral".
(In future releases (higher than 2.10-0) in this case ”Phase – neutral“ and ”Phase -
Phase“ will be monitored.)
[Default]
Notes
8831 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
General notes
Both monitors behave similar but each with a separate Fault-Ride-Through (FRT) curve.
[Default]
On Time-dependent voltage
monitoring does cause a
decoupling.
4951 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
If the measured voltage falls below/exceeds this curve, the monitoring function triggers
and LogicsManager 07.28 becomes TRUE. The mains decoupling function is incorporated,
if configured. If the measured voltage falls below/exceeds the configured "Fallback
threshold" (parameter ╚═▷ 4978) for at least the configured "Fallback time" (parameter
╚═▷ 4968), the time-dependent voltage monitoring sequence will be reset.
The threshold curve results from seven configurable points and a linear interpolation
between these points. ╚═▷ Fig. 187 shows an example of a Low-Voltage-Ride-Through
(LVRT) curve for time-dependent voltage monitoring. The curve is configured by default
according to a typical grid code requirement.
The time points should always have an ascending order. The fallback threshold
(parameter ╚═▷ 4978) should always be configured to a value higher/lower than the
initial threshold (parameter ╚═▷ 4970).
The monitor behaves according to the configured »AND characteristic« (parameter 4960).
When the AND characteristic is configured to "On", all 3 phases are taken into account.
Only if all phases are below/above the configurable curve, the monitor will trip. When the
AND characteristic is configured to "Off", the single phases are taken into account. Even if
only one phase runs below/above the configurable curve, the monitor will trip.
The monitoring starts with passing the initial threshold. The tripping time is determined
by the voltage deviation and its according curve location. The monitoring is disabled, if
the voltage value (values) have crossed the fallback threshold. The monitor trips the
LogicsManager 07.28 command variable 10877.
Parameter "Mains voltage monitoring" ╚═▷ 1771 determines, if the Ph-Ph, Ph-N, or all
measurements are used.
If type "All" is available and configured, and 3Ph4W is configured, "Time dependent
Voltage Monitoring" is calculated with phase-phase and phase-neutral voltages. If All and
1Ph3W is configured, only PH-N values are used.
Due the higher prioritization of the Dynamic Mains Stabilization (FRT) as the ROCOF
monitor, the ROCOF monitor must be disabled for longest 5 seconds when any FRT curve
was initiated. Therefore each FRT (=Time-dependent voltage monitoring) function
provides a flag. The flag is set, if the particular initiation threshold is passed. The flag is
reset if all monitored voltages are back in band (parameter ╚═▷ 4978).
The 3 flags are OR’ed and results in one “FRT initiated” flag. This flag will be kept TRUE
for maximal 5 seconds. Finally this ROCOF blocking flag will be inverted and entered as
LM Command Variable “07.34 FRT ROCOF enable”.
Time-dep. voltage 1
[Default]
[Default]
Notes
4971 Point {x} voltage 2 0.0 to 150.0% The voltage values of time-
dependent voltage monitoring
4972 [x = 1 to 7] 4971: [45.0%] voltage points are configured
here.
4973 4972: [45.0%]
4977: [90.0%]
Notes
4961 Point {x} time 2 0.00 to 320.00 s The time values of time-
dependent voltage monitoring
4962 [x = 1 to 7] 4961: [0.00 s] time points are configured here.
4966: [3.00 s]
[Default]
It serves a LogicsManager 07.31 command variable "Time-dep. voltage 2" 11750 to trip a
relay or to incorporate the monitoring into the mains decoupling feature of the device.
The alarm class and the self-acknowledge feature is taken from the original time
dependent voltage monitoring (see ╚═▷ “General settings for Mains decoupling and
Monitoring Voltage 1 - 3”.
Time-dep. voltage 2
[Default]
Notes. It is an additional
independent FRT monitoring. It
serves a LogicsManager command
variable to trip a relay or to
incorporate the monitoring into
the mains decoupling function of
the device. The alarm class and
the self-acknowledge setting is
shared with the other time
dependent voltage monitoring. (Id
4951 and Id 4959)
[Default]
Notes
[Default]
4991 Point {x} voltage (2) 2 0.0 to 200.0% The voltage values of time-
dependent voltage 2 monitoring
4992 [x = 1 to 7] 4991: [10.0%] voltage points are configured
here.
4993 4992: [10.0%]
4997: [90.0%]
Notes
4981 Point {x} time 2 0.00 to 320.00 s The time values of time-
dependent voltage 2 monitoring
4982 [x = 1 to 7] 4981: [0.00 s] time points are configured here.
4987: [40.00 s]
It serves a LogicsManager 07.33 command variable "Time-dep. voltage 3" 11750 to trip a
relay or to incorporate the monitoring into the mains decoupling feature of the device.
The alarm class and the self-acknowledge feature is taken from the original time
dependent voltage monitoring (see ╚═▷ “General settings for Mains decoupling and
Monitoring Voltage 1 - 3”.
Time-dep. voltage 3
[Default]
[Default]
Notes. It is an additional
independent FRT monitoring. It
serves a LogicsManager command
variable to trip a relay or to
incorporate the monitoring into
the mains decoupling function of
the device. The alarm class and
the self-acknowledge setting is
shared with the other time
dependent voltage monitoring. (Id
4951 and Id 4959)
[Default]
Notes
9149 Point {x} voltage (2) 2 0.0 to 150.0% The voltage values of time-
dependent voltage monitoring
9150 [x = 1 to 7] 9149: [125.0%] voltage points are configured
here.
9151 9150: [125.0%]
9155: [110.0%]
Notes
[Default]
9140 Point {x} time 2 0.00 to 320.00 s The time values of time-
dependent voltage monitoring
9141 [x = 1 to 7] 9140: [0.00 s] time points are configured here.
9146: [60.00 s]
The 3 Time dependent voltage monitorings can be allocated to the mains decoupling
function. With a configuration general all 3 FRT monitors are included.
[Default]
On Time-dependent voltage
monitoring does cause a
decoupling.
4.5.3.11 QV Monitoring
General notes
In case of mains undervoltage some grid codes require a special monitoring function to
avoid the import of inductive reactive power at the mains interchange point. The
monitoring function measures close to the generator. For this reason the QV monitoring is
a function of generator voltage and generator reactive power.
QV monitoring is triggered if the following conditions are fulfilled: (Refer to ╚═▷ Fig. 188
for details)
• Measured reactive power is higher than the configured “Reactive power threshold”
(parameter ╚═▷ 3291)
• Measured voltages are below the configured “Limit undervoltage” (parameter ╚═▷
3285)
As a result Timer 1 and Timer 2 are starting. If the delay time "Delay step 1" (parameter
╚═▷ 3283) has exceeded, LogicsManager 07.29 becomes TRUE and the corresponding
alarm message "QV monitoring 1" is indicated. If the delay time "Delay step 2"
(parameter ╚═▷ 3284) has exceeded, LogicsManager 07.30 becomes TRUE and the
corresponding alarm message "QV monitoring 2" is indicated.
If parameter “Mains decoupling by QV” (parameter ╚═▷ 3296) is configured to "On" the
decoupling function is assigned to “Delay step 1” (parameter ╚═▷ 3283).
• The LogicsManager command flags 07.29 and 07.30 can be additionally used to
cause other actions according to the corresponding regulations of the grid.
• The QV Monitoring function according the German grid code VDE-AR-N 4105
depends on the parameter ╚═▷ 1770 "phase-phase/phase-neutral monitoring".
[Default]
Notes
Notes
Notes
3280 Alarm class 2 Class A/B/C/D/E/F, Control The alarm class specifies what
action should be taken when at
[B] least one delay has been
exceeded.
Notes
Notes
Phase shift
A vector/phase shift is defined as the sudden variation of the voltage curve which may be
caused by a major generator load change. It usually occurs, if the utility opens the MCB,
which causes a load change for the genset.
The genset control measures the duration of a cycle, where a new measurement is
started with each voltage passing through zero. The measured cycle duration will be
compared with an internal quartz-calibrated reference time to determine the cycle
duration difference of the voltage signal.
The phase shift monitoring is a very sensitive functionality and reacts according to the
settings on each sinus wave constellation.
Please be aware that under special circumstances it may come to a phase shift trip,
when switching elements are taken into the mains measurement lines because mains
voltage sensing lines are switched nearby the genset control.
A vector/phase shift as shown in ╚═▷ Fig. 189 causes a premature or delayed zero
passage. The determined cycle duration difference corresponds with the occurring phase
shift angle.
The voltage cycle duration exceeds the configured limit value for the phase/vector shift.
The result is, that the power circuit breaker that disconnects from the mains, is opened,
the message "Mains phase shift" is displayed, and the logical command variable "07.14"
is enabled.
The prerequisite for phase/vector shift monitoring is that the generator is operating in a
mains parallel operation (the MCB and GCB are both closed).
df/dt (ROCOF)
df/dt (rate of change of frequency) monitoring measures the stability of the frequency.
The frequency of a source will vary due to changing loads and other effects. The rate of
these frequency changes due to the load variances is relatively high compared to those of
a large network.
The control unit calculates the unit of measure per unit of time. The df/dt is measured
over 4 sine waves to ensure that it is differentiated from a phase shift. This results in a
minimum response time of approximately 100 ms (at 50 Hz).
[Default]
Notes
3054 Phase shift: Limit 1 2 3 to 30° If the electrical angle of the mains
phase voltage shifts more than this
[20°] configured value in any single
phase, an alarm with the class
configured in parameter ╚═▷ 3051
is initiated.
3055 Phase shift: Limit 3 2 3 to 30° If the electrical angle of the mains
phase voltage shifts more than this
[8°] configured value in all three
phases, an alarm with the class
configured in parameter ╚═▷ 3051
is initiated.
3051 Phase shift: Alarm 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
class independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
3056 Phase shift: Enabled 2 [Always] Monitoring for this fault condition
is continuously enabled.
LM: Flag{xx}
3104 df/dt: df/dt Limit 2 0.1 to 9.9 Hz/s The df/dt threshold is defined
here. If this value is reached or
exceeded for at least the delay
3101 df/dt: Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
LM: Flag{xx}
General notes
NOTICE!
• Please ensure during installation that all voltages applied to this unit are wired
correctly to both sides of the circuit breaker.
Failure to do so may result in damage to the control unit and/or generation equipment
due to closing the breaker asynchronous or with mismatched phase rotations and phase
rotation monitoring enabled at all connected components (engine, generator, breakers,
cable, busbars, etc.).
This function will block a connection of systems with mismatched phases only under the
following conditions:
• The voltages being measured are wired correctly with respect to the phase rotation
at the measuring points (i.e. the voltage transformer in front and behind the circuit
breaker)
• The measuring voltages are wired without angular phase shift or interruption from
the measuring point to the control unit
• The measuring voltages are wired to the correct terminals of the control unit (i.e. L1
of the generator is connected with the terminal of the control unit which is intended
for the L1 of the generator)
• The LogicsManager function "Enable MCB" (refer to parameter ╚═▷ 12923) is false in
case of a incorrect rotation field
Correct phase rotation of the phase voltages ensures that damage will not occur during a
breaker closure to either the mains or the generator. The voltage phase rotation alarm
checks the phase rotation of the voltages and the configured phase rotation to ensure
they are identical.
The directions of rotation are differentiated as "clockwise" and "counter clockwise". With
a clockwise field the direction of rotation is "L1-L2-L3"; with a counter clockwise field the
direction of rotation is "L1-L3-L2".
If the control is configured for a clockwise rotation and the voltages into the unit are
calculated as counterclockwise the alarm will be initiated. The direction of configured
rotation being monitored by the control unit is displayed on the screen.
If this protective function is triggered, the display indicates "Mns.ph.rot. mismatch" and
the logical command variable "07.05" will be enabled.
This monitoring function is only enabled if Mains voltage measuring (parameter ╚═▷
1853) is configured to "3Ph 4W" or "3Ph 3W" and the measured voltage exceeds 50 % of
the rated voltage (parameter ╚═▷ 1768) or if Mains voltage measuring (parameter ╚═▷
1853) is configured to "1Ph 2W" (in this case, the phase rotation is not evaluated, but
defined by the 1Ph2W phase rotation (parameter ╚═▷ 1859)).
[Default]
3971 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
It is possible to monitor two independently configurable mains import power limit values.
This function makes it possible to initiate external load shedding.
If this protective function is triggered, the display indicates "Mains import power 1" or
"Mains import power 2" and the logical command variable "07.21" or "07.22" will be
enabled.
[Default]
Notes
Notes
3201 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
3207 3201: [A] specifies what action should be
taken when the limit is surpassed.
3207: [B]
Notes
General notes
It is possible to monitor two independently configurable mains export power limit values.
This function makes it possible to initiate external load shedding.
If this protective function is triggered, the display indicates "Mains export power 1" or
"Mains export power 2" and the logical command variable "07.23" or "07.24" will be
enabled.
[Default]
Notes
Notes
3226 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
3234 3226: [A] specifies what action should be
taken when the limit is surpassed.
3234: [B]
Notes
General notes
If enabled, this monitoring function becomes only active if generator power control is
enabled and the active power setpoint is configured to "Import" or "Export" (refer to ╚═▷
“4.4.4.5 Load Control”). If the measured import or export power deviates from the power
setpoint by a value exceeding the limit configured in parameter ╚═▷ 2935 for a time
exceeding the delay configured in parameter ╚═▷ 2933, an alarm will be issued.
If this protective function is triggered, the display indicates "Mns act.pwr mismatch" and
the logical command variable "07.16" will be enabled.
[Default]
Notes
Notes
2931 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
The power factor is monitored for becoming more lagging (i.e. inductive) than an
adjustable limit. This limit may be a lagging or leading power factor limit. There are two
lagging power factor alarm levels available in the control. This monitoring function may
be used for monitoring or controlling the power factor compensation. Both alarms are
definite time alarms.
Power Factor
-0.40 +0.85
-0.50 -0.75 1.00 +0.75 +0.50
╚═▷ Fig. 190 shows an example of a leading and a lagging power factor limit and the
power factor range, for which the lagging power factor monitoring issues an alarm.
If this protective function is triggered, the display indicates "Mains PF lagging 1" or
"Mains PF lagging 2" and the logical command variable "07.17" or "07.18" will be
enabled.
[Default]
Notes
2987 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
2988 [B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
The power factor is monitored for becoming more leading (i.e. capacitive) than an
adjustable limit. This limit may be a leading or lagging power factor limit. There are two
leading power factor alarm levels available in the control. This monitoring function may
be used for monitoring or controlling the power factor compensation. Both alarms are
definite time alarms.
╚═▷ Fig. 191 shows an example of a leading and a lagging power factor limit and the
power factor range, for which the leading power factor monitoring issues an alarm.
If this protective function is triggered, the display indicates "Mains PF leading 1" or
"Mains PF leading 2" and the logical command variable "07.19" or "07.20" will be
enabled.
[Default]
Notes
3037 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
3038 [B] specifies what action should be
taken when the limit is surpassed.
Notes
96.{xx} Example:
4.5.4 Breaker
General notes
Circuit breaker monitoring contains two alarms: A "breaker reclose" alarm and a "breaker
open" alarm.
If the control initiates a close of the breaker and the breaker fails to close after the
configured number of attempts the monitoring CB alarm will be initiated (refer to
parameter "GCB maximum closing attempts", parameter ╚═▷ 3418).
If this protective function is triggered, the display indicates "GCB fail to close" and the
logical command variable "08.05" will be enabled.
If the control is attempting to open the circuit breaker and it fails to see that the CB is
open within the configured time in seconds after issuing the breaker open command then
the monitoring CB alarm will be initiated (refer to parameter "GCB open monitoring",
parameter ╚═▷ 3420).
NOTICE!
If this protective function is triggered, the display indicates "GCB fail to open" and the
logical command variable "08.06" will be enabled.
[Default]
2601 GCB Alarm class 2 Class A/B/C/D/E/F/Control Each limit may be assigned an
independent alarm class that
3420 GCB open monitoring 2 0.10 to 5.00 s If the "Reply GCB" is not detected
as energized once this timer
[2.00 s] expires, a "GCB fail to open" alarm
is issued. This timer initiates as
soon as the "open breaker"
sequence begins. The alarm
configured in parameter ╚═▷ 2601
is issued.
General notes
50BF is a breaker monitoring function which is tripping if the breaker reply is indicating an
open breaker but there is still a current measured which is exceeding a configurable
threshold. It is a kind of plausibility check between breaker reply and measurement.
This monitoring function is only working if the measured current is below 320% of rated
current.
[Default]
Notes
General notes
NOTICE!
[Default]
3061 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
If an alarm class higher than 'B' class has been selected it will not be possible to start the
engine with the setting "Emergency start with MCB failure" (parameter ╚═▷ 3408) =
configured as "On" in an emergency power condition.
Circuit breaker monitoring contains two alarms: A breaker reclose alarm and a breaker
open alarm.
If the control unit initiates a close of the breaker and the breaker fails to close after the
configured number of attempts the monitoring CB alarm will be initiated.
If this protective function is triggered, the display indicates "MCB fail to close" and the
logical command variable "08.07" will be enabled.
If the control unit is attempting to open the circuit breaker and it fails to see that the CB is
open within the configured time in seconds after issuing the breaker open command then
the monitoring CB alarm will be initiated.
If this protective function is triggered, the display indicates "MCB fail to open" and the
logical command variable "08.08" will be enabled.
If the MCB cannot be closed, the busbar remains without voltage, until the MCB
breaker fault is acknowledged.
• Parameter ╚═▷ 2802 "Emergency run" = On, parameter ╚═▷ 3408 "Emergency start
with MCB failure" = Off;
If the MCB cannot be closed, the busbar remains without voltage, until the MCB
breaker fault is acknowledged.
• Parameter ╚═▷ 2802 "Emergency run" = On, parameter ╚═▷ 3408 "Emergency start
with MCB failure" = On;
If the MCB cannot be closed, an emergency power operation is initiated (the engine
is started and the GCB is closed; the busbar is supplied by the generator).
If the alarm is acknowledged and if the MCB can be closed, the load is switched to
mains supply and the emergency power operation terminates.
This alarm class has the following influence to the function of the unit:
• This fault is processed according to the action described within the alarm classes. As
long as the reply is present that the MCB is still closed, the GCB cannot be closed.
[Default]
2621 MCB Alarm class 2 Class A/B/C/D/E/F/Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
3421 MCB open monitoring 2 0.10 to 5.00 s If the "Reply MCB" is not detected
as energized once this timer
[Default]
3071 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
50BF is a breaker monitoring function which is tripping if the breaker reply is indicating an
open breaker but there is still a current measured which is exceeding a configurable
threshold. It is a kind of plausibility check between a breaker reply and a measurement.
This monitoring function is only working if the measured current is below 320% of rated
current!
[Default]
Notes
If breaker mode GCB/MCB is configured, this alarm trips (according to the monitor
settings) if the number of closed MCBs is different to the number of easYgen devices in
the same segment.
[Default]
1943 Alarm class 2 Class A/B/C/D/E/F, Control An alarm can be assigned that
specifies what action should be
[B] taken when the conditions are
fulfilled.
Notes
General notes
The monitoring of the Neutral Contactor (NC) feedback "Neutral contactor reply
mismatch" 17.09 is performed always, if the Neutral Interlocking (parameter ╚═▷ 1840)
and the Monitoring function are enabled (parameter ╚═▷ 5148). The monitor checks, if
the feedback behaves according to the NC command. With a configurable delay time, the
alarm is activated with a general alarm text. Open failure or closure failure are not
differentiated.
[Default]
Notes
5153 Alarm text - [N-cont. reply mism.] Text is visible in display during
alarm is detected.
General notes
CAUTION!
Flexible Limits must not be used for protective functions, because the monitoring
function is not guaranteed beyond an exceeding of 320 %.
This control unit offers 40 flexible limits. They may be used for "limit switch" functions of
all measured analog values. It is possible to choose between alarm (warning and
shutdown) and control operation via the LogicsManager.
If an alarm class is triggered, the display indicates "Flexible limit {x}", where {x}
indicates the flexible limit 1 to 40, or the text configured using ToolKit and the logical
command variable "15.{x}" will be enabled.
The flexible limits 25 through 32 are configurable additionally with a 'Fallback time' e.g.,
for load shedding.
The flexible limits 33 through 40 are disabled during idle mode operation (refer to ╚═▷
“4.4.1.4 Idle Mode”).
The following parameter description refers to flexible limit 1. The flexible limits 2 through
40 are configured accordingly. The parameter IDs of the flexible limits 2 through 40 are
listed below.
[Default]
Notes
Notes
Beginning: For flexible limit 25 ... 32 only; sample refers to flexible limit #25.
End: For flexible limit 25 ... 32 only; sample referred to flexible limit #25.
4201 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
4206 AM FlexLim 1 source 2 Determined by AnalogManager Any possible data sources may be
82.01 selected. Analog and digital OUT
value/signal are available as
[A1 = 10.01 ZERO] sources for AnalogManager and
LogicsManager.
Parameter IDs
Flexible Descrip‐ Monitor‐ Monitor‐ Monitor‐ Limit Hyster‐ Delay Alarm Self Enabled
limit # tion ing ed ing at esis class acknow‐
analog Fallback ledge
value
1 4208 4200 4206 4204 4205 4216 4207 4201 4202 4203
2 4225 4217 4223 4221 4222 4233 4224 4218 4219 4220
3 4242 4234 4240 4238 4239 4250 4241 4235 4236 4237
4 4259 4251 4257 4255 4256 4267 4258 4252 4253 4254
5 7108 4270 4276 4274 4275 4278 4277 4271 4272 4273
6 7116 4280 4286 4284 4285 4288 4287 4281 4282 4283
Flexible Descrip‐ Monitor‐ Monitor‐ Monitor‐ Limit Hyster‐ Delay Alarm Self Enabled
limit # tion ing ed ing at esis class acknow‐
analog Fallback ledge
value
7 7124 4290 4296 4294 4295 4298 4297 4291 4292 4293
8 7132 6000 6006 6004 6005 6008 6007 6001 6002 6003
9 7140 6010 6016 6014 6015 6018 6017 6011 6012 6013
10 7148 6020 6026 6024 6025 6028 6027 6021 6022 6023
11 7156 6030 6036 6034 6035 6038 6037 6031 6032 6033
12 7164 6040 6046 6044 6045 6048 6047 6041 6042 6043
13 7172 6050 6056 6054 6055 6058 6057 6051 6052 6053
14 7180 6060 6066 6064 6065 6068 6067 6061 6062 6062
15 7188 6070 6076 6074 6075 6078 6077 6071 6072 6073
16 7196 6080 6086 6084 6085 6088 6087 6081 6082 6083
17 7204 6090 6096 6094 6095 6098 6097 6091 6092 6093
18 7212 6100 6106 6104 6105 6108 6107 6101 6102 6103
19 7220 6110 6116 6114 6115 6118 6117 6111 6112 6113
20 7228 6120 6126 6124 6125 6128 6127 6121 6122 6123
21 7236 6130 6136 6134 6135 6138 6137 6131 6132 6133
22 7244 6140 6146 6144 6145 6148 6147 6141 6142 6143
23 7252 6150 6156 6154 6155 6158 6157 6151 6152 6153
24 7260 6160 6166 6164 6165 6168 6167 6161 6162 6163
25 7268 6170 6176 6174 6175 6178 6177 6171 6172 6173
6646
26 7276 6180 6186 6184 6185 6188 6187 6181 6182 6183
6647
27 7284 6190 6196 6194 6195 6108 6197 6191 6192 6193
6648
28 7292 6200 6206 6204 6205 6208 6207 6201 6202 6203
6649
29 7300 6210 6216 6214 6215 6218 6217 6211 6212 6213
6650
30 7308 6220 6226 6224 6225 6228 6227 6221 6222 6223
6651
31 7316 6230 6236 6234 6235 6238 6237 6231 6232 6233
6652
32 7324 6240 6246 6244 6245 6248 6247 6241 6242 6243
6653
33 7332 6250 6256 6254 6255 6258 6257 6251 6252 6253
34 7340 6260 6266 6264 6265 6268 6267 6261 6262 6263
Flexible Descrip‐ Monitor‐ Monitor‐ Monitor‐ Limit Hyster‐ Delay Alarm Self Enabled
limit # tion ing ed ing at esis class acknow‐
analog Fallback ledge
value
35 7348 6270 6276 6274 6275 6278 6277 6271 6272 6273
36 7356 6280 6286 6284 6285 6288 6287 6281 6282 6283
37 7364 6290 6296 6294 6295 6298 6297 6291 6292 6293
38 7372 6300 6306 6304 6305 6308 6307 6301 6302 6303
39 7380 6310 6316 6314 6315 6318 6317 6311 6312 6313
40 7388 6320 6326 6324 6325 6328 6327 6321 6322 6323
Examples
Example value Desired limit Reference value / display Limit entry format
value
01.24 Total generator real 160 kW Generator rated real power 8000 (= 80.00%)
power in % (parameter ╚═▷ 1752) =
200 kW
06.03 Analog input 3 4.25 bar Display in 0.01 bar 00425 (= 4.25 bar)
(configured to VDO 5 bar)
The flexible limits must be used to monitor analog inputs like oil pressure or coolant
temperature for example. We recommend to change the flexible limit description
accordingly.
The table below gives some configuration examples. The analog inputs must be
configured accordingly.
Parameter Example for low oil pressure Example for high coolant
monitoring temperature monitoring
Monitoring On On
Parameter Example for low oil pressure Example for high coolant
monitoring temperature monitoring
Hysteresis 10 2
Delay 0.50 s 3s
Alarm class F B
Self acknowledgment No No
4.5.6 Miscellaneous
[Default]
1756 Time until horn reset 0 0 to 1,000 s After each alarm of alarm class B
through F occurs, the alarm LED
[180 s] flashes and the horn (command
variable 03.05) is enabled. After
the delay time "time until horn
reset" has expired, the horn
(command variable 03.05) is
disabled. The alarm LED flashes
until the alarm has been
acknowledged either via the push
button, the LogicsManager, or the
interface.
Notes
Notes
1849 Stop mode with 2 If operating mode is not fixed via LogicsManager (see chapter ╚═▷
stopping alarm “6.3.5 Performing Remote Start/Stop And Acknowledgment” for details)
with this parameter it can be decided if the operation mode changes to
STOP mode when a shutdown alarm of class C, D, E, F occurs.
Notes
Notes
Notes
General Notes
• A LogicsManager equation
• Delay time
• Alarm class
• Self acknowledgment
[Default]
8121 Alarm class 2 Class A/B/C/D/E/F, Control The assigned independent alarm
class specifies what action should
[Class B] be taken when the alarm becomes
TRUE.
Parameter IDs
Free alarm # Description Logics‐ Alarm class Self acknow‐ Enabled Delay
Manager ledge
General notes
The CANopen interface 1 is monitored. If the interface does not receive a Receive Process
Data Object (RPDO) before the delay expires, an alarm will be initiated.
If this protective function is triggered, the display indicates "CANopen interface 1" and
the logical command variable "08.18" will be enabled.
[Default]
Notes
General notes
The CANopen interface 2 is monitored. If the interface does not receive a message from
the external expansion board (Node-ID) before the delay expires, an alarm will be
initiated. This is indicated in menu [Next Page/STATUS MENU / Diagnostic / Interfaces /
CAN / CAN 2 state]
If this protective function is triggered, the display indicates "CANopen interface 2" and
the logical command variable "08.19" will be enabled.
If you are not using the exact amount of external I/O modules you have defined, the
monitoring function does not work correctly.
[Default]
Notes
General notes
This monitor function can monitor messages of up to 4 different J1939 devices separately
by their source addresses.
If the easYgen doesn’t receive any message from the corresponding device within the
configured time the command variable 08.10 “CAN fault J1939” becomes active.
Additionally a specific alarm 08.37: “J1939 ECU timeout”, 08.38: “J1939 dev. 1 timeout”,
08.39: “J1939 dev. 2 timeout”, or 08.40: “J1939 dev. 3 timeout” will be triggered.
ECU settings
[Default]
Notes
[Default]
Device 1 settings
[Default]
[1 s]
Notes
[Default]
Device 2 settings
[Default]
[1 s]
[Default]
Notes
Device 3 settings
[Default]
[1 s]
[Default]
Notes
General notes
This monitor monitors, whether a specific alarm bit is received from the CAN J1939
interface. This enables to configure the easYgen in a way that a reaction is caused by this
bit (e.g. warning, shutdown).
If this protective function is triggered, the display indicates "Red stop lamp" and the
logical command variable "05.13" will be enabled.
[Default]
Notes
General notes
This monitor monitors, whether a specific alarm bit is received from the CAN J1939
interface. This enables to configure the easYgen in a way that a reaction is caused by this
bit (e.g. warning, shutdown).
If this protective function is triggered, the display indicates "Amber warning lamp" and
the logical command variable "05.14" will be enabled.
[Default]
Notes
General notes
This monitor monitors, whether a specific alarm bit is received from the CAN J1939
interface. This enables to configure the easYgen in a way that a reaction is caused by this
bit (e.g. warning, shutdown).
If this protective function is triggered, the display indicates "Protection lamp DM1" and
the logical command variable "03.44" will be enabled.
[Default]
Notes
General notes
This monitor monitors, whether a specific alarm bit is received from the CAN J1939
interface. This enables to configure the easYgen in a way that a reaction is caused by this
bit (e.g. warning, shutdown).
If this protective function is triggered, the display indicates "Emission lamp DM1" and the
logical command variable "03.45" will be enabled.
[Default]
Notes
This monitor is a switch to transfer the content of the DM1 alarm message onto the alarm
screen of the easYgen. The event log is as well considered.
[Default]
Notes
General notes
The devices reacts on an abnormal rate of Ethernet UDP-messages per time scale e.g.
“broadcast storm”. If a maximal allowed number of messages is received, the device
closes all Ethernet ports to give the own device more calculation time. After about 100ms
the Ethernet ports are opened again to recheck the UDP message traffic. As long the
traffic is still high the device remains in this protection state.
If this protective function is triggered, after the configured delay time the display
indicates the alarm “Ethernet issue” and the logical command variable “08.62 Ethernet
issue” will be enabled.
[Default]
Notes
General notes
There are two battery overvoltage alarm levels available in the control. Both alarms are
definite time alarms and. Monitoring of the voltage is done in two steps.
If this protective function is triggered, the display indicates "Bat. overvoltage 1" or
"Bat. overvoltage 2" and the logical command variable "08.01" or "08.02" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
Notes
3451 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
3457 [B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
There are two battery undervoltage alarm levels available in the control. Both alarms are
definite time alarms. Monitoring of the voltage is done in two steps.
If this protective function is triggered, the display indicates "Bat. undervoltage 1" or
"Bat. undervoltage 2" and the logical command variable "08.03" or "08.04" will be
enabled.
Refer to ╚═▷ “9.1.1 Triggering Characteristics” for the triggering characteristic of this
monitoring function.
[Default]
3501 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
3507 [B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
The PV load reference function contains a monitor for generator reverse power. It is
enabled if parameter ╚═▷ 8911) is configured to ”Regulated“. The monitor observes the
system generator load and trips the alarm ”08.71 PV disconnect“ if the real generator
load underruns the configured disconnect level e.g. in case of reverse power. Then the PV
power can be cut. This can be maintained if the LogicsManager ”08.71 PV disconnect“ is
assigned to a relay output.
Parameter
[Default]
(Hysteresis is 0.5%.)
Notes
General notes
The multi-unit parameter alignment functionality requires that the relevant parameters
are all configured identically at all participating units.
If at least one of these parameters is configured different in at least one of the units, the
display indicates "Parameter alignment" on all units and the logical command variable
"08.16" will be enabled. To identify different configured units, please use the diagnostic
screen "Genset parameter alignment": [Next Page / Status Menu / System Overview /
Multi-unit / Genset parameter alignment]
This alarm is always self-acknowledging, i.e. the control automatically clears the alarm if
it is no longer valid.
Parameter ID
Parameter ID
[Default]
4071 Alarm class 2 Alarm class Class A/B/C/D/E/F, This function may be assigned an
Control independent alarm class that
specifies what action should be
[B] taken when this function triggers
an alarm.
Notes
General notes
The multi-unit missing easYgen monitoring function checks whether all participating units
are available (sending data on the load share line).
If the number of available units is less than the number of displayed "Monitored easYgen"
╚═▷ 9925 (initiated by parameter ╚═▷ 13356 System update) for at least the delay time,
the display indicates "Missing easYgen" and the logical command variables "08.17" and
"08.27" will be enabled.
After energizing the easYgen, a delay is started, which allows a possible "Missing
easYgen" alarm to become active.
For using only a CAN bus connection, this delay depends on the Node-ID of the easYgen
(parameter ╚═▷ 8950) and the transfer rate of a load share fast message (parameter ╚═▷
9921) and may last for approx. 140 seconds for a high Node-ID (e.g. 127). This delay
serves for detecting the Master of the CAN bus* connection. Approximately two minutes
after energizing the easYgen, the alarm delay will be set to a fix time, which depends on
the setting of parameter ╚═▷ 9921 (Transfer rate LS fast message) and is in the range
between 3 to 12 seconds.
For Ethernet connections, this delay time is 12 seconds. Approximately 12 seconds after
energizing the easYgen, the alarm delay will be set to 1 second.
[Default]
4061 Alarm class 2 Class A/B/C/D/E/F, Control This function may be assigned an
independent alarm class that
[B] specifies what action should be
taken when this function triggers
an alarm.
Notes
General notes
The multi-unit system update monitoring function checks whether only the participating
units are available (sending data on the load share line).
If the number of available easYgen units is more than the number of displayed "Monitored
easYgen" ╚═▷ 9925 (initiated by parameter ╚═▷ 13356 System update), the display
indicates "System Update easYgen" and the logical command variables "08.43" and
"08.65" will be enabled.
[Default]
Notes
[Default]
7833 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
General notes
The operating range failure monitoring issues an Operating Range Failure Alarm
"Oper.range failed XX" (where XX is the number of Check 01 to 12) if one of the following
conditions is fulfilled. Example: Check 4 failed causes »Oper.range failed 4«.
Only the first incoming operation range failure will tripp an alarm. Because in most cases
this will be the root cause for eventually incoming further operating range alarms. Any
other operating range alarm can only be tripped if there is no active or latched operating
range alarm.
If there are more than one failures only the first incoming failure will be indicated and is
available at protocol 5014.
• Check 1: The easYgen tries to close the GCB, but the generator is not within its
operating range (parameters ╚═▷ 5800, ╚═▷ 5801, ╚═▷ 5802, or ╚═▷ 5803).
• Check 2: The easYgen tries to synchronize the GCB, but the busbar is not within the
generator operating range (parameters ╚═▷ 5800, ╚═▷ 5801, ╚═▷ 5802, or ╚═▷
5803).
• Check 3: The easYgen tries close the GCB in breaker transition mode "Open
transition" with GCB and MCB open status. In this condition the busbar is expected
as dead, but the busbar voltage is NOT below the dead busbar detection limit
(parameter ╚═▷ 5820).
• Check 4: The easYgen wants to close the GCB onto a dead busbar, but the device
cannot close the breaker because there is at least one neighbor device recognized
with a closed GCB.
• Check 5: The easYgen tries to synchronize the GCB, the MCB is closed, but mains
and/or bussbar are not within its operating range (parameters ╚═▷ 5810, ╚═▷ 5811,
╚═▷ 5812, or ╚═▷ 5813).
• Check 11: The easYgen checks the plausibility of generator and busbar, if GCB is
closed and the engine runs without run-up synchronization, but the operating range
of generator OR busbar is not matched.
• Check 12: The easYgen checks the phase rotation of generator, busbar, and mains
and a synchronisation shall be executed, but the phase rotation of all systems does
not match. (Synchronisation is blocked.)
No alarm will be issued in idle mode. This monitoring function is disabled below firing
speed.
NOTICE!
If this protective function is triggered, the display indicates "Operat. range failed" /
("Operating Range failed") and the logical command variable "06.31" will be enabled.
[Default]
2661 Alarm class 2 Class A/B/C/D/E/F, Control Each limit may be assigned an
independent alarm class that
[B] specifies what action should be
taken when the limit is surpassed.
Notes
[Default]
General
Beside the automatic handling of redundant load share line messages the easYgen can
inform the operator if a redundant load share communication line get lost. Preassumption
for that is an enabled redundant load share line like CAN/Ethernet A in conjunction with a
successful system update procedure.
If the according alarm has occurred the operator usually checks the "Diagnostic devices"
screen. Available on device display or over ToolKit. There he will be informed which
channel is affected. Refer to system update for more information.
Function
If the parameter "9924 Load share interface" is configured to "CAN/Ethernet A" and the
system update was executed, the monitoring becomes active. The monitor needs
minimum
The devices observes if the both load share messages are correctly receipt. If a channel
fails the alarm "LS interf. redundancy" is triggered.
[Default]
[Default]
If the genset control is intended to operate a genset in parallel to the mains, the mains
voltage measuring inputs must be connected.
Dependencies
S
Q
PF=cosφ
1 φ
PF Power Factor
The AC power triangle illustrates the dependencies between active power, apparent
power, reactive power and power factor.
• PF = P/S = cos Φ
• Q = √(S2-P2)
• S = √(P2+Q2)
• P = S * PF
[Default]
1825 System rated active 2 0.5 to 99999.9 This value specifies 100% of the
power [kW] system rated power, which is used
[200.0 kW] for system related indications and
calculations.
Notes
Notes
4.6.2 Generator
[Default]
• synchronous generators
• asynchronous generators
(induction generators)
Notes
Recommended settings
Notes
1752 Gen. rated active 2 0.5 to 99999.9 kW This value specifies the generator
power [kW] real power rating, which is used as
[200.0 kW] a reference figure for related
functions. The generator rated
active power is the generator
apparent power multiplied by the
generator power factor (typically
~0.8). These values are indicated
in the generator data plate (╚═▷
“Dependencies”).
1758 Gen. rated react. 2 0.5 to 99999.9 kvar This value specifies the generator
power [kvar] reactive power rating, which is
[200.0 kvar] used as a reference figure for
related functions. The generator
rated reactive power also depends
on the generator values (╚═▷
“Dependencies”).
• VL1N, VL12
Notes
Notes
General notes
The setpoints for specific parameters will differ depending upon the setting of
parameter »Generator current range«╚═▷ 1830.
[Default]
[5 A]
4.6.3 Busbar
The busbar parameters in the device are often named with the affix "1". This preparation
is done to avoid confusion e.g., if a model with a second busbar measurement is
introduced.
[Default]
5820 Dead bus detection 2 0 to 30% If the busbar voltage falls below
max. volt. this percentage of the busbar 1
[10%] rated voltage (parameter ╚═▷
1781), a dead bus condition is
detected and the logical command
variable 02.21 (Busbar 1 is dead)
becomes TRUE.
[Default]
Notes
4.6.4 Mains
[Default]
1768 Mains rated voltage 2 50 to 650000 V This value refers to the rated
voltage of the mains and is the
[400 V] voltage measured on the potential
transformer primary.
1748 Mains rated active 2 0.5 to 99999.9 kW This value specifies the mains real
power [kW] power rating, which is used as a
[200.0 kW] reference figure for related
functions. The mains rated active
power is a reference value used
by several monitoring and control
functions (╚═▷ “Dependencies”).
1746 Mains rated react. 2 0.5 to 99999.9 kvar This value specifies the mains
pwr. [kvar] reactive power rating, which is
[200.0 kvar] used as a reference figure for
related functions.
1785 Mains rated current 2 1 to 32000 A This value specifies the mains
rated current, which is used as a
• VL1N, VL12
Notes
1852 Mains current 2 [Phase L1] / Phase L2 / Phase L3 Phase L{1/2/3} Measurement is
measuring performed for the selected phase
only. The measurement and
display refer to the selected
phase.
Notes
General notes
The setpoints for specific parameters will differ depending upon the setting of
parameter »Mains current range«╚═▷ 1832.
[Default]
Notes
Notes
[Default]
2966 External mains active 2 Yes The mains active power is coming
power from an external source.
Notes
0.1 kW 100.0 kW
[1 kW] 1000 kW
0.01 MW 10.00 MW
0.1 MW 100.0 MW
[Default]
Notes
4.6.5 Engine
[Default]
1601 Engine rated speed 2 100 to 4,000 rpm Number of revolutions per minute
of the engine at rated engine
[1,500 rpm] speed. The speed control with an
ECU via J1939 CAN bus refers to
this value.
There is no configuration to do for the USB Service Port but the driver installer .exe from
CD-ROM must be proceeded: [Software / USB driver / Click here]
The USB service port is restricted for ToolKit communication, Woodward service
communication, and - if provided by factory side - read only files.
• 1. Wait until the easYgen-XT is recognized again through the PC (as an external hard
drive)
• 2. Start via ToolKit at new by "Disconnect" and then "Connect" again
[Default]
3170 Baudrate 2 2.4 / 4.8 / 9.6 / [19.2] / 38.4 / 56 / This parameter defines the baud
115 kBaud rate for communications. Please
note, that all participants on the
bus must use the same baud rate.
3171 Parity 2 [No] / Even / Odd The used parity of the interface is
set here.
3172 Stop bits 2 [One] / Two The number of stop bits is set
here.
Modbus Interface
3189 Reply delay time 2 0.00 to 2.55 s This is the minimum delay time
between a request from the
[0.00 s] Modbus master and the sent
response of the slave. This time is
required in half-duplex mode.
Notes
[Default]
Notes
Notes
Notes
Notes
Notes
Note
Power measurement:
Setting Possible
Transfer value
value Meaning Calculation display
(16 Bit, max. 32767) format
3181
Voltage measurement:
Current measurement:
General notes
The CAN bus is a field bus and subject to various disturbances. Therefore, it cannot be
guaranteed that every request will be answered. We recommend to repeat a request,
which is not answered within reasonable time.
Parameters ╚═▷ 9100 and ╚═▷ 9101 use synchronization and time messages that adhere
to the following structure.
29 X N/A
28-11 0 Always
On Bit 30 = 0; Bit 31 = 0 No No
[Default]
3156 Baudrate 2 20 / 50 / 100 / 125 / 250 / 500 / This parameter defines the used
800 / 1000 kBaud baud rate. Please note, that all
participants on the CAN bus must
[250 kBd] use the same baud rate.
If configured to "No",
parameter »Device number
« 1702 is visible and will not be
overwritten.
Notes
8950 Node-ID CAN bus 1 2 1 to 127 (dec) A number that is unique to the
control must be set in this
[1] parameter so that this control unit
can be correctly identified on the
CAN bus.
Notes
Notes
If no "Start_Remote_node"
message would be sent, the
complete system would not be
operational.
Notes
8940 Producer SYNC 2 0 to 65000 ms This is the cycle time of the SYNC
Message time message. If the unit is configured
[20 ms] for this function (parameter ╚═▷
9100) it will send the SYNC
message with this interval. The
time configured here will be
rounded up to the next 10 ms
step.
9101 COB-ID TIME Message 2 1 to FFFFFFFF hex This parameter defines whether
the unit generates the TIME
[100 hex] message or not.
Notes
9102 Cycle of TIME sync. 2 1.0 to 6500.0 s This is the cycle time of the TIME
message message. If the unit is configured
[10.0 s] for this function (parameter ╚═▷
9101) it will send the TIME
message with this interval.
Notes
Notes
General notes
The CAN bus is a field bus and subject to various disturbances. Therefore, it cannot be
guaranteed that every request will be answered. We recommend to repeat a request,
which is not answered within reasonable time.
The first Node-ID is the standard Node-ID of CAN interface 1 (parameter ╚═▷ 8950).
[Default]
General notes
RPDO Objects can be remote signals (parameter 503; please refer to╚═▷ “Remote control
word 1” for details), DI states and AI measured values.
30 X N/A
29 X N/A
28-11 0 Always
PDO valid / not valid allows to select, which PDOs are used in the operational state.
[Default]
Notes
Notes
65002
65003
12832 Notes
12833 Notes
12834 Notes
12835 Notes
General notes
CANopen allows to send 8 byte of data with each Transmit PDO. These may be defined
separately if no pre-defined data protocol is used.
All data protocol parameters with a parameter ID may be sent as an object with a
CANopen Transmit PDO.
The data length will be taken from the data byte column (see ╚═▷ “9.2 Data Protocols”):
The object ID is identical with the parameter ID when configuring via front panel or
ToolKit.
30 X N/A
29 X N/A
28-11 0 Always
PDO valid / not valid allows to select, which PDOs are used in the operational state.
Transmission types
Parameters ╚═▷ 9602/╚═▷ 9612/╚═▷ 9622/╚═▷ 9632/╚═▷ 12793 are used to select one of
the following transmission types.
1-240 X X
254 X
255 X
A value between 1 and 240 means that the PDO is transferred synchronously and
cyclically. The transmission type indicating the number of SYNC messages, which are
necessary to trigger PDO transmissions.
Transmit PDOs are always triggered by the following SYNC upon reception of data
independent of the transmission types 0 to 240. For TPDOs, transmission type 254 and
255 means, the application event is the event timer.
[Default]
Notes
Notes
12795 Notes
12796 Notes
12797 Notes
12798 Notes
General notes
General Settings
[Default]
3157 Baudrate 2 20 / 50 / 100 / 125 / 250 kBaud This parameter defines the used
baud rate.
[250 kBd]
Notes
• One part is located at the CAN2 interface pages and defines the Node IDs and the
types of external devices and is described here.
An application description explains the setup in detail (refer to ╚═▷ “6.3.10 Setup
Expansion Modules at CAN 2”).
• One other part is located at the external analog/digital inputs/outputs pages and
defines how many inputs/outputs are used and the scaling of the analog types. Refer
to chapters ╚═▷ “4.4.2.4 Analog Inputs” for reference.
• A number of well defined combinations is available for Woodward IKD and/or third
party expansion modules from Phoenix and WAGO: ("Select external terminals",
parameter ╚═▷ 15320)
This parameter defines the type and the maximal number of DI, DO, AI, AO
combinations.
Such files can be prepared by Woodward. Please ask you local Woodward partner for
an offer.
For basic configuration see ╚═▷ “6.3.10 Setup Expansion Modules at CAN 2” - especially
the flow charts of ╚═▷ “Configuration process help”ff.
Assignment of selectable Combinations CAN 2 (Node 1-6) used for DI/DO – Only Digital
Inputs and Digital Outputs:
Select # of 1st Node- 2nd Node- 3rd Node- 4th Node- 5th Node- 6th Node-
external ID ID ID ID ID ID
terminals terminals:
I/O ID 9930 ID 9931 ID 9932 ID 9933 ID 9934 ID 9935
ID 15320
Select # of 1st Node- 2nd Node- 3rd Node- 4th Node- 5th Node- 6th Node-
external ID ID ID ID ID ID
terminals terminals:
I/O ID 9930 ID 9931 ID 9932 ID 9933 ID 9934 ID 9935
ID 15320
DI/DO 1-16
Assignment of selectable Combinations CAN 2 (Node 1-6) used for AI/AO – Only Analog
Inputs and Analog Outputs:
Select # of 1st Node- 2nd Node- 3rd Node- 4th Node- 5th Node- 6th Node-
external ID ID ID ID ID ID
terminals terminals:
I/O ID 9930 ID 9931 ID 9932 ID 9933 ID 9934 ID 9935
ID 15320
16 x AI / 4 x AI 1-16
AO
AO 1-4
16 x AI / 4 x AI 1-16
AO
AO 1-4
Select # of 1st Node- 2nd Node- 3rd Node- 4th Node- 5th Node- 6th Node-
external ID ID ID ID ID ID
terminals terminals:
I/O ID 9930 ID 9931 ID 9932 ID 9933 ID 9934 ID 9935
ID 15320
1 Phoenix: AO 1-4
Select # of 1st Node- 2nd Node- 3rd Node- 4th Node- 5th Node- 6th Node-
external ID ID ID ID ID ID
terminals terminals:
I/O ID 9930 ID 9931 ID 9932 ID 9933 ID 9934 ID 9935
ID 15320
16 x AI / 4 x
AO
1 Phoenix: AO 1-4
16 x AI / 4 x
AO
1 Phoenix: AO 1-4
16 x AI / 4 x
AO
1 Phoenix: AO 1-4
16 x AI / 4 x
AO
1 Phoenix: AO 1-4
16 x AI / 4 x
AO
16 x AI / 4 x P16AI4AO
AO
AI 1-16
AO 1-4
16 x AI / 4 x W16AI4AO
AO
AI 1-16
AO 1-4
P16AI4AO
Select # of 1st Node- 2nd Node- 3rd Node- 4th Node- 5th Node- 6th Node-
external ID ID ID ID ID ID
terminals terminals:
I/O ID 9930 ID 9931 ID 9932 ID 9933 ID 9934 ID 9935
ID 15320
16 x AI / 4 x AI 1-16
AO
AO 1-4
W 32D 16AI 1 WAGO,: W32DIDO
4AO
32 x DI/DO DI/DO 1-32
16 x AI / 4 x W16AI4AO
AO
AI 1-16
AO 1-4
1 Phoenix: AO 1-4
16 x AI / 4 x
AO
1 Phoenix: AO 1-4
16 x AI / 4 x
AO
16 x AI / 4 x AI 1-16
AO
AO 1-4
1 Wago: AO 1-4
16 x AI / 4 x
AO
1 Wago: AO 1-4
16 x AI / 4 x
AO
1 Wago: AO 1-4
Select # of 1st Node- 2nd Node- 3rd Node- 4th Node- 5th Node- 6th Node-
external ID ID ID ID ID ID
terminals terminals:
I/O ID 9930 ID 9931 ID 9932 ID 9933 ID 9934 ID 9935
ID 15320
16 x AI / 4 x
AO
1 Wago: AO 1-4
16 x AI / 4 x
AO
If you need only four analog inputs, select “P16AI4AO” and configure only four inputs to
ON at the configuration for the external analog inputs.
This is the case if the WAGO CAN-Coupler is new or if there was any change in
number or kind of WAGO modules.
• Configure and check parameters at the easYgen (Select external terminals, Node-ID,
DI/DOs, AI/AOs)
• If WAGO terminals are connected and the configuration of the external AIs and/or
AOs is done, the easYgen must send a configuration string to the WAGO coupler one
time. This can be done by setting parameter »Configure external devices« ╚═▷
15134 to "YES". This must be repeated if there is any change in number or kind of
WAGO modules.
• If you have changed parameter »Select external terminals « ╚═▷ 15320: reboot the
device
The update procedure described above must be repeated if there is any change in
number or kind of Wago modules.
[Default]
9940 This device 2 Node-ID 1-126 The Node-ID for the control unit
(this device) is configured here.
[Node-ID 7]
9930 1st Node-ID 2 Node-ID 1-126 This Node-ID's are used for the
communication with CANopen
[Node-ID 1] devices.
[Node-ID 3]
[Node-ID 4]
[Node-ID 5]
[Node-ID 6]
P16D
P32D
P16D_16D
P16AI4AO
1IKD_ P16AI4AO
2IKD_ P16AI4AO
3IKD_ P16AI4AO
4IKD_ P16AI4AO
[Default]
P16D_16AI4AO
P16D16AI4AO
P32D16AI4AO
2P16D_16AI4AO
P32D_16AI4AO
W16AI4AO
1IKD_W16AI4AO
2IKD_W16AI4AO
3IKD_W16AI4AO
4IKD_W16AI4AO
W16D
W32D
W16D16AI4AO
W32D16AI4AO
Notes
Notes
• Load default values (via a temporary change in number or kind of Wago modules-run
configuration again.
If configurable WAGO devices are used, the mode of the terminal must be configured via
the PC software WAGO I/O Check. These configuration cannot be done via the easYgen
parameters. Be aware that the easYgen parameters for the corresponding channels must
be consistent with the Wago configuration done with the WAGO I/O Check.
To use the 8 channel RTD device (750-451) the following process image must be
configured via the Wago I/O-Check.
The following types are not supported: Ni1000 (high resolution), Ni1000 (TK5000),
Pt1000 (EN 60751 high resolution), and 1200 Ohm.
Therefore a special scaling of the easYgen-XT parameters “Sender value at display min.”
and “Sender value at display max” is required like described in the table below:
Voltage measuring range “Sender value at display “Sender value at display max.”
min.”
General notes
Parameter 15102 »Device type « allows to select an ECU either by name or - for even
more flexibility - via an ECU file; then the name of the preferred ECU file must be entered
into parameter 15167 »ECU file name«. Please ask your local Woodward partner for
further information.
[Default]
Notes
[Default]
Notes
[Default]
Notes
15106 J1939 own address 2 0 to 255 The easYgen sends J1939 request
and control messages with this
[234] source address. It must be
changed for different ECU types
according to the following table.
The ECU listens only to control
messages, if they are sent to the
correct address.
• S6 Scania: 39
• EMR2 Deutz: 3
• EMS2 Volvo: 17
• ADEC ECU7 MTU: 1
• EGS Woodward: 234
• MFR/EDC7 MAN: 253
• EEM SISU: N/A
• Cummins: 220
• ADEC ECU8/ECU9 MTU: 234
• Hatz EDC17: 3
• Standard: Please refer to ╚═▷
“7.5 J1939 Protocol” and to
the manual of your J1939
ECU manufacturer.
• S6 Scania: 0
• EMR2 Deutz: 0
[Default]
• EMS2 Volvo: 0
• ADEC ECU7 MTU: 128
• EGS Woodward: 0
• MFR/EDC7 MAN: 39
• EEM SISU: 0/(1)
• Cummins: 0
• ADEC ECU8/ECU9 MTU: 0
• Hatz EDC17: 0
• Standard: Please refer to ╚═▷
“7.5 J1939 Protocol” and to
the manual of your J1939
ECU manufacturer.
[Default]
Notes
5537 Speed deviation ECU 2 0 to 1,400 rpm This parameter adjusts the range
of the speed deviation around the
[120 rpm] rated speed, which is sent to the
ECU.
Speed offset
Islanded operation
[Default]
Speed setpoint
Islanded operation
• 50 = rated speed
Notes
[Default]
Notes
12939 ECU Power Mode 2 [Low power mode] Prepared for MTU - Low mode
Notes
[Default]
Notes
Notes
Notes
[Default]
General notes
The Ethernet network provides a fast communication capability to different devices, like
remote panel, PLC or SCADA systems. The common protocol Modbus TCP is there for the
preferred communication protocol. Additionally the Ethernet connection supports the
Woodward protocol Servlink for ToolKit and other Woodward own monitoring tools (like
remote panel and SCADA visualization tool). At least the easYgen provides a UDP protocol
for system relevant and time discrete information exchange.
Do not connect the easYgen with the internet as long the security aspects are not
considered. Consider an IP responsible person to discuss proper security procedures like
placing routers and fire walls.
If the easYgen (or -system) shall be connected to an already existing Ethernet network, a
network responsible person must arrange and allocate the IP Addresses. He takes care
about IP-Address, the subnet mask, and when needed the gateway IP Address.
7488 Transmission rate [80 ms] The transmission rate defines the refresh rate (time) of
the UDP messages, for example load share messages.
80 to 400 ms
7489 Timeout cycles [5] The control monitors the expected amount of received
UDP messages. This entry is the number of LDSS
2 to 10 messages that can be lost before it is detected as
"connection missing".
7485 Modbus/TCP 2 [1] Your local Modbus device address, which is used to
Slave ID identify the device via Modbus/TCP (Ethernet), must be
1 to 255 entered here.
decimal binary
Network address = IP address AND Subnet mask 192.168.002.000 11000000 10101000 00000010 00000000
The device (host) part is the individual part of the network address for a dedicated
device. The device part is the result of the binary AND connection of the IP address and
the inverted subnet mask:
decimal binary
Device part = IP address AND Subnet mask 000.000.000.001 00000000 00000000 00000000 00000001
inverted
The actual IP address, subnet mask, gateway IP address (all hex values) can be viewed
under Next Page (Status Menu) / Diagnostic / Interfaces / Ethernet / Ethernet A.
IP address
Each port within the Ethernet network must have its own network address. As long the
Ethernet network is only used by the easYgen-XT system, the address range is free
configurable. For better troubleshooting use the default Ethernet address range and
configure the single IP addresses according to their device numbers.
The "device part" is the logical result of »IP Address« AND NOT »Network Mask«. The bits
(dual system 02/12) of the device part must be different from being all the same - neither
all zero 02 nor all 12 (broadcast).
Gateway IP address
The gateway IP address defines a node within a local area network (LAN), which is
directed to external networks. It is usually not needed in an easYgen Ethernet network.
Refer to your network responsible contact person, if a gateway capability is required.
HEX values
The addresses and subnet masks are known as hex values but are displayed in HMI and
ToolKit as decimal values.
5330 IP address 2 [10, 31, 140, 0] Field 1,2,3,4 for IP address Ethernet port A. This setting
will be not valid automatically. The »Set IP
5331 address« parameter must be set to »ON« for enabling.
5332 Notes
5333 Device part bits are not allowed to be either all 00...2
or all 11...2 (broadcast).
5334 Subnet mask 2 [255, 255, 240, 0] Set byte 1,2,3,4 of the subnet mask Ethernet port A.
This setting will be not valid automatically. The »Set
5335 subnet mask« parameter must be set to »ON« for
enabling.
5336
5337
7413 Set subnet mask 2 Off Set subnet mask Ethernet port A.
5338 Gateway IP 2 [0, 0, 0, 0] Field 1,2,3,4 for gateway IP-Address for Ethernet port A.
This setting will be not valid automatically. The »Set IP
5339 address« parameter must be set to »ON« for enabling.
If 0.0.0.0 is set, the gateway's functionality is switched
5340 off.
5341
5342 Set Gateway IP 2 Off Set Gateway IP Address for Ethernet port A
address
4.7.5.3 SNTP
SNTP feature
The Simple Network Time Protocol (SNTP) is a common procedure to synchronize clocks in
computer systems via packaged based communication networks. In this manner, the
easYgen-XT can be configured as a SNTP client. The easYgen-XT is also usable as a SNTP
server within the local area network by its own IP address.
The easYgen-XT requests time and date information from an external SNTP server,
marked with an own IP address.
The easYgen-XT requests time and date information from the easYgen with the
smallest device number, if the load sharing over Ethernet is enabled.
The SNTP client mechanism is disabled. The own real time clock determines clock
and date.
HEX values
The addresses and subnet masks are known as hex values but are displayed in HMI and
ToolKit as decimal values.
7780 SNTP address 2 [10, 14, 128, 128] Set byte 1,2,3,4 of the IP address of the external SNTP-
Server.
7781 0 to 255 (4x)
7782
7783
7784 Rate 2 [1200s] Set the time rate of the SNTP-Server request.
60 to 6000
7785 Timeout 2 [60s] Set the timeout of the SNTP-Server. This feature is
prepared for the future and has currently no influence
30 to 600 on the function.
7786 Mode 2 [Internal clock] The device provides different SNTP modes.
External SNTP Internal clock: The clock information comes from the
internal clock. The SNTP function is disabled.
Load share
[Default]
9921 Transfer rate LS fast 2 0.10 to 0.30 s The transfer rate defines the time
message delay between two fast CAN
[0.10 s] messages.
(CAN)
In case of CAN systems with a
high bus load (e.g. long distance
between the units with low baud
rate), a shorter transfer rate
(higher time setting) helps to
reduce the bus load.
9920 Load Share CAN-ID 2 2xx hex / 3xx hex / 4xx hex / 5xx The first digit of the CAN ID or the
hex range (i.e. 2xx means 200 through
2FF hex) is configured here.
[5xx hex]
The last two digits will be assigned
by the control with the settings
from the device number
(parameter ╚═▷ 1702).
The easYgen LogicsManager screens show logical symbols according to the IEC standard
by default. However, it is also possible to change the LogicsManager screens to ASA
standard.
[Default]
Refer to ╚═▷ “9.3.3 Logical Symbols” for a table of symbols according to the different
standards.
Internal flags
Internal flags within the LogicsManager logical outputs may be programmed and used for
multiple functions.
Flag {x} Flag 1 Flag 2 Flag 3 Flag 4 Flag 5 Flag 6 Flag 7 Flag 8
Flag {x} Flag 9 Flag 10 Flag 11 Flag 12 Flag 13 Flag 14 Flag 15 Flag 16
Flag {x} Flag 17 Flag 18 Flag 19 Flag 20 Flag 21 Flag 22 Flag 23 Flag 24
Flag {x} Flag 25 Flag 26 Flag 27 Flag 28 Flag 29 Flag 30 Flag 31 Flag 32
[Default]
{yyyyy} Flag {x} 2 Determined by LogicsManager The flags may be used as auxiliary
{XX.XX} flags for complex combinations by
using the logical output of these
[(0 & 1) & 1] flags as command variable for
other logical outputs.
= {nnnnn}
Notes
[Default]
For conditions and explanation of programming please refer to ╚═▷ “9.3.1 LogicsManager
Overview”.
Utilizing the LogicsManager it is possible to establish specific times of the day that
functions (i.e. generator test run or or engine pre-lubrication) can be enabled.
The two daily time flags are activated each day at the configured time. The both flags
will be RESET at the end of the day on exact 23h.59m.59s. The both timer flags are
independent of each other and are considered as intermediate flags to create a special
control flag or function. Using the LogicsManager, the flags can be configured individually
or both flags can be combined to create a time range. Refer to chapter example to
understand their meaning better. Refer to ╚═▷ “6.3.17 Examples timer configuration”).
Note:
If the RTC time is within the configured time (with hour, minute and second), a latch with
the corresponding LM Timer flag (11.01, 11.02) becomes TRUE. This latch and the LM
flags will be reset each day at the time the RTC time 23:59:59 is reached. It is very
important to consider that, when testing the function. For a complete test of the
configuration it is recommended to let the RTC pass the configured time (even the
23.59.29 reset time).
The setpoints may be configured individually or combined via the LogicsManager. You
may configure for each month: daily, hourly, minutely, and/or even secondly time
setpoints depending on how you combine the setpoints in the LogicsManager.
Utilizing the LogicsManager it is possible to establish specific days of the week that
functions (i.e. generator exerciser) can be enabled.
The weekly time setpoint is enabled during the indicated day from 0:00:00 hours to
23:59:59 hours.
[Default]
1652 Timer {x}: Hour 2 0 to 23 h Enter the hour of the daily time
setpoint here.
1657 1652: [8 h]
Example
1657: [17 h]
• 0 = 0th hour of the day
(midnight).
• 23 = 23rd hour of the day
(11pm).
1651 Timer {x}: Minute 2 0 to 59 min Enter the minute of the daily time
setpoint here.
1656 [0 min]
Example
1650 Timer {x}: Second 2 0 to 59 s Enter the second of the daily time
setpoint here.
1655 [0 s]
Example
[Default]
1663 Active day 2 Day 1 to 31 Enter the day of the active switch
point here.
[1]
The active time setpoint is
enabled during the indicated day
from 0:00:00 hours to 23:59:59
hours.
Example
[Default]
Example
Example
Example
[Default]
[Default]
4.9.1 Operations
Inputs:
in conjunction with
The AM processes the inputs listed above depending on the selected "Type". The result
is always provided in form of
• a Boolean (BR).
• Freely usable AM to process signals and use the results for output as control.
• The analog result is accessible via the AnalogManager command variable pool.
• The resulting Boolean is accessible via the LogicsManager command variable pool.
3. ▷ Prepare each digital input by selecting source (parameter) and logical function.
4. ▷ Enter with "Apply"
▶ Press »Apply« button to send current settings to device.
5. ▷ Use analog and boolean result for intended (re)action.
*) Please be aware that the boolean information passes an operator. So the input for the
AnalogManager function block is the result of this!
AnalogManager Description
C1 Analog Constant input (constant) defined via HMI, ToolKit, or other (remote) interface
Notes
Type AnalogManager type (operation) selected via HMI, ToolKit, or other (remote) interface
Notes
Notes
Internal values within the AnalogManager analogue and logical outputs may be
programmed and used for multiple functions.
Flag {x} Value 1 Value 2 Value 3 Value 4 Value 5 Value 6 Value 7 Value 8
Default values
Factory settings of the internal values come with Type = "Pass Through" so the analog
result AR is same as analog input A1 (Default: A1 = 10.01 ZERO). The boolean result BR
is "FALSE".
[Default]
{yyyyy} AM Internal Value 2 Determined by AnalogManager The data source may be selected
{x} from the available data sources.
[A1 = 10.01 ZERO]
Notes
[Default]
{yyyyy} Internal value {x}: 2 user-defined (up 22 to characters) The text may have 0 through 22
Description characters.
[AM Internal Value {x}]
[Default]
Notes
The analog and/or logic result can be used via command variable 91.{x} AM Internal
value {x}.
Examples
Value: 65.1252
Value: 25.2360
Name: LM FALSE
Value: 0
Name: LM FALSE
Value: 0
Value: 25.0000
Name: ZERO
Value: 0
O1 Operator 1 L1 [passed]
O2 Operator 2 L2 [passed]
Please be aware that the input values stay "as is" (are NOT changed) if a new Type is
selected. Check all input settings A1, A2, C1, L1, L2, O1, O2 before applying!
Example:
If C1 = 0 and you select Type »Division«, you would ask the AnalogManager to divide by
zero ...
Boolean Result = L1
Boolean Result = L1
C1 = Hysteresis
L2 = Resets Hysteresis.
Notes
Notes
Notes
Notes
A1 = Limit
A1 = Value 1
Notes
A1 = Tracked Value
A2 not used
C1 = Limit
A1 = Tracked Value
C1 = Limit
Notes
Notes
Notes
One Shot Analog Result = Remaining time to fall back to FALSE [s]
Notes
General note
For even more flexibility and use of "self explaining" parameters 16 constants can be
defined. These constants are available as AnalogManager input AM 13.01 to AM 13.16.
Each parameter can be named individually and its value can be defined in a wide range:
AnalogManager Constants 1 to 16
AM 1 2 3 4 5 6 7 8
Constant
#
AM 9 10 11 12 13 14 15 16
Constant
#
Constant's name
The AM inputs selectable for A1 or A2 come with the predefined name of the Constant
e.g. "13.01 Free constant 1" but not with the customizable AM Description e.g. the value
of 15567 Description constant 1.
[Default]
{mmm} Description constant 2 user-defined (up 22 to characters) The text may have 0 through 22
{#} characters.
[13.yy Free constant {#}]
Notes
[Default]
The following chapters describe all available and configurable counters of the device.
The standard/basic counters - available in all devices of this product family - are
described in the chapter ╚═▷ “4.10.1 Generator Preset Values”. For special counters
please see the chapters following.
General notes
Maintenance call
A maintenance call will be issued if the configured number of maintenance hours has
expired or the configured number of days has expired since the last maintenance.
[Default]
2542 Number of starts set 2 Yes The current value of the start
counter is overwritten with the
value configured in "Number of
starts preset" (parameter ╚═▷
2541). After the counter has been
(re)set, this parameter changes
back to "No" automatically.
General notes
Maintenance call
A maintenance call will be issued if the configured number of maintenance hours has
expired or the configured number of days has expired since the last maintenance.
The easYgen device handles operating hours internally in floating format. To indicate the
operating hours on a display or to provide it in the data protocol the value is transferred
into an integer variable. This can cause display errors within 4*10-6 % in relation to the
absolute value.
[Default]
Notes
Notes
Notes
- menu path:
(symbol: wrench)]
Notes
Notes
Notes
- menu path:
(symbol: wrench)]
0 Operator
1 Service level
3 Commissioner
Notes
[Internal]
The operation hours are counted
internal from the easYgen
2574 Operation hours set 01 Yes The current value of this counter
is overwritten with the value
configured in "Operation hours
preset" (parameter ╚═▷ 2509).
After the counter has been (re)set,
this parameter changes back to
"No" automatically.
Notes
2515 Period of use preset 2 0 to 999,999.99 When setting the period of use
hours counter (refer to parameter
[0] ╚═▷ 2579), the counter always will
be set up to the value configured
here.
2579 Period of use set 01 Yes The current value of this counter
is overwritten with the value
configured in "Period of use
preset" (parameter ╚═▷ 2515).
After the counter has been (re)set,
this parameter changes back to
"No" automatically.
Notes
5 Operation
In operation the genset controller can be manually or remote controlled.
Front panel access is described in chapter ╚═▷ “4.1 Front Panel Access”.
Access via Remote Panel PR-3000XT is described in chapter ╚═▷ “4.3.6 Configure Remote
Panel Mode” and the Technical Manual »37593 RP-3000XT«.
Access via PLC depends on the interface and the data telegram used for communication.
For menu structure/menu tree see ╚═▷ “Menu structure (menu tree)”.
5.1 Power ON
Behavior during starting easYgen-3000XT
The start-up procedure of the easYgen-XT device can be caused by the following reasons:
• Power ON
This process is visualized by the HMI of the plastic housing version or the LEDs of the
metal housing version.
With power ON and a PC/laptop connected via USB service port it can happen that the
USB window that pops up doesn't show all files and/or the correct available free memory
at the device: Please unplug/plug the USB connection after the easYgen finished starting.
With power ON and connected USB service port it can happen that a connected USB
device is not detected correctly: Please unplug/plug the USB connection after the
easYgen finished starting.
With power cycle or reboot of the easYgen-XT the USB connection is lost: Please unplug/
plug and/or start USB connection again after the easYgen finished starting.
Power cycling
• HOME screen appears with the same measured values and state information as
before power cycling
Power cycling
The genset controls starts in the operating mode defined by parameter 1795 »Startup in
mode«. Refer to ╚═▷ “4.4.5 Configure Operation Modes” for details.
• front panel buttons (plastic housing variant or Remote Panel RP-3000XT or VNC
client),
• HMI configuration (plastic housing variant or Remote Panel RP-3000XT or VNC client),
• ToolKit
Usage
▶ STOP LED is illuminated at the front panel; ToolKit home page shows STOP icon left
beside the prime mover.
System reaction
In operating mode STOP neither the engine nor the GCB can be operated. Dependent on
the application mode the power circuit breakers cannot be operated.
CAUTION!
Selecting the operating mode STOP is not the same as an EMERGENCY STOP.
In some cases the easYgen will perform additional logic functions, such as an engine cool
down period, before the engine is stopped.
If the operating mode STOP is selected while the engine was already stopped the
following applies:
If the operating mode STOP is selected while the engine was running the following
applies:
• Dependent on the current application mode a soft shut down will be executed.
• If the STOP button is pressed again, the cool down will be interrupted.
If the operating mode STOP is selected while the engine performs a cool down the
following applies:
• Pressing the STOP button again causes an immediate stop of the cool down and
stops the engine.
If the conditions of the LogicsManager function "Enable MCB" (parameter ╚═▷ 12923) are
TRUE, the MCB will be closed again if it is open in STOP operating mode.
General usage
In the MANUAL operating mode (mode button »MAN« illuminated) both the engine circuit
breaker and the power circuit breaker can be operated via the push buttons along the
bottom of the display (softkeys). Additionally the Start(I)/Stop(O) buttons can be used to
start or stop the engine.
1. ▷ Use the mode button »MAN« to activate operating mode MANUAL.
NOTICE!
To open the breaker in a no-load condition, reduce the load manually in the setpoints
screen (╚═▷ “4.1.5 Specialized Menu Screens”).
▶ Success: The engine starts and the circular arrow and the eye symbol appear.
Failure: No change in the display until the "start failure" message appears.
▶ Success: The engine stops and the circular arrow and the eye symbol disappear.
Failure: No change in the display until the "stop failure" message appears.
Overview
No defined breaker ✔
state
Symbol Description
Indicates that the engine delayed monitoring has expired and the monitoring
functions are enabled.
General usage
In the AUTOMATIC operating mode (»AUTO«), all engine, GCB, and/or MCB functions are
operated via an interface, or automatically by the control unit (i.e. a mains failure).
The function of the easYgen depends on the configuration of the unit and how the
external signals are used.
For a more detailed description of the start/stop sequence of the engine and the
associated parameters refer to ╚═▷ “4.4.5.2 Operation Mode AUTO - Automatic Run”.
Start engine
Prerequisites:
• No shut down alarm is present. (for explanation of the alarm classes refer to ╚═▷
“9.5.4 Alarm Classes”).
If the AUTOMATIC operating mode is enabled and the mains fail, the engine and the
power circuit breakers will be operated according to the current application mode.
Prerequisites:
• No shut down alarm is present. (for explanation of the alarm classes refer to ╚═▷
“9.5.4 Alarm Classes”).
General usage
The operating mode (»TEST«) usually is a temporary operating mode. The idea is to test
the genset.
TEST operating mode always starts the engine, when changing into this mode
independent on an AUTOMATIC start order. Additionally the TEST operating mode
supports the emergency and critical run as well (if a mains failure occurs during the test
run). The operating mode TEST supports different sub modes so the operator can choose
if the breakers shall be closed during test run or whether the operating mode is changed
after the test run.
The function of the easYgen depends on the configuration of the unit and how the
external signals are used.
The illumination of the button becomes twinkling a short time before TEST
run is over.
For a more detailed description of the start/stop sequence of the engine and the
associated parameters refer to ╚═▷ “4.4.5.3 Operation Mode TEST”.
ᐳ In order to change the language setting via HMI, press the (soft)keys in the following
order:
Language parameter is on code level "0", so the instruction will work with
each code level.
6 Application Field
Device status
The following applications are described for devices with status "factory settings". This is
mandatory because parameters not changed during sample setup may have influence to
the devices' behavior!
If you want to use the same setup as described with the sample, please ensure factory
settings status of the device before changing it.
Otherwise you have to take care that the changes you did before do not "disturb" sample
settings!
Application Modes
For application modes overview see chapter ╚═▷ “2.2 Application Modes Overview”.
This application mode ( A01 ) may be used, where the breaker control is done external. In
this case, the easYgen will function as an engine control with generator and engine
protection. The control does not operate any breaker. Emergency mode (AMF operation) is
not supported in this application mode.
The easYgen requires the feedback reply from GCB and MCB in this application mode.
These replies are used to define, whether the easYgen controls frequency, shares the
load with other gensets or performs active load control.
The following feedback signals are used in this application mode and fixed to the
respective discrete inputs:
If the easYgen is intended to be operated in parallel with the mains, the mains voltage
measuring inputs must be connected.
Engine starts, if
Engine stops, if
• The reply GCB is open AND the LogicsManager "Start req. in AUTO" is not fulfilled
(FALSE) OR
Being parallel to mains or to other generator, the generator power will be reduced before.
Refer to ╚═▷ “4.4.5.2 Operation Mode AUTO - Automatic Run” for details.
This application mode ( A02 ) may be used for islanded operation applications.
In this case, the easYgen will function as an engine control with generator and engine
protection. The control unit can only open the GCB. Emergency mode (AMF operation) is
not supported in this application mode.
The easYgen requires the feedback reply from GCB and MCB in this application mode.
These replies are used to define, whether the easYgen controls frequency, shares the
load with other gensets or performs active load control.
The following feedback signals and commands are used in this application mode and
fixed to the respective discrete inputs and outputs:
If the easYgen is intended to be operated in parallel with the mains, the mains voltage
measuring inputs must be connected.
Engine starts, if
Engine stops, if
• The reply GCB is open AND the LogicsManager "Start req. in AUTO" is not fulfilled
(FALSE) OR
Being parallel to mains or to other generator, the generator power will be reduced before.
Refer to ╚═▷ “4.4.5.2 Operation Mode AUTO - Automatic Run” for details.
This application mode ( A03 ) may be used in applications, where only the GCB is operated
by the easYgen.
The easYgen will function as an engine control with generator and engine protection. The
control unit can open and close the GCB. Emergency mode (AMF operation) is not
supported in this application mode.
The easYgen requires the feedback reply from GCB and MCB in this application mode.
These replies are used to define, whether the easYgen controls frequency, shares the
load with other gensets or performs active load control.
The following feedback signals and commands are used in this application mode and
fixed to the respective discrete inputs and outputs:
If the easYgen is intended to be operated in parallel with the mains, the mains voltage
measuring inputs must be connected.
Engine starts, if
• If the voltage of generator and generator busbar is in range, the GCB will be
synchronized
If the voltage of generator is in range, and the generator busbar is dead, and no other
GCB is closed, and the MCB is closed the GCB will not be closed but an »operating
range failure« occurs.
Engine stops, if
Being parallel to mains or to other generator, the generator power will be reduced, before
the GCB will be opened.
Refer to ╚═▷ “4.4.5.2 Operation Mode AUTO - Automatic Run” for details.
This application mode ( A04 ) may be used for mains parallel operation. In this case, the
easYgen will function as an engine control with generator, mains and engine protection.
The control unit can open and close the GCB and the MCB. The breaker transition modes
“Open Transition”, “Closed Transition”, “Interchange” and “Parallel” are possible.
The easYgen requires the feedback reply from both circuit breakers in this application
mode. These replies are used to define, whether the easYgen controls frequency, shares
the load with other gensets or performs active load control.
The following feedback signals and commands are used in this application mode and
fixed to the respective discrete inputs and outputs:
Engine starts, if
According to the current active breaker transition mode the GCB and MCB will be
operated.
Engine stops, if
According to the current active breaker transition mode the GCB and MCB will be
operated.
Refer to ╚═▷ “4.4.5.2 Operation Mode AUTO - Automatic Run” for details.
Engine starts, if
With successful start the MCB will be opened and the GCB will be closed.
Engine stops, if
According to the current active breaker transition mode the GCB and MCB will be
operated.
In a multiple-unit mains parallel application, all easYgens need the same signals for:
The open and close contacts from all controls must be wired in parallel.
MCB Control
Voltage (3Ph)
Voltage (3Ph)
Voltage (3Ph)
Current (1Ph)
Current (1Ph)
Current (1Ph)
Open/Close
Open/Close
Open/Close
LOAD LOAD
Optional
Voltage (3Ph) Voltage (3Ph) Voltage (3Ph)
Configuration example
The following example describes the configuration of a typical mains parallel operation
with import/export power control at the interchange point and load-dependent start/stop.
Multiple generators are to be operated in parallel to the mains maintaining a stable power
at the interchange point. The generators shall be started depending on the momentary
load at the plant. An emergency operation in case of a mains failure is also intended.
The load dependent start/stop function (LDSS) shall be enabled with a remote start
request. LDSS shall depend on the reserve power on the busbar. In case of a dead busbar
(caused by a mains failure) all capable generators shall be started and operated with
their minimum running time.
1. ▷ Either on the front panel or using ToolKit navigate to menu [ Parameter / Configuration /
Configure application / Configure application modes / Load dependent start/stop /
General LDSS settings].
2. ▷ Configure the parameters below.
ID Parameter Value Comment
5752 Start stop Reserve The reserve power at the interchange point is to be
mode power considered for LDSS
5753 Dead All All generators shall start in case of a dead busbar (mains
busbar failure)
start mode
5754 Fit size of No The generator rated power is not considered for LDSS
engine
5755 Fit service Equal The remaining hours until next service are considered for
hours LDSS
5777 LDSS sort Off LDSS priority follows settings without permanently
priority refreshing.
always
3. ▷
Configure the LogicsManager 86.86 function »12930 LD start stop« as shown in (╚═▷
“6.2 Multiple Genset Applications”) to enable LDSS if a start request in automatic
operating mode or emergency mode are enabled.
• The first generator is only started if it is able to operate at a minimum load of 40 kW.
• The delay for removing a generator from the busbar shall be 60 seconds.
1. ▷ Either on the front panel or using ToolKit navigate to menu [ Load dependent start/stop /
Mains parallel operation].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
5772 MOP Add 30 s The add on delay in mains parallel operation is 20 seconds
on delay
5773 MOP Add 10 s The add on delay at rated load in mains parallel operation
on delay at is 10 seconds
rated load
5774 MOP Add 60 s The add off delay in mains parallel operation is 60 seconds
off delay
Additional assumptions are valid for islanded operation (IOP), i.e. in case of an mains
failure (emergency) operation:
• The delay for adding another generator shall be reduced to 3 seconds if a generator
at the busbar is operating above its rated load (accelerated start of the next
generator).
• The delay for removing a generator from the busbar shall be 180 seconds.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Parameter / Configuration /
Configure application / Configure application modes / Load dependent start/stop /
islanded operation].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
5765 IOP Add on 3s The add on delay at rated load in islanded operation is 3
delay at seconds
rated load
5766 IOP Add off 180 s The add off delay in islanded operation is 180 seconds
delay
1. ▷ Either on the front panel or using ToolKit navigate to menu [PARAMETER / Configuration /
Configure application / Configure operation modes / Operation mode AUTO].
2. ▷
Configure the LogicsManager 86.90 function »12120 Start req in AUTO« as shown in
(╚═▷ Fig. 211) to start the generator in Automatic operating mode if discrete input [DI
02] ("09.02 Discrete input 2") is energized or a remote start request ("04.13 Remote
request" = start via interface) is issued.
Configure emergency operation to be initiated if the mains fails for at least 3 seconds or
the MCB cannot be closed.
2800 Mains fail 3.00 s Emergency operation is initiated if the mains fail for a t
delay time least 3 seconds
3408 Emerg. Yes Emergency operation is initiated if the MCB fails to close
start with
MCB failure
Configure the power controller to use the internal power setpoint 1, which must be set to
0 kW import power.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure load control].
2. ▷ Configure the parameters listed below .
ID Parameter Value Comment
5526 Load Import The internal power setpoint 1 is a import power value
setpoint 1
General notes
The Communication Management gives an overview of all devices on the load share bus
in the system with regard to their different interfaces (Ethernet and CAN). See screen ╚═▷
Fig. 213).
Is the overall procedure that, if triggered, saves after 30 seconds the actual
constellation of members.
Triggers the System Update function. ╚═▷ “How to initiate a system update”
A timer of 30 second that starts after the System Update order was triggered.
This flag is active while the System Update delay timer is running.
After the System Update function was triggered and is finished, the saved
constellation is monitored in regards of any change.
Occurs if an additional device is recognized that does not exist in the actual saved
constellation. See Alarmlist for more details.
Occurs if a device is not recognized but exists in the actual saved constellation. See
Alarmlist for more details.
With the System Update order, a delay timer of 30 seconds is triggered and will be sent to
all other members on the load share and control bus. During this time the System Update
and missing member monitoring is disabled to not interrupt a well working plant by
upcoming alarm messages and control reactions on them due to shutting down a device
for maintenance. Short before the delay timer ends, the System Update function saves
the actual constellation of recognized devices.
During the delay time the LogicsManager flag 04.65 System update active is active.
NOTICE!
A change of the device ID or of parameter »9924 Load share interface« will reset the
saved constellation and a new System Update order needs to be triggered.
After the System Update function is finished, the saved constellation will be monitored.
Any deviation to this constellation will be recognized and noticed by an alarm that
describes the type of change.
To configure the »System update« Monitoring see ╚═▷ “4.5.6.18 Multi-Unit System
Update”:
By default the Missing Member alarm is incorporated into the frequency droop
LogicsManager ╚═▷ 12904.
Diagnostic screens
The easYgen-XT provides several overview screens to check all members on the load
share and control bus to help trouble shooting. These screens should be watched, before
the system update order is executed. They are located under [Status Menu / Next page /
Multi-unit / Diagnostic devices].
Availability
The system update function is available for all choices of »9924 Load share interface«:
The system update order can be initiated with the following options:
• By Softkey button »Syst. upd.« in the HMI. Navigate to [Next page / Multi-unit /
Diagnostic Devices]
• By ToolKit switch ╚═▷ 13356 »System update«. Navigate to [Status Menu / Multi-
unit / Diagnostic easYgen]
NOTICE!
Please ensure, if you are using the LogicsManager »7801 System update« or the
parameter »13356 Syst. upd«., that the signal goes false after executing. Otherwise, all
buttons relating to system update are locked.
The actual constellation of all members on the load share and control bus is displayed on
the according diagnostic screens in HMI and ToolKit.
The diagnostic screens are helping the operator to recognize the current communication
state of the load share and control bus. These screens should be reviewed before
executing a system update order. It is highly recommended to review the diagnostic
screen of each device that is participating on the load share/control bus. The system
update function will save exactly the states which are displayed in these screens.
In case of a missing member or system update alarm, these screens will also help the
operator to detect the root cause and for general troubleshooting.
The status of each device in the system will be indicated by a status ”LED“ in conjunction
with a status text.
Load Share Gateways (LSG) will be shown in the diagnostic screens as easYgen devices.
[Default]
= 11974
9925 Monitored easYgen -/- Latest result of members count Result of members count driven
by system update parameter
13356.
9951 Valid easYgen -/- Actual count of valid devices Actual count of devices that has
devices sent valid data.
All Diagnostic Screen Parameters are accessible via communication interfaces. The
system update command can be initiated through a free control flag.
The HMI diagnostic screen shows, additional to the Status of each device, the number of
Monitored devices and the »System Update« Button to activate the System Update order,
see ╚═▷ Tab. 101. While the System Update is active, the Event indication will
show »System Update«.
Because of space restrictions on the display, the status text of each device is realized
with symbols. Use ToolKit for text indications.
The ToolKit diagnostic screen shows, additional to the Status of each device, the number
of »Monitored devices«, the number of »Valid devices« and the ╚═▷ 13356 »System
update« to activate the System Update order, see ╚═▷ Tab. 101. While the System
Update is active, the remaining time will be shown. An active System Update Alarm is
also shown by the »System Update Layer 1« LED.
It is possible, that several system status messages are active at same time. So the
indication is prioritized:
It is possible, that several system status are causing different LED messages. So the
indication is prioritized:
Single bus topology means there is no redundant bus topology in use. Single bus
topologies are load share over CAN bus or a single Ethernet network.
Unit available This device is recognized and monitored with the missing
member monitor according to the latest System Update
GREEN order.
Add Device This device is recognized but not registered according to the
latest system update order. Therefore, the missing member
YELLOW monitoring does not observe the device.
Unit not recognized This device is not recognized according to the latest system
update order. (Missing Member Alarm)
RED
Not installed This device is neither recognized nor registered through the
latest system update order.
BLACK
Unit not recognized / This only applies to the own device. There is no other device
( / )
Not installed recognized according to the latest system update. Therefore
this unit is suspected to have an interface error as it does not
RED / BLACK
(twinkling) (twinkling) see any device on the bus.
(twinkling)
Redundant bus topology like CAN/Ethernet A to provide more safety in regards of load
share communication.
(Redundant CAN/EthernetA)
Unit available This device is recognized and monitored with the missing
member monitor according to the latest System Update
GREEN order.
Add Device This device is recognized but not registered according to the
latest system update order. Therefore, the missing member
YELLOW monitoring does not observe the device.
Only NW CAN This device is not recognized on the Ethernet A bus according
to the latest system update. Therefore, a Redundancy Lost
YELLOW Alarm is triggered.
Only NW CAN / Not This only applies to the own device. There is no other device
installed recognized on the Ethernet A bus according to the latest
YELLOW / system update. Therefore this unit is suspected to have an
(twinkling) (twinkling) interface Ethernet A error as it does not see any device on
BLACK
Ethernet A. A Redundancy Lost Alarm is triggered.
(twinkling)
Only NW A / Not This only applies to the own device. There is no other device
installed recognized on the CAN bus according to the latest system
YELLOW / update. Therefore this unit is suspected to have a CAN
(twinkling) (twinkling) interface error as it does not see any device on the CAN. A
BLACK
Redundancy Lost Alarm is triggered.
(twinkling)
Unit not recognized This device is not recognized according to the latest system
update order. (Missing Member Alarm)
RED
Not installed This device is neither recognized nor registered through the
latest system update order.
BLACK
Unit not recognized / This only applies to the own device. There is no other device
( / )
Not installed recognized according to the latest system update. Therefore
this unit is suspected to have an interface Ethernet A and
RED / BLACK
(twinkling) (twinkling) CAN error as it does not see any device on the bus. A
(twinkling) Redundancy Lost Alarm is triggered.
⚙ Commissioning
1. ▷ If the devices are connected to a network system, during the first commissioning it is to
observe in the diagnostic screens, whether all devices are recognized. Additional to that
the sum of all easYgens devices must match the number shown at parameter »9951
Valid easYgens devices«, see ╚═▷ Tab. 101.
If all these conditions are fulfilled the system update order can be executed. If any
condition is not fulfilled do trouble shooting before you hit any system update order.
NOTICE!
If you are removing the device before you hit the system update order, it is
important to know that it will come to a missing member alarm with the
consequence that the system goes into a droop function (if configured). If
that has happened, this issue can be solved by a system update order. But
do not forget to make a system check via the diagnostic screens.
2. ▷ You have now 30 seconds time to remove the device, without getting any consequences
on the system
The easYgen controller provides the user with power factor monitoring. These monitoring
functions permit for protection of the generator over- and under-excitation. The power
factor monitoring consists of a warning alarm and/or a shutdown alarm when enabled.
An alarm and the specified action will be initiated if the monitored power factor surpasses
the defined limits. Typically the generator is monitored for loss of excitation and/or over
excitation in a mains parallel application.
When a generator plant is paralleled against a utility, it is possible to control the power
factor at a desired reference. When the plant is operated in an island mode or islanded
parallel application, it is not possible to control the power factor. The load will dictate
what the power factor is due to the reactive nature of the load.
╚═▷ Fig. 214 shows a typical power factor (generator excitation) protection range, where
the desired range of operation (green area) is from 0.7 lagging (inductive) to 0.8 leading
(capacitive).
When the power factor exceeds either of these limits by entering the yellow shaded areas
starting at 0.7 lagging or 0.8 leading for more than 30 seconds, a class B warning alarm is
initiated.
If the power factor exceeds the desired range further and enters the red shaded areas
starting at 0.5 lagging or 0.6 leading for 1 second, a class E alarm is initiated and the
generator is shut down.
Configuration
1. ▷ In order to achieve the described protection, the power factor monitoring parameters
(╚═▷ “4.5.1.6.1.1 Generator Lagging Power Factor (Level 1 & 2)” or ╚═▷ “4.5.1.6.1.1
Generator Lagging Power Factor (Level 1 & 2)”) have to be configured as shown below.
Generator power factor lagging level 1 Generator power factor lagging level 2
Generator power factor leading level 1 Generator power factor leading level 2
The following example illustrates how to configure an easYgen to use an external load
setpoint via analog input [AI 03].
The external setpoint may be enabled using a switch, wired to discrete input [DI 09].
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure measurement].
2. ▷ Configure the parameter listed in ╚═▷ Tab. 102.
ID Parameter Value Comment
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure analog inputs /
Analog input 3].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
1101 User +0.00e0 A value of 0.00 is displayed at the minimum of the input
defined range
10116 Filter time Off No filter time constant is applied to the analog signal
constant
1103 Monitoring Low If the analog signal falls below 2 mA, a wire break is
wire break indicated
1104 Wire break Class B An alarm of class B will be issued in case of a wire break
alarm class
1105 Self No A wire break is not automatically cleared after it has been
acknowledge repaired
wire break
3636 Bargraph +0.00 The start value for the bargraph display of the analog input
minimum is 0.00
3637 Bargraph +2000.00 The end value for the bargraph display of the analog input
maximum is 2000.00
3. ▷
Configure the following parameters using ToolKit. They facilitate a more detailed display
of the analog value.
ID Parameter Value Comment
1125 Description ActivePower Analog input [AI 03] is labeled with "ActivePower SP (%)" on
SP the display
The load controller is to be configured that it uses a fixed load setpoint 1 of 2 MW unless
a switch energizes discrete input [DI 04] for enabling a variable load setpoint 2, which is
controlled by analog input [AI 03].
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure load control].
2. ▷ Configure the parameters listed below.
5526 Load Import The internal power setpoint 1 is a import power value
setpoint 1
5527 Load Steady The internal power setpoint 1 is a import power value
setpoint 2
3. ▷
Configure the LogicsManager function 12919 "Setp. 2 load" as shown in (╚═▷ Fig. 215) to
enable load setpoint 2 if discrete input [DI 09] is energized.
4. ▷ Continue similarly with setpoint 3 and setpoint 4
1. ▷
After the unit is configured as described above, the "Setpoint" screen may be viewed
from the main screen by selecting [Next page / Setpoints / Setpoints generator].
2. ▷
The "Analog inputs" screen may be viewed from the main screen by selecting [Next
page / Measured values / Analog inputs/outputs].
This is a simple example of a relay output that toggles from energized to de-energized in
automatic mode with adjustable on and off time.
This pulsing relay may be combined with a flexible limit, which can be programmed with a
function like low battery voltage to get a blinking warning light.
• Relay 2 is the discrete output [DO 2] and Flag 5 is used as an auxiliary flag.
• Relay 2 will be ON (energized) for 2 seconds and then OFF (de-energized) for 2
seconds as long as the easYgen is in automatic mode.
1. ▷
Configure the LogicsManager function "Flag 5" as shown in (╚═▷ Fig. 218).
▶ In this example is the Delay ON time in the LogicsManager of Flag 5 indicates how long
the pause is. The Delay OFF time of Relay 2 is the pulse duration.
1. ▷
Configure the LogicsManager function "Relay 2" as shown in (╚═▷ Fig. 219).
The following programming example shows how two relay outputs are energized in turns
when discrete input 9 is energized.
At first discrete output 11 will be energized, then, discrete output 12 will be energized,
then discrete output 11 and so on.
This logic may be used to change between two starter battery sets for each starting
cycle.
Configuration
Configure Relay 11 and Relay 12 as well as the Flags 2, 3, 4, and 5 as shown in the
following example.
You may also use the discrete input, which starts the engine by default [DI 02] or any
other input command instead of discrete input 9; for example the command variable
03.06 "Engine released".
1. ▷
Configure the LogicsManager function "Relay 11" as shown in (╚═▷ Fig. 220).
2. ▷
Configure the LogicsManager function "Relay 12" as shown in (╚═▷ Fig. 221).
3. ▷
Configure the LogicsManager function "Flag 2" as shown in (╚═▷ Fig. 222).
4. ▷
Configure the LogicsManager function "Flag 3" as shown in (╚═▷ Fig. 223).
5. ▷
Configure the LogicsManager function "Flag 4" as shown in (╚═▷ Fig. 224).
6. ▷
Configure the LogicsManager function "Flag 5" as shown in (╚═▷ Fig. 225).
Refer to ╚═▷ “4.1.1 Basic Navigation” for a detailed description of the navigation through
the various display screens.
Be sure to enter the password for code level 2 or higher to be able to access the required
configuration screens.
Refer to ToolKit Manual for a description of the installation, configuration and usage of
the ToolKit visualization and configuration application.
Preliminary Conditions
The LogicsManager factory settings are shown in ╚═▷ “9.3.5 Factory Settings”.
• AUTOMATIC
• STOP
It is possible to fix the operating mode using the LogicsManager function 86.16 "Operat.
mode AUTO" (parameter ╚═▷ 12510).
AUTOMATIC
1. ▷
The LogicsManager function "Operat. mode AUTO" (parameter ╚═▷ 12510) can be
configured as shown in (╚═▷ Fig. 226).
▶ AUTOMATIC operation mode is always enabled.
If an alarm of alarm class C through F occurs in AUTOMATIC operating mode, the control
does not return to STOP operating mode. If the alarm is cleared after Acknowledgment a
restart is initiated.
It is also possible to configure a discrete input for controlling the operating mode using
the LogicsManager function 86.16 "Operat. mode AUTO" (parameter ╚═▷ 12510) and
86.18 "Operat. mode STOP" (parameter ╚═▷ 12530).
1. ▷
The LogicsManager function "Operat. mode AUTO" (parameter ╚═▷ 12510) can be
configured as shown in (╚═▷ Fig. 227).
▶ AUTOMATIC operation mode is enabled as soon as discrete input 9 is energized.
STOP
1. ▷
The LogicsManager function "Operat. mode STOP" (parameter ╚═▷ 12530) can be
configured as shown in (╚═▷ Fig. 228).
▶ STOP operation mode is enabled as soon as discrete input 9 is de-energized.
There are a lot of different opinions of the behavior of a proper test mode. The easYgen
controller is supporting the following two modes:
In cases the dedicated TEST operation mode shall be not taken, the following procedure
can be taken to execute an TEST run in the operation mode AUTOMATIC.
This is the LogicsManager function "Start req. in AUTO" (parameter ╚═▷ 12120). No
special message appears on the display.
If the mains fail during start in auto, the unit keeps running until the mains return and the
mains settling time is expired or the conditions for "Start req. in AUTO" are FALSE again.
The result depends on which condition is active longer.
This is the LogicsManager function "Start w/o load" (parameter ╚═▷ 12540). If the
conditions for this LogicsManager function are TRUE, the engine will provide an automatic
starting sequence and keep the generator running until this function is FALSE again.
Then the unit will perform an automatic stop sequence and remain in standby in auto
mode.
The message "Start w/o load" is displayed during the test without load. If the mains fails
during test without load and the emergency mode is enabled, the unit will take over the
load.
The unit will open the MCB and close the GCB. When the mains return, it will transfer the
load back to the mains according to the configured breaker transition mode after the
mains settling timer has expired. The engine will keep running until the conditions for
"Start w/o load" are FALSE again.
The engine shall start once a month and run for one hour without overtaking the load.
The test day shall be every fifteenth of a month (with flag 2). A relay output can be
configured to indicate if this test is running, e.g. for a signal lamp.
1663 Active day 15 The active day is enabled every fifteenth of the month
1662 Active hour 10 The active hour is enabled between 10:00 and 11:00 am
every day
Configure the LogicsManager function "Flag 2" (parameter ╚═▷ 10701) as shown in (╚═▷
Fig. 229).
▶ Flag 2 becomes TRUE as soon as the configured active day and active time is reached.
3. ▷
The LogicsManager function "Start without load" (parameter ╚═▷ 12540) can be
configured as shown in (╚═▷ Fig. 230).
▶ Start without load mode is enabled as soon as Flag 2 becomes TRUE.
The easYgen may be start, stop, shut down, or acknowledged alarms with Modbus or CAN
protocol via the interface.
Therefore, two logical command variables (04.13 and 04.14) have to be configured with
the LogicsManager. 03.40 can handle Remote shutdown only.
A Remote shutdown 03.40 can be configured via LogicsManager internal flag (e.g.12230
Flag 1) combined with a free alarm LogicsManager (e.g. Free alarm 1) configured with
shutdown alarm class.
How to handle a Remote request 04.13 and a Remote acknowledge 04.14 is described
below in detail.
1. ▷ Either on the front panel or using ToolKit navigate to menu [PARAMETER: /
Configuration / Configure application / Configure operation modes / Operation mode
AUTO].
2. ▷ Open the LogicsManager 12120 for entry "Start req in AUTO".
3. ▷
Configure the LogicsManager function "Start req in AUTO" as shown in (╚═▷ Fig. 231).
▶ With this setting, the "Start req in AUTO" LogicsManager output becomes TRUE as soon
as the remote request signal is enabled.
External Acknowledgment
1. ▷ Either on the front panel or using ToolKit navigate to menu [PARAMETER / Configuration /
Configure monitoring / Miscellaneous / General monitoring settings].
2. ▷ Open the LogicsManager 86.15 for entry "Ext. acknowledge".
3. ▷
Configure the LogicsManager function "Ext. acknowledge" as shown in (╚═▷ Fig. 232).
▶ With this setting, the "Ext. acknowledge" LogicsManager output becomes TRUE as soon
as the remote acknowledge signal is enabled.
Please refer to ╚═▷ “6.5 Modbus Applications” for a description of how to configure the
LogicsManager functions via Modbus.
All interfaces access the same bits. The command variable "04.13 Remote request"
remains enabled in the easYgen until a new command is sent or the power supply failed
or is removed.
Remote start:
• The command variable "04.13 Remote request" changes to "1" (high) if the start bit
(ID 503, bit 0) changes from "0" to "1".
• The command variable "04.13 Remote request" changes to "0" (low) if the stop bit
(ID 503, bit 1) changes from "0" to "1" (╚═▷ Fig. 233).
Acknowledgment:
◦ 1st change of the logical output "External acknowledge" from "0" to "1":
Silence horn
◦ 2nd change of the logical output "External acknowledge" from "0" to "1":
System reaction
The easYgen does NOT react on the disabling of the start bit, but only on the enabling of
the stop bit.
This has the advantage that it is not required to maintain the connection established for
the whole time in case of a remote start.
The following figure shows the reaction of the command variable on the various changes
of the bits:
The control bits are sent on address 503 for a start via Modbus:
• Bit 0: Start
• Bit 1: Stop
• Bit 4: Acknowledgment
Please refer to ╚═▷ “6.5 Modbus Applications” for a description of how to enable control
bits via Modbus.
For further information on the CANopen protocol refer to ╚═▷ “7.4 CANopen Protocol” and
the CANopen file *.eds, which is delivered with the unit.
Please refer to ╚═▷ “6.5 Modbus Applications” for a description of how to enable control
bits via Modbus.
Remote Shutdown
For controlling the device with Remote Shutdown 03.40 please run setup as described
above but with 03.40 instead of 04.14 and using Bit 9 instead of Bit 0, 1, and 4.
Additionally
We recommend to connect external expansion boards, like the Woodward IKD 1 to CAN
bus 2. This CAN bus offers preconfigured settings for operating several expansion boards
including the IKD 1.
Refer to the ╚═▷ “4.7.4.1.2 Receive PDO {x} (Process Data Object)” and ╚═▷ “4.7.4.1.2
Receive PDO {x} (Process Data Object)” for the configuration of the parameters
concerned.
Refer also to ╚═▷ “7.4 CANopen Protocol” for a description of the data objects.
The easYgen may either be configured directly using the front panel or externally using
the ToolKit software.
Transmit PDO
The easYgen must be configured for sending to data protocol 65000 (external DOs 1 to 8)
and CAN ID 181 (hex) every 20 ms on TPDO1.
The upper described ID 181 (hex) can not be used if a LSG and a legacy device like GCP
30, GCP 20, MFR-2 are connected on CAN 1! The legacy devices are using IDs 181 - 18E
(hex) but can not be switched to another ID.
9600 COB-ID 181 (hex) / The COB-ID is configured to 181 (hex) or 385 (dec)
385 (dec)
╚═▷ Fig. 234 and ╚═▷ Tab. 104 display the example TPDO configuration for IKD 1.
Receive PDO
The easYgen must be configured for receiving data on an RPDO. The data received on
CAN ID 201h is interpreted as data protocol 65000 (external DIs 1 to 8).
9300 COB-ID 201 (hex) / The COB-ID is configured to 201 (hex) or 513 (dec)
513 (dec)
╚═▷ Fig. 236 and ╚═▷ Tab. 105 display the example RPDO configuration for IKD 1.
General notes
The IKD 1 is a Woodward I/O expansion board. It can be connected via CAN bus to
Woodward easYgen generator controllers or DTSC 200 Automatic Transfer Switch
Controllers. The configuration of the IKD 1 can be done with the IKD Configuration Tool
running on a PC/laptop, connected via serial interface to the IKD 1.
IKD Configuration Tool (P/N: 9927-2094) is a tool to quickly configure an IKD for
connection with the easYgen series or DTSC 200. It will check the parametrization of the
IKD 1 and allows to set it to one of the four different connection modes. The IKD
Configuration Tool replaces the LeoPC configuration tool.
6.3.6.1.1 Installation
Prerequisites
⚙ Installation
ᐳ The following steps needs to be performed for installing the IKD Configuration Tool
1. ▷ Uninstall any previous installation of IKD Configuration Tool
2. ▷ If software is not available on product CD-ROM: Please download from Woodward web
site
On start of the configuration software, you should get the following screen with fields,
buttons and selectors available:
⚙ Configuring an IKD
1. ▷
»COM port«
▶ Select between all serial ports your PC is providing. If there is no serial port available,
then this field is empty. Select the COM port to which the IKD is connected. (“COM1” for
example)
2. ▷ »Connect«
▶ Opens the selected serial port and tries to connect to the IKD. If successful, it will read
out the data from the IKD but it won’t change any data on the IKD. It will populate the
“CAN Baud rate” field with the CAN baud rate the IKD is currently configured. If the IKD
is already configured to one of the four different CAN node-IDs usable for an easYgen,
the corresponding button “IKD 1 on Node-ID x” will be colored green.
3. ▷ »Disconnect«
▶ Closes the serial port if it was opened. Must be used, if accidentally the wrong COM port
was selected and connected
4. ▷ »Status field« (yellow background)
▶ Shows messages about the status of the connection
5. ▷ »IKD on Node-ID X«
▶ Each of these four buttons has two functionalities:
1) After connecting, if the IKD 1 is already configured to one of the four different CAN
node-IDs usable for an easYgen, the corresponding button will be colored green.
2) By pressing the button the program will configure the IKD 1 to the selected node-ID
and CAN baud rate. After that it will read it out for check.
6. ▷ »CAN Baud rate«
Set up TPDO2 for the easYgen on the front panel as shown in (╚═▷ “ Transmit PDO”).
▶
Set up TPDO2 for the easYgen in ToolKit as shown in (╚═▷ “ Transmit PDO”).
2. ▷
Set up RPDO2 for the easYgen on the front panel as shown in (╚═▷ “Receive PDO”).
▶
Set up RPDO2 for the easYgen in ToolKit as shown in (╚═▷ “Receive PDO”).
If a PWM signal shall be used with a CAT ADEM speed controller, the duty cycle must be
limited between 10% and 85%.
For this, the following settings must be made to the respective analog output
Connect DI common (terminal 66) to power supply 12/24 V (terminal 63, minimum wire
size 0.5 mm² (20 AWG)).
▶ This enables to energize the discrete inputs against ground.
The Protective Earth terminal 61 is not connected on the sheet metal housing.
• Use the protective earth (PE) connector located at the bottom center of the sheet
metal housing instead.
The analog inputs of the easYgen-3000XT series are galvanically isolated to the power
supply. This allows for example to share a power setpoint 0/4 to 20 mA with up to three
devices.
Make sure that the source can drive the resulting burden.
The graphic above shows the terminal numbers for the analog input 3, but in principle it
works for all analog inputs which support a 0/4 to 20 mA signal.
General notes
The easYgen is supporting several expansion modules for external analog and digital
terminals. It is possible to connect up to four Woodward IKDs for digital inputs and
outputs and some third party devices e.g. from Phoenix or WAGO for analog and digital
inputs and outputs. Also a combination of the devices listed is possible.
• One part is located at the external analog/digital inputs/outputs pages and defines
how many inputs/outputs are used and the scaling of the analog types. Refer to
chapters ╚═▷ “4.4.2.4 Analog Inputs” for reference.
• The other part is located at the CAN2 interface pages and defines the Node IDs and
the types of external devices. Refer to chapter ╚═▷ “4.7.4.2.1 Expansion Modules at
CANopen Interface” for reference.
Additionally the external device must be configured to the correct baud rate and Node ID.
This could be done via DIP switches at Phoenix and WAGO, for the IKD with a Woodward
IKD configuration tool.
Phoenix ...
Bus coupler Discrete outputs Discrete inputs Analog outputs Analog inputs
IB IL 24 DO 8 IB IL 24 DI 4 IB IL TEMP 2 UTH
(only)
IB IL 24 DO 16 IB IL 24 DI 8 IB IL TEMP 2 RTD
(only)
IB IL 24 DO 32 (only) IB IL 24 DI 16
Phoenix ...
Bus coupler Discrete outputs Discrete inputs Analog outputs Analog inputs
IB IL 24 DI 32 (only)
ILB CO 24 DI 16 DO ILB CO 24 DI 16 DO
16 16
There is a maximum of three Phoenix bus couplers on the CAN bus. There is also a
maximum of 16AI 4AO 32DI and 32DO, which must not exceeded in all possible
combinations.
WAGO …
Type P/N two channel P/N four "Wire break" detection TYPE: Settings
version channel
version
Type P/N two channel P/N four "Wire break" detection TYPE: Settings
version channel
version
If adjustable variant
(750-469/003-000) is used:
use “Wago-I/O-CHECK” to
adjust (default Type is "K").
For details refer to ╚═▷
“Configurable WAGO
devices”
RTD 750-451 depends on the configured TYPE and Sender type: according to the type
type configured by “Wago-I/O-CHECK”
0/4 – 20 mA 750-496 4-20 mA: underrun TYPE: Linear or table Sender type: 4-20 mA or
0-20 mA
0-20 mA: no detection
Use “Wago-I/O-CHECK ” to configure the
different channels (Default type is 4-20 mA).
For details refer to ╚═▷ “Configurable WAGO
devices”.
# of DIs 2 x DI 4 x DI 8 X DI 16 X DI
# of DOs 2 x DO 4 x DO 8 X DO 16 X DO
There is a maximum of 16 WAGO analog inputs and up to 4 WAGO analog outputs with
up to 32 WAGO digital inputs and 32 WAGO digital outputs or up to 4 IKDs.
For all configurations with WAGO devices at least one WAGO CANopen fieldbus
coupler 750-337 is required!
If configurable WAGO devices are used, the mode of the terminal must be configured via
the PC software »Wago I/O Check«. This configuration cannot be done via easYgen
parameters. The easYgen parameters for the corresponding channels must be consistent
with the Wago configuration!
Configure this 8 channel device RTD (750-451) via the »Wago I/O-Check« with the
following process image:
The following types are not supported: Ni1000 (high resolution), Ni1000 (TK5000),
Pt1000 (EN 60751 high resolution), and 1200 Ohms.
Combinations of modules
All combinations of external terminals up to the maximum of 16AI, 4AO, 32DI, and 32DO
are possible.
There is a maximum of three bus couplers on the CAN bus for PHOENIX modules but (for
the moment) only one bus coupler on the CAN bus for WAGO modules.
So WAGO devices must use one and the same CAN address only.
The following table shows the possible configuration combination of the "Type" settings
(parameter ╚═▷ 5851) and the "Sender type" setting (parameter ╚═▷ 5856) for Phoenix
devices.
If Thermocouple is configured together with “Table A”, “Table B“, or “Linear” the input
works with a range from -15 mV to 85mV. In this case the values for parameters “Sender
value at display min./max.” must be entered in [mV] (e.g.: min: 0.00, max: 85.00).
The following flow charts step-by-step guide you through the configuration of external
CANopen devices.
The flow charts below use "P..." for Phoenix external interfaces but it works similar with
"W..." for WAGO devices.
WARNING!
Check parameters!
Ensure the parameters are configured correctly! Incorrect wiring of the system cannot be
compensated for with this parameter.
General notes
This feature allows the easYgen to adapt the phase angle measurement system according
to the transformer type. The phase angle of the "generator to busbar" and the "busbar to
mains" measurement can be compensated . The phase angle compensation is activated
with the parameters "Phase angle compensation GCB" (parameter ╚═▷ 8825) and "Phase
angle compensation MCB" (parameter ╚═▷ 8841) .
The controller provides an adjustment for a phase angle deviation in a range of +/-180.0°.
The range can be configured with the parameters "Phase angle GCB" (parameter ╚═▷
8824) and "Phase angle MCB" (parameter ╚═▷ 8842). This parameters compensate the
phase angle deviation, which can be caused by transformers (i.e. a delta to wye
transformer) located within the electrical system.
The easYgen generator voltage is connected to the low voltage side of a transformer with
the vector group Dyn5. The easYgen busbar voltage is connected to the high voltage
side. Because of the transformer, the phase angles between generator and busbar differs
due the closed GCB. The synchronization function of the easYgen can be compensated by
a configurable phase angle deviation.
Using vector group 5 (Dyn5) implies: α = 5 x 30° = 150°. Since 150° < 180° and the
easYgen busbar measurement is connected to the high voltage side, this results into "α"
to be used as phase difference. Configure parameter "Phase angle GCB" (parameter ╚═▷
8824) to "150°" to compensate the phase difference between generator/busbar.
The easYgen mains voltage is connected to the high voltage side of a transformer with
the vector group Yd11. The easYgen busbar voltage is connected to the low voltage side.
Because of the transformer, the phase angles between mains and busbar differs due the
closed MCB. The synchronization function of the easYgen can be compensated by a
configurable phase angle deviation.
Using vector group 11 (Yd11) implies: α = 11 x 30° = 330°. Since 330° > 180° and the
easYgen mains measurement is connected to the high voltage side, this results into
"-360° - α" to be used as phase difference. Configure parameter "Phase angle MCB"
(parameter ╚═▷ 8842) to "-30°" to compensate the phase difference between mains/
busbar.
General notes
The start/stop sequence in the easYgen is completely disabled. This function is needed in
applications where the control of the start/stop logic is completely done by an external
device (e.g. PLC).
The LogicsManager “Release engine monitoring” (parameter ╚═▷ 12999) has a special
function, if the "Start/stop logic mode" (parameter ╚═▷ 3321) is configured to “Off”.
When the LogicsManager becomes TRUE, the delayed monitoring function alarms are
triggered, which are delayed by the engine speed. If they become FALSE all engine speed
related monitoring functions are switched off. The LogicsManager "Start req. in AUTO"
(parameter ╚═▷ 12120) gets a special function if the "Start/stop logic mode" (parameter
╚═▷ 3321) is configured to “Off”. When the LogicsManager becomes TRUE the
operational mode begins. With becoming FALSE the operational mode will be left.
To operate the easYgen in this configuration correctly, the following needs to be done:
• The easYgen requires an external feedback, that the drive system will be started.
That is the precondition for the easYgen to trigger the delayed monitoring function,
which activates, after a delay time, the speed related monitoring functions.
(underspeed, underfrequency, undervoltage, etc.)
• The easYgen requires an external feedback, that the drive system will be stopped.
That is the precondition for the easYgen to deactivate the speed related monitoring
functions. This avoids upcoming alarms due the drive system is stopped.
• The easYgen must be directed to switch into the active operational mode or to exit
this operational mode. The operational mode proceeds with the actions according to
the configured application and transition modes.
Example
The following section shows a practical example, to explain in detail the described above
configuration.
╚═▷ Fig. 255 shows the LogicsManager “Release engine monitoring” (parameter ╚═▷
12999). The LogicsManager could be configured as follows:
• The external start/stop device gives an feedback to the easYgen via discrete input
[DI 02] ("09.02 Discrete input 2") that the drive system will be started or already is
started.
• Additionally the reply GCB closed ("04.06 GCB closed") must be true to get the result
true.
• The voltage controller is triggered, if the generator reaches the "Start value"
(parameter ╚═▷ 5616) and after the expired "Start delay" (parameter ╚═▷ 5617)
time. The voltage controller is switched off, if the engine speed (generator
frequency) falls below the “Release engine monitoring” (parameter ╚═▷ 12999)
level.
To activate the operational mode in the easYgen, discrete input [DI 02] ("09.02 Discrete
input 2") is used in the LogicsManager "Start req. in AUTO" (parameter ╚═▷ 12120) .
With removing the start request in AUTOMATIC the operational mode will be left.
• The closing (synchronization) of the GCB is triggered when LogicsManager "Start req.
in AUTO" (parameter ╚═▷ 12120) becomes TRUE.
• The opening (including power down ramping) of the GCB is triggered when
LogicsManager "Start req. in AUTO" (parameter ╚═▷ 12120) becomes FALSE.
General notes
feed-in power to stabilize mains. Ripple control is one form of power limitation and is used
in many countries around the world.
Functionality
The energy supply company provides a signal to the ripple control receiver to reduce the
feed-in power of the generating plant. The ripple control receiver switches four relay
contacts according to the required energy power level. This relay contacts correspond for
example to the following energy power levels:
• 60% - Step 2
• 30% - Step 3
The reduction of the feed-in power must be established within a certain time frame
(depending on national regulations).
Derating of power
The power reduction is realized by using the LogicsManager "Free derating" (parameter
╚═▷ 15146). This function is using an analog signal. For this reason the relay outputs of
the ripple control receiver must be converted into a corresponding analog signal. We
recommend a resistor array like shown in ╚═▷ Fig. 259 to convert the relay outputs into a
analog signal (0 to 500 Ohms).
R3 = 150 Ohms
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure analog inputs /
Analog input 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
1001 User +100.00 A value of 100 is displayed at the minimum of the input
defined range
min display
value
1040 Sender 500.000 The sender value at maximum display is 500 Ohms
value at
display
max.
1020 Sender 0 - 2000 A 0 to 2000 Ohms sender is used on the analog input
type Ohm
3632 Bargraph +0.00 The start value for the bargraph display of the analog input
minimum is 0
3633 Bargraph +100.00 The end value for the bargraph display of the analog input
maximum is 100 and indicates the derating
3. ▷ Configure the following parameters using ToolKit. They facilitate a more detailed display
of the analog value.
ID Parameter Value Comment
1025 Description Derating Analog input [AI 01] is labeled with "Derating" on the
display
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure load control /
Derating of power].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
15149 Direct On Only the analog source is used for the derating
derating
3. ▷
Configure the LogicsManager function »87.60 Free derating« as shown in (╚═▷ Fig. 260)
to enable derating of power if discrete input [DI 09] is energized.
Please configure "Alarm class" (parameter ╚═▷ 1362) of discrete input [DI 09] to
"Control".
After the unit is configured as described above, the maximal power setpoint looks like
shown in ╚═▷ Fig. 261.
General Notes
The Logic ensures that with changing of generators or a lacking neutral breaker the
neutral link is passed over to another active running generator. This requires information
exchange between the genset controls. The load share protocol in the easYgen provides
the according information.
Application Examples
L3
L2
L1
N
GCB 1 GCB 2
L1 L2 L3 L1 L2 L3
G G
N N
NC 1 NC 2
Function
The genset control closes principally after each successful start (firing speed reached) the
NC. The genset control proceeds with closing the GCB, if the NC has been closed
successfully. If the NC closure was not successful the easYgen issues an alarm. The NC
and GCB closure procedure is blocked from now on, until the alarm is acknowledged.
When the GCB is closed the genset control begins to figure out, whether the own NC can
remain closed or must be opened. This monitoring is done continuously.
AND
OR
◦ there is minimum one other NC in the same segment closed but the own
generator has a higher neutral interlocking priority
OR
◦ there is minimum one other NC in the same segment closed which has the
same neutral interlocking priority but the own genset control has a lower device
number
As long the engine/generator is running and the GCB is open the NC will be closed or
remains closed until the engine/generator is stopped.
The discrete input 12 (DI 12) is used as feedback of the Neutral contactor and cannot be
configured onto another discrete input. If the input is energized, the neutral contactor is
recognized as closed.
Monitoring NC Feedback
If the Neutral Interlocking is enabled, following event entries shall take place:
The priority for closing GCB is configurable. This priority is independent from the LDSS
priority. The customer can freely decide which generator shall get which priority.
The advantage of this determination is that the application is not fixed with rated power
settings. Maybe there are other circumstances which shall determine the neutral
interlocking priority.
6.3.15.1 Introduction
Please read the ╚═▷ “4.4.5.5.6 LDSS with predicted load” first, before you continue. The
chapter here shall give you additional information to dedicated application.
The easYgen is autarkic handling the function. The easYgen serves the GGB and the
MCB.
The easYgen cooperates with an external ATS control (e.g. Woodward DTSC-200).
The ATS control measures the mains power and serves the MCB and GGB. The ATS
device communicates over CANopen with the easYgen.
For parameter refer to ╚═▷ “4.4.5.5.6 LDSS with predicted load”. The easYgen informs the
user with AnalogManager variables and LogicsManager command variables about their
content.
For the relevant analog variables (10.73-10.78, 81.30 and group 21) refer to ╚═▷ “9.4
AnalogManager Reference”.
For the relevant logic variables 04.68, 04.69, 86.36, groups 32 – 36 refer to ╚═▷ “9.3.2
Logical Command Variables”.
6.3.15.2.1 General
Pre-assumption:
The AnalogManager ID9059 "Consumer load [kW]" passes the mains active power (02.74
Mains active power [W] * -0.001) to the LDSS PL function.
The Procedure:
As long as LM ID12120 “Start req in AUTO” is FALSE, the value of the AM ID9059
"Consumer load [kW]" goes into the 5-minute average power calculation which is passed
to the LDSS.
In that moment the LM ID12120 “Start req in AUTO” becomes TRUE, the last result of the
5-minute average calculation will be kept.
• The configuration ID5752 “Start stop mode” is ignored and forced to “Reserve
power”.
• The GGB close release will be internally blocked in the easYgen and the “Inhibit ATS
flag” LM 04.69 becomes true.
• The easYgen(s) starts in dead busbar start mode "LDSS", the according amount of
engines which are required to maintain the consumer load. (The parameter ID5753
is ignored in that moment).
If the rated power on the generator busbar is higher than the 5-minute average value
plus the active reserve power,
• the internal GGB close will be released and the “Inhibit ATS flag” 04.69 becomes
false.
• The generator load measurement easYgen is passed to the LDSS. So the LDSS is now
working like in the original mode.
• The configuration ID5752 “Start stop mode” is considered again. So the start stop
argue could change now.
• The 5-minute average value is now supplied by the real busbar load. Thus the 5-
minute average value is still tracked with the consumer load.
The procedure is stopped from that moment on the LM ID12120 “Start req in AUTO”
becomes FALSE. The generators will go into cooldown and stop.
6.3.15.2.2 Example “Emergency power unit” with internal GGB control (only easYgen 3400XT/
3500XT)
The example here shows what is to do if the easYgen shall start the correct amount of
engines in emergency mode. The GGB and MCB is operated by the easYgen. The breaker
transition mode is “Open transition”.
To incorporate the easYgen emergency mode into the procedure, the flag 04.09
“Emergency mode” is to include in the LM ID12120 “Start req in AUTO”.
The minimum generator power is set according to the largest expected load. The GGB is
released with the signal 04.69 “Inhibit ATS”. Minimum generator power (ID3440) is set to
the maximum expected load.
Fig. 270: Bypass minimum Pgen. (12936) becomes active if “Inhibit ATS” is false. That is
the case if there is enough generator rated power on busbar.
6.3.15.3.1 General
The external source mode is basically running like the internal source mode but the mains
measurement, the MCB and GGB control is provided by an external control. This control,
usually an ATS control (e.g. DTSC-200), sends the mains power and required condition
flags as CANopen TPDO messages to the easYgen device. Through configuration of the
RPDO in the easYgen the mains power and the condition flags are appearing
automatically in the LDSS PL function. The system allows to connect up to 5 ATS controls.
Pre-assumption
The explanation here is performed for an application with one ATS control. The principle is
expandable on up to 5 ATS controls.
In the external mode the Parameter ID9066 "Predicted load source” is configured as
“External”.
The ATS start signal 04.68 is entered in the LM ID12120 “Start req in AUTO”.
Fig. 272: Example of an application with predicted load source „external“. Additionally,
there is a hardwired inhbit signal from easYgens to the ATS".
Inhibit Signal
To inhibit the switching over of the ATS (e.g. DTCSs) before the nominal power on bus
matches the predicted load plus the active reserve power the easYgens activate an
inhibit signal.
For this reason every easYgen must have a relay configured with the command variable
04.69 “Inhibit ATS”. These signals must be hardwired as OR and connected to the ATS
inhibit input.
The procedure
As long as LM ID12120 “Start req in AUTO” is FALSE and the MCB is closed, the RPDO1
Word2 (ID3372) load 1 [kW] goes into the individual 5-minute average power calculation.
In the moment the mains fails [see RPDO1 Word1 (ID3371)] the feeding of the 5-minute
average value is stopped. So the last result of average calculation will be kept. If the GGB
is open [see RPDO1 Word1 (ID3371)] the value will be passed over as consumer load to
the LDSS function.
The ATS start signal from extern [see RPDO1 Word1 (ID3371)] sets the LM command
variable “ATS Start request” 04.68 on TRUE. So the LM ID12120 “Start req in AUTO”
becomes TRUE.
◦ The configuration ID5752 “Start stop mode” is ignored and forced to “Reserve
power”.
◦ The easYgen(s) starts in dead busbar start mode "LDSS", the according amount
of engines which are required to maintain the consumer load. (The parameter
ID5753 is ignored in that moment).
If the rated power on the generator busbar is higher than the 5-minute average value
plus the active reserve power,
• The generator load measurement easYgen is passed to the LDSS. So the LDSS is now
working like in the original mode.
• The configuration ID5752 “Start stop mode” is considered again. So the start stop
argue could change now.
The procedure is stopped from that moment on the LM ID12120 “Start req in AUTO”
becomes FALSE. The generators will go into cooldown and stop.
The easYgen emergency mode ID2802 must be disabled. The control over the start of the
engines is maintained by the ATS control.
The following chapter summarize the CANopen analog and binary variables within the
LDSS PL function. If the RPDO mapping is configured the LDSS PL function is supported.
Parallel to that the easYgen makes the binary and analog variables available via the
Logics- and AnalogManager. (see table below). These values can be taken for visualization
or additional logical purposes.
Each ATS must send a transmit PDO with minimal two words (INT16):
These two words are mapped inside the easYgen to according database identifiers.
The word with the binary flags is filled up on the last 4 bits. This word is mapped in the
easYgen to the according database index. (According to the ATS number)
The word with mains power is an 16INT signed. This word is mapped in the easYgen to
the according database index.
variable LDSS PL
variable LDSS PL
10.78 Average load sum [kW] If LDSS PL external is active, 10.78 is the load value
which is passed to the LDSS. It is the sum of all
averages (10.73 – 10.77) which have “Mains not
okay” and “GGB not closed”. In internal mode it is
the value of the 5 min. average of the AM
“Consumer load”.
81.30 AM Consumer load [kW] This analog variable provides the load for the LDDS
with load prediction in internal source mode.
6.3.15.4 Tables
RPDO Summary
RPDO Summary
RPDO Summary
RPDO Summary
RPDO Summary
ID Function
LMCV
86.36 LM: LDSS predicted 12606 Result of the LM LDSS with load
prediction.
General notes
The idea of direct derating of power is that the user can control with an analog value,
usually from outside, the amount of reduction. For this purposes mainly an analog input
would be taken. Additionally in some applications are uprating desired, for example
during load sharing procedures, which can be as well executed in determined
circumstances.
Derating
Uprating
If parameter Direct Derating (ID ╚═▷ 15149) is enabled, the output value of the
AnalogManager AM Derating source (ID15147) determines the uprating directly. This
value is also provided as AnalogManager variable under "81.21 AM Derating source". For
uprating the value shall vary between 100% (no uprating) and higher (uprating begins).
The scaling with parameters 15143, 15144, 15145 is not in use.
For derating the active power setpoint goes under 100%, for uprating the value goes over
100%, and with exact value of 100% the normal setpoint becomes active.
General notes
Some application require a functionality to reduce the active power dependent on a well
defined measured value. This could be for example a temperature measurement: The
load should decrease with higher temperatures according to a configured characteristic.
If parameter "Direct derating" (ID ╚═▷ 15149) is OFF, the LogicsManager “Free derating"
(ID ╚═▷ 15146) becomes TRUE and the analog value of power exceeds the value “Start
derating at” (ID ╚═▷ 15143), the unit begins to reduce the present active power setpoint.
The grade of reducing depends on the value “Stop derating at” (ID ╚═▷ 15144) and the
value of “Max. power deviation” (ID ╚═▷ 15145) which are configurable.
If the LogicsManager "Free derating" becomes FALSE, the unit ramps back to its original
setpoint. If derating/uprating is active, the display shows the indication
“Derating”/"Uprating".
The derating/uprating function can be used in islanded operation, too. The available rated
power from an engine can be reduced (derated) or increased (uprated) with an analog
value without adjusting a parameter value. With this function the engine can be
individually loaded within of an multiple gen islanded operation (asynchronous load
sharing).
The easYgen-XT offers a characteristic which is linearly decreasing the momentary active
power setpoint according to the value offered by the AnalogManager ╚═▷ 15147.
When the LogicsManager "Free derating" becomes active and the analog value crosses
the reducing start value, the configured derating line becomes active. If the derating line
falls below the active power setpoint the derating becomes effective. The grade of
reduction depends on the reducing stop value and the power deviation freely
configurable. If the LogicsManager "Power Reduction" becomes FALSE, the unit shall ramp
back to its original setpoint.
Fig. 273: Derating: Mains parallel operation; setpoint below rated power
If the engine is running and the LogicsManager "Free derating" is TRUE, the unit
monitors the water temperature. If the water temperature remains below the value
“Start derating at”, the reduction becomes not active and remains on 0%. If the water
temperature increases and so exceeds the value “Start derating at” the reduction
becomes active (the unit starts to derate the current active power setpoint). The rate of
reduction (slope) is determined by the values of “Start derating at”, “Stop derating at”,
and "Max. power deviation" ("Max. power deviation" also defines the minimum power).
In this example the power reduction would increase and so reduce power from 75% at
86.5 °C down to 60% = 120 kW at 90 °C. Temperature over 90 °C would cause the same
reduction of 40% in this example. So it is guaranteed that the engine is not running with
too less load.
A Setpoint below the Minimum (e.g. 55%) would not run into reduction.
With a smaller Maximum deviation (e.g. 20%) Minimum would be higher than Setpoint
and so not cause reduction.
If the engine is running and the LogicsManager "Free derating" is TRUE, the unit
monitors the water temperature. If the water temperature remains below the value
“Start derating at”, the reduction becomes not active and remains on 0%. If the water
temperature increases and so exceeds the value “Start derating at” the reduction
becomes active (the unit starts to derate the current active power setpoint). The rate of
reduction (slope) is determined by the values of “Start derating at”, “Stop derating at”,
and "Max. power deviation" ("Max. power deviation" also defines the minimum power).
The power reduction would increase and so reduce power from 100% at 80 °C down to
60% = 120 kW at 90 °C. Temperature over 90 °C would cause the same reduction of
40% in this example. So it is guaranteed that the engine is not running with too less
load.
In islanded parallel operation the derating factor is correlated to the utilization factor of
all engines! This becomes the new Maximum for derating.
The engine is running with 95% (190 kW). If the LogicsManager is enabled and
temperature has reached 80 °C the derating becomes effective (the unit starts to derate
the current active power setpoint). If the temperature is 90 °C or higher the maximum
reduction value of 40% becomes active. The current power of 95% will be reduced by
40% to 60%.
95% x 0.6 = 57% ≙ 0.57
This engine will run now with 200 kW x 0.57 = 114 kW.
In islanded parallel operation the derating is limited to 50%. It is not possible to get the
utilization factor lower than 50% by derating function.
If the derating signals are digital (e.g. different relay outputs from a ripple control
receiver; refer to ╚═▷ “6.3.13 Ripple Control Receiver”), the digital signals can be
transformed to an analog signal with a simple set of resistors.
General notes
In some conditions -- for example when knocking of the engine is detected -- the ECU
(Engine Control Unit) is requesting a load reduction via J1939 standard message SPN
3644. This message is only supported by some ECUs e.g. Woodward EGS.
To allow J1939 ECU derating parameter 15142 »J1939 derating « must be configured
to »ON«. The derating value of SPN 3644 is defined as a percentage value related to
rated power, with 0% = no derating and 100% = maximum derating (= no load).
If parameter 15142 »J1939 derating «is on and the power P is limited to:
In islanded parallel operation this behavior does not meet exactly the derating required
by the ECU. Because of the influence of load share, in the first moment the derating is
stronger than required by the ECU.
Example 1:
• Incorporate this internal flag into the LogicsManager equation which enables the
desired function.
Example 2:
Each working day (Monday to Friday) a function shall be activated at 10.15am for the
duration of 1 minute
• Incorporate this internal flag into the LogicsManager equation which enables the
desired function.
Example 3:
Each day a function shall be activated at 7am for the duration of 1 hour
• Incorporate this internal flag into the LogicsManager equation which enables the
desired function.
Refer to ╚═▷ “6.3.5 Performing Remote Start/Stop And Acknowledgment” for detailed
information.
The easYgen may start, stop, shut down, or acknowledge alarms with CAN/Modbus.
Therefore, two logical command variables (04.13 and 04.14) have to be configured with
the LogicsManager. 03.40 can handle Remote shutdown only.
A Remote Shutdown 03.40 can be configured via LogicsManager internal flag (e.g.12230
Flag 1) combined with a free alarm LogicsManager (e.g. Free alarm 1) configured with
shutdown alarm class.
No validation of the received answer Validation answer, if message has been received by the
unit
Only working in operational mode May take longer in case of communication with two
messages
6.4.1.1.1 RPDO
CANopen Master (parameter ╚═▷ 8993) must be enabled, if there is no PLC taking over
the master function.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface /
Configure CAN interface 1].
2. ▷ Configure the parameter listed below.
ID Parameter Value Comment
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00503 The 1st mapped object is set to control parameter 503.
Object
▶ Setting the COB-ID to 201 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is configured to overtake the received data coming in
by COB-ID 201 into the ID 503. The number of mapped objects is here 1.
CANopen message
The following table shows four data examples the device is receiving on the CANopen
bus. These data are sent as TPDO to the device (COB-ID 201). The settings above map
the received data to the easYgen address ID 503.
Notes
The following examples show the request format on CANopen with different Node-IDs.
The request on the bus is sent via the control parameter ID 503 of the device.
Please note that high and low bytes are exchanged in the sent address. The data (hex)
shows the state of parameter 503 to achieve the required control.
The following table shows exemplary request data for the device on the CANopen bus.
2B F7 21 01 00 00 00 00, 2B F7 21 01 10
00 00 00; 2B F7 21 01 00 00 00 00, 2B F7
21 01 10 00 00 00;
Notes
The message 2B F7 21 01 10 00 00 00
must be sent twice to acknowledge an
alarm completely. The first rising edge
(2B F7 21 01 00 00 00 00 followed by 2B
F7 21 01 10 00 00 00) disables the horn
and the second rising edge resets the
alarm.
If the Node-ID of the device is intended to be different from the standard value, the
parameter "Node-ID CAN bus 1" (parameter ╚═▷ 8950) must be configured accordingly.
Node-ID 2 is used in the following example.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface /
Configure CAN interface 1].
2. ▷ Configure the parameter listed below.
ID Parameter Value Comment
▶ With this setting, the Node-ID of the CAN interface 1 is set to 002.
The request on the bus is sent via the control parameter 503 of the device.
Please note that high and low bytes are exchanged in the sent address.
The data (hex) shows the state of parameter 503 to achieve the required control.
The following table shows exemplary request data for the device on the CANopen bus.
2B F7 21 01 00 00 00 00, 2B F7 21 01 10
00 00 00; 2B F7 21 01 00 00 00 00, 2B F7
21 01 10 00 00 00;
Notes
The message 2B F7 21 01 10 00 00 00
must be sent twice to acknowledge an
alarm completely. The first rising edge
(2B F7 21 01 00 00 00 00 followed by 2B
F7 21 01 10 00 00 00) disables the horn
and the second rising edge resets the
alarm.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Additional Server SDOs].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
The control request is equal to the request via default SDO communication channel, but
the device will listen to messages including the configured address as well.
The device listens to the CAN ID 600 (hex) + 2. Node-ID internally to perform the desired
control, the reply from the easYgen is sent on CAN ID 580 (hex) + 2. Node-ID.
The same is valid for the additional SDO communication channels 3, 4, and 5.
The following table shows exemplary request data for the device on the CANopen bus.
If parameters are written or read via two or more SDO communication channels at the
same time (before the first has answered), the second one will be refused.
Two different methods to transmit a frequency setpoint via CANopen are detailed below.
These are "Transmitting a frequency setpoint via RPDO" and "Transmitting a frequency
setpoint via default SDO communication channel". The advantages and the
disadvantages of these two methods are as follows.
No validation of the received answer Validation answer, if message has been received by the
unit
Only working in operational mode May take longer in case of communication with two
messages
6.4.1.2.1 RPDO
CANopen Master (parameter ╚═▷ 8993) must be enabled, if there is no PLC taking over
the master function.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface /
Configure CAN interface 1].
2. ▷ Configure the parameter listed below.
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00509 The 1st mapped object is set to control parameter 509.
Object
▶ Setting the COB-ID to 321 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is set to the address, for which the device is listening
on the bus. The number of mapped objects is 1 since 1 mapped object is used. The
request on the bus is sent with the control parameter 509 of the device as mapped
object 1.
CANopen message
The following table shows exemplary send data for the device on the CANopen bus.
Another possibility for transmitting a frequency setpoint is to send the value via default
SDO communication channel. The device listens to the CAN ID 600 (hex) + Node-ID
internally to perform the desired control, the reply is on CAN ID 580 (hex) + Node-ID.
The following example shows the send format on CANopen with Node-ID 1.
The value is sent on the bus via the control parameter 509 of the device.
Please note that high and low bytes are exchanged in the sent value.
The data (hex) shows the state of parameter 509 to achieve the required control.
The following table shows exemplary send data for the device on the CANopen bus.
It is possible to transmit a voltage setpoint value via the CANopen protocol. Prerequisite
for the use of a voltage setpoint via an interface is the configuration of the voltage
setpoint sources with AnalogManager ╚═▷ 5618 for voltage setpoint 1 or AnalogManager
╚═▷ 5619 for voltage setpoint 2 .
The respective voltage setpoint source is to be configured to 05.59 "Interface V setp [V]".
With "...-XT" the former used parameters 5618 and 5619 became AnalogManagers with
the same ID but changed from »%« to »V«. AnalogManagers whose Analog result is an
absolute value need absolute input(s). For this example, both »Analog
input« and »Analog result« must be the same type: »Hz«.
With "...-XT" the former used 05.09 "Interface volt.setp." became a % value 05.09
"Interface v setp [%]" and so cannot be used for setpoint transmission because an
absolute value is mandatory! The parameter of the absolute value of the interface
frequency setpoint is 05.59 "Interface v setp [V]".
Two different methods to transmit a voltage setpoint setpoint via CANopen are detailed
below.
These are "Transmitting a voltage setpoint via RPDO" and "Transmitting a voltage setpoint
via default SDO communication channel". The advantages and the disadvantages of
these two methods are as follows.
No validation of the received answer Validation answer, if message has been received by the
unit
Only working in operational mode May take longer in case of communication with two
messages
6.4.1.3.1 RPDO
CANopen Master (parameter ╚═▷ 8993) must be enabled, if there is no PLC taking over
the master function.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface /
Configure CAN interface 1].
2. ▷ Configure the parameter listed below.
ID Parameter Value Comment
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00510 The 1st mapped object is set to control parameter 510.
Object
▶ Setting the COB-ID to 321 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is set to the address, for which the device is listening
on the bus. The number of mapped objects is 1 since 1 mapped object is used. The
request on the bus is sent with the control parameter 510 of the device as mapped
object 1.
CANopen message
The following table shows exemplary send data for the device on the CANopen bus in line
1.
Another possibility for transmitting a voltage setpoint is to send the value via default SDO
communication channel. The device listens to the CAN ID 600 (hex) + Node ID internally
to perform the desired control, the reply is on CAN ID 580 (hex) + Node ID.
The following example shows the send format on CANopen with Node ID 1.
The value is sent on the bus via the control parameter 510 of the device.
Please note that high and low bytes are exchanged in the sent value.
The data (hex) shows the state of parameter 510 to achieve the required control.
It is possible to transmit a power factor setpoint value via the CANopen protocol.
Prerequisite for the use of a power factor setpoint via an interface is the configuration of
the power factor setpoint source (parameter ╚═▷ 5638 for power factor setpoint 1 source
or parameter ╚═▷ 5639 for power factor setpoint 2 source)
Two different methods to transmit a power factor setpoint via CANopen are detailed
below.
These are "Transmitting a power factor setpoint via RPDO" and "Transmitting a power
factor setpoint via default SDO communication channel". The advantages and the
disadvantages of these two methods are as follows.
No validation of the received answer Validation answer, if message has been received by the
unit
Only working in operational mode May take longer in case of communication with two
messages
6.4.1.4.1 RPDO
CANopen Master (parameter ╚═▷ 8993) must be enabled, if there is no PLC taking over
the master function.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface /
Configure CAN interface 1].
2. ▷ Configure the parameter listed below.
ID Parameter Value Comment
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00508 The 1st mapped object is set to control parameter 508.
Object
▶ Setting the COB-ID to 321 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is set to the address, for which the device is listening
on the bus. The number of mapped objects is 1 since 1 mapped object is used. The
request on the bus is sent with the control parameter 508 of the device as mapped
object 1.
CANopen message
The following table shows exemplary send data for the device on the CANopen bus. A
power factor setpoint of 0.85 capacitive/leading is transmitted (64689 (dec) [65536-850]
= FCAE (hex) → AE FC according to the CANopen protocol) in line 1. Please note that
negative (capacitive or leading) power factor values are deducted from 65536 (dec) or
FFFF (hex).
Another possibility for transmitting a power factor setpoint is to send the value via default
SDO communication channel. The device listens to the CAN ID 600 (hex) + Node-ID
internally to perform the desired control, the reply is on CAN ID 580 (hex) + Node-ID.
The following example shows the send format on CANopen with Node-ID 1.
The value is sent on the bus via the control parameter 508 of the device.
Please note that high and low bytes are exchanged in the sent value.
The data (hex) shows the state of parameter 508 to achieve the required control.
The following table shows exemplary send data for the device on the CANopen bus.
It is possible to transmit a power setpoint value via the CANopen protocol. Prerequisite for
the use of a power setpoint via an interface is the configuration of the power setpoint
sources with AnalogManager ╚═▷ 5539 for power setpoint 1 or AnalogManager ╚═▷ 5540
for power setpoint 2.
The respective power setpoint source is to be configured to 05.56 "Interface P setp [kW]".
With "...-XT" the former used parameters 5539 and 5540 became AnalogManagers with
the same ID but changed from »%« to »W«. AnalogManagers whose Analog result is an
absolute value need absolute input(s). For this example, both »Analog
input« and »Analog result« must be the same type: »W«.
With "...-XT" the former used 05.06 "Interface pow. setp." became a % value 05.06
"Interface P setp [%]" and so cannot be used for setpoint transmission because an
absolute value is mandatory! The parameter of the absolute value of the interface power
setpoint is 05.56 "Interface P setp [kW]".
Please note that the type of the power setpoint (Steady, Import, or Export) must also be
defined (parameter ╚═▷ 5526 for load setpoint 1 or parameter ╚═▷ 5527 for load setpoint
2).
Two different methods to transmit a power setpoint via CANopen are detailed below.
These are "Transmitting a power setpoint via RPDO" and "Transmitting a power setpoint
via default SDO communication channel". The advantages and the disadvantages of
these two methods are as follows.
No validation of the received answer Validation answer, if message has been received by the
unit
Only working in operational mode May take longer in case of communication with two
messages
6.4.1.5.1 RPDO
CANopen Master (parameter ╚═▷ 8993) must be enabled, if there is no PLC taking over
the master function.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface /
Configure CAN interface 1].
2. ▷ Configure the parameter listed below.
ID Parameter Value Comment
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00507 The 1st mapped object is set to control parameter 507.
Object
▶ Setting the COB-ID to 321 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is set to the address, for which the device is listening
on the bus. The number of mapped objects is 1 since 1 mapped object is used. The
request on the bus is sent with the control parameter 507 of the device as mapped
object 1.
CANopen message
The following table shows exemplary send data for the device on the CANopen bus in line
1.
Another possibility for transmitting a power setpoint is to send the value via default SDO
communication channel. The device listens to the CAN ID 600 (hex) + Node-ID internally
to perform the desired control, the reply is on CAN ID 580 (hex) + Node-ID.
The following example shows the send format on CANopen with Node-ID 1.
The value is sent on the bus via the control parameter 507 of the device.
Please note that high and low bytes are exchanged in the sent value.
The data (hex) shows the state of parameter 507 to achieve the required control.
The table above shows exemplary send data for the device on the CANopen bus in line 2.
A single RPDO can transmit multiple objects. The receive PDO can be used for four
objects with 16 bits (2 bytes).
If larger objects - for example 32 bits (4 bytes), like for voltage and power setpoints - are
used, the maximum number of objects is reduced.
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00509 The 1st mapped object is set to control parameter 509.
Object
9912 2. Mapped 00507 The 2nd mapped object is set to control parameter 507.
Object
9913 3. Mapped 00508 The 3rd mapped object is set to control parameter 508.
Object
▶ Setting the COB-ID to 321 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is set to the address, for which the device is listening
on the bus. The number of mapped objects is 1 since 1 mapped object is used. The
request on the bus is sent with the control parameters 509, 507, and 508 of the device
as mapped object 1.
CANopen message
The following table shows exemplary send data for the device on the CANopen bus in line
1. The following setpoints are transmitted:
• Power factor 0.9 lagging (900 (dec) = 0384 (hex) → 84 03 according to the CANopen
protocol)
Two different methods for remotely switch between setpoints via CANopen are detailed
below.
These are switching between setpoints via »RPDO« or »Default SDO communication
channel«. The advantages and the disadvantages of these two methods are as follows:
No validation of the received answer Validation answer, if message has been received by the
unit
Only working in operational mode May take longer in case of communication with two
messages
6.4.1.7.1 RPDO
CANopen Master (parameter ╚═▷ 8993) must be enabled, if there is no PLC taking over
the master function.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface /
Configure CAN interface 1].
2. ▷ Configure the parameter listed below.
ID Parameter Value Comment
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00504 The 1st mapped object is set to control parameter 504.
Object
▶ Setting the COB-ID to 321 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is set to the address, for which the device is listening
on the bus. The number of mapped objects is 1 since 1 mapped object is used. The
request on the bus is sent with the control parameter 504 of the device as mapped
object 1.
CANopen message
The following table shows exemplary send data for the device on the CANopen bus. The
respective bits are enabled by sending the data of the respective lines.
Another possibility for changing a setpoint is to enable the bit via default SDO
communication channel. The device listens to the CAN ID 600 (hex) + Node-ID internally
to perform the desired control, the reply is on CAN ID 580 (hex) + Node-ID.
The following example shows the send format on CANopen with Node-ID 1.
The value is sent on the bus via the control parameter ID 504 of the device.
Please note that high and low bytes are exchanged in the sent value.
The data (hex) shows the state of parameter 504 to achieve the required control.
The following table shows exemplary send data for the device on the CANopen bus.
It is possible to transmit a remote control bit via the CANopen protocol. Such a remote
control bit can be sent by a PLC to remotely control the easYgen if this remote control bit
is used as a command variable in a LogicsManager function.
Configure RPDO
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Receive PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9911 1. Mapped 00505 The 1st mapped object is set to control parameter 505.
Object
▶ Setting the COB-ID to 334 (hex) is exemplary; usually, the PDOs are in the
range of 181 (hex) to 57F (hex).
With this setting, the Receive PDO is set to the address, for which the device is listening
on the bus. The number of mapped objects is 1 since 1 mapped object is used. The
request on the bus is sent with the control parameter 505 of the device as mapped
object 1.
CANopen message
The following table shows exemplary send data for the device on the CANopen bus.
Another possibility for transmitting a power setpoint is to send the value via default SDO
communication channel. The device listens to the CAN ID 600 (hex) + Node-ID internally
to perform the desired control, the reply is on CAN ID 580 hex) + Node-ID.
The following example shows the send format on CANopen with Node-ID 1.
The value is sent on the bus via the control parameter 249 of the device.
Please note that high and low bytes are exchanged in the sent value.
The data (hex) shows the state of parameter 249 to achieve the required control.
The table above shows exemplary sends data for the device on the CANopen bus in line
2.
This is a configuration example for sending an object (data protocol 5003) on CAN ID 2AE
(hex) every 20 ms on TPDO1. For this, TPDO1 must be configured as follows:
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Transmit PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
9602 Transmission 255 The number of required sync messages is set to 255.
type
The data to be sent (Mapped Objects) may be provided on request by configuring the
Sync Message (parameter ╚═▷ 9100) and the Transmission Type (parameter ╚═▷ 9602,
╚═▷ 9612, ╚═▷ 9622, ╚═▷ 9632, or ╚═▷ 12793) of a TPDO. The unit is requested to send
its data by sending a Sync Message.
The number of required Sync Messages is determined by the setting of the Transmission
Type.
If the data is to be sent on request, Bit 30 of the Sync Message (parameter ╚═▷ 9100)
must be configured to "0" and the CANopen Master (parameter ╚═▷ 8993) function must
be configured to "Off".
Additional example
The Transmission Type of TPDO 1 (parameter ╚═▷ 9602) is configured to "2" in the
following example. This means that a message of the configured TPDO is sent by the unit
after two Sync Messages have been sent to the unit.
1. ▷ Either on the front panel or using ToolKit navigate to menu [Configure CAN interface 1 /
Transmit PDO 1].
2. ▷ Configure the parameters listed below.
ID Parameter Value Comment
The recorded data shows that the data of the Mapped Object (in this example Mux 5) is
sent (╚═▷ Tab. 114) after sending the Sync Message twice (╚═▷ Tab. 115).
80 - -
1 2 80 -
2 1 2AE 8B 13
6.4.3 Troubleshooting
General diagnosis
Connected device (Phoenix I/O board) Are all LEDs at the expansion modules illuminated green (i.e. correctly
cannot be configured connected)?
No data is sent by the Woodward Is the unit in operational mode (heartbeat - CAN ID 700 (hex) + Node-ID has the
controller content 5 (hex)?
No data is received by the Woodward Is the unit in operational mode (heartbeat - CAN ID 700 (hex) + Node-ID has the
controller content 5 (hex)?
Is the unit in operational mode? If not, start it via another device or put in NMT
Master (parameter ╚═▷ 8993).
No SDOs (configuration messages) are Is the CAN ID assigned more than once?
received by the unit
Is the CAN ID 600 (hex) + Node-ID of the easYgen already used in a PDO (COB-
ID)?
Are RPDOs or TPDOs higher then 580 (hex) or lower than 180 (hex) used?
Data Format(s)
Modbus registers are read and written according to the Modbus standard as Big-endian.
Composite data types like LOGMAN, ANALOGMANAGER, and TEXT use separate
descriptions.
Please find remote control parameter 505 described at: ╚═▷ “ Remote control word 3”. It
works similar like 503 described below.
The following descriptions refer to the remote control parameter 503 as described in ╚═▷
“9.2.9 Additional Data Identifier”.
It may be necessary to shift the address by 1 depending on the used PC software. In this
case, the address would be 504 for example.
In order to issue a command, the respective bit of object 21F7 (hex), i.e. parameter 503,
must be enabled. The following bits are used for this:
This bit activates the LogicsManager command variable 04.13 "Remote request" and
enables a remote start.
This bit deactivates the LogicsManager command variable 04.13 "Remote request"
and disables a remote start.
This bit activates the LogicsManager command variable 03.40 "Remote Shutdown-
Status". With this function the engine is immediately shut down without auxiliary
service and cool down. This works independent from beaker conditions.
The following Modscan32 screenshot (╚═▷ Fig. 276) shows the configurations made to
remote control parameter 503. It is possible to set the format to binary to view single bits
using the "display options".
╚═▷ Fig. 277 shows how bit 0 is set using the ModScan32 Software.
╚═▷ Fig. 278 shows how bit 1 is set using the ModScan32 Software.
╚═▷ Fig. 279 shows how bit 4 is set using the ModScan32 Software.
╚═▷ Fig. 280 shows how bit 9 is set using the ModScan32 Software.
This (remote) shutdown request can be taken by LogicsManager equation 12230 to set
Flag 1 (see ╚═▷ Fig. 281). To perform an immediately shutdown, the free alarm has to be
configured as alarm class F. Free alarm 1 configuration ╚═▷ Fig. 282 shows how the
Monitoring source LM ╚═▷ 8120 »Free alarm 1« is set to Flag 1 and the Alarm class 8121
is set to Class F.
For a remote setting of the control setpoints, it is necessary to use the interface setpoints
instead of the internal setpoints.
For example, use data source 05.56 "Interface P setp [kW]" in AnalogManager ╚═▷ 5539
(AM ActPower SP1 [kW]) to transmit a load setpoint via interface. No password is required
to write this value.
Screen shots beside show an exemplary configuration of the load setpoint 1 source. All
other setpoint sources are configured accordingly.
The interface setpoints may be set using the objects for active power, power factor,
frequency, and voltage (refer to ╚═▷ “9.2.9 Additional Data Identifier” for detailed
information).
The active power setpoint value must be written to object 21FB (hex), i.e. parameter
507.
A power value of 50 kW = 500 (dec) = 01F4 (hex) is to be transmitted.
The high word must be written to the lower address and the low word must be written to
the higher address.
Open the "Preset Multiple Registers" dialog by selecting [Setup / Extended / Preset Regs]
from the menu.
2. ▷
The power factor setpoint value must be written to object 21FC (hex), i.e. parameter
508.
A power factor of 1 = 1000 (dec) = 03E8 (hex) is to be transmitted.
1. ▷
Analogous to ╚═▷ Chapter 6.5.1.2 set the parameter address as shown in ╚═▷ Fig. 289.
The frequency setpoint value must be written to object 21FD (hex), i.e. parameter 509.
A frequency value of 50.00 Hz = 5000 (dec) = 1388 (hex) is to be transmitted.
Analogous to ╚═▷ Chapter 6.5.1.2 set the parameter address as shown in ╚═▷ Fig. 290.
The voltage setpoint value must be written to object 21FE (hex), i.e. parameter 510.
A voltage value of 400 V = 400 (dec) = 0190 (hex) is to be transmitted.
The high word must be written to the lower address and the low word must be written to
the higher address.
Analogous to ╚═▷ Chapter 6.5.1.2 set the parameter address as shown in ╚═▷ Fig. 291.
☼ Example
Using the "display options" set the format to binary to view single bits (╚═▷ Fig. 293).
╚═▷ Fig. 294 shows how bit 7 is set to enable the active power setpoint 2.
╚═▷ Fig. 295 shows how bit 6 would be set to enable the power factor setpoint 2.
╚═▷ Fig. 296 shows how bit 5 would be set to enable the frequency setpoint 2.
╚═▷ Fig. 297 shows how bit 4 would be set to enable the voltage setpoint 2.
The example tables below are excerpts. Refer to the following chapters for the complete
parameter lists:
Be sure to enter the password for the code level that is needed to get access for
changing parameter settings via the preferred interface.
The new entered value must comply with the parameter setting range when changing
the parameter setting.
☼ Example
1. ▷
Set the configuration to address parameter 1766 as shown in ╚═▷ Fig. 298.
3Ph 3W
1Ph 2W
1Ph 3W
☼ Example
If the setting range contains a list of parameter settings like in this example, the
parameter settings are numbered and start with 0 for the first parameter setting. The
number corresponding with the respective parameter setting must be configured.
1. ▷
Set the configuration to address parameter 1851 as shown in (╚═▷ Fig. 299).
▶ The parameter is configured to "3Ph 4W".
Next to HMI and ToolKit, LogicsManager can also be configured via Modbus.
The LogicsManager screens below show parts of the command chain. How to generate
hex code words is described for each part of the Modbus message.
Word 0 and word 1 contain the hex code of the Delay times but in the reverse order of
double-byte words, i.e. low byte before high byte.
Words 4, 5, and 6 contain the hex codes of the respective command variable ID's decimal
value but in the reverse order of double-byte words, i.e. low byte before high byte.
The command variable prefix e.g., "04.13" is the number of the command variable not
it's ID.
Refer to ╚═▷ “9.3.2 Logical Command Variables” for the command variable IDs.
Words 2 and 3 contain a sequence of nibbles each representing a sign or operator of the
equation.
The Data words table below shows the sequence how to arrange the LogicsManager
setting that build the command chain.
Word 2 Word 3
Sign 1 Operator 1 Sign 2 Operator 2 Sign 3 not used not used not used
Signs Operators
"NOT" 0 "AND" 0
"—" 1 "NAND" 1
"TRUE" 2 "OR" 2
"FALSE" 3 "NOR" 3
"XOR" 4
"NOT-XOR" 5
The hex code of words 2 and 3 is taken "as is" ¾ don't swap high byte and low byte.
It may be necessary to shift the address by 1 depending on the software you use for
Modbus communication.
1. ▷ Copy the complete message of 7 words to the address [parameter number +1] in one
step.
Delay ON Delay OFF Logic equation 1 Logic equation 2 Command Command Command
1 2 3
low high low high Sign Ope‐ Sign Ope‐ Sign 0x00 0x00 0x00 low high low high low high
byte byte byte byte 1 rator 2 rator 3 byte byte byte byte byte byte
1 2
Example
Delay ON Delay OFF Logic equation 1 Logic equation 2 Command Command Command
1 2 3
3.00 sec 10.00 sec ¾ Or False Or ¾ -/- -/- -/- No. 09.02 No. 00.08 No. 04.13
ID = ID = ID =
low high low high Sign Ope‐ Sign Ope‐ Sign 0x00 0x00 0x00 low high low high low high
byte byte byte byte 1 rator 2 rator 3 byte byte byte byte byte byte
1 2
2C 01 E8 03 1 2 3 2 1 0 0 0 08 02 07 00 FB 00
The Modbus message for the LogicsManager equation used for description above is
2C01 / E803 / 1232 / 1000 / 0802 / 0700 / FB00 (hex).
The following chapters describe how to parametrize the LogicsManager via Modbus for
the following basic remote control functions:
To fix the operating mode use the LogicsManager function 86.16 "Operat. mode AUTO"
(parameter ╚═▷ 12510).
The operating mode AUTO LogicsManager function (parameter ╚═▷ 12510) can be
configured in two different ways:
Refer to ╚═▷ “6.3.5 Performing Remote Start/Stop And Acknowledgment” for a detailed
configuration of the LogicsManager via HMI or ToolKit.
Example
To configure the "Operat. mode AUTO" LogicsManager function (parameter ╚═▷ 12510)
as indicated in (╚═▷ Fig. 304) the following Modbus message must be sent to the
easYgen:
See table ╚═▷ Tab. 121 below
1. ▷
Copy the complete message of 7 words to address 12511 ff (12510+1) in one step.
This is shown in ╚═▷ Fig. 305 using the ModScan32 software.
Delay ON Delay OFF Logic equation 1* Logic equation 2* Command Command Command
1 2 3
Sign Op. Sign Op. Sign -/- -/- -/-
1 1 2 2 3
0.00 sec 0.00 sec ¾ And True And True 00 00 00 No. 09.09 No. 96.01 No. 96.01
ID = ID = ID =
0000 (hex) 0000 (hex) 1 0 2 0 2 0 0 0 020F (hex) 0000 (hex) 0000 (hex)
low high low high "as is" "as is" low high low high low high
byte byte byte byte byte byte byte byte byte byte
0000 (hex) 0000 (hex) 1020 (hex) 2000 (hex) 0F02 (hex) 0000 (hex) 0000 (hex)
Refer to ╚═▷ “6.3.5 Performing Remote Start/Stop And Acknowledgment” for a detailed
configuration of the LogicsManager via HMI or ToolKit.
The easYgen may start, stop, shut down, or acknowledge alarms with CAN/Modbus.
Therefore, two logical command variables (04.13 and 04.14) have to be configured with
the LogicsManager. 03.40 can handle Remote shutdown only.
The "Start req. in AUTO" LogicsManager function (parameter ╚═▷ 12120) can be
configured in a way that a start request in AUTOMATIC operating mode is enabled as soon
as a remote request is issued.
Refer to ╚═▷ “6.3.5 Performing Remote Start/Stop And Acknowledgment” for a detailed
configuration of the LogicsManager via HMI or ToolKit.
The remote request may be enabled by setting bit 0 (start) of the remote control word
503 to HIGH and may be disabled by setting bit 1 (stop) of the remote control word 503 to
HIGH (refer to ╚═▷ “9.2.9 Additional Data Identifier”).
Example
To configure the "Start req. in AUTO" LogicsManager function (parameter ╚═▷ 12120) as
indicated in (╚═▷ Fig. 306) the following Modbus message must be sent to the easYgen:
See table ╚═▷ Tab. 122 below.
1. ▷
Copy the complete message of 7 words to address 12121 ff (12120+1) in one step.
This is shown in (╚═▷ Fig. 307) using the ModScan32 software.
Refer to ╚═▷ “6.3.5 Performing Remote Start/Stop And Acknowledgment” for a detailed
configuration of the LogicsManager via HMI or ToolKit.
Example
Copy the complete message of 7 words to address 12491 ff (12490+1) in one step.
This is shown in ╚═▷ Fig. 309 using the ModScan32 software.
Delay ON Delay OFF Logic equation 1* Logic equation 2* Command Command Command
1 2 3
Sign Op. Sign Op. Sign -/- -/- -/-
1 1 2 2 3
0.00 sec 0.00 sec ¾ Or ¾ Or False 00 00 00 No. 09.05 No. 04.14 No. 96.01
ID = ID = ID =
low high low high "as is" "as is" low high low high low high
byte byte byte byte byte byte byte byte byte byte
0000 (hex) 0000 (hex) 1212 (hex) 3000 (hex) 0B02 FC00 (hex) 0000 (hex)
(hex)
The Start w/o load LogicsManager function (parameter ╚═▷ 12540) can be configured in a
way that it is always enabled.
Refer to ╚═▷ “6.3.5 Performing Remote Start/Stop And Acknowledgment” for a detailed
configuration of the LogicsManager via HMI or ToolKit.
Example
To configure the "Start w/o Load" LogicsManager function (parameter ID ╚═▷ 12540) as
indicated in ╚═▷ Fig. 310 the following Modbus message must be sent to the easYgen:
See table ╚═▷ Tab. 124 below.
1. ▷
Copy the complete message of 7 words to address 12541 ff (12540+1) in one step.
This is shown in ╚═▷ Fig. 311 using the ModScan32 software.
Delay ON Delay OFF Logic equation 1* Logic equation 2* Command Command Command
1 2 3
Sign Op. Sign Op. Sign -/- -/- -/-
1 1 2 2 3
0.00 sec 0.00 sec False And True And True 00 00 00 No. 00.01 No. 96.01 No. 96.01
ID = ID = ID =
Single alarm messages can be acknowledged remotely through the Modbus by sending
the respective parameter ID of the alarm to be acknowledged on parameter 522. The
required procedure is detailed in the following steps.
The parameter ID of the alarm to be acknowledged must be written to object 220A (hex),
i.e. parameter 522.
Example
A "Mains undervoltage 1" alarm (ID 3012) shall be acknowledged (refer to ╚═▷ “9.5.5
Alarm Messages”).
1. ▷ Use the "display options" to set the format to decimal view.
2. ▷ Double-click the address to issue a Write Register command.
▶
╚═▷ Fig. 313 shows how the parameter ID of the alarm to be acknowledged is written
using the ModScan32 Software.
The event history can be cleared remotely through the Modbus. The required procedure is
detailed in the following steps.
In order to clear the event history, bit 0 of object 26AA (hex), i.e. parameter 1706, must
be enabled.
1. ▷ Use the "display options" to set the value format to binary.
╚═▷ Fig. 315 shows how bit 0 is enabled using the ModScan32 Software.
6.5.2.6.1
1. ▷ Use the "display options" to set the value format to decimal.
2. ▷ Double-click the address to issue a Write Register command.
▶
╚═▷ Fig. 317 shows how the parameter is enabled using the ModScan32 Software. The
value must be set to "1" to enable the parameter.
In order to reset the default values, parameter ╚═▷ 1701 must be enabled.
CAUTION!
Don't run ╚═▷ 1701 »Set factory default values« during controlling a genset because it
causes a power cycle of the easYgen control.
1. ▷ Use the "display options" to set the value format to decimal.
2. ▷ Double-click the address to issue a Write Register command.
▶
╚═▷ Fig. 319 shows how the parameter is enabled using the ModScan32 Software. The
value must be set to "1" to enable the parameter.
The Modbus protocol has multiple exception responses to show that a request could not
be executed. Exception responses can be recognized if the response telegram contains
the request function code with an offset of 128 (0x80 hex).
╚═▷ Tab. 125 explains possible reasons for an exception response that occurred.
01 ILLEGAL FUNCTION The sent request function code is not supported by the Modbus
protocol.
03 ILLEGAL DATA VALUE The data value exceeds the min. and max. limitations of the
parameter upon a write request.
6.5.4.1 Introduction
The Modbus Telegram Mapper offers the possibility to generate customer defined Modbus
protocols. It is possible to create individual Modbus Address Point lists for Modbus RTU
and TCP. Therefore the address range (4)50000 can be taken. The user will be able to
arrange contents from the easYgen database (Index No.), AnalogManager Variables and
LogicsManager Command Variables to a customer specific protocol.
6.5.4.2 Configuration
Woodward offers the TelegramMapper PC software for free and enables easYgen-XT to
import, make accessible, and proceed customer specific Modbus protocols. The
TelegramMapper software can be installed separately from other Woodward software.
After starting the program the HELP file can guide through the required settings
• AnalogManager variables
• LogicsManager variables
The according data types must be defined and each address entry can be commented.
There is a maximum length of 300 addresses.
The final protocol can be saved with a protocol number from 65100 to 65199 used
as file name(!) as an
• HTML-file for easy to read documentation of the (self) created data protocol
To load your created Data Protocol(s) - the scp-file(s) - into your easYgen device use
ToolKit.
To switch to your Data Protocol and use it for communication: Configure parameter ╚═▷
3184 »Modbus protocol number« to your customer specific protocol number and reboot
╚═▷ 10419 the control.
Summary: The self-mappable address range is defined with a protocol number from
65100 to 65199 and has a maximum length of 300 addresses. Communication using
customer specific data protocols is configurable similar to other already existing protocols
The easYgen provides an information whether the Modbus TelegramMapper mapping file
could be successful parsed and interpreted. Navigate to “Status Menu/Interfaces/
Ethernet/Modbus TCP/IP” to get an error code.
Error codes:
• 0: No error
• 100000 + error line: There is a syntax error -- for any misformatted line
• 200000: File not found -- when file corresponding to selected protocol does not exist
6.5.5.1 Introduction
The Modbus Master does not work with the serial interface (RS-485, Modbus RTU).
All analog values which are present in the device as AnalogManager values and all flags
which are present as LogicsManager values can be written. Boolean flags can be grouped
into 16 bit values. Reading and writing each can be combined to read/write multiple
values in one command. Different variable types and Modbus modes are supported.
Multiple write and read rates can be defined, in order to access some datapoints more
often than others.
6.5.5.2 Configuration
• AnalogManager variables
• LogicsManager variables
The according data types, addresses, rates must be defined and each read/write entry
can be commented.
Note: Modbus master has for read and write a limitation of maximum about 120 words.
The ModbusMasterMapper PC software detects an overrun and will issue a warning.
The final protocol can be saved as a mapping file (*.mmap) file for further processing.The
tool creates a *.SCP-file for uploading the Modbus Master control file into the device using
Toolkit. After uploading and restarting the Modbus Master process can be started via
configuring parameter 3219 to “On”. Now the configured communication will be
executed.
Note
This field shows the "Description" from the loaded Modbus Master config file. This will be
read in at start-up.
Code Meaning
0 No error
2 Not a mapping file: The file is not a Modbus master mapping file or a malformed
one.
4 Wrong version of mapping file: The version of the mapping file does not match. This
can appear when the file was generated by an older version of the PC tool.
8 Mapping file has wrong check-sum: The mapping file was corrupted and is invalid. It
has to be newly created.
16 Wrong SIZES statement: This is an internal file error, this shall not happen when the
file was correctly created by the PC tool.
32 APPLICATION line wrong in file. The file was created for an application which does
not match to the application running on the device. It has to be newly created for
this application.
Code Meaning
64 RELEASE line wrong in file. The file was created for a software release which does
not match to the application running on the device. It has to be newly created for
this release.
This “parameter” activates a debug mode when a number is entered higher than 0. This
function enables the user to test the connections to different devices separately.
Only the selected WRITE or READ line of the mapping file will be executed. All other reads
and writes are suppressed.
Indication Meaning
16616 This output shows the device number [1..] as defined in the mapping file of the
Debug selected debug line command. It is 0, if “Select debug line” set to 0.
device
16617 This output shows the rate in [s] of the selected debug line command. It is 0, if
Debug rate “Select debug line” set to 0.
16618 This output shows the Modbus address of the selected debug line command. It is 0,
Debug if “Select debug line” set to 0.
address
16619 This output shows the read or wrote value for the selected Debug line command.
Debug When multiple read or multiple write was selected, it shows the first value. It is 0, if
value “Select debug line” set to 0.
16620 This output is TRUE (LED is green), if the selected Debug line command was a read,
Debug line otherwise FALSE. It is FALSE too if “Select debug line” set to 0.
is READ
The LED s of LM variables 08.72 to 08.76 “Modbus dev.x timeout” inform about time outs
of the corresponding slave devices.
• The slave is answering but in a rate slower than defined in the mapping file. This can
happen, when the slave is inherently slow or when the mapping was set up in a way
that too many requests were scheduled in the scheduled rate time.
One Modbus read or write command to one slave will take at least 50 msec. The
minimum permitted rate group is 100 msec. If now a mapping is configured in a way that
it requires more writes to a device than fits into the required rate, or the slave has very
long answer times, there will be a timeout error. The device will still read/write but it will
not do it as quickly as required. This issue can be mitigated by defining slower rate
groups or reducing the number of read/write commands.
The CAN interface 1 is a freely configurable CANopen interface with 5 RPDOs (receive
messages), 5 TPDOs (send messages) and 4 additional Server SDOs.
The CAN interface 2 supports the CANopen and J1939 protocol simultaneously. It supports
the connection of a wide range of engine control units (ECUs) and J1939 analog input
extension modules, which comply with the J1939 standard (e.g. Axiomatic). CANopen
extension modules are also supported.
CAN interface 2 is pre-configured for several expansion units. These include the I/O
expansion boards Woodward IKD 1, several combinations of the expansion boards of the
Phoenix Inline Modular (IL) series, and the support of Wago terminals.
The Ethernet network provides a fast communication capability to different devices, like
remote panel, PLC or SCADA systems. The common protocol Modbus TCP is there for the
preferred communication protocol. Additionally the Ethernet connection supports the
Woodward protocol Servlink for ToolKit and other Woodward own monitoring tools (like
remote panel and SCADA visualization tool). At least the easYgen provides a UDP protocol
for system relevant and time discrete information exchange.
The actual IP address in Network A, subnet mask and gateway IP address can be viewed
under Next Page (Status Menu) / Diagnostic / Interfaces / Ethernet / Ethernet A.
A freely configurable RS-485 Modbus RTU Slave interface is provided to add PLC
connectivity. It is also possible to configure the unit, visualize measured data and alarm
messages, and control the unit remotely.
Service port
The USB interface follows the USB 2.0 standard but is - as a service port - reserved for
ToolKit and special Woodward usage.
monitoring and communication between nodes, including a simple transport layer for
message segmentation/de-segmentation.
Protocol description
MUX Data byte Data byte Data byte Data byte Data byte Data byte Internal
The MUX byte is counted up, the meaning of the data byte changes according to the
value of the MUX byte.
In the protocol tables is listed which parameter at which MUX on which position is
transmitted. The meaning of the parameter can be taken by means of the number of the
parameter description (For details refer to ╚═▷ “9.2 Data Protocols”).
☼ Example
In MUX 1 (byte 0 has got value 1) the value of parameter 118 is included in the byte 1
up to byte 4 (mains voltage 1-2). In byte 6 up to byte 6 the value of parameter 147 is
included (mains frequency). Byte 7 includes internal definitions and can be ignored.
UNSIGNED type data has positive integers as values. The range is between 0 and 2n-1.
The data is shown by the bit sequence of length n.
• Bit sequence:
b = b0 to b–1
• Value shown:
Please note that the bit sequence starts on the left with the least significant byte.
Example: Value 266 = 10A hex of type UNSIGNED16 is transmitted on the bus in two
octets, first 0A hex and then 01 hex.
Octet Number 1. 2. 3. 4. 5. 6. 7. 8.
UNSIGNED8 b7 to b0
UNSIGNED16 b7 to b0 b15 to b8
Octet Number 1. 2. 3. 4. 5. 6. 7. 8.
UNSIGNED48 b7 to b0 b15 to b8 b23 to b16 b31 to b24 b39 to b32 b47 to b40
UNSIGNED56 b7 to b0 b15 to b8 b23 to b16 b31 to b24 b39 to b32 b47 to b40 b55 to b48
UNSIGNED64 b7 to b0 b15 to b8 b23 to b16 b31 to b24 b39 to b32 b47 to b40 b55 to b48 b63 to b56
SIGNED type data has integers as values. The range is between 0 and 2–1. The data is
shown by the bit sequence of length n.
• Bit sequence:
b = b0 to b–1
• Value shown:
if b–1 = 0
SIGNEDn(b) = SIGNEDn(^b)-1
if b–1 = 1
Please note that the bit sequence starts on the left with the least significant byte.
Example: The value -266 = FEF6 hex of type SIGNED16 is transmitted in two octets, first
F6 hex and then FE hex.
Octet Number 1. 2. 3. 4. 5. 6. 7. 8.
SIGNED8 b7 to b0
SIGNED16 b7 to b0 b15 to b8
SIGNED48 b7 to b0 b15 to b8 b23 to b16 b31 to b24 b39 to b32 b47 to b40
SIGNED56 b7 to b0 b15 to b8 b23 to b16 b31 to b24 b39 to b32 b47 to b40 b55 to b48
SIGNED64 b7 to b0 b15 to b8 b23 to b16 b31 to b24 b39 to b32 b47 to b40 b55 to b48 b63 to b56
Most of the J1939 data is standardized and has a SPN (Suspect Parameter Number), which
describes the data (e.g. SPN 110 is representing the value of the current “Engine Coolant
Temperature”). The SPNs are packed in different PGNs (Parameter Group Numbers). The
PGN is a part of the CAN ID and is representing one CAN message (e.g. SPN 110 is packed
in PGN 65263). J1939 defines several hundred SPNs. However, only a small part is
important for most of the applications. For this reason only a part of the SPNs is
supported by the J1939 devices and by the easYgen.
'SAE J1939' also allows manufacturer-specific data areas, so called proprietary data,
which are not defined in the standard. In most cases, these proprietary data is used for
remote control purposes (like start/stop, speed set point) of ECUs (Engine Control Unit).
Some manufacturers also issue specific error messages using manufacturer-specific data.
Besides important standardized data, the easYgen is also supporting some proprietary
data for the different ECUs. Please refer to ╚═▷ “7.5.2 Supported J1939 ECUs & Remote
Control Messages” for details.
The easYgen is able to display all values listed in the table ╚═▷ “Standard visualization
messages” if they are supported by the connected device as well.
If a message is used but its sensor/signal is damaged HMI and ToolKit display »ERROR«.
Unused messages/SPN are monitored by ToolKit with »Missing« but HMI doesn't display
unused messages/SPN (neither message/SPN nor status).
In the J1939 status screen the first 10 active alarm messages (Active Diagnostic Trouble
Codes - DM1) and the first 10 unacknowledged alarm messages (Previously Active
Diagnostic Trouble Codes - DM2) with text, SPN, FMI, and OC are displayed.
• SPN (= Suspect Parameter Number) indicates the measured value that the alarm
code is referring (e.g. SPN = 100 corresponds to oil pressure).
• FMI (= Failure Mode Indicator) specifies the alarm more precisely (e.g. FMI = 3
means: value is above predefined limits)
The indication of fault texts for DM1 and the entry in the respective alarm list is only
possible for SPNs which are listed in the SPN list (refer to ╚═▷ “Standard visualization
messages”)!
For SPNs without text: Refer to the J1939 specification for a list of all SPNs.
In case of ...
106 65270 Turbo air inlet pressure 1 kPa 0 to 500 kPa 15221
107 65270 Air filter 1 difference pressure 0.01 kPa 0 to 12.5 kPa 15222
157 65243 Fuel rail pressure 0.1 MPa 0 to 251 MPa 15225
1137 65187 Exhaust gas port 1 temperature 0.1 °C -273 to 1735 °C 15242
1138 65187 Exhaust gas port 2 temperature 0.1 °C -273 to 1735 °C 15243
1139 65187 Exhaust gas port 3 temperature 0.1 °C -273 to 1735 °C 15244
1140 65187 Exhaust gas port 4 temperature 0.1 °C -273 to 1735 °C 15245
1141 65186 Exhaust gas port 5 temperature 0.1 °C -273 to 1735 °C 15246
1142 65186 Exhaust gas port 6 temperature 0.1 °C -273 to 1735 °C 15247
1143 65186 Exhaust gas port 7 temperature 0.1 °C -273 to 1735 °C 15248
1144 65186 Exhaust gas port 8 temperature 0.1 °C -273 to 1735 °C 15249
1145 65185 Exhaust gas port 9 temperature 0.1 °C -273 to 1735 °C 15250
1146 65185 Exhaust gas port 10 temperature 0.1 °C -273 to 1735 °C 15251
1147 65185 Exhaust gas port 11 temperature 0.1 °C -273 to 1735 °C 15252
1148 65185 Exhaust gas port 12 temperature 0.1 °C -273 to 1735 °C 15253
1149 65184 Exhaust gas port 13 temperature 0.1 °C -273 to 1735 °C 15254
1150 65184 Exhaust gas port 14 temperature 0.1 °C -273 to 1735 °C 15255
1151 65184 Exhaust gas port 15 temperature 0.1 °C -273 to 1735 °C 15256
1152 65184 Exhaust gas port 16 temperature 0.1 °C -273 to 1735 °C 15257
1153 65183 Exhaust gas port 17 temperature 0.1 °C -273 to 1735 °C 15258
1154 65183 Exhaust gas port 18 temperature 0.1 °C -273 to 1735 °C 15259
1155 65183 Exhaust gas port 19 temperature 0.1 °C -273 to 1735 °C 15260
1156 65183 Exhaust gas port 20 temperature 0.1 °C -273 to 1735 °C 15261
1172 65178 Turbo 1 compressor inlet temperature 0.1 °C -273 to 1735 °C 15273
1173 65178 Turbo 2 compressor inlet temperature 0.1 °C -273 to 1735 °C 15274
1174 65178 Turbo 3 compressor inlet temperature 0.1 °C -273 to 1735 °C 15275
1175 65178 Turbo 4 compressor inlet temperature 0.1 °C -273 to 1735 °C 15276
1176 65177 Turbo 1 compressor inlet pressure 1 kPa -250 to 251 kPa 15277
1177 65177 Turbo 2 compressor inlet pressure 1 kPa -250 to 251 kPa 15278
1178 65177 Turbo 3 compressor inlet pressure 1 kPa -250 to 251 kPa 15279
1179 65177 Turbo 4 compressor inlet pressure 1 kPa -250 to 251 kPa 15280
1203 65172 Engine auxiliary coolant pressure 1 kPa 0 to 1000 kPa 15289
1382 65130 Fuel filter difference pressure 1 kPa 0 to 500 kPa 15292
2433 65031 Right exhaust gas temperature 0.1 °C -273 to 1735 °C 15297
2434 65031 Left exhaust gas temperature 0.1 °C -273 to 1735 °C 15298
2629 64979 Turbo 1 compr. outlet tmp. 0.1 °C -273 to 1736 °C 15310
3251 64946 DPF Differential press. 0.1 kPa 0 to 6,425.5 kPa 15550
4151 64851 Exhaust Gas Temp. Avr. 0.1 °C -273 to 1734 °C 12807
4152 64851 Exh. Gas Temp. Avr. B2 0.1 °C -273 to 1734 °C 12812
4153 64851 Exh. Gas Temp. Avr. B1 0.1 °C -273 to 1734 °C 12809
1If the total engine hours sent by the ECU exceed 419,000 hrs, the display in the unit is
not correct anymore.
• If the sent values exceed the limits of the specification, the displayed value is not
defined.
• If a value of the ECU is not sent or sent as not available or defective, the value will
be displayed as indicated in the table before.
Please refer to the ECU manual for the engine specific stop codes.
No No
• Low engine oil level
Missing Missing
• High engine oil level
Yes Yes
• Low oil pressure
The following table lists all ECUs, which are supported by the easYgen beyond the J1939
standard with the appropriate settings. We recommend device type (parameter ╚═▷
15102) "Standard" for all ECUs, which are not listed here. All other parameters shall be
clarified with the ECU manufacturer.
Standard ECUs Standard N/A N/A N/A Please refer to ╚═▷ “7.5.3 Device Type
Standard” for more details.
MTU ADEC ECU7 ADEC ECU7 MTU 1 128 N/A The easYgen is connected with the
SAM via CAN. The SAM communicates
with the ADEC using an own bus.
Volvo EDC4
Deutz EMR4
(EDC 17)
Volvo EMS2 EMS2 Volvo 17 0 N/A The rated speed of the EMS1 and
EDC3 cannot be switched via the
Volvo EMS1 easYgen.
Volvo EDC3
MAN MFR/EDC7 MFR/EDC7 MAN 253 39 N/A The easYgen is connected with the
MFR via CAN. The MFR communicates
with the EDC7 using an own bus.
MTU ADEC ECU8/ ADEC ECU8 MTU 234 0 N/A The easYgen is connected with the
ECU9 MTU system: ADEC ECU8 &
SmartConnect or ADEC ECU9.
The addresses listed here are only valid, if the ECU is not configured to other values. In
case of doubt, please check the corresponding settings of the ECU with the service tool.
The following data is only transmitted to the corresponding ECU, if parameter "ECU
remote controlled" is configured to "On", and parameter "Device type" is configured to
one of the available ECU modes (if "Off" is configured, no J1939 remote control messages
will be sent as well).
Please note that some ECU manufacturers require that this functionality must be enabled
first. In some cases, this is only possible by the manufacturer. Please consider this when
ordering the ECU.
1 Woodward EGS
2 Scania S6
4 Volvo EMS2
5 Volvo EMS1/EDC3
7 MAN MFR/EDC7
8 Standard
10 Cummins
12 Hatz EDC 17
Remote Availability with supported ECU number ... Comment
control
parameter 1 2 3 4 5 6 7 8 9 10 11 12
Engine No Yes No Yes Yes Yes Yes No No / Yes Yes Yes If an engine start command
Start Yes is initiated by the easYgen,
this information is
transmitted in the form of a
J1939 message bit to an
ECU. If ignition speed is
reached, this bit will be
reset (LogicsManager
command variable 03.02.
"Starter").
Engine Yes Yes No Yes Yes Yes Yes Yes No / Yes Yes Yes This J1939 bit information is
Stop Yes set, if a "Stop" command in
automatic or manual mode
is present in the easYgen.
The "Stop" bit information
remains set, until ignition
speed is fallen below. After
ignition speed has been
fallen below, the "Stop" bit
will be reset
(LogicsManager command
variable 03.27. "Stop
solenoid").
Droop Yes Yes No Yes Yes Yes Yes Yes Yes Yes No No This J1939 bit information is
mode set, if a "Start" command in
automatic or manual mode
is initiated by the easYgen.
The bit remains set until the
engine has been stopped.
Notes
Idle No Yes No1 Yes Yes No No1 No1 No Yes Yes No This J1939 bit information is
Mode set, if "Idle" mode is active
(LogicsManager command
variable 04.15. "Idle run
active" is TRUE).
50/60 Hz Yes Yes No Yes2 No Yes No1 No No Yes Yes No The J1939 information for
switch 50 or 60 Hz mode is sent to
the ECU depending on the
"Rated system frequency"
parameter setting (╚═▷
1750) within the easYgen .
Speed Yes3 Yes4 Yes3 Yes4 Yes3 Yes3 Yes3 Yes3 Yes3 Yes4 Yes3 Yes3 Refer to parameter ╚═▷
bias 5537 for detailed
information.
Notes
Override No Yes No Yes No Yes No Yes No Yes Yes No This J1939 bit information is
set, if the easYgen is in
critical mode
(LogicsManager command
1Please contact manufacturer to clarify whether both frequencies (50/60 Hz) may be
controlled by the speed bias.
2 In case the rated speed of the easYgen and the ECU don't match, please make sure
that the CAN connections works and change parameter ╚═▷ 1750 of the easYgen once.
General notes
If the used ECU is not specific listed in the chapter ╚═▷ “7.5 J1939 Protocol” (e.g. Deutz
(EMR3 & EMR4), John Deere, Daimler, Perkins, Iveco, Caterpillar, Liebherr, etc.) we
recommend to configure the "Device type" (parameter ╚═▷ 15102) to the setting
“Standard”. Visualization via J1939 is working with every J1939 ECU. Concerning remote
control most ECUs are also supporting the speed offset via J1939 standard message TSC1.
This chapter supplies you with the details of the device type standard, to help you to
clarify with the manufacturer how the ECU is supported.
In standard mode, the easYgen is able to display all values listed in the table ╚═▷
“Standard visualization messages” if they are supported by the connected ECU.
In standard mode, the easYgen diagnostic messages DM1 (Active Diagnostic Trouble
Codes) and DM2 (Previously Active Diagnostic Trouble Codes) are displayed. It is also
possible to reset DM1 and DM2 failure codes via DM3 and DM11 messages.
The following table shows the transmitted remote control messages. These messages are
only transmitted if the parameter "ECU remote controlled" (parameter ╚═▷ 15127) is
configured to "On".
Not all SPNs of the supported PGNs are listed here, in such case the easYgen transmits
“Not available”.
61441 F001 EBC1 Electronic Brake 970 Engine Auxiliary Shutdown Switch 100
Controller 1
65029 FE05 GTACP Generator Total AC 2452 Generator Total Real Power 100
Power
64913 FD91 ACS AC Switching Device 3545 Generator Circuit Breaker Status 250
Status
3546 Utility Circuit Breaker Status
64971 FDCB OHECS Off-Highway Engine 2881 Engine Alternate Droop 500
Control Selection Accelerator 1 Select
Notes
65265 FEF1 CCVS Cruise Control/Vehicle 1237 Engine Shutdown Override Switch 100
Speed
59904 EA00 — Request (specific) 247 Engine Total Hours of Operation 10,000
(at PGN FEE5)
Notes
Notes
For the visualization the “J1939 own address” (parameter ╚═▷ 15106) and the “Engine
control address” (parameter ╚═▷ 15103) are not relevant. But for remote control e.g.
speed biasing these addresses must be configured correctly. Please refer to your ECU
manual for the correct address. Normally the “Engine control address” (parameter ╚═▷
15103) is “0” and the “J1939 own address” (parameter ╚═▷ 15106) is often "234" or "3".
and
The Modbus RTU Slave expects that a Master node polls the controller slave node.
Modbus RTU can also be multi-dropped, or in other words, multiple Slave devices can
exist on one Modbus RTU network, assuming that the serial interface is a RS-485.
The Modbus/TCP Server fulfills the same role as Modbus client for RTU mode. Also here it
is possible to have one client connected to many servers.
Temporary restriction
With the current easYgen-XT one server can handle only one client at a time.
Detailed information about the Modbus protocol is available on the following website:
• ══▷ http://www.modbus.org/specs.php
There are also various tools available on the internet. We recommend using ModScan32
which is a Windows application designed to operate as a Modbus Master device for
accessing data points in a connected Modbus Slave device. It is designed primarily as a
testing device for verification of correct protocol operation in new or existing systems.
• ══▷ http://www.win-tech.com/html/modscan32.htm
Address range
The controller Modbus Slave module distinguishes between visualization data and
configuration & remote control data. The different data is accessible over a split address
range and can be read via the "Read Holding Register" function.
Furthermore, controller parameters and remote control data can be written with the
"Preset Single Registers" function or "Preset Multiple Registers" (╚═▷ Fig. 326)
All addresses in this document comply with the Modicon address convention. Some PLCs
or PC programs use different address conventions depending on their implementation.
Then the address must be increased and the leading 4 may be omitted.
Please refer to your PLC or program manual for more information. This determines the
address sent over the bus in the Modbus telegram. The Modbus starting address 450001
of the visualization data may become bus address 50000 for example.
Visualization
The visualization over Modbus is provided in a very fast data protocol where important
system data like alarm states, AC measurement data, switch states and various other
information may be polled.
According to the Modbus addressing range, the visualization protocol can be reached on
addresses starting at 450001. On this address range it is possible to do block reads from
1 up to 128 Modbus registers at a time.
............
╚═▷ “4.7.3 Modbus Protocol” is only an excerpt of the data protocol. It conforms to the
data protocol 5010.
Please refer to the Data Protocols chapter, ╚═▷ “9.2 Data Protocols”
The following ModScan32 screenshot shows the configurations made to read the
visualization protocol with a block read of 128 registers.
Configuration
The Modbus interface can be used to read/write parameters. According the Modbus
addressing range for the configuration addresses, the range starts at 40001 and ends at
450000. You can always access only one parameter of the system in this address range.
The Modbus address can be calculated depending on the parameter ID as illustrated
below:
Block reads in this address range depend on the data type of the parameter. This makes
it important to set the correct length in Modbus registers which depends on the data type
(UNSIGNED 8, INTEGER 16, etc.).
UNSIGNED 8 1
UNSIGNED 16 1
INTEGER 16 1
UNSIGNED 32 2
INTEGER 32 2
TEXT/X X/2
The Modbus RTU response time can increase under certain conditions (display versions /
plastic housing only):
Woodward recommends to make a break time of 10 ms after receiving the data of the
last Modbus request.
The maximum number of participating easYgen-3000XT Series devices for load sharing is
32. Both CAN and Ethernet interfaces can handle load share. Load share via Ethernet
interface uses UDP broadcast messages.
Multi-master principle
It is important to know that the load share and load-dependent start/stop functionality is
subject to a multi-master principle. This means that there is no dedicated master and
slave function. Each easYgen decides for itself how it has to behave.
The benefit is that there is no master control, which may cause a complete loss of this
functionality in case it fails. Each control is also responsible for controlling common
breakers like a mains circuit or generator group breaker.
The multi-unit missing members monitoring function checks whether all participating
units are available (sending data on the load share line). For additional information
refer to ╚═▷ “4.5.6.17 Multi-Unit Missing easYgen”.
The following parameters allows to select the interface for load share communication.
Refer to ╚═▷ “4.4.4.3.5 Load-Share Interface” for detailed information.
Off
Ethernet A
CAN/EthA by LM*
CAN/Ethernet A
Notes
Notes
• FALSE: CAN
• TRUE: Ethernet A
Woodward recommends to configure the Node-IDs (parameter ╚═▷ 8950) for units, which
participate in load sharing, as low as possible to facilitate a fast establishing of
communication.
Bus load
The bus load increases with the number of units participating in load sharing.
• Baud rate
We recommend to consider whether all data has to be sent on the CAN bus when
planning the CAN bus. It is also possible to send visualization data via RS-485 for
example.
If you need to reduce the bus load of the load share CAN bus, the following methods may
be used:
• Increase the baud rate (parameter ╚═▷ 3156) under consideration of the bus length
(refer to ╚═▷ “3.4.4 CAN Bus Interfaces”).
• Reduce the transfer rate of the load share message (parameter ╚═▷ 9921).
• Reduce the transfer rate of the visualization message, i.e. the event timer
(parameter ╚═▷ 9604).
• Disable the transmission visualization data on the CAN bus and use the RS-485
interface to transmit visualization data.
• Disable SYNC message (parameter ╚═▷ 9100) and/or TIME message (parameter ╚═▷
9101) and/or the producer heartbeat time SYNC message (parameter ╚═▷ 9120), if
possible.
The following parameters are available for configuring the CAN bus interfaces. Refer to
╚═▷ “4.7.6 Load Share Parameters” for detailed information.
9920 Load Share CAN-ID 2xx Hex / 3xx Hex / 5xx Hex
4xx Hex / 5xx Hex
Load share and other system relevant messages are handled with UDP messages. The
construction of the UDP messages allows (load share) communication with other
Woodward devices.
For configuration of the Ethernet interface see chapters ╚═▷ “4.7.5 Ethernet Interfaces”
and ╚═▷ “7.2 Ethernet Interfaces”.
8 Technical Specifications
9 Approval Approvals
Battery inside
This device contains a battery, and therefore it is labeled with the symbol shown beside
according to the EU Directive 2006/66/EC.
WARNING!
In general, appropriate local guidelines and regulations must be followed when disposing
of electrical devices and batteries.
Voltages
Currents
With External CT
For correct measuring with external CT the input has to be one side grounded by the
customer.
Battery Voltage
CAUTION!
Connect the unit only to a DC power source that complies with the safety extra-low
voltage (SELV) requirements.
Degree of pollution 2
8.1.3 Inputs/Outputs
Configurable via
LogicsManager
Resolution 16 Bit
Analog outputs 'AO 01' "Speed Biasing" (Type 1: ±20 mA | ±10 V | PWM)
Analog outputs 'AO 02' "Voltage Biasing" (Type 1: ±20 mA | ±10 V | PWM)
(decoupled by capacitors)
8.1.4 Interfaces
USB (slave)
Bus Voltage 5V
RS-485 interface
Ethernet interface
Type Lithium
(Heater ON/OFF)
8.1.7 Housing
Housing type
easYpack Custom
Wiring Screw-plug-terminals
2.5 mm²
Protection
8.1.8 Approvals
EMC test (CE) Tested according to applicable EMC standards. Refer to ╚═▷ “8.2
Environmental Data” for details
Listings CE marking
cUL
CSA
EAC
Acceleration 4G
Shock
Temperature
Plastic Cold, Dry Heat (storage) -30 °C (-22 °F) / 80 °C (176 -30 °C (-22 °F) / 80 °C (176
°F) °F)
Cold, Dry Heat (operating) -20 °C (-4 °F) / 70 °C (158 -40 °C (-40 °F) / 70 °C (158
°F) °F)
Sheet metal Cold, Dry Heat (storage) -40 °C (-40 °F) / 80 °C (176 °F)
Humidity
Electromagnetic Compatibility
8.3 Accuracy
The accuracy declaration is defined by the according measurement ranges. The rated
maximum of the single ranges are taken as 100%.
Frequency
Voltage
Power supply/Battery 0 to 40 VDC ±0.5% related to 40 Related on the 0.5% equals 0.2 V
V measurement range (±0.2 V)
8 to 40 V
Current
Generator 0 to 32,000 A 0.5% (of 1/5 A)3 Class 1% (of 1.3/6.5 A)3
0.5
Max. value
Mains/ground current
Real power
Reactive power
Actual value in L1, L2, -2 to 2 Gvar 1% (of 69/277 V x 1/5 Measuring starts with
L3 A) 2/3 detecting the zero
passage of current/
voltage
Power factor
Actual value power lagging 0.000 to 1% 1% (of 1.3/6.5 A)3 1.000 is displayed for
factor L1 1.000 to measuring values
leading 0.000 below the measuring
start
Miscellaneous
Real energy 0 to 4,200 GWh 0.36% (of 1.3/6.5 A)3 Not calibrated
Phase angle -180 to 180° ± 1 degree 1.25% (of PT 180° is displayed for
secondary volt. measuring values
setting) below measuring
start
Analog Inputs
Analog Outputs
4 Some senders, like the VDO senders, are operating in the working range 0 to 200
Ohms. For sure, the 0.5% accuracy cannot be directly assigned to these senders.
Therefore the accuracy percentage tolerance will be expanded accordingly. On the other
hand, measurements have shown that under usual circumstances (at 20°C, no EMC
surge or burst present) an accuracy of 1% for such senders can be kept.
Reference conditions
The reference conditions for measuring the accuracy are listed below.
Ambient temperature 23 °C ± 2 K
Unbalanced load 46
Synch Check 25
Instantaneous overcurrent 50
Power factor 55
Rotation field
Cylinder temperature
9 Appendix
9.1 Characteristics
This triggering characteristic is used for generator, mains and battery overvoltage,
generator and mains overfrequency, overload IOP and MOP and engine overspeed
monitoring.
This triggering characteristic is used for generator, mains and battery undervoltage,
generator and mains underfrequency, and engine underspeed monitoring.
Since VDO sensors are available in different types, the index numbers of the
characteristic curve tables are listed.
1. ▷ Always order VDO sensors with the correct characteristic curve. Manufacturers of VDO
sensors usually list these tables in their catalogs.
P [psi] 0 7.25 14.50 21.76 29.00 36.26 43.51 50.76 58.02 65.27 72.52
P 0 7.25 14.50 21.76 29.00 43.51 58.02 72.52 87.02 101.53 116.03 123.28 130.53 145.04
[psi]
Fig. 340: Characteristics diagram VDO -40 to 120 °C - full range, Index "92-027-004"
R 17162.4 12439.5 9134.5 6764.5 5067.6 3833.9 2929.9 2249.4 1743.1 1364.0 1075.6
[Ohm]
Temp. 15 20 25 30 35 40 45 50 55 60 65
[°C]
R 850.1 677.0 543.5 439.3 356.6 291.5 239.6 197.3 161.5 134.0 114.0
[Ohm]
Temp. 158 167 176 185 194 203 212 221 230 239 248
[°F]
R 97.1 82.4 70.1 59.7 51.2 44.3 38.5 33.4 29.1 25.5 22.4
[Ohm]
Fig. 342: Characteristics diagram VDO 0 to 120 °C - full range, Index "92-027-006"
Temp. 0 5 10 15 20 25 30 35 40 45 50
[°C]
R 3240.18 2743.6 1905.87 1486.65 1168.64 926.71 739.98 594,9 481,53 392.57 322.17
[Ohm]
Temp. 131 140 149 158 167 176 185 194 203 212 221
[°F]
R 266.19 221.17 184.72 155.29 131.38 112.08 96.40 82.96 71.44 61.92 54.01
[Ohm]
Temp. 110 115 120 125 130 135 140 145 150
[°C]
Temp. 230 239 248 257 266 275 284 293 302
[°F]
R 18.5 39.7 60.25 80.7 100 103.9 107.8 111.7 115.5 119.4 123.2
[Ohm]
Temp. 158 176 194 212 257 302 347 392 437 482 572
[°F]
R 127.1 130.9 134.7 138.5 147.9 157.3 166.6 175.8 188.6 194.1 212.0
[Ohm]
Temp. 350 400 450 500 550 600 650 700 750 800 850
[°C]
Temp. 662 752 842 932 1022 1112 1202 1292 1382 1472 1562
[°F]
R 229.7 247.0 264.1 280.9 297.4 313.6 329.5 345.1 360.5 375.5 390.25
[Ohm]
The characteristic of the Pt1000 temperature sender accords the characteristic diagram
Pt100 at which the R value is to multiply with 10. Refer to ╚═▷ “9.1.2.3 Pt100 RTD” for
details.
The following data protocols / data telegrams are describing the currently defined full set
of data for each protocol. Please ignore data your device does not support.
CANopen/Modbus
CANopen
Modbus
50058 19 3-6 int32 136 Total gen. reactive power var *1 All
50061 20 3-6 int32 150 Total mains reactive power var *1 All
EG3500XT-
P2
EG3500XT-
P2
50121 40 3-6 int32 2520 Gen. real energy MWh *100 All
50124 41 3-6 int32 2522 Gen. positive reactive energy Mvarh *100 All
50126 42 1-2 int16 2558 Hours until next maintenance h *100 All
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
50166 55 3-6 int32 219 Nominal active power in system (in own kW *1 All
segment)
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
50169 56 3-6 int32 218 Active real power in system (in own kW *1 All
segment)
50172 57 3-6 int32 217 Active power reserve in system (in own kW *1 All
segment)
50174 58 1-2 int16 15109 J1939 MTU ADEC ECU Failure Codes *1 All
50177 59 1-2 uint16 15304 J1939 EMR Engine Stop Information All
"Missing" Value="65535"
"Error" Value="65279"
50181 60 3-4 int16 15313 Aftertreatment 1 Diesel Exhaust Fluid % *10 All
Tank Level
Malfunction Lamp
Protect Lamp
Malfunction Lamp
Protect Lamp
50246 82 1-4 int32 15200 Engine Speed (j1939-EEC1) rpm *10 All
50252 84 1-4 int32 15204 Engine Oil Temperature (j1939-ET1) °C *100 All
50254 84 5-6 int16 15205 Engine Oil Pressure (j1939-EFL/P1) kPa *1 All
50255 85 1-4 int32 15211 Fuel Rate (j1939-LFE) L/h *100 All
50260 86 5-6 int16 15210 Engine oil level (j1939-EFL/P1) % *10 All
50263 87 5-6 int16 15212 Barometric Pressure (j1939-AMB) kPa *10 All
50266 88 5-6 int16 15315 Aftertreatment 1 Diesel Exhaust Fluid % *10 All
Tank 2 Level
EG3500XT-P2
05.14 ECU yellow (amber) lamp alarm latched Mask: 0001h All
17 1-4 int32 2522 Positive reactive gen energy Mvarh *100 All
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
07.27 Mains slow voltage increase (10 min) Mask: 0008h All
50001 int16 3181 Skaling Power (16 bits) Exponent 10* W All
(5;4;3;2)
50002 int16 3182 Skaling Volts (16 bits) Exponent 10* V All
(2;1;0;-1)
50003 int16 3183 Skaling Amps (16 bits) Exponent 10* A (0;-1) All
50004 Internal
50005 Internal
50006 Internal
50007 Internal
50008 Internal
50011 int16 247 Total generator reactive power var format All
defined by
index 3181
(Modbus-
Address
50001)
50032 int16 259 Total mains reactive power var format All
defined by
index 3181
(Modbus-
Address
50001)
50043 int16 267 Average LSx Delta Mains voltage L-L V format EG3500XT-P1
defined by
index 3182 EG3500XT-P1
(Modbus-
Address
50002)
50044 int16 268 Average LSx Wye Mains voltage L-N V format EG3500XT-P1
defined by
index 3182 EG3500XT-P1
(Modbus-
Address
50002)
50050 int16 4608 Average LSx Mains delta frequency L-L Hz *100 EG3500XT-P1
EG3500XT-P1
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
Subtopic General
EG3500XT-P2
05.14 ECU yellow (amber) lamp alarm latched Mask: 0001h All
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
Subtopic Engine
Subtopic Generator
Subtopic Mains
07.27 Mains slow voltage increase (10 min) Mask: 0008h All
EG3500XT-P2
Subtopic Active Diagnostic Trouble Code (DM1) 1-10 (SPN Range 0…65535)full SPN value at 450425-450444
50193 int16 15109 J1939 MTU ADEC ECU Failure Codes *1 All
"Missing" Value="65535"
"Error" Value="65279"
Subtopic Values
50204 int16 15309 Engine Oil Temperature 1 (SPN 175) °C *10 All
50205 int16 15205 Engine Oil Pressure (SPN 100) kPa *1 All
50206 int16 15307 Fuel Rate (SPN 183) L/h *10 All
50210 int16 15210 Engine oil level (SPN 98) % *10 All
50213 int16 15212 Barometric Pressure (SPN 108) kPa *10 All
50219 int16 15219 Fuel Filter Differential Pressure (SPN95) kPa *1 All
50221 int16 15221 Turbo Air Inlet Pressure (SPN106) kPa *1 All
50222 int16 15222 Air Filter 1 Differential Pressure (SPN107) kPa *100 All
50225 int16 15225 Fuel Rail Pressure (SPN157) MPa *10 All
50243 int16 15242 Exhaust Gas Port 1 Temperatures (SPN1137) °C *10 All
50244 int16 15243 Exhaust Gas Port 2 Temperatures (SPN1138) °C *10 All
50245 int16 15244 Exhaust Gas Port 3 Temperatures (SPN1139) °C *10 All
50246 int16 15245 Exhaust Gas Port 4 Temperatures (SPN1140) °C *10 All
50247 int16 15246 Exhaust Gas Port 5 Temperatures (SPN1141) °C *10 All
50248 int16 15247 Exhaust Gas Port 6 Temperatures (SPN1142) °C *10 All
50249 int16 15248 Exhaust Gas Port 7 Temperatures (SPN1143) °C *10 All
50250 int16 15249 Exhaust Gas Port 8 Temperatures (SPN1144) °C *10 All
50251 int16 15250 Exhaust Gas Port 9 Temperatures (SPN1145) °C *10 All
50252 int16 15251 Exhaust Gas Port 10 Temperatures (SPN1146) °C *10 All
50253 int16 15252 Exhaust Gas Port 11 Temperatures (SPN1147) °C *10 All
50254 int16 15253 Exhaust Gas Port 12 Temperatures (SPN1148) °C *10 All
50255 int16 15254 Exhaust Gas Port 13 Temperatures (SPN1149) °C *10 All
50256 int16 15255 Exhaust Gas Port 14 Temperatures (SPN1150) °C *10 All
50257 int16 15256 Exhaust Gas Port 15 Temperatures (SPN1151) °C *10 All
50258 int16 15257 Exhaust Gas Port 16 Temperatures (SPN1152) °C *10 All
50259 int16 15258 Exhaust Gas Port 17 Temperatures (SPN1153) °C *10 All
50260 int16 15259 Exhaust Gas Port 18 Temperatures (SPN1154) °C *10 All
50261 int16 15260 Exhaust Gas Port 19 Temperatures (SPN1155) °C *10 All
50262 int16 15261 Exhaust Gas Port 20 Temperatures (SPN1156) °C *10 All
50278 int16 15277 Turbo 1 Compressor Inlet Pressure (SPN1176) kPa *1 All
50279 int16 15278 Turbo 2 Compressor Inlet Pressure (SPN1177) kPa *1 All
50280 int16 15279 Turbo 3 Compressor Inlet Pressure (SPN1178) kPa *1 All
50281 int16 15280 Turbo 4 Compressor Inlet Pressure (SPN1179) kPa *1 All
50282 int16 15281 Turbo 1 Turbine Inlet Temperature (SPN1180) °C *10 All
50283 int16 15282 Turbo 2 Turbine Inlet Temperature (SPN 1181) °C *10 All
50284 int16 15283 Turbo 3 Turbine Inlet Temperature (SPN 1182) °C *10 All
50285 int16 15284 Turbo 4 Turbine Inlet Temperature (SPN1183) °C *10 All
50286 int16 15285 Turbo 1 Turbine Outlet Temperature (SPN1184) °C *10 All
50287 int16 15286 Turbo 2 Turbine Outlet Temperature (SPN1185) °C *10 All
50288 int16 15287 Turbo 3 Turbine Outlet Temperature (SPN °C *10 All
1186)
50289 int16 15288 Turbo 4 Turbine Outlet Temperature (SPN1187) °C *10 All
50290 int16 15289 Engine Aux. Coolant Pressure (SPN1203) kPa *1 All
50293 int16 15292 Fuel Filter Differential Pressure (SPN1382) kPa *1 All
50298 int16 15297 Right Exhaust Gas Temperature (SPN2433) °C *10 All
50299 int16 15298 Left Exhaust Gas Temperature (SPN2434) °C *10 All
50300 int16 15310 Turbo 1 Compr. Outlet Temperature (SPN2629) °C *10 All
50303 int16 15313 Aftertreatment 1 Diesel Exhaust Fluid Tank 1 % *10 All
Level (SPN1761)
50305 int16 15315 Aftertreatment 1 Diesel Exhaust Fluid Tank 2 % *10 All
Level (SPN4367)
50307 int16 12807 Exhaust Gas Temperature Average(SPN 4151) °C *10 All
50308 int16 12809 Exhaust Gas Temperature Average Bank 1 °C *10 All
(SPN 4153)
50309 int16 12812 Exhaust Gas Temperature Average Bank 2 °C *10 All
(SPN 4152)
Int32 (Long)
50368 int32 2522 Gen. positive reactive energy Mvarh *100 All
EG3500XT-P2
50412 int32 217 Reserve real power in system (valid if LDSS is kW *1 All
on)
50414 int32 218 Real power in system (vaild if LDSS is on) kW *1 All
50416 int32 219 Nominal real power in system (vaild if LDSS is kW *1 All
on)
Subtopic Values
EG3500XT-P2
Topic LSx
50454 int32 267 Average LSx Delta Mains voltage L-L V *10 EG3500XT-P1
EG3500XT-P2
50456 int32 268 Average LSx Wye Mains voltage L-N V *10 EG3500XT-P1
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
Subtopic Generator
Subtopic Mains
07.27 Mains slow voltage increase (10 min) Mask: 0008h All
Subtopic Engine
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
05.11 Charge alt. low voltage (D+) latched Mask: 1000h All
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
50058 19 3-6 int32 136 Total Generator reactive power var *1 All
50061 20 3-6 int32 150 External total mains reactive power var *1 All
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
50109 36 3-4 int16 15310 SPN 2629 Turbo Charger 1 temp °C *1 All
50121 40 3-6 uint32 2520 Gen. real energy MWh *100 All
50124 41 3-6 uint32 2522 Gen. positive reactive energy Mvarh *100 All
50126 42 1-2 int16 2558 Hours until next maintenance h *10 All
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
50166 55 3-6 uint32 219 Nominal active power in system (in own *1 All
segment)
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
50169 56 3-6 int32 218 Active real power in system (in own kW *1 All
segment)
50172 57 3-6 int32 217 Active power reserve in system (in own kW *1 All
segment)
50175 58 3-4 int16 239 System actual nominal power % *100 All
50176 58 5-6 int16 240 System total real power % *100 All
50178 59 3-4 int16 241 System reserve active power % *100 All
EG3500XT-
P2
50187 62 3-6 int32 5642 Setpoint reactive power kvar *10 All
0,1 : internal
3: Preglow
4: Crank
5: Run
6: Cool down
7: Spin down
8: Start pause
9: Idle
2: Static
3: Isochronous
2: Static
3: Isochronous
5: Export/import control
50211 70 3-4 int16 8904 81.25 Engine Oil Pressure (HMI) bar *1 bar All
[0.1bar]
psi 1 psi
8909
[psi]
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
EG3500XT-
P2
50219 73 1-4 int32 2526 Generator negative reactive energy Mvarh *100 All
50222 74 1-4 int32 05.70 Active power set point ramped kW *1 All
50225 75 1-4 int32 05.92 Reactive power set point ramped kvar *1 All
50001 int16 3181 Skaling Power (16 bits) Exponent 10x W All
(5;4;3;2)
50002 int16 3182 Skaling Volts (16 bits) Exponent 10x V All
(2;1;0;-1)
50003 int16 3183 Skaling Amps (16 bits) Exponent 10x A (0;-1) All
50004 Internal
50005 Internal
50006 Internal
50007 Internal
50011 int16 247 Total generator reactive power var format All
defined by
index 3181
(Modbus-
Address
50001)
50032 int16 259 Total mains reactive power var format All
defined by
index 3181
(Modbus-
Address
50001)
50043 int16 267 Average LSx Delta Mains voltage L-L V format EG3500XT-P1
defined by
index 3182 EG3500XT-P1
(Modbus-
Address
50002)
50044 int16 268 Average LSx Wye Mains voltage L-N V format EG3500XT-P1
defined by
index 3182 EG3500XT-P2
(Modbus-
Address
50002)
50050 int16 4608 Average LSx Mains delta frequency L-L Hz *100 EG3500XT-P1
EG3500XT-P2
50095 Internal
50098 Internal
50101 Internal
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
Subtopic General
EG3500XT-P2
05.14 ECU yellow (amber) lamp alarm latched Mask: 0001h All
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
Subtopic Engine
Subtopic Generator
Subtopic Mains
07.27 Mains slow voltage increase (10 min) Mask: 0008h All
2: Off
3: Preglow
4: Crank
5: Run
6: Cool down
7: Spin down
8: Start pause
9: Idle
2: Static
3: Isochronous
0, 1, 5, 6, 7, 8, 9, 11, … : internal
2: Static
3: Isochronous
5: Export/import control
50137 Internal
50156 Internal
50157 Internal
50158 Internal
50163 Internal
50164 Internal
EG3500XT-P2
EG3500XT-P2
Subtopic Active Diagnostic Trouble Code (DM1) 1-10 (SPN Range 0…65535)full SPN value at 450425-450444
50193 int16 15109 J1939 MTU ADEC ECU Failure Codes *1 All
"Missing" Value="65535"
"Error" Value="65279"
50198 Internal
50199 Internal
50200 Internal
Subtopic Values
50204 int16 15309 Engine Oil Temperature 1 (SPN 175) °C *10 All
50205 int16 15205 Engine Oil Pressure (SPN 100) kPa *1 All
50206 int16 15307 Fuel Rate (SPN 183) L/h *10 All
50210 int16 15210 Engine oil level (SPN 98) % *10 All
50213 int16 15212 Barometric Pressure (SPN 108) kPa *10 All
50219 int16 15219 Fuel Filter Differential Pressure (SPN95) kPa *1 All
50221 int16 15221 Turbo Air Inlet Pressure (SPN106) kPa *1 All
50222 int16 15222 Air Filter 1 Differential Pressure (SPN107) kPa *100 All
50225 int16 15225 Fuel Rail Pressure (SPN157) MPa *10 All
50243 int16 15242 Exhaust Gas Port 1 Temperatures (SPN1137) °C *10 All
50244 int16 15243 Exhaust Gas Port 2 Temperatures (SPN1138) °C *10 All
50245 int16 15244 Exhaust Gas Port 3 Temperatures (SPN1139) °C *10 All
50246 int16 15245 Exhaust Gas Port 4 Temperatures (SPN1140) °C *10 All
50247 int16 15246 Exhaust Gas Port 5 Temperatures (SPN1141) °C *10 All
50248 int16 15247 Exhaust Gas Port 6 Temperatures (SPN1142) °C *10 All
50249 int16 15248 Exhaust Gas Port 7 Temperatures (SPN1143) °C *10 All
50250 int16 15249 Exhaust Gas Port 8 Temperatures (SPN1144) °C *10 All
50251 int16 15250 Exhaust Gas Port 9 Temperatures (SPN1145) °C *10 All
50252 int16 15251 Exhaust Gas Port 10 Temperatures (SPN1146) °C *10 All
50253 int16 15252 Exhaust Gas Port 11 Temperatures (SPN1147) °C *10 All
50254 int16 15253 Exhaust Gas Port 12 Temperatures (SPN1148) °C *10 All
50255 int16 15254 Exhaust Gas Port 13 Temperatures (SPN1149) °C *10 All
50256 int16 15255 Exhaust Gas Port 14 Temperatures (SPN1150) °C *10 All
50257 int16 15256 Exhaust Gas Port 15 Temperatures (SPN1151) °C *10 All
50258 int16 15257 Exhaust Gas Port 16 Temperatures (SPN1152) °C *10 All
50259 int16 15258 Exhaust Gas Port 17 Temperatures (SPN1153) °C *10 All
50260 int16 15259 Exhaust Gas Port 18 Temperatures (SPN1154) °C *10 All
50261 int16 15260 Exhaust Gas Port 19 Temperatures (SPN1155) °C *10 All
50262 int16 15261 Exhaust Gas Port 20 Temperatures (SPN1156) °C *10 All
50278 int16 15277 Turbo 1 Compressor Inlet Pressure (SPN1176) kPa *1 All
50279 int16 15278 Turbo 2 Compressor Inlet Pressure (SPN1177) kPa *1 All
50280 int16 15279 Turbo 3 Compressor Inlet Pressure (SPN1178) kPa *1 All
50281 int16 15280 Turbo 4 Compressor Inlet Pressure (SPN1179) kPa *1 All
50282 int16 15281 Turbo 1 Turbine Inlet Temperature (SPN1180) °C *10 All
50283 int16 15282 Turbo 2 Turbine Inlet Temperature (SPN 1181) °C *10 All
50284 int16 15283 Turbo 3 Turbine Inlet Temperature (SPN 1182) °C *10 All
50285 int16 15284 Turbo 4 Turbine Inlet Temperature (SPN1183) °C *10 All
50286 int16 15285 Turbo 1 Turbine Outlet Temperature (SPN1184) °C *10 All
50287 int16 15286 Turbo 2 Turbine Outlet Temperature (SPN1185) °C *10 All
50288 int16 15287 Turbo 3 Turbine Outlet Temperature (SPN °C *10 All
1186)
50289 int16 15288 Turbo 4 Turbine Outlet Temperature (SPN1187) °C *10 All
50290 int16 15289 Engine Aux. Coolant Pressure (SPN1203) kPa *1 All
50293 int16 15292 Fuel Filter Differential Pressure (SPN1382) kPa *1 All
50298 int16 15297 Right Exhaust Gas Temperature (SPN2433) °C *10 All
50299 int16 15298 Left Exhaust Gas Temperature (SPN2434) °C *10 All
50300 int16 15310 Turbo 1 Compr. Outlet Temperature (SPN2629) °C *10 All
50303 int16 15313 Aftertreatment 1 Diesel Exhaust Fluid Tank 1 % *10 All
Level (SPN1761)
50305 int16 15315 Aftertreatment 1 Diesel Exhaust Fluid Tank 2 % *10 All
Level (SPN4367)
50307 int16 12807 Exhaust Gas Temperature Average(SPN 4151) °C *10 All
50308 int16 12809 Exhaust Gas Temperature Average Bank 1 °C *10 All
(SPN 4153)
50309 int16 12812 Exhaust Gas Temperature Average Bank 2 °C *10 All
(SPN 4152)
Topic Miscellenous
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
Int32 (Long)
50456 int32 2522 Gen. positive reactive energy Mvarh *100 All
EG3500XT-P2
EG3500XT-P2
50470 int32 2526 Gen. negative reactive energy Mvarh *100 All
50500 int32 217 Reserve real power in system (valid if LDSS is kW *1 All
on)
50502 int32 218 Real power in system (vaild if LDSS is on) kW *1 All
50504 int32 219 Nominal real power in system (vaild if LDSS is kW *1 All
on)
50506 int32 - 05.70 Active power set point ramped kW *10 All
50508 int32 - 05.92 Reactive power set point ramped kvar *10 All
Subtopic Values
50532 int32 15201 Total engine hours (j1939-HOURS, SPN 247) h *1 All
50536 int32 15319 Engine Total Fuel Used (SPN250) L *10 All
Topic LS5
50542 uint32 267 Average LSx Delta Mains voltage L-L V *10 EG3500XT-P1
EG3500XT-P2
50544 uint32 268 Average LSx Wye Mains voltage L-N V *10 EG3500XT-P1
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
Topic Miscellenous
50600 int32
Subtopic Generator
Subtopic Mains
07.27 Mains slow voltage increase (10 min) Mask: 0008h All
Subtopic Engine
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
05.11 Charge alt. low voltage (D+) latched Mask: 1000h All
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
EG3500XT-P2
6 1 Internal
byte
EG3500XT-P2
EG3500XT-P2
General notes
The device accepts receive data from outside. These data are usually remote control
data, with which the genset control starts and stops the operation or runs different
setpoints.
These data do not require a password level to be accepted. They are overtaken into a
non-volatile memory and are lost, if the device is powered down.
Ensure Security!
Transmitting data from outside of the remote control needs secure (network)
communication. Do not connect the easYgen with the internet as long the security
aspects are not considered! Consider an IP responsible person to discuss proper security
procedures like placing routers and fire walls.
This object is required for remote control. The data type is UNSIGNED16.
The internal parameter 503 of the easYgen must be set to react on the remote control
instructions. This is performed by sending rising signals for the respective bits (refer to
╚═▷ Fig. 345 for the priority of start and stop signals).
Bit 0 With the rising edge of the bit, the easYgen activates the remote request command
(LogicsManager input command variable 04.13).
Start bit
The condition of the start command will be stored and may be used as command variable
for the LogicsManager.
Bit 1 With the rising edge of the bit, the easYgen deactivates the remote request command
(LogicsManager input command variable 04.13).
Stop bit
The condition of the start command will be stored and may be used as command variable
for the LogicsManager.
Bit 4 This bit controls the LogicsManager input command variable 04.14. The remote
acknowledge bit must be set and reset twice to acknowledge an alarm completely. The first
"Reset alarms" rising edge disables the horn and the second rising edge resets the alarm.
Bit 9 This bit is directly influencing the LogicsManager command variable: “03.40 Remote
Shutdown“ and can be taken to create an engine shut down and/or an alarm over an
"Shutdown command" internal flag.
Remote start /stop The command variable "04.13 Remote request" changes to "1" (high) if the start bit is
enabled and changes back to "0" (low) if the stop bit is enabled.
Ext. acknowledge The command variable "04.14 Remote acknowledge" is the reflection of the control bit. The
easYgen deactivates the horn with the first change from "0" to "1" of the logical output
"External acknowledge", and acknowledges all alarm messages, which have occurred and
are no longer active, with the second change from "0" to "1".
╚═▷ Fig. 345 shows the reaction of the command variable on the various status changes
of the bits.
The easYgen does not react on the disabling of the start bit, but only on the enabling of
the stop bit. This has the advantage that it is not required to maintain the connection
established for the whole time in case of a remote start via a modem.
This object is required for remote control. The data type is UNSIGNED16.
Bit 15 = 1
Bit 14 = 1
Bit 13 = 1
Bit 12 = 1
Bit 11 = 1
Bit 10 = 1
Bit 9 = 1
Bit 8 = 1
Bit 7 = 1 Request active power setpoint 2 – this bit activates the LogicsManager command variable
[04.40] "Remote power setpoint 2" and is dedicated for switching from active power
setpoint 1 to active power setpoint 2
Bit 6 = 1 Request power factor setpoint 2 – this bit activates the LogicsManager command variable
[04.39] "Remote PF setpoint 2" and is dedicated for switching from power factor setpoint 1
to power factor setpoint 2
Bit 5 = 1 Request frequency setpoint 2 – this bit activates the LogicsManager command variable
[04.38] "Remote frequency setpoint 2" and is dedicated for switching from frequency
setpoint 1 to frequency setpoint 2
Bit 4 = 1 Request voltage setpoint 2 – this bit activates the LogicsManager command variable
[04.37] "Remote voltage setpoint 2" and is dedicated for switching from voltage setpoint 1
to voltage setpoint 2
Bit 3 = 1
Bit 2 = 1
Bit 1 = 1
Bit 0 = 1
This object is required for remote control. These remote control bits can be used by a PLC
to send control signals via SDO or PDO, which can then be used as command variables in
the LogicsManager to control the easYgen. The data type is UNSIGNED16.
This value may be used as data source "[05.56] Interface P setp [kW]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the active power setpoint for active power control.
Example
This value may be used as data source "[05.12] Interface PF sp [%]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the power factor setpoint for power factor control.
Example
This value may be used as data source "[05.53] Interface f setp [Hz]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the frequency setpoint for frequency control.
Example
This value may be used as data source "[05.59] Interface V setp [V]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the voltage setpoint for voltage control.
Example
This value may be used as data source "[05.83] Interf.kvar sp [kvar]" via the
AnalogManager. No password is required to write this value. This object is required to
transmit the reactive power setpoint for the kvar control.
Examples:
This is the Setpoint for the reactive power - voltage function Q(V). [VDE-AR-N 4110]
Interface reference value VQ0 has the resolution of (1/100) steps. The “starting” value is
1.00. A value limitation is included.
This value may be used to modify LDSS reserve power value [kW] for island operation via
interface.
Notes:
• Parameters “5760 IOP Reserve power”, “5648 IOP Reserve power 2” and LM
“120604 IOP Reserve power 2” are not overwritten by this write command.
• The last change either via interface or via the parameter selected with the LM is
effective.
• If there is no change anymore, the last change will be kept until power cycling the
device.
• After power cycling, the parameter value is used until the easYgen receives a
different value via interface.
• The parameter alignment is still done with the active parameter value.
This value may be used to modify LDSS reserve power value [kW] for parallel to mains
operation via interface.
Notes:
• Parameter “5768 MOP Reserve power”, “5649 MOP Reserve power 2” and LM
“120605 MOP Reserve power 2” are not overwritten by this write command.
• The last change either via interface or via the parameter selected with the LM is
effective.
• If there is no change anymore, the last change will be kept until power cycling the
device.
• After power cycling, the parameter value is used until the easYgen receives a
different value via interface.
• The parameter alignment is still done with the active parameter value.
The device provides identifier “Free analog values” for receiving 16 bit signed integers for
free purposes. The values are available in the AnalogManager group 24. Refer to ╚═▷
“9.2.9.3.4 Free Analog Values”
This object is required to receive the state of the external discrete inputs 1 to 16 (e.g. of
a Phoenix expansion card). The data type is UNSIGNED16.
This object is required to receive the state of the external discrete inputs 17 to 32 (e.g. of
a Phoenix expansion card). The data type is UNSIGNED16.
This unscaled value is transmitted by the external expansion board. The easYgen must
be configured to format this value accordingly. The data type is UNSIGNED16.
AI # 1 2 3 4 5 6 7 8
AI # 9 10 11 12 13 14 15 16
The device sends data out which are receipt by external devices. These data usually are
commands to control expansion boards or annunciators running CANopen.
This object is required to control the external outputs (relays) 1 to 16 (e.g. of a Phoenix
expansion card). The data type is UNSIGNED16.
This object is required to control the external outputs (relays) 17 to 32 (e.g. of a Phoenix
expansion card). The data type is UNSIGNED16.
This unscaled value is transmitted by the external expansion board. The easYgen must
be configured to format this value accordingly. The data type is UNSIGNED16.
AI # 1 2 3 4
9.2.9.3.1 Introduction
The easYgen provides different possibilities to receive data from other CAN or Modbus
devices. The received data are available in the AnalogManager or LogicsManager system.
There are:
The table below shows data which can be received via CAN RPDO or Modbus from any
other devices. These data are available as analog variables (of group 21) and can be
assigned to analog manager equations e.g. for free alarms or setpoints. For usage with
CAN the corresponding indices must be mapped to the RPDOs. It is also possible to write
via Modbus to these indices.
If “LDSS with predicted load” is used in “External” mode, RPDOx Word1 and RPDOx
Word2 are used for LDSS and are not available for other functions. (Refer to ╚═▷ “6.3.15
LDSS with predicted load”).
The single bits 1-16 of RPDO1 Word1 (3371), RPDO2 Word1 (3375), RPDO3 Word1 (3379),
RPDO4 Word1 (3383) and RPDO5 Word1 (3387) are available as command variables of
groups 32 to 36 which can be assigned to LogicsManagers.
The figure below shows how the name of these Command Variables are composed. (The
naming of the variables was chosen with regard to their usage as CAN1 RPDOs.)
LogicsManager
Word
Command variable
Bit
Group No.
The figure below shows an example of how CAN 1 RPDOs can be configured for
interconnectivity. The 4 data words received at
• COB-ID 1026 (dec) are assigned to the Analog Variables 21.01, 21.02, 21.03 and
21.04 via configuration. The bits of 21.01 are assigned internally to the Command
Variables 32.01 - 32.16.
• COB-ID 1030 (dec) are assigned to the Analog Variables 21.17, 21.18, 21.19 and
21.20 via configuration. The bits of 21.17 are assigned internally to the Command
Variables 36.01 - 36.16.
These Analog Variables and Command Variables can be used in AnalogManagers and
LogicsManagers equations to control different functions.
LogicsManager
Receive PDO1
AnalogManager Command
9300 COB-ID 1026 dec Analog Variables Variables
9121 Event timer 2000 ms
Group 32
8970 Selected Data Protocol 0
Group 21 Index 32.01 CAN1 RPDO1.1.1
9910 Number of mapped Objects 4 32.02 CAN1 RPDO1.1.2
21.01 CAN1 RPDO1.1 3371
9911 1. Mapped Object 3371 21.02 CAN1 RPDO1.2 3372 32.03 CAN1 RPDO1.1.3
9912 2. Mapped Object 3372 21.03 CAN1 RPDO1.3 3373 32.04 CAN1 RPDO1.1.4
Receive PDO5
12806 COB-ID 1030 dec Group 33
9125 Event timer 2000 ms 33.01 CAN1 RPDO2.1.1
Group 36
36.01 CAN1 RPDO5.1.1
Additionally the device provides “Free analog values” for receiving data for free
purposes. These indices can be mapped to RPDOs or can be written via Modbus. The
values are available in the AnalogManager group 24.
In future releases (higher than 2.10-0) the variables 24.05-24.08 will be write-protected
with code level CL1.
The communication interface programmer needs often for single data transfer the
identifier of the easYgen variable. To figure that out he has here some tips.
The data protocol document shows usually in the column “Parameter ID” the identifier for
a single use. Please check the type. Usually it is a signed INT16 (Short) variable but
depending on the function it can also be a signed INT32 (Long). Typical values for long are
voltages, currents and power measurement values.
Nearly each parameter in ToolKit shows the according identifier in front of the data. The
data type is to check. Usually it is a signed INT16 (Short) variable but depending on the
function it can also be a signed INT32 (Long). Typical values for long are voltages,
currents and power measurement values.
With a few minor exceptions the reading of parameter are always possible. Writing of
parameter is only accepted if the correct code level was passed for the according
interface channel.
The access on AnalogManager variables is provided as a signed 4 byte float value without
decimals.
The LogicsManager is used to customize the sequence of events in the control unit such
as the start command of the engine or the operation of control unit relay outputs. For
example, the start routine may be programmed so that it requires the closing of a
discrete input or a preset time of day.
Depending on the application mode of the unit, the number of available relays that may
be programmed with the LogicsManager will vary.
Two independent time delays are provided for the configured action to take place and be
reset.
Please do not use the output of an equation as input at the same time. Such a
configuration could decrease the performance of the interface.
• Command (variable)
A list of over 400 parameters and functions is provided for the command inputs.
Examples of the parameters that may be configured into these commands are
generator undervoltage thresholds 1 and 2, start fail, and cool down.
These command variables are used to control the output function or relay.
Refer to ╚═▷ “9.3.2 Logical Command Variables” for a complete list of all command
variables.
• Sign
The sign field can be used to invert the state of the command or to fix its output to a
logical true or false if the command is not needed. Setting the sign to the NOT state
changes the output of the command variable from true to false or vice versa.
• Operator
• (Logical) output
The action or control sequence that occurs when all parameters set into the
LogicsManager are met.
For a complete list of all logical outputs refer to ╚═▷ “9.3.4 Logical Outputs”.
0 [False; always "0"] The value [Cx] is ignored and this logic path will
always be FALSE.
1 [True; always "1"] The value [Cx] is ignored and this logic path will
always be TRUE.
OR Logical OR
XOR Exclusive OR
For the various display formats of the corresponding logical symbols refer to ╚═▷ “9.3.3
Logical Symbols”.
Using the values specified in the above table, the chain of commands of the
LogicsManager (for example: operating the relays, setting the flags, specification of the
automatic functions) is configured as follows:
[Ax] = ( ( [C1] & [S1] ) & [O1] & ( [C2] & [S2] ) ) & [O2] & ( [C3] & [S3] )
• Relay [R2] shall energize, whenever "Discrete input [DI 02]" is energized "AND" the
control does "NOT" have a fault that is "Alarm class C" "AND" does "NOT" have a
fault that is "Alarm class D"
For the description of the alarm classes refer to chapter 'Alarm classes'.
latched.
latched.
latched.
latched.
latched.
latched.
01.07 All alarm classes TRUE as long as at least one alarm of the alarm classes
A / B / C / D / E / F is active or latched.
01.08 Warning alarm TRUE as long as at least one alarm of the alarm classes A / B
is active or latched.
01.09 Shutdown alarm TRUE as long as at least one alarm of the alarm classes
C / D / E / F is active or latched.
01.10 Centralized alarm TRUE as long as at least one alarm of the alarm classes
B / C / D / E / F is active or latched.
01.11 New alarm triggered TRUE if any alarm of the Alarm classes B / C / D / E / F has been
02.03 Gen. voltage ok TRUE as long as the generator voltage is within the
operating range.
02.04 Gen. frequency ok TRUE as long as the generator frequency is within the
operating range.
02.05 Gen. volt. / freq. ok TRUE as long as the generator voltage and frequency
TRUE).
02.06 Busbar 1 voltage ok TRUE as long as the busbar 1 voltage is within the
02.07 Busbar 1 freq. ok TRUE as long as the busbar 1 frequency is within the
02.08 Busb1 volt. / freq. ok TRUE as long as the busbar 1 voltage and frequency
02.09 Mains voltage ok TRUE as long as the mains voltage is within the operating range.
02.10 Mains frequency ok TRUE as long as the mains frequency is within the operating range.
02.11 Mains volt. / freq. ok TRUE as long as the mains voltage and frequency are within the operating ranges
(02.09. and 02.10 are
TRUE).
02.12 Gen. rotation CCW TRUE as long as the respective rotation field is
02.14 Mains rotation CCW TRUE as long as the respective rotation field is
02.16 Busb.1 rotation CCW TRUE as long as the respective rotation field is
02.21 Dead busbar1 TRUE as long as the busbar voltage is below the value configured in parameter
5820 (Dead
• voltage
• frequency
• phase angle
• acceleration range
• lead angle
• voltage
• frequency
• phase angle
• acceleration range
• lead angle
02.34 Firing speed electr. True if generator frequency value matches firing speed.
02.35 Firing speed rpm True if rpm (via MPU or J1939) value matches firing speed.
02.36 Speed electr. True if generator frequency value matches speed detected.
02.37 Speed rpm True if rpm (via MPU or J1939) value matches speed detected.
dec." is TRUE
03.05 Horn True if a new alarm (higher A) is triggered and time (parameter
03.06 Engine released TRUE if the engine is requested and the start is released.
03.07 Engine delay expired TRUE after expiration of the "delayed engine monitoring" timer
03.08 Break. delay expired TRUE after expiration of the Generator Stable Time until the fuel
relay is de-energized.
03.13 Blinking lamp ECU TRUE as soon as the ECU activates the diagnosis light (only
03.14 ECU special ignition TRUE as long as a reset or read-out of the Scania S6 ECU
easYgen is activated.
03.15 ECU seq. B_OUT_1 This flag is for special ECU indications:
03.16 ECU seq. B_OUT_2 This flag is for special ECU indications:
03.17 ECU seq. B_OUT_3 This flag is for special ECU indications:
03.18 ECU seq. B_OUT_4 This flag is for special ECU indications:
03.20 Governor raise TRUE if the "Three Position Controller Frequency / Active Power" raise pulse is
active.
03.21 Governor lower TRUE if the "Three Position Controller Frequency / Active Power" lower pulse is
active.
03.22 AVR raise TRUE if the "Three Position Controller Output Voltage / Reactive Power" raise pulse
is active.
03.23 AVR lower TRUE if the "Three Position Controller Output Voltage / Reactive Power" lower pulse
is active.
03.25 Engine shall run TRUE if engine start conditions are fulfilled.
03.27 Stop solenoid TRUE if a stop signal is issued until the stop time of engine
expires
03.28 Start / Gas TRUE if the fuel solenoid (Diesel) or gas valve (gas) is released.
03.32 + PID1 controller TRUE if the "Free PID 1" raise pulse is active.
03.33 - PID1 controller TRUE if the "Free PID 1" lower pulse is active.
03.34 + PID2 controller TRUE if the "Free PID 2" raise pulse is active.
03.35 - PID2 controller TRUE if the "Free PID 2" lower pulse is active.
03.36 + PID3 controller TRUE if the "Free PID 3" raise pulse is active.
03.37 - PID3 controller TRUE if the "Free PID 3" lower pulse is active.
03.39 Close neutral cont. TRUE if neutral contactor close command is active.
03.40 Remote Shutdown TRUE if remote shutdown (ID 503, Bit 9) is acitve.
03.44 Protection lamp DM1 TRUE if ECU Protection lamp DM1 (SPN 987) is active.
03.45 Emission lamp DM1 TRUE if ECU Emission lamp DM1 (SPN 1213) is active.
03.46 DPF lamp solid on TRUE if ECU Diesel Particulate Filter Lamp Command: ON solid
03.47 DPF lamp fast blink TRUE if ECU Diesel Particulate Filter Lamp Command: fast blinking (SPN 3697) is
active.
03.48 DPF regenerat.active TRUE if ECU Diesel Particulate Filter Active Regeneration Status: active (SPN 3700)
is active.
03.49 DPF regenerat.needed TRUE if ECU Diesel Particulate Filter Active Regeneration Status: regeneration
needed (SPN 3700) is active.
03.50 DPF reg. needed low TRUE if ECU Diesel Particulate Filter Status: Regeneration needed: lowest level
(SPN 3701) is active.
03.51 DPF reg. needed mod. TRUE if ECU Diesel Particulate Filter Status: Regeneration needed: moderate level
(SPN 3701) is active.
03.52 DPF reg. needed high TRUE if ECU Diesel Particulate Filter Status: Regeneration needed: highest level
(SPN 3701) is active.
03.53 Exh. temp. lamp on TRUE if ECU Exhaust System High Temperature Lamp Command: on (SPN 3698) is
active.
03.54 Wait to start lamp TRUE if ECU Engine Wait to Start Lamp: on (SPN 1081) is active.
03.57 DPF: Pass.regeneration TRUE if ECU Diesel Particulate Filter Passive Regeneration Status: Active (SPN
3699) is active.
03.58 DPF: Act.reg.inhibit TRUE if ECU Diesel Particulate Filter Active Regeneration Inhibited Status: Inhibited
(SPN 3702) is active.
(This condition is TRUE for approx. 40 ms and must be extended utilizing a delay
time.)
04.09 Emergency mode TRUE if the emergency "Mains fail delay time" has exceed.
04.10 Cool down TRUE as long as the cool down time is running.
04.13 Remote request TRUE if a remote start request is active (Control word 503)
04.14 Remote acknowledge TRUE if a remote acknowledge is active (Control word 503)
04.15 Idle run active TRUE if the idle mode is active. This may be used to issue an "Idle" command to a
speed controller.
04.19 Opening GCB relay act TRUE if the GCB open relay is energized.
04.20 Closing GCB active TRUE if the GCB close relay is energized.
04.30 Limited prerun TRUE if prerun with warm up load limitation is active.
04.31 Segment no.2 act. TRUE if the result LM "12929 segment number 2" is true.
04.32 Segment no.3 act. TRUE if the result LM "12928 segment number 3" is true.
04.33 Segment no.4 act. TRUE if the result LM "12927 segment number 4" is true.
04.34 LDSS Priority 2 TRUE if the result of LM "12926 LDSS Priority 2" is true.
04.35 LDSS Priority 3 TRUE if the result of LM "12925 LDSS Priority 3" is true.
04.36 LDSS Priority 4 TRUE if the result of LM "12924 LDSS Priority 3" is true.
04.37 Remote volt. setp. 2 TRUE if "Request Voltage Setpoint 2" is set via interface (control word 504).
04.38 Remote freq. setp. 2 TRUE if "Request Frequency Setpoint 2" is set via interface (control word 504).
04.39 Remote PF setp. 2 TRUE if "Request Power Factor Setpoint 2" is set via interface (control word 504).
04.40 Remote pwr. setp. 2 TRUE if "Request Active Power Setpoint 2" is set via interface (control word 504).
1" is true.
2" is true.
04.44 RemoteControl Bit 1 TRUE if remote control bit 1 is activated. (Control word 505)
04.45 RemoteControl Bit 2 TRUE if remote control bit 2 is activated. (Control word 505)
04.46 RemoteControl Bit 3 TRUE if remote control bit 3 is activated. (Control word 505)
04.47 RemoteControl Bit 4 TRUE if remote control bit 4 is activated. (Control word 505)
04.48 RemoteControl Bit 5 TRUE if remote control bit 5 is activated. (Control word 505)
04.49 RemoteControl Bit 6 TRUE if remote control bit 6 is activated. (Control word 505)
04.50 RemoteControl Bit 7 TRUE if remote control bit 7 is activated. (Control word 505)
04.51 RemoteControl Bit 8 TRUE if remote control bit 8 is activated. (Control word 505)
04.52 RemoteControl Bit 9 TRUE if remote control bit 9 is activated. (Control word 505)
04.53 RemoteControl Bit 10 TRUE if remote control bit 10 is activated. (Control word 505)
04.54 RemoteControl Bit 11 TRUE if remote control bit 11 is activated. (Control word 505)
04.55 RemoteControl Bit 12 TRUE if remote control bit 12 is activated. (Control word 505)
04.56 RemoteControl Bit 13 TRUE if remote control bit 13 is activated. (Control word 505)
04.57 RemoteControl Bit 14 TRUE if remote control bit 14 is activated. (Control word 505)
04.58 RemoteControl Bit 15 TRUE if remote control bit 15 is activated. (Control word 505)
04.59 RemoteControl Bit 16 TRUE if remote control bit 16 is activated. (Control word 505)
04.60 Crit. mode postrun TRUE as long as the critical mode postrun time is running.
04.64 Key activation TRUE as long as the "Key activation time" is running.
04.65 System update active TRUE if System Update (teach in process) is active.
04.66 Mains failure ended TRUE if "Mains Settling Time" is triggered OR mains frequency dependent power
up- / derating becomes deactive.
Reset if
GCB is opened OR
04.68 ATS start request TRUE if LDSS with predicted load wants to start the engines. This command
variable
AUTO"
lower than the predicted load. It shall be passed to a relay to inhibit the ATS
control to switch load in any direction.
04.70 Opening GCB active TRUE if the GCB is to be opened. (Independent of the relay NC / NO.)
04.75 PV load ref. 30% TRUE if the PV inverter shall be limited to 30 % of rated.
04.76 PV load ref. 60% TRUE if the PV inverter shall be limited to 60 % of rated.
04.77 PV load ref. 100% TRUE if the PV inverter shall provide up to 100 % of rated.
(Change of frequency)
07.27 Mains volt. incr. Mains slow voltage (10 minutes moving average)
07.34 FRT ROCOF enable This flag is FALSE if any "Time-dependent voltage monitoring" (FRT) is initialized.
Otherwise it is TRUE.
It can be used to block temporary "Phase shift" and "df / dt" monitoring if FRT is
initialized. . (This is no alarm, only a LM.)
There is a LSx detected in the communication network which is not taught in.
(alarm class B, not selfackn.) becomes active if CPU overload is longer than 10s,
Red twinkle: if there is no device recognized according to the last system update.
Yellow twinkle: if there is no device detected according to the last system update
on one redundant interface. (This is no alarm, only a LM.)
08.70 CAN1 EthA redundancy Load share interface redundancy CAN1 / Ethernet A lost
08.72 Modbus dev.1 timeout Modbus Master communication timeout device 1 (This is no alarm, only a LM.)
08.73 Modbus dev.2 timeout Modbus Master communication timeout device 2 (This is no alarm, only a LM.)
08.74 Modbus dev.3 timeout Modbus Master communication timeout device 3 (This is no alarm, only a LM.)
08.75 Modbus dev.4 timeout Modbus Master communication timeout device 4 (This is no alarm, only a LM.)
08.76 Modbus dev.5 timeout Modbus Master communication timeout device 5 (This is no alarm, only a LM.)
11.09 Engine 10h Running hours 10h over (toggles every 10 running hours)
11.10 Engine 100h Running hours 100h over (toggles every 100 running hours)
TRUE, if "out of range" or "wire break" of the external analog input is detected. (Only if
this function is supported by the external device.)
86.87 LM: Segment no.2 act. LM set group / node number to 2 for load share
86.88 LM: Segment no.3 act. LM set group / node number to 3 for load share
86.89 LM: Segment no.4 act. LM set group / node number to 4 for load share
87.77 LM: 2nd load SP ramp LM Enable 2nd load setpoint ramp
87.79 LM: 3rd load SP ramp LM Enable 3rd load setpoint ramp
99.01 LM: Ready for op. OFF LM Relay 1 ready for operation
(This flag has negative logic: if the LM flag is true, the relay is not energized.)
The following symbols are used for the graphical programming of the LogicsManager. The
easYgen displays symbols according to the IEC standard by default.
B DIN 40 700
C ASA
US MIL (configurable)
D IEC617-12
1 2 3 4 5 6
x1 x2 y x1 x2 y x1 x2 y x1 x2 y x1 x2 y x1 x2 y
0 0 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0
0 1 0 0 1 1 0 1 1 0 1 0 0 1 0 0 1 1
1 0 0 1 0 1 1 0 1 1 0 0 1 0 0 1 0 1
1 1 1 1 1 1 1 1 0 1 1 0 1 1 1 1 1 0
• Internal functions
• Relay outputs
The numbers of the logical outputs in the third column may again be used as input
variable for other outputs in the LogicsManager.
Internal flags
Internal functions
LM: Start req in AUTO Start in AUTOMATIC operating mode (parameter ╚═▷ 12120) 86.09 10708
LM: Stop req. in AUTO Stop in AUTOMATIC operating mode (parameter ╚═▷ 12190) 86.10 10709
LM: Inhibit emerg.run Blocking or interruption of an emergency power operating in 86.11 10710
AUTOMATIC operating mode (parameter ╚═▷ 12200)
LM: Undelay close Immediately closing of the GCB after engine start without waiting for the 86.12 10711
GCB engine delayed monitoring and generator stable timer to expire
(parameter ╚═▷ 12210)
LM: LS interf. EthA Enables to switch load share interface between CAN and Ethernet A 86.13 11987
(parameter ╚═▷ 11986)
LM: Constant idle run Enables idle/rated speed modes (parameter ╚═▷ 12550). 86.14 10713
LM: Ext. acknowledge The alarm acknowledgement is performed from an external source 86.15 10714
(parameter ╚═▷ 12490)
LM: Operat. mode Activation of the AUTOMATIC operating mode (parameter ╚═▷ 12510 ) 86.16 10715
AUTO
LM: Operat. mode Activation of the MANUAL operating mode (parameter ╚═▷ 12520) 86.17 10716
MAN
LM: Operat. mode Activation of the STOP operating mode (parameter ╚═▷ 12530) 86.18 10717
STOP
LM: Start w/o load Starting the engine without closing the GCB (parameter ╚═▷ 12540) 86.19 10718
LM: Auto idle mode Automatic idle mode (blocks the undervoltage, underfrequency, and 86.20 10719
underspeed monitoring for a configured time automatically,
parameter ╚═▷ 12570)
LM: Discrete f/P + Raise frequency / real power setpoint (parameter ╚═▷ 12900) 86.21 11600
LM: Discrete f/P - Lower frequency / real power setpoint (parameter ╚═▷ 12901) 86.22 11601
LM: Discrete V/PF + Raise voltage / power factor setpoint (parameter ╚═▷ 12902) 86.23 11602
LM: Discrete V/PF - Lower voltage / power factor setpoint (parameter ╚═▷ 12903) 86.24 11603
LM: Freq. droop act. Activation of the frequency droop (parameter ╚═▷ 12904) 86.25 11604
LM: Volt. droop act. Activation of the voltage droop (parameter ╚═▷ 12905) 86.26 11605
LM: Ext. mns.decoupl. Activation of the mains decoupling function (parameter ╚═▷ 12922) 86.27 11606
LM: Critical mode Activation of critical mode operation (parameter ╚═▷ 12220) 86.28 11607
LM: Operat. mode Activation of the TEST operating mode (parameter ╚═▷ 12271) 86.29 12272
TEST
LM: Lock keypad 1 Activation of the Lock keypad 1 (parameter ╚═▷ 12978) 86.30 11924
LM: ECU seq. B_IN_1 Activation of a special ECU function (parameter ╚═▷ 15164) depending 86.31 11647
on the selected ECU
LM: ECU seq. B_IN_2 Activation of a special ECU function (parameter ╚═▷ 15165) depending 86.32 11648
on the selected ECU
LM: 2nd disp.bright. Enabling of the 2nd display brightness (parameter ╚═▷ 7794) 86.33 11971
LM: Enable heater Enabling of the front foil heater (parameter ╚═▷ 7799) 86.34 11972
LM: Syst. update Trigger system update (parameter ╚═▷ 7801) 86.35 11974
LM: Syn. mode Activation of CHECK synchronization mode (parameter ╚═▷ 12906) 86.38 11617
CHECK
LM: Syn. mode Activation of PERMISSIVE synchronization mode (parameter ╚═▷ 12907) 86.39 11618
PERMIS.
LM: Syn. mode RUN Activation of RUN synchronization mode (parameter ╚═▷ 12908) edge 86.40 11619
controlled
LM: IOP Res.power 2 Select IOP Reserve power 2 (parameter ╚═▷ 12604) 86.41 11975
LM: MOP Res.power 2 Select MOP Reserve power 2 (parameter ╚═▷ 12605) 86.42 11976
LM: RP Full mode Select remote panel full mode (parameter ╚═▷ 7857) 86.43 11994
LM: RP Annunciator Select remote panel annunciator mode (parameter ╚═▷ 7858) 86.44 11995
LM: RP Off mode Select remote panel off mode (parameter ╚═▷ 7859) 86.45 11996
LM: AVR V(f) enabled Enable AVR V(f) characteristic (only easYgen-3400XT and -3500XT) 86.46 10848
LM: Setpoint 2 freq. Activates the frequency setpoint 2 (parameter ╚═▷ 12918) 86.81 11910
LM: Setp. 2 load Activates the load setpoint 2 (parameter ╚═▷ 12919) 86.82 11911
LM: Setp. 2 voltage Activates the voltage setpoint 2 (parameter ╚═▷ 12920) 86.83 11912
LM: Setp.2 pwr.factor Activates the power factor setpoint 2 (parameter ╚═▷ 12921) 86.84 11913
LM: Enable MCB Enables the MCB (parameter ╚═▷ 12923) 86.85 11914
LM: LDSS enabled Activation of load-dependent start/stop (parameter ╚═▷ 12930) 86.86 11915
LM: Segment no.2 Assigns the genset to load share segm. #2 (parameter ╚═▷ 12929) 86.87 11916
act.
LM: Segment no.3 Assigns the genset to load share segm. #3 (parameter ╚═▷ 12928) 86.88 11917
act.
LM: Segment no.4 Assigns the genset to load share segm. #4 (parameter ╚═▷ 12927) 86.89 11918
act.
LM: LDSS Priority 2 Sets the LDSS priority to 2 (parameter ╚═▷ 12926) 86.90 11919
LM: LDSS Priority 3 Sets the LDSS priority to 3 (parameter ╚═▷ 12925) 86.91 11920
LM: LDSS Priority 4 Sets the LDSS priority to 4 (parameter ╚═▷ 12924) 86.92 11921
LM: Transition mode 1 Activates breaker transition mode 1 (parameter ╚═▷ 12931) 86.93 11922
LM: Transition mode 2 Activates breaker transition mode 2 (parameter ╚═▷ 12932) 86.94 11923
LM: Release f-control Release frequency control (parameter ╚═▷ 12909) 86.96 11925
LM: Release V-control Release voltage control (parameter ╚═▷ 12938) 86.97 11926
LM: P-control active Activates P-control (parameter ╚═▷ 12940) 86.98 11927
LM: Q control active Activates Q-control (parameter ╚═▷ 12941) 86.99 11928
LM: PID1 ctrl.release Release PID1 control (parameter ╚═▷ 5580) 87.17 11406
LM: PID2 ctrl.release Release PID2 control (parameter ╚═▷ 5593) 87.18 11407
LM: PID3 ctrl.release Release PID3 control (parameter ╚═▷ 5679) 87.19 11408
Reserved 87.23
Reserved 87.24
Reserved 87.25
Reserved 87.26
Reserved 87.27
Reserved 87.28
Reserved 87.29
Reserved 87.30
LM: Enable Mns dec. Enables mains decoupling (parameter ╚═▷ 12942) 87.31 11420
LM: GCB open in MAN Opens GCB in manual (parameter ╚═▷ 12976) 87.46 11435
LM: GCB close in MAN Closes GCB in manual (parameter ╚═▷ 12977) 87.47 11436
LM: MCB open in MAN Opens MCB in manual (parameter ╚═▷ 12974) 87.48 11437
LM: MCB close in MAN Closes MCB in manual (parameter ╚═▷ 12975) 87.49 11438
LM: MAN engine start Starts the engine in manual (parameter ╚═▷ 12970) 87.50 11439
LM: MAN engine stop Stops the engine in manual (parameter ╚═▷ 12971) 87.59 11448
LM: Free derating Activates free derating (parameter ╚═▷ 15146) 87.60 11449
Reserved 87.61
Reserved 87.62
LM: Inhibit cranking Inhibits cranking (parameter ╚═▷ 4871) 87.66 11455
LM: Setp. 3 load Activates the load setpoint 3 (parameter ╚═▷ 12998) 87.67 11456
LM: Firing speed Activate firing speed detected flag (parameter ╚═▷ 12951) 87.68 11457
LM: Speed detected Activate speed detected flag (parameter ╚═▷ 12989) 87.69 11458
LM: Release eng.mon. Release engine monitoring (parameter ╚═▷ 12999) 87.70 11459
LM: Release cyl.temp. Release cylinder temperature deviation monitoring (parameter ╚═▷ 87.71 11460
15158)
LM: Disable mns.mon. Disables mains monitoring (parameter ╚═▷ 15159) 87.72 11461
LM: Mains Enables mains decoupling via MCB (parameter ╚═▷ 15160) 87.73 11462
decoupl.MCB
LM: Inh.dead bus GCB Inhibit dead bus closure GCB (parameter ╚═▷ 15161) 87.74 11463
LM: Setp. 4 load Activates the load setpoint 4 (parameter ╚═▷ 12269) 87.75 11464
LM: Disable load Disable load setpoint ramp (parameter ╚═▷ 12853) 87.76 11465
ramp
LM: 2nd load SP ramp Select 2nd load control setpoint ramp (parameter ╚═▷ 11978) 87.77 11979
LM: 3rd load SP ramp Select 3rd load control setpoint ramp (parameter ╚═▷ 11998) 87.79 11999
LM: Free alarm 1 Select source of free alarm 1 (parameter ╚═▷ 8120) 88.01 11550
LM: Free alarm 2 Select source of free alarm 2 (parameter ╚═▷ 8124) 88.02 11551
LM: Free alarm 3 Select source of free alarm 3 (parameter ╚═▷ 8128) 88.03 11552
LM: Free alarm 4 Select source of free alarm 4 (parameter ╚═▷ 8132) 88.04 11553
LM: Free alarm 5 Select source of free alarm 5 (parameter ╚═▷ 8136) 88.05 11554
LM: Free alarm 6 Select source of free alarm 6 (parameter ╚═▷ 8140) 88.06 11555
LM: Free alarm 7 Select source of free alarm 7 (parameter ╚═▷ 8144) 88.07 11556
LM: Free alarm 8 Select source of free alarm 8 (parameter ╚═▷ 8148) 88.08 11557
LM: Free alarm 9 Select source of free alarm 9 (parameter ╚═▷ 8154) 88.09 11558
LM: Free alarm 10 Select source of free alarm 10 (parameter ╚═▷ 8158) 88.10 11559
LM: Free alarm 11 Select source of free alarm 11 (parameter ╚═▷ 8165) 88.11 11560
LM: Free alarm 12 Select source of free alarm 12 (parameter ╚═▷ 8170) 88.12 11561
LM: Free alarm 13 Select source of free alarm 13 (parameter ╚═▷ 8174) 88.13 11562
LM: Free alarm 14 Select source of free alarm 14 (parameter ╚═▷ 8178) 88.14 11563
LM: Free alarm 15 Select source of free alarm 15 (parameter ╚═▷ 8182) 88.15 11564
LM: Free alarm 16 Select source of free alarm 16 (parameter ╚═▷ 8186) 88.16 11565
The following table contains the priority relationships between the start conditions of the
logical outputs in the LogicsManager:
Start req. in Auto The behavior of the system depends on the configuration of
the related parameters.
Start w/o load Start req. in Auto The GCB remains open / will be opened.
Emergency power Start w/o load The GCB will be closed nevertheless.
Critical mode The GCB will be closed nevertheless. The alarm class
management is still performed like for the critical mode. If
emergency power is already enabled and the critical mode
will be enabled then, a pause time may be configured for
the emergency power operation.
Emergency power during The generator keeps on running without taking over load.
Start w/o load
Relay outputs
All relays may be controlled directly by the LogicsManager depending on the respective
application mode.
Relay 1 If this logical output becomes true, the relay output 1 will 99.01 11870
be activated
(Ready for
operation OFF)
Relay 2 If this logical output becomes true, the relay output 2 will 99.02 11871
be activated
Relay 3 If this logical output becomes true, the relay output 3 will 99.03 11872
be activated
Relay 4 If this logical output becomes true, the relay output 4 will 99.04 11873
be activated
Relay 5 If this logical output becomes true, the relay output 5 will 99.05 11874
be activated
Relay 6 If this logical output becomes true, the relay output 6 will 99.06 11875
be activated
Relay 7 If this logical output becomes true, the relay output 7 will 99.07 11876
be activated
Relay 8 If this logical output becomes true, the relay output 8 will 99.08 11877
be activated
Relay 9 If this logical output becomes true, the relay output 9 will 99.09 11878
be activated
Relay 10 If this logical output becomes true, the relay output 10 will 99.10 11879
be activated
Relay 11 If this logical output becomes true, the relay output 11 will 99.11 11880
be activated
Relay 12 If this logical output becomes true, the relay output 12 will 99.12 11881
be activated
External DO 1 If this logical output becomes true, the external relay 98.01 11892
output 1 will be activated
External DO 2 If this logical output becomes true, the external relay 98.02 11893
output 2 will be activated
External DO 3 If this logical output becomes true, the external relay 98.03 11894
output 3 will be activated
External DO 4 If this logical output becomes true, the external relay 98.04 11895
output 4 will be activated
External DO 5 If this logical output becomes true, the external relay 98.05 11896
output 5 will be activated
External DO 6 If this logical output becomes true, the external relay 98.06 11897
output 6 will be activated
External DO 7 If this logical output becomes true, the external relay 98.07 11898
output 7 will be activated
External DO 8 If this logical output becomes true, the external relay 98.08 11899
output 8 will be activated
External DO 9 If this logical output becomes true, the external relay 98.09 11900
output 9 will be activated
External DO 10 If this logical output becomes true, the external relay 98.10 11901
output 10 will be activated
External DO 11 If this logical output becomes true, the external relay 98.11 11902
output 11 will be activated
External DO 12 If this logical output becomes true, the external relay 98.12 11903
output 12 will be activated
External DO 13 If this logical output becomes true, the external relay 98.13 11904
output 13 will be activated
External DO 14 If this logical output becomes true, the external relay 98.14 11905
output 14 will be activated
External DO 15 If this logical output becomes true, the external relay 98.15 11906
output 15 will be activated
External DO 16 If this logical output becomes true, the external relay 98.16 11907
output 16 will be activated
External DO 17 If this logical output becomes true, the external relay 98.17 11390
output 17 will be activated
External DO 18 If this logical output becomes true, the external relay 98.18 11391
output 18 will be activated
External DO 19 If this logical output becomes true, the external relay 98.19 11392
output 19 will be activated
External DO 20 If this logical output becomes true, the external relay 98.20 11393
output 20 will be activated
External DO 21 If this logical output becomes true, the external relay 98.21 11394
output 21 will be activated
External DO 22 If this logical output becomes true, the external relay 98.22 11395
output 22 will be activated
External DO 23 If this logical output becomes true, the external relay 98.23 11396
output 23 will be activated
External DO 24 If this logical output becomes true, the external relay 98.24 11397
output 24 will be activated
External DO 25 If this logical output becomes true, the external relay 98.25 11398
output 25 will be activated
External DO 26 If this logical output becomes true, the external relay 98.26 11399
output 26 will be activated
External DO 27 If this logical output becomes true, the external relay 98.27 11400
output 27 will be activated
External DO 28 If this logical output becomes true, the external relay 98.28 11401
output 28 will be activated
External DO 29 If this logical output becomes true, the external relay 98.29 11402
output 29 will be activated
External DO 30 If this logical output becomes true, the external relay 98.30 11403
output 30 will be activated
External DO 31 If this logical output becomes true, the external relay 98.31 11404
output 31 will be activated
External DO 32 If this logical output becomes true, the external relay 98.32 11405
output 32 will be activated
No. Term. None A01 GCB open A02 GCB A03 GCB/MCB A04
No. Term. None A01 GCB open A02 GCB A03 GCB/MCB A04
CAUTION! Only relay [R 01] has an inverse logic. The relay opens (all other
relays close), if the logical output of the LogicsManager becomes TRUE.
[R 04] 45/46 LogicsManager; pre-assigned with 'Diesel: Fuel solenoid, Gas: Gas valve'
ID Name Function
7794 Enable 2nd display brightness (Not 04.64 Key activation And True) And True
7799 Enable front foil heater (True And True) And True
ID Name Function
11978 2nd load control setpoint ramp (False And 02.02 LM TRUE) And 02.02 LM TRUE
11988 3rd load control setpoint ramp (02.01 LM FALSE And True) And True
12037 Reserved
12120 Start req in AUTO (09.02 Discrete input 2 Or False) Or 04.13 Remote request
12210 Undelay close GCB (04.09 Emergency mode And True) And True
12220 Critical mode (False And Not 05.08 Start fail) And Not 09.01 Discrete input 1
ID Name Function
ID Name Function
12490 Ext. acknowledge (09.05 Discrete input 5 And True) Or 04.14 Remote acknowledge
12580 Ready for op. OFF (False And False) And True
12853 Disable load setpoint ramp (02.01 LM FALSE And True) And True
12904 Freq. droop act. (08.17 Missing members Or 08.06 GCB fail to open) And True
12905 Volt. droop act. (08.17 Missing members Or 08.06 GCB fail to open) And True
ID Name Function
12923 Enable MCB (09.06 Discrete input 6 And Not 08.07 MCB fail to close) And Not
07.05 Mns.ph.rot. mismatch
12927 Segment no.4 act. (02.01 LM FALSE And True) And True
12928 Segment no.3 act. (02.01 LM FALSE And True) And True
12929 Segment no.2 act. (02.01 LM FALSE And True) And True
12936 Reserved
12937 Reserved
12940 P control (04.07 MCB closed And 04.06 GCB closed) And True
12941 Q control (04.07 MCB closed And 04.06 GCB closed) And True
12942 Enable mains decoupl. (02.02 LM TRUE And True) And True
12951 Firing speed detection (02.34 Firing speed electr. Or 02.35 Firing speed rpm) And True
12972 Reserved
12973 Reserved
12979 Reserved
12980 Reserved
12981 Reserved
ID Name Function
12982 Reserved
12983 Reserved
12984 Reserved
12989 Speed detection (02.36 Speed electr. Or 02.37 Speed rpm) And True
12999 Release eng.mon. (02.34 Firing speed electr. Or 02.35 Firing speed rpm) And 03.28
Start/Gas
15026 LDSS with predicted load (False And True) And True
Relay outputs
Deactivated by default
In application mode
Deactivated by default
Deactivated by default
Deactivated by default
Deactivated by default
Prepared for:
Deactivated by default
Prepared for:
Deactivated by default
Discrete inputs
All analog values may be used as data sources for the analog outputs (refer to ╚═▷
“4.4.2.5 Analog Outputs”), the flexible limit monitoring (refer to ╚═▷ “4.5.5 Flexible
Limits”), and the controller setpoints (refer to ╚═▷ “4.4.4 Configure Controller”).
AnalogManager Variables
Groups 1 to 79 make available even more than the already arranged analog variables out
of the easYgen system.
AnalogManager Results
The description/name of these analog variables starts always with 'AM ...'.
The description/name of these analog variables starts always with 'AM ...'.
• power factor 1
01.86 Number pole slip Actual number of pole slip events for the analog manager.
• power factor 1
03.01 Busb1 volt. L-L [%] Busbar 1: voltage delta average [%]
• power factor 1
05.28 P derating (f) [%] Generator acive power derating dependent on mains ferquency, value of reduction
07.05 95: Fuel Filt.Diff. Pr. 95: Fuel Filter Differential Pressure
07.11 106: Air Intake Press. 106: Turbo Air Inlet Pressure
07.12 107: Air Filt1 Diff.Pr 107: Air Filter 1 Differential Pressure
07.39 1134: Cooler Therm.Op. 1134: Engine Charge Air Cooler Thermostat Opening
07.42 1137: Exh.Gas P.1 Temp 1137: Exhaust Gas Port 1 Temperature
07.43 1138: Exh.Gas P.2 Temp 1138: Exhaust Gas Port 2 Temperature
07.44 1139: Exh.Gas P.3 Temp 1139: Exhaust Gas Port 3 Temperature
07.45 1140: Exh.Gas P.4 Temp 1140: Exhaust Gas Port 4 Temperature
07.46 1141: Exh.Gas P.5 Temp 1141: Exhaust Gas Port 5 Temperature
07.47 1142: Exh.Gas P.6 Temp 1142: Exhaust Gas Port 6 Temperature
07.48 1143: Exh.Gas P.7 Temp 1143: Exhaust Gas Port 7 Temperature
07.49 1144: Exh.Gas P.8 Temp 1144: Exhaust Gas Port 8 Temperature
07.50 1145: Exh.Gas P.9 Temp 1145: Exhaust Gas Port 9 Temperature
09.04 4153: Exh.Gas T Avr.B1 4153: Exhaust Gas Temperature average Bank 1
09.05 4152: Exh.Gas T Avr.B2 4152: Exhaust Gas Temperature average Bank 2
09.08 1761: Aft1Exh.Tank1Lev 1761: Aftertreatment 1 Diesel Exhaust Fluid Tank 1 Level
09.09 3031: Aft1 Exh.Tank1 T 3031: Aftertreatment 1 Diesel Exhaust Fluid Tank 1 Temperature
09.10 4367: Aft1Exh.Tank2Lev 4367: Aftertreatment 1 Diesel Exhaust Fluid Tank 2 Level
09.11 4368: Aft1Exh.Tank2 T 4368: Aftertreatment 1 Diesel Exhaust Fluid Tank 2 Temperature
09.12 250: Total fuel used 250: Engine Total Fuel Used
09.16 3719: DPF 1 Soot Load 3719: Diesel Particulate Filter 1 Soot Load Percent
09.17 3720: DPF 1 Ash Load 3720: Diesel Particulate Filter 1 Ash Load Percent
09.18 3251: DPF Diff. P 3251: Aftertreatment 1 Diesel Particulate Filter Differential Pressure
10.04 Battery voltage [%] Battery voltage (percentage value related on battery voltage 24V)
10.11 System nominal P [%] Active nominal power in system (percentage value related on system rated active
power)
10.12 System real P [%] Total real power in system (percentage value related on system rated active
power)
10.13 Syst.res.real P [%] Reserve real power in system (percentage value related on system rated active
power)
10.65 React. power LSx [var] Reactive power LSx (Reactive mains power in own segment)
Mains delta voltage of the LSx with the smallest device number
Mains wye voltage of the LSx with the smallest device number
10.90 Generator load [kW] Generator load from the generators with closed GCB [kW]
11.01 Engine speed [%] Engine speed (percentage value related on engine rated speed)
11.04 Analog input D + [%] Analog input D + (percentage value related on battery voltage 24V)
21.01 CAN1 RPDO1.1 CAN1 RPDO1.1 (value index 3371, signed short)
21.02 CAN1 RPDO1.2 CAN1 RPDO1.2 (value index 3372, signed short)
21.03 CAN1 RPDO1.3 CAN1 RPDO1.3 (value index 3373, signed short)
21.04 CAN1 RPDO1.4 CAN1 RPDO1.4 (value index 3374, signed short)
21.05 CAN1 RPDO2.1 CAN1 RPDO2.1 (value index 3375, signed short)
21.06 CAN1 RPDO2.2 CAN1 RPDO2.2 (value index 3376, signed short)
21.07 CAN1 RPDO2.3 CAN1 RPDO2.3 (value index 3377, signed short)
21.08 CAN1 RPDO2.4 CAN1 RPDO2.4 (value index 3378, signed short)
21.09 CAN1 RPDO3.1 CAN1 RPDO3.1 (value index 3379, signed short)
21.10 CAN1 RPDO3.2 CAN1 RPDO3.2 (value index 3380, signed short)
21.11 CAN1 RPDO3.3 CAN1 RPDO3.3 (value index 3381, signed short)
21.12 CAN1 RPDO3.4 CAN1 RPDO3.4 (value index 3382, signed short)
21.13 CAN1 RPDO4.1 CAN1 RPDO4.1 (value index 3383, signed short)
21.14 CAN1 RPDO4.2 CAN1 RPDO4.2 (value index 3384, signed short)
21.15 CAN1 RPDO4.3 CAN1 RPDO4.3 (value index 3385, signed short)
21.16 CAN1 RPDO4.4 CAN1 RPDO4.4 (value index 3386, signed short)
21.17 CAN1 RPDO5.1 CAN1 RPDO5.1 (value index 3387, signed short)
21.18 CAN1 RPDO5.2 CAN1 RPDO5.2 (value index 3388, signed short)
21.19 CAN1 RPDO5.3 CAN1 RPDO5.3 (value index 3389, signed short)
21.20 CAN1 RPDO5.4 CAN1 RPDO5.4 (value index 3390, signed short)
Note: In future releases (higher than 2.10-0) the variables 24.05-24.08 will be write-
protected with code level CL1.
24.01 Free analog value 1 Free analog value 1 (value index 587, signed short)
24.02 Free analog value 2 Free analog value 2 (value index 588, signed short)
24.03 Free analog value 3 Free analog value 3 (value index 589, signed short)
24.04 Free analog value 4 Free analog value 4 (value index 590, signed short)
24.05 Free analog value 5 Free analog value 5 (value index 591, signed short)
24.06 Free analog value 6 Free analog value 6 (value index 592, signed short)
24.07 Free analog value 7 Free analog value 7 (value index 593, signed short)
24.08 Free analog value 8 Free analog value 8 (value index 594, signed short)
User defined max. output value = 100% means, that the 100% refer to the generator
rated voltage. If parameter “Source value at maximal output” is set to “+100.00%” this
will result in that the Analog output delivers its maximum output value if for example
400V Phase-phase are the nominal value and 400V are measured. If only 200 V are
measured this will result in an analog output value of 50% end scale.
User defined max. output value = 100% means, that the 100% refer to the mains rated
voltage. If parameter “Source value at maximal output” is set to “+100.00%” this will
result in that the Analog output delivers its maximum output value if for example 400V
are the nominal value and 400V are measured. If only 200 V are measured this will result
in an analog output value of 50% end scale.
User defined max. output value = 100% means, that the 100% refer to the nominal
frequency. If parameter “Source value at maximal output” is set to “+100.00%” this will
result in that the Analog output delivers its maximum output value if a for example 50Hz
are the nominal value and 50V are measured.
User defined max. output value = 100% means, that the 100% refer to the rated active
power value. If parameter “Source value at maximal output” is set to “+100.00%” this
will result in that the Analog output delivers its maximum output value if a for example
1000kW are the nominal value and 1000kW are measured. If only 200kW are measured
this will result in an Analog output value of 20% end scale.
User defined max. output value = 100% means, that 50% refers to power factor 1.00.
If the power factor moves to lagging (inductive) the output goes to 100%. If the power
factor goes to leading (capacitive), the output goes to 0%.
Examples:
0,05% = -0,001(capacitive)
99,95% = 0,001(inductive)
100% = 0% = cosphi 0
User defined max. output value = 100% means, that the 100% refer to the rated
generator current. If parameter “Source value at maximal output” is set to “+100.00%”
this will result in that the Analog output delivers its maximum output value if a for
example 1000A are the nominal value and 1000A are measured. If only 200A are
measured this will result in an Analog output value of 20% end scale.
User defined max. output value = 100% means, that the 100% refer to the rated mains
current. If parameter “Source value at maximal output” is set to “+100.00%” this will
result in that the Analog output delivers its maximum output value if a for example 1000A
are the nominal value and 1000A are measured. If only 200A are measured this will result
in an Analog output value of 20% end scale.
Pickup speed
User defined max. output value = 100% means, that the 100% refer to the parametrized
nominal speed. If parameter “Source value at maximal output” is set to “+100.00%” this
will result in that the Analog output delivers its maximum output value if a for example
1500 RPM are the nominal value and 1500 RPM are measured. If only 750 RPM are
measured this will result in an Analog output value of 50% end scale.
User defined max. output value = 100% means, that the 100% refer to a voltage of 24.0
Volts . If parameter “Source value at maximal output” is set to “+100.00%” this will result
in that the Analog output delivers its maximum output value if a for example 24.0 Volts
are the nominal value and 24.0 Volts are measured. If only 12.0 Volts are measured this
will result in an Analog output value of 50% end scale.
User defined max. output value = 100% means, that the 100% refer to a fixed value of
10000. If parameter “Source value at maximal output” is set to “+100.00%” this will
result in that the Analog output delivers its maximum output value if a for example
“10000” is delivered by GAP.
User defined max. output value = 100% means, that the 100% refer to the nominal
busbar 1 voltage. If parameter “Source value at maximal output” is set to “+100.00%”
this will result in that the Analog output delivers its maximum output value if a for
example 400V are the nominal value and 400V are measured.
The analog input values refer to the display value format (refer to parameter ╚═▷ 1035).
Delimiters like decimal points or commas are ignored. If the display value format is 0.01
bar for example, a value of 5 bar corresponds with 00500.
• If a value of 20 °C (or below) is measured, the analog output issues its lower limit
(i.e. 0 mA).
• If a value of 100 °C (or above) is measured, the analog output issues its upper limit
(i.e. 20 mA).
• If a value of 60 °C is measured, the analog output issues 50% of its upper limit (i.e.
10 mA).
• If a value of 84 °C is measured, the analog output issues 80% of its upper limit (i.e.
16 mA).
Analog input type Display value format Example value Example format
VDO 120 °C 1 °C 69 °C 69
VDO 150 °C 1 °C 73 °C 73
5518 AM Frequency SP1[Hz] Analog1 ("A1 =") 05.51 Internal f setp1 [Hz]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5519 AM Frequency SP2[Hz] Analog1 ("A1 =") 05.52 Internal f setp2 [Hz]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5539 AM ActPower SP1 [kW] Analog1 ("A1 =") 05.54 Internal P setp1 [kW]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5540 AM ActPower SP2 [kW] Analog1 ("A1 =") 05.55 Internal P setp2 [kW]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5606 AM ActPower SP3 [kW] Analog1 ("A1 =") 05.80 Internal P setp3 [W]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5609 AM ActPower SP4 [kW] Analog1 ("A1 =") 05.84 Internal P setp4 [kW]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5638 AM PF/var SP1[-/kvar] Analog1 ("A1 =") 05.10 Intern. PF setp1 [%]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5639 AM PF/var SP2[-/kvar] Analog1 ("A1 =") 05.11 Intern. PF setp2 [%]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5618 AM Voltage SP1 [V] Analog1 ("A1 =") 05.57 Internal V setp1 [V]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5619 AM Voltage SP2 [V] Analog1 ("A1 =") 05.58 Internal V setp2 [V]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5577 AM PID1 setpoint Analog1 ("A1 =") 05.75 Int. PID1 setpoint
Operators
Operators-Unary1 —————
Operators-Unary2 —————
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5590 AM PID2 setpoint Analog1 ("A1 =") 05.76 Int. PID2 setpoint
Operators
Operators-Unary1 —————
Operators-Unary2 —————
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5676 AM PID3 setpoint Analog1 ("A1 =") 05.77 Int. PID3 setpoint
Operators
Operators-Unary1 —————
Operators-Unary2 —————
Operators
Operators-Unary1 —————
Operators-Unary2 —————
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5200 AM Data source AO1 Analog1 ("A1 =") 11.03 Speed bias [%]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
5214 AM Data source AO2 Analog1 ("A1 =") 11.02 Voltage bias [%]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
10237 AM Data source ext.AO1 Analog1 ("A1 =") 11.03 Speed bias [%]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
10247 AM Data source ext.AO2 Analog1 ("A1 =") 11.03 Speed bias [%]
Operators
Operators-Unary1 —————
Operators-Unary2 —————
10257 AM Data source ext.AO3 Analog1 ("A1 =") 11.03 Speed bias [%]
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
10267 AM Data source ext.AO4 Analog1 ("A1 =") 11.03 Speed bias [%]
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
Operators-Unary1 —————
Operators-Unary2 —————
6026 + (N x AM FlexLim 10 + N source ((N = Function Type ("Type =") Pass through
(+10)) 1, 2, ...))
Logic1 "L1" 02.01 LM FALSE
... ...
Logic2 "L2" 02.01 LM FALSE
Operators-Unary1 —————
Operators-Unary2 —————
7705 AM Customer screen 1.4 Function Type ("Type =") Pass through
8891 AM Engine speed Analog1 ("A1 =") 11.51 Engine speed [rpm]
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
8893 AM Engine oil pressure Analog1 ("A1 =") 07.07 100:Engine Oil Press.
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
8897 AM Engine fuel level Analog1 ("A1 =") 06.03 Analog input 3
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
8899 AM Engine batt.voltage Analog1 ("A1 =") 10.54 Battery voltage [V]
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
8901 AM Engine coolant temp. Analog1 ("A1 =") 07.15 110:Eng.Coolant Temp.
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
9059 AM Consumer load [kW] Analog1 ("A1 =") 02.74 Mains act.power [W]
Operators 5
Operators-Unary1 —————
Operators-Unary2 —————
The unit is waiting for a start signal in Automatic operating mode and no alarm of
class C, D, E, or F is present.
Before the engine is started the signal "aux. services prerun" is enabled, so that all
required equipment which is necessary for the operation of the engine can be
initialized, started or switched.
The no load operation is performed prior to the stopping of the engine. The no load
operation is utilized to cool the engine.
To prevent the starter from being damaged by an engine that is rotating, a crank
protection delay is active to ensure that the engine has time to stop rotating.
After the engine has stopped, auxiliary operations are enabled. These operations
ensure that required equipment which is necessary for the operation of the engine
continues to run (i.e. electric cooling fan).
Start - Pause 13207 Start pause while starting the engine is active
If the engine could not be started, the controller will pause for the configured time
prior to attempting to issuing a start command again.
The engine will be stopped. The engine stop delay will be started when ignition
speed has been fallen below. A restart is only possible if the engine stop delay has
been expired.
After the "Prerun auxiliary operation" expires, the engine is started according to
the configured start logic (Diesel or gas engine). When the start sequence is
active, various relays are enabled and representative signals are passed via the
CAN bus to a secondary engine control.
After firing speed has been exceeded, the engine monitoring delay timer starts.
This message is displayed during this period.
The real power setpoint is limited to the warm up power limit for the configured
warm up time.
After the purging operation and before the fuel solenoids opened.
Before the fuel solenoid opens and the ignition of the gas engine is energized the
remaining fuel, that may be present in the combustion chamber, will be removed
by a purging operation. The starter turns the engine without enabling the ignition
for a specified time to complete the purging operation. After the purging process,
the ignition is energized.
After the control unit detects that a mains fault has occurred, the engine is started
after the emergency delay timer expires. The MCB is opened, the GCB is closed,
and the generator set assumes the load. If the generator set is already running,
During regulation kvar at the interchange point the maximum allowed excitation
current is reached.
Loading generator 13258 The generator power will be increased to the setpoint
The generator power will be increased to the configured setpoint with a rate
defined by the power control setpoint ramp.
The real power setpoint is increased with the configured rate after synchronizing
the generator in interchange transition mode. After the mains have been
unloaded, the MCB will be opened.
The generator power will be decreased after a stop command has been issued
with a rate defined by the power control setpoint ramp before the GCB will be
opened.
GCB - > MCB Delay 13261 GCB - MCB delay time is active
If the breaker logic is configured to Open Transition and a transfer from generator
to mains supply is initiated, the transfer time delay will start after the replay "GCB
is open" is received. The MCB close command will be issued after the transfer time
has expired.
MCB dead bus close 13210 Dead bus closing of the MCB
The MCB is closed onto the de-energized busbar. The measured busbar voltage is
below the configured dead bus detection limit.
MCB - > GCB Delay 13262 MCB - GCB delay time is active
If the breaker logic is configured to Open Transition and a transfer from mains to
generator supply is initiated, the transfer time delay will start after the reply "MCB
is open" is received. The GCB close command will be issued after the transfer time
has expired.
When the control unit detects that the mains fault is no longer present and power
has been restored, the mains settling timer begins counting down. If the mains are
stable after the expiration of the timer (the mains voltage has not fallen below or
risen over the configured monitoring limits), the load is transferred from the
generator supply to the mains supply.
GCB dead bus close 13209 Dead bus closing of the GCB
The GCB is closed onto the de-energized busbar. The measured busbar voltage is
below the configured dead bus detection limit.
The frequency / voltage regulation for synchronization is disabled. The close pulse
is disabled.
General notes
The event history is a 1000 entry FIFO (First In/First Out) memory for logging alarm events
and operation states of the unit. As new event messages are entered into the history, the
oldest messages are deleted once 1000 events have occurred.
Make sure to have set the appropriate code level to reset the event history.
If you have not entered the correct password for the required code level, the parameters
for resetting the event history are not available (for additional information refer to ╚═▷
“4.3.4.1 Password System - Parameter Overview”).
• ToolKit: Click the »Clear all « button at [STATUS MENU / Diagnostic: Event History].
(To read Event History go to: [Next Page / Diagnostic / Event History])
Gen excitation lim. 13288 The limit of the generator's excitation is exceeded
Alarm class Visible in the LED "Alarm" Relay Shut-down Engine blocked
display "Command: engine until ack.
& horn open GCB" sequence has
been
performed
A Yes No No No No
Warning Alarm This alarm does not interrupt the unit operation. A message output without a centralized alarm
occurs:
• Alarm text.
B Yes Yes No No No
Warning Alarm This alarm does not interrupt the unit operation. An output of the centralized alarm occurs and the
command variable 3.05 (horn) is issued.
Shutdown Alarm With this alarm the GCB is opened and the engine is stopped. Coasting occurs.
• Alarm text + flashing LED "Alarm" + Relay centralized alarm (horn) + GCB open + Coasting +
Engine stop.
Shutdown Alarm With this alarm the GCB is opened and the engine is stopped. Coasting occurs.
• Alarm text + flashing LED "Alarm" + Relay centralized alarm (horn) + GCB open + Coasting +
Engine stop.
Shutdown Alarm With this alarm the GCB is opened immediately and the engine is stopped.
• Alarm text + flashing LED "Alarm" + Relay centralized alarm (horn) + GCB open + Engine stop.
Alarm class Visible in the LED "Alarm" Relay Shut-down Engine blocked
display "Command: engine until ack.
& horn open GCB" sequence has
been
performed
Shutdown Alarm With this alarm the GCB is opened immediately and the engine is stopped.
• Alarm text + flashing LED "Alarm" + Relay centralized alarm (horn) + GCB open + Engine stop.
Control No No No No No
Control Signal This signal issues a control command only. It may be assigned to a discrete input for example to get a
control signal, which may be used in the LogicsManager. No alarm message and no entry in the alarm
list or the event history will be issued. This signal is always self-acknowledging, but considers a delay
time and may also be configured with an engine delay.
CAUTION!
If an alarm of class C, D, or E is present and the GCB cannot be opened, the engine will
not be stopped. This can only be achieved by enabling GCB monitoring (parameter ╚═▷
2600) with the alarm class configured to "F" (parameter ╚═▷ 2601).
If an alarm has been configured with a shutdown alarm that has been enabled to self-
acknowledge, and has been configured as engine delayed the following scenario may
happen:
• The alarm shuts down the engine because of its alarm class.
• Due to the engine stopping, all engine delayed alarms are ignored.
• The alarm will self-acknowledge and clear the fault message that shut the engine
down.
This prevents the fault from being analyzed. After a short delay, the engine will
restart.
• After the engine monitoring delay expires, the fault that originally shut down the
engine will do so again.
9.5.5.1 No alarm
The generator frequency has exceeded the limit value 1 for generator
overfrequency.
The generator frequency has exceeded the limit value 2 for generator
overfrequency.
The generator frequency has fallen below the limit value 1 for generator
underfrequency.
The generator frequency has fallen below the limit value 2 for generator
underfrequency.
The generator voltage has exceeded the limit value 1 for generator overvoltage.
The generator voltage has exceeded the limit value 2 for generator overvoltage.
The generator voltage has fallen below the limit value 1 for generator
undervoltage.
The generator voltage has fallen below the limit value 2 for generator
undervoltage.
The generator current has exceeded the limit value 1 for the generator
overcurrent.
The generator current has exceeded the limit value 2 for the generator
overcurrent.
The generator current has exceeded the limit value 3 for the generator
overcurrent.
The generator current has exceeded the limit based on the inverse time
overcurrent setting.
Gen. rev / red. pwr.1 2262 Generator reverse power, limit value 1 / Generator reduced power, limit value 1
The generator power has exceeded the limit value 1 for generator reverse power /
generator reduced power.
Gen. rev / red. pwr.2 2263 Generator reverse power, limit value 2 / Generator reduced power, limit value 2
The generator power has exceeded the limit value 1 for generator overload in
islanded operation (MCB is open).
The generator power has exceeded the limit value 2 for generator overload in
islanded operation (MCB is open).
The generator power has exceeded the limit value 1 for generator overload in
mains parallel operation.
The generator power has exceeded the limit value 2 for generator overload in
mains parallel operation.
The generator current has exceeded the limit value 1 for generator unbalanced
load.
The generator current has exceeded the limit value 2 for generator unbalanced
load.
The measured or calculated ground current has exceeded the limit value 1 for the
generator ground current.
The measured or calculated ground current has exceeded the limit value 2 for the
generator ground current.
The generator rotating field does not correspond with the configured direction.
The power factor limit 1 has been exceeded at the generator towards inductive.
The power factor limit 2 has been exceeded at the generator towards inductive.
The power factor limit 1 has fallen below at the generator towards capacitive.
The power factor limit 2 has fallen below at the generator towards capacitive.
The deviation between the generator power and the active power setpoint has
exceeded the limit.
The easYgen failed to reduce the generator power below the configured unload
limit.
A pole slip was detected during running the generator mains parallel.
Busbar voltage and frequency are not in range according to the configured limits.
The mains frequency has exceeded the limit value 1 for mains overfrequency.
The mains frequency has exceeded the limit value 2 for mains overfrequency.
The mains frequency has fallen below the limit value 1 for mains underfrequency.
The mains frequency has fallen below the limit value 2 for mains underfrequency.
The mains voltage has exceeded the limit value 1 for mains overvoltage.
The mains voltage has exceeded the limit value 2 for mains overvoltage.
The mains voltage has fallen below the limit value 1 for mains undervoltage.
The mains voltage has fallen below the limit value 2 for mains undervoltage.
A mains df / dt, which has exceeded the configured limit, has occurred. Triggering
this monitoring function causes the mains decoupling function to trigger.
Decoupling GCB < - > 5147 Decoupling GCB < - > MCB
MCB
During decoupling there was a change over from the preferred breaker to the
other.
The mains rotating field does not correspond with the configured direction.
The mains import power has exceeded or fallen below the limit value 1 for mains
import power.
The mains import power has exceeded or fallen below the limit value 2 for mains
import power.
The mains export power has exceeded or fallen below the limit value 1 for mains
export power.
The mains export power has exceeded or fallen below the limit value 2 for mains
export power.
Mains PF lagging 1 2985 Mains power factor lagging exceeded, limit value 1
The power factor limit 1 has been exceeded at the mains interchange point
towards inductive.
Mains PF lagging 2 2986 Mains power factor lagging exceeded, limit value 2
The power factor limit 2 has been exceeded at the mains interchange point
towards inductive.
Mains PF leading 1 3035 Mains power factor leading exceeded, limit value 1
The power factor limit 1 has fallen below at the mains interchange point towards
capacitive.
Mains PF leading 2 3036 Mains power factor leading exceeded, limit value 2
The power factor limit 1 has fallen below at the mains interchange point towards
capacitive.
The deviation between the import / export power and the active import / export
power setpoint has exceeded the limit.
Mains volt. incr. 8834 Mains voltage increase monitor has tripped
The generator reactive power has exceeded the limit with delay time 1.
The generator reactive power has exceeded the limit with delay time 2.
The engine speed has exceeded the limit value 1 for engine overspeed.
The engine speed has exceeded the limit value 2 for engine overspeed.
The engine speed has fallen below the limit value 1 for engine underspeed.
The engine speed has fallen below the limit value 2 for engine underspeed.
The easYgen expects the generator to be running but a sudden underrun of the
ignition speed has been detected.
There is still recognized a turning engine (by electrical frequency or speed signal)
even the engine is stopped.
The generator set has failed to start after the configured number of attempts.
Cyl.tmp.wire brk. 14584 Cylinder temperature monitoring has detected sensor wire as broken
The generator run time has exceeded the configured number of days since the last
maintenance call RESET.
The generator run time has exceeded the configured number of operating hours
since the last maintenance call RESET.
Oper. range failed 1 2665 Check 1: The easYgen wants close the GCB, but the generator is not within its
operating range.
Oper. range failed 2 2666 Check 2: The easYgen wants close the GCB, but the busbar is not within the
generator operating range.
• Busbar is undefined (Busbar not dead AND not within the operation range)
Oper. range failed 3 2667 Check 3: The easYgen wants close the GCB in breaker transistion mode "Open
transition" with GCB and MCB open status. In this condition the busbar is expected
as dead, but there is still voltage on busbar measured.
Oper. range failed 4 2668 Check 4: The easYgen wants close the GCB onto a dead busbar. The device cannot
close the breaker onto busbar, because there is minimum one neighbor device
recognized with a GCB closed.
Oper. range failed 5 2669 Check 5: The easYgen wants synchronize the GCB, the MCB is closed, but the
mains or busbar is not within its operating range.
Oper. range failed 6 2670 Check 6: The easYgen wants close the GGB, but the generator minimum power is
not reached.
Oper. range failed 7 2671 Check 7: The easYgen wants close the GGB in the Open Transition Mode, but the
generator minimum power is not reached.
Oper. range failed 12 2676 Check 12: The easYgen checks the phase rotation of generator, busbar and mains.
If the phase rotation of all systems does not match and a synchronisation shall be
executed this will occur. (Synchronisation is blocked)
The easYgen has attempted to close the GCB the configured maximum number of
attempts and failed.
The easYgen has attempted to open the GCB within the configured time and
failed.
The easYgen has failed to synchronize the GCB within the configured
synchronization time.
Generator current is measured even if the mains repliy signals GCB open.
The easYgen has attempted to close the MCB the configured maximum number of
attempts and failed. Depending on the configuration, the easYgen will continue to
attempt to close the GCB as long as the conditions for closing the MCB are
fulfilled.
The easYgen is still receiving the reply MCB closed" after the MCB open monitoring
timer has expired.
The easYgen has failed to synchronize the MCB within the configured
synchronization time.
There is a mains current measured even the MCB reply signals MCB open.
The number of closed MCBs is different to the number of easYgen devices in the
same segment.
No Receive Process Data Object ( RPDO) is received within the configured time.
No message is received from the external expansion board (Node-ID) within the
configured time.
No Receive Process Data Object ( RPDO) is received within the configured time.
The ECU sends a red stop lamp signal. There is a critical failure detected in the
ECU.
The ECU sends a amber warning lamp signal. There is a warning failure detected in
the ECU.
The easYgen has detected that not all LDSS parameters are configured identically
at all participating units.
Refer in the manual to the chapter "Multi-unit Parameter Alignment" to see the
relevant LDSS parameter.
CAN EthA redundancy 2439 The Load share interface CAN / Ethernet A redundancy is lost.
The device warns that the Ethernet redundancy CAN / EthA is lost. Check the
communication diagnostic screen of the layer 1.
40 flexible limits. This text may be assigned customer defined. The Indication here
is the default text.
9.5.5.15 Wire Break Monitoring (of internal and external analog inputs)
Analog input x Wb: Analog input 1-3, wire break (internal analog inputs)
Wb: External Analog input 1-16, wire break (external analog inputs)
During the measurement of the analog input a wire break was detected. The text
begins with Wb: for wire break. The second part of the text may be assigned
customer defined. The Indication here is the default text.
16 free configurable Alarms. The alarm text is configurable. The indication here is
the default text.
The battery voltage has exceeded the limit value 2 for battery overvoltage.
The battery voltage has fallen below the limit value 1 for battery undervoltage.
The battery voltage has fallen below the limit value 2 for battery undervoltage.
One or more of the generator voltages are wrong wired (detected by plausibility
checking of frequencies).
One or more of the busbar voltages are wrong wired (detected by plausibility
checking of frequencies).
One or more of the mains voltages are wrong wired (detected by plausibility
checking of frequencies).
PV disconnect level 8927 The PV source level drives generator into revers power.
The generator power has reached a reverse power with a critical rate. The PV
source penetration is interrupted.
The own 4105 relevant mains measurement is different to the 4105 partner.
The own 4105 relevant parameter are different to the 4105 partner.
9.6 Formulas
Temperature
Pressure
The following formulas are used by the load-dependent start/stop function to determine
whether a genset is to be started or stopped.
Abbreviations
Abbreviation Parameter
PGN real active Momentary active generator real power on the busbar
Preserve islanded 5760 Minimum permissible reserve power on busbar in islanded operation
Preserve parallel 5768 Minimum permissible reserve power on busbar in mains parallel
operation
Pmax. load islanded 5762 Maximum permissible generator load in islanded operation
Pmin. load islanded 5763 Minimum permissible generator load in islanded operation
Pmax. load parallel 5770 Maximum permissible generator load in mains parallel operation
Pmin. load parallel 5771 Minimum permissible generator load in mains parallel operation
Task Formula
Islanded Operation
Changing the Engine Combination to Increase Rated Power PGNreal active + Preserve islanded > Prated active
Changing the Engine Combination to Reduce Rated Power PGN real active + Preserve islanded + Physteresis IOP < Prated
active
Starting the First Engine Combination (no engine supplies PMNsetpoint – PMN real + PGN real active > PMOP minimum
the busbar)
Changing the Engine Combination to Increase Rated Power PMNsetpoint – PMN real + PGN real active + Preserve parallel >
Prated active
Changing the Engine Combination to Reduce Rated Power PMNsetpoint – PMNreal + PGNreal active + Preserve parallel +
Physteresis MOP < Prated active
Task Formula
Stopping the Last Engine Combination (load close to PMN setpoint – PMN real + PGN real active < PMOPminimum –
minimum load) Physteresis MOP
Task Formula
Islanded Operation
Changing the Engine Combination to Increase Rated Power PGN real active > Pmax. load islanded
Changing the Engine Combination to Reduce Rated Power PGN real active < Pmin. load islanded
Starting the First Engine Combination PMNsetpoint – PMN real + PGN real active > PMOPminimum
Changing the Engine Combination to Increase Rated Power PGNreal active > Pmax. load parallel
Changing the Engine Combination to Reduce Rated Power PGN real active < Pmin. load parallel
Stopping the Last Engine Combination (load close to PMN setpoint – PMN real + PGN real active < PMOPminimum –
minimum load) Physteresis MOP
LDSS dynamic
Dynamic characteristic = [(max. generator load – min. generator load) * dynamic] + (min. generator
load)
Moderate = 50 %
dynamic
High dynamic = 75 %
OC Occurrence Count
CB Circuit Breaker
CL Code Level
CT Current Transformer
DI Discrete Input
GC Group Controller
GCP Woodward device series (Genset Control) - not preferred for new
design!
HMI Human Machine Interface e.g., a front panel with display and
buttons for interaction
LM LogicsManager©
PF Power Factor
PV Photovoltaic
NC Neutral Contactor
V Voltage
I Current
P Real power
Q Reactive power
S Apparent power
Index
A
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 542█
...........
BDEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 484█
..........
Battery
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561,
. . . . 562█
...........
CAN
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 546,
. . . . 547█
...........
Droop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321█
..........
Engine
Overspeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 452█
...........
Underspeed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454█
...........
Engine/Generator
Engine/Mains
Ethernet
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 559█
...........
GCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526█
...........
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261█
...........
Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 529█
...........
Generator
Overfrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413█
...........
Overvoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406█
...........
Underfrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 415█
...........
Undervoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408█
...........
HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44█
.........
IOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387█
..........
LDSS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 377█
...........
MCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530█
...........
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 268█
...........
MOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393█
...........
Mains
Decoupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 474█
..........
Underfrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 487█
...........
Undervoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 491█
...........
Measurement
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 572█
..........
Modbus
Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 801█
...........
PV Photovoltaic
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355█
...........
Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38█
.........
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37█
.........
Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35█
.........
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 568█
...........
Temperature
Toolkit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147█
..........
Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37█
.........
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37█
..........