Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
3AST004143R0501
EN
EFFECTIVE: 24.03.2011
Table of Content
Table of Content
Safety instructions
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Fault tracing
Fault signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Alarm signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Safety instructions
Overview
These safety instructions must be followed when installing, operating and servicing
the DCS800. If neglected, physical injury and death may follow, or damage may
occur to the DC converter, the motor and driven equipment. The material in this
chapter must be studied before attempting any work on, or with the unit.
Warnings
Readers are informed of situations that can result in serious physical injury and/or
serious damage to equipment with the following symbols:
Notes
Readers are notified of the need for special attention or additional information
available on the subject with the following symbols:
CAUTION! Caution aims to draw special attention to a particular issue.
Note: Note gives additional information or points out more information
available on the subject.
WARNING! All electrical installation and maintenance work on the DCS800 should
be carried out by a qualified electrician.
The DCS800 motor cable terminals are at a dangerously high voltage when mains
power is applied, regardless of motor operation.
There can be dangerous voltages inside the DCS800 from external control circuits
when the DCS800 mains power is turned off. Exercise appropriate care when
working with the unit. Neglecting these instructions can cause physical injury and
death.
WARNING! The DCS800 introduces electric motors, drive train mechanisms and
! driven machines to an extended operating range. It should be determined from the
outset that all equipment is up to these conditions.
All insulation tests must be carried out with the DCS800 disconnected from the
cabling. Operation outside the rated capacities should not be attempted. Neglecting
these instructions can result in permanent damage to the DCS800.
Overview
This chapter describes the purpose, contents and the intended audience of this
manual. It also explains the conventions used in this manual and lists related
publications. This DCC800 Firmware Manual Supplement is compatible with
DCC800 Application Software version 1.40 (signal 4.12).
The DCC800 1.40 complies with the DCS800 firware version 3.6
Software identification of DCS800 CraneDrive:
Motor Control Firmware 3.6 (signal 4.01, Firmware version)
+ Crane Application software 1.40 (signal 4.12, Application version)
Reader
The audience for this manual is expected to have:
• Knowledge of standard electrical wiring practices, electronic components, and
electrical schematic symbols.
• Minimal knowledge of ABB product names and terminology.
Content
• The Safety instructions describe the formats for various warnings and notations
used in this manual. This chapter also states the general safety instructions which
must be followed.
• Introduction to the manual, the chapter you are reading now, introduces you to
the DCC800 Firmware Manual Supplement and conventions used throughout the
manual.
• Crane program description defines the Crane program by describing the included
crane specific functions and presenting them in a block diagram.
• Signals and parameters describes the actual signals and parameters of the drive.
• Fault tracing lists the fault and alarm messages with the possible causes and
remedies.
• Appendix A - Complete signal and parameter list and default settings
• Appendix B - Signal and parameter cross reference list: DCC600 to DCC800
• Appendix C - Signals and parameters, overwritten by the DCC800
• Appendix D - User I/O interface diagrams.
Revision history
The table below describes the updates of the different document revisions.
Revision Description Issued date/By
External connections
The following connection example is applicable when the crane program is used in
Fieldbus mode.
External connections in Fieldbus mode
Term inal
IOB-21 & Function
CON-4
Term inal
+24V Com. IOB-21 Function
X5:3 DO 6 ”programmable”
X5:4 (transistor output)
X5:5 DO 7 ”programmable”
X5:6 (transistor output)
FIELDBUS
DataSet1,
Word 1
Bit 2 and 4 EXTERNAL SPEED CONTROLLER
MAX
DataSet 1, M1SpeedMin 20.01
23.01 SPEED REF SELECTOR
Word 2 M1SpeedMax 20.02
Power
SELECT optimiza-
DS1.1 TORQ. CTRL tion SPEED CONTROL
Bit 7
KEYPAD Group 24
DataSet 1,
TORQUE REF
Word 3
TORQUE CONTROLLER
SPEED CORR.
DS3,2 TorqMax 20.05
LOC
REM
EXTERNAL
ON/START
KEYPAD
One DI is used for connecting slowdown limit switches in series, and one DI is used
for Fast stop order from mechanical overload and slack rope indications.
The mechanical brake is controlled from e.g. DO4 and the acknowledgement is
connected to e.g. DI6.
Two analogue and five digital output signals are available on terminal blocks. Default
signals for the Actual Signal Display Mode of the control panel are SPEED,
TORQUE and CURRENT.
The feedback data through Fieldbus communication: between drive and PLC is
available also in stand alone mode by enabling parameter CommModule (98.02).
Operation diagram for Stand alone mode
LOC 1470 rpm Reference and Start/Stop and
1470 rpm Direction commands are given
Input 400 V
Power 40 A
from the control panel. To
Ext. Controls change to External ctrl, press
DIR 11:21:01 P MENU LOC REM key at standstill.
~ rpm Speed
rpm
Torque
Relay
= REM 1470 rpm Speed reference is read from
Outputs
1470 rpm analogue input AI1
400 V (Terminal Block X21). On/
40 A
Start and Direction com-
Brake RESET 11:21:04 P MENU mands are generated from
Motor M
=
External connections
The following connection example is applicable when the Crane program with Stand
alone control mode and Joystick control is used.
External DI connections to DCC800 in Stand alone mode, Joystick control
Terminal Function
IOB-21 &
CON-4
X6:1 DI 1 Converter Fan ackn. (def.)
X6:2 DI 2 Zero Pos
X6:3 DI 3 Main Contactor Ackn. (def.)
X6:4 DI 4 Electrical disconnect (fixed)
X6:5 DI 5 Programmable
X6:6 DI 6 Brake ackn. (def.)
X6:7 DI 7 Start Dir A (Fixed)
X6:8 DI 8 Start Dir B (Fixed)
X7:3,4 +48 V IOB-21: 48 V DC, max 50 mA
X6:9 +48 V CON-4: 48 V DC, max 50 mA
Terminal Function
24 VDC RDIO-xx
X11:1 DI 9 Slow down limits = Slowdown-N
X11:2
X12:1 DI 10 Fast stop-N
X12:2
X12:3 DI11 STEP REF 2
X12:4
0 VDC
Terminal Function
24 VDC RDIO-xx
X11:1 DI 12 STEP REF 3
X11:2
X12:1 DI 13 STEP REF 4
X12:2
X12:3 DI14
X12:4
0 VDC
Terminal Terminal
IOB-3 CON-4 Function
Terminal
+24V Com. IOB-21 Function
X5:3 DO 6 ”programmable”
X5:4 (transistor output)
X5:5 DO 7 ”programmable”
X5:6 (transistor output)
STAND
ALONE
LOC
REM
EXTERNAL ON/START
KEYPAD
66 TORQUE PROVING *
66.03 Torq Prov Ref 20 %
66.04 Regen Test Sel False *
RUNNING
RESET SYNC RDY 7.10 bit 13 7.02 bit 11 RESET SYNC RDY
Parameter Sp Der Blk Lev (62.04), rate of actual speed change in % per second,
can be set so that it blocks the protection during acceleration/deceleration. As long
as the actual rate of change (derivative) of the motor speed during acceleration/
deceleration is faster than the setting of parameter Sp Der Blk Lev, the torque fault
protection is blocked.
Example: The acceleration ramp time is set to e.g. 5 seconds. With Sp Der Blk Lev
set to 7.5 s, the drive will not trip for torque fault if reaching torque limit during
deceleration, as long as the actual deceleration time (100–0%) is below
7.5 seconds.
To use FAST STOP 11 for: … set FastStop Type 11 (63.01) equal to:
Fast stop 1 FAST STOP 1
Fast stop 2 FAST STOP 2
Fast stop 3 FAST STOP 3
When using Stand alone mode, the parameter FastStop Type 12 (63.02) can be
programmed to give anyone of the three types of fast stop. The fast stop is activated
by digital input, e.g. DI 10 (FAST STOP-N) = “0” (see function module Crane (64) on
page 20 for more details).
For settings of FastStop Type 12 (63.02), see FastStop type11 (63.01) above.
Crane (64)
General
Stand alone default I/O signal interface and functions.
Signal Input Function
(DI set in Group60)
ZERO POS DI2 Zero position contact from joystick
START DIR A DI7 (fixed) Direction A (pos.) from joystick, to be connected
in series with Stop Lim A and contact from
mechanical overload protection equipment
START DIR B DI8 (fixed) Direction B (neg.) from joystick, to be connected
in series with Stop Lim B and contact from slack
rope protection equipment
SLOWDOWN-N Ext DI9 Slow down limits A and B. Direction from START
DIR inputs. After a power down (CPU init), only
slow speed is possible until this input is "1"
FAST STOP-N Ext DI10 Fast stop signal to the converter
SPEED REF AI1 (fixed) Speed reference signal from joystick.
0–10 V for 0–100 %
TORQ REF AI2 (fixed) Torque reference signal from joystick. 0–10 V for
0 to maximum torque reference (maximum set
with parameter Torq ref scale (64.09))
SPEED CORR AI3 (fixed) Speed correction signal from e.g. electric shaft
control unit. 0 – (+/-)10 V for 0 – (+/-)100% speed
correction signal
BRAKE LIFT DO4 Output to brake contactor
WATCHDOG-N DO5 Closed contact indicates "healthy" drive. Open
contact makes hardwired emergency stop; main
contactor(s) off and brakes on.
START
The drive starts when one of the signals START DIR A or START DIR B is "1" and
ZERO POS is "0", unless any of the above listed fault conditions occur. The
sequence starts with a magnetising phase = ON (unless already magnetised) which
is immediately followed by the reference ramp-up.
SLOWDOWN
The SLOWDOWN function allows for the drive to decelerate to a preset slow speed
when, for instance, a limit switch connected to a digital input is actuated.
Single Direction SlowDown
a) One digital input used to activate the slowdown function:
When the parameter SlowDownMode (64.19) is set to SingleDir, and if the selected
SLOWDOWN-N (60.03) input (for instance Ext DI9) is set to zero, then the speed
decelerates to the preset level – SlowDownSpeedRef (64.07) .
The converter remembers the motion direction and allows full speed in the opposite
direction, as long as the auxilliary supply voltage (CON-4 board supply) is not
switched off.
If this supply voltage is switched off and the input SLOWDOWN-N = "0", then only
the preset slow speed is allowed in both direction.
If SLOWDOWN-N goes from "1" to "0" during standstill, then only the preset slow
speed is allowed in both directions.
b) Two digital inputs used to activate the slowdown function:
When the parameter SlowDownMode (64.19) is set to SingleDir, and if the selected
SLOWDOWN-N (60.03) input is, for instance, DI2_DI5, then the speed decelerates
to the preset level – SlowDownSpeedRef (64.07) – in the following cases:
- If DI2 is set to zero, then the slow speed in forward direction is activated.
- If DI5 is set to zero, then the slow speed in backward direction is activated.
When DI2 is set to zero, (forward slow down) full speed is still allowed in backward
direction.
When DI5 is set to zero, (backward slow down) full speed is still allowed in forward
direction.
Backward slow Backward slow Forward slow down Forward slow down
down area and down area and area and running area and running
running backward running forward backward forward
Singel direction Low speed Normal speed Normal speed Low speed
Slow down
Dual direction Slow Low speed Low speed Low speed Low speed
down
FAST STOP
When the FAST STOP-N input, e.g. Ext DI10, changes to "0" (activates on a
negative edge) while running, the drive is fast stopped (active in both speed and
torque control). Three alternatives can be selected by parameter FastStop Type 12
(63.02), see Fast stop (63) on page 19.
After reaching zero speed and the "ZEROPOS" input has been set to "1", with a
positive edge required for reset of fast stop condition, for a time longer than
parameter ZeroPosOk TD (64.08), the drive is allowed to start. That is, the joystick
must be returned to the neutral position for a minimum of 0.3 seconds (default value)
before starting in other direction is possible.
To avoid running in the same direction (hoisting after overload indication or lowering
after slack rope indication), the appropriate direction input must be wired in series
with an additional contact from the protection equipment. These contacts must be
normally open (NO) which are closed when the protection equipment is energised
and opens when a fault occurs.
TORQUE CONTROL
Activated when the voltage level of input AI2 TORQ REF the first time (after each
power on) passes the level 1 V, and if the speed reference to AI1 is below 1 V.
Speed reference is activated the first time AI1 passes the level 1 V (and after each
power on = default).
If both inputs are above limit, then speed control is active.
Updating time for speed and torque references are 20 ms.
SPEED CORRECTION
The additional speed reference input, Speed correction (AI3), is a reference without
any ramp that is added to the output of the normal speed reference ramp generator.
Can be used as a correction input from an "electric shaft" control unit. The updating
time is 20 ms for the speed correction input.
0 V signal is 0 % reference level and the 0 – (+)10 V range corresponds to 0 –
(+)100 % speed. 0 – (-) 10 V range corresponds to 0 – (-)100 % speed.
The speed correction reference is limited so that the sum of the normal "ramped"
speed reference and the speed correction reference cannot exceed maximum/
minimum speed setting (parameters M1SpeedMin (20.01) & M1SpeedMax (20.02)).
WATCHDOG
The signal WATCHDOG-N (digital output 5 as default) is used to indicate a healthy
drive. This output is zero-set if the software detects any of the following faults:
• Fieldbus communication fault
• Brake long falling time
• CPU stalls out
If this relay output contact opens, the supply contactor to the converter must
immediately be opened and the mechanical brakes applied by removing power from
the brake contactor = emergency stop of the crane drive.
Joystick mode
When connecting a joystick directly to the drive I/O, parameter Control Type (64.10)
should be set to "Joystick" (default).
Crane stand alone logic using Joystick control type.
&
=1 Start
& &
&
1V
REFERENCE CURVE
The joystick for giving reference has parameters for setting the deadzone in direction
A and B (Dead Zone A (64.04) and Dead Zone B (64.05)).
Reference shape (64.06) is used for giving the reference a parabolic shape:
Setting of REF SHAPE parameter Reference curve shape
“20” x2 curve
“100” x3 curve
JOYSTICK CHECKS
If any of the following conditions occur for a duration longer than Joystick Warn TD
(64.12):
• START DIR A= "1" and START DIR B="1" at the same time,
• SPEED REF is > 1 V or TORQUE REF is > 1 V when the joystick is in the neutral
position (ZERO POS = "1", DIR A = "0" and DIR B = "0") (this indicates a possibly
loose ground connection),
then the drive is ramp stopped and prevented from a new start until the joystick is
moved back to the neutral position. That is, zero position must be indicated for
longer than the time set by ZeroPosOk TD (64.08).
The panel also indicates this with an alarm text: "WARNING JOYSTICK".
Dir A (DI 7)
&
Dir B (DI 8)
Start
=1 &
S Fast stop 12
Zero speed & R
Dir A (DI 7)
&
Dir B (DI 8)
Start
=1 &
Accelerate (DI 2)
Ramp output
Fault
On “FieldBus” R
Trigg On
Start “Panel” _>1 S
Start “I/O”
Start 2
_>1 &
Start “FieldBus”
NOTE: For description of mechanical brake control, see DCS800 Firmware manual,
Group 42.
30
8.15 b0 RDY FOR ON
7.10 b1 DRIVE ON
8.15 b3 RUNNING
Copyright © 2008 ABB. All rights reserved.
7.01 b1 DRIVE ON
8.01 b2 RUNNING
Copyright © 2008 ABB. All rights reserved.
Start and stop sequence, Stand alone mode, where “first” start order gives “On” order
Crane program description
31
32
MxTorqProvTime > 0 s
Torq prov OK
_>1
Motor torque S
R
t 0
Torq prov flt
RUNNING &
<MxTorqProvTime>
LoadTorque is the torque needed to hold the load, and is calculated by the module. If
the module gets the order HIGH SPEED OK = "1", commonly given when the master
switch is in its outermost position, the output PowOpSpeedRef (1.52) is set to the
calculated maximum speed reference. The quality of the calculation depends on the
measurements done before reaching 90% of base speed. The speed should have a
linear acceleration and be without excessive ripple (use parameter 50.06).
If the input signal HIGH SPEED OK goes to zero, the output power optimizing speed
reference is set to zero .The calculated maximum reference is reset to zero when the
actual speed signal MotSpeed (1.04) has decreased to a speed corresponding to the
parameter PowOpResetLevel (68.08).
9. Check that the final speed in the field weakening area is the same every time
within 1–2 %, for each autotune run in the same direction.
10. Adjusting TorqLimUp (68.06) and TorqLimDown (68.07):
a. Connect rated load.
b. From the DriveWindow, record with the signal PowOpSpeedRef (1.52).
c. Test run from the joystick by giving a full reference up (resp. down).
d. Check that Base Speed is reached in signal PowOpSpeedRef (1.52). If not
adjust TorqLimUp (or TorqLimDown, respectively) in steps of 5% until
reaching reaching Base Speed (68.02) within 1–2% every time.
e. Verify that the hoist reaches 100% speed with no load.
An alternative to steps 4–8 above for finding the inertia values is:
1. Monitor the signal LoadTorque 1.53 with the drives window while making start
and stop test runs (acceleration, constant speed for a couple of seconds and
deceleration) with different settings on Inertia parameter.
– Any load 20–100% is possible to use.
– Do not run faster than base speed.
– Perform the first run in hoisting direction.
2. When you have found the correct value for parameter InertiaTotalUp (68.04),
then signal LoadTorque 1.53 will show the same level during acceleration and
deceleration as during constant speed.
– If the LoadTorque signal is showing a higher value during acceleration than
during constant speed, the parameter InertiaTotalUp (68.04) should be
increased.
– If LoadTorque is showing a lower value during acceleration than during
constant speed, then InertiaTotalUp (68.04) should be lowered.
3. Next make similar test runs in lowering direction to find correct value for
parameter InertiaTotalDown (68.05).
– If the LoadTorque signal is showing a higher value during acceleration than
during constant speed, the parameter InertiaTotalDown (68.05) should be
decreased.
– If LoadTorque is showing a lower value during acceleration than during
constant speed, then InertiaTotalDown (68.05) should be increased.
4. Verify with different loads.
<BrakeRefDly>
Start t 0
Local
Speed ref local
SpeedRef MAX
PowOpSpeedRef
"0"
Master/Follower (72)
General
The Master/Follower is a load sharing application, where the system is run by two
CraneDrives and the motor shafts are coupled together via gearing, rail, shaft, etc.
The Master/Follower application controls the load distribution between the drives.
The Master drive sends order signals and references (speed and torque) through the
Master/Follower bus to the follower drive. The master also reads status information
from the follower drive to ensure a safe operation, that is, a two way communication.
For single Master/Follower communication, the DCS link (group 94) has to be used.
It is an electrical (two wire) point-to-point communication link (duplex) which requires
the DCS link board to be installed. (SDCS-DSL-4). (For broadcast communication,
see Broadcast mode on page 38)
The settings of parameters 72.01 ((OFF), MASTER, or FOLLOWER) and 72.11
(always = NO!) automatically configures the communication parameters in group 94.
(Refer to Appendix A, and the DCS800 Firmware manual.)
The Master/Follower application can be used for both hoist and travel motions, in
both Fieldbus mode and Standalone mode.
The Master station shall always be speed controlled and the Follower station usually
is Torque controlled.
To ensure correct Follower load sharing, the Follower speed limits 20.1 and 20.2,
and 42.19 and 42.20 must be set 5 % higher than the setting of Master parameter
69.1 SPEED SCALING.
Local control
For local M/F operation, point-to-point (parameter 72.11 “M/F Broadcast mode” =
NO):
Set the master drive in “Local” and the follower in “Remote” operation. The master
will then control that both drives run together.
If the two drives do not run together, an “M/F run Fault” is given.
To run only one of the drives, either set parameter 72.01 “Mast/Foll mode” to Off,
or – from fieldbus or I/O – ‘Set’ bit 5 (SEPARATE) in 7.10, “FBCommandWord”.
0 = Bit 0, LSB ComTestBitMaster ”1” ”0” Communication test bit from master
Broadcast mode
For broadcast M/F communication – where the master controlls more than one
follower drive – the DDCS link (group 70) has to be used. The DDCS link is a one
way, fiber optic communication (on CH2), and can be used for broadcast only
(communication, group 90).
Copyright © 2008 ABB. All rights reserved.
Crane program description 3AST004143R0501
39
Receive
Signals from a superior controller (for instance AC800) are received by a specific
module in the crane control application. The signals may be transferred via a high
speed serial bus in the form of a Fieldbus, e.g. Advant Module bus (max 30 words/
dir), or Profibus (max 10 words/dir).
The receiving module includes an element for unpacking the Command word signal
to 16 boolean signals. Upon processing by the crane logic, the signals are
transferred to the standard DCS800 main control word (MCW)
MCW Used MCW
Scalings
Speed signals have the scaling: 20 000 corresponds to 100 % (parameter 50.01)
Torque signals have the scaling: 10 000 corresponds to 100 % of motor nominal
torque (signal 4.23).
If "next edge" is not received within a certain time, Ch0 TimeOut (70.04), the
MAS OSC FLT fault occurs and the drive trips.
The drive is inverting the bit received from the superior controller (PLC): COMTEST
REC and sending it back on transmission DS11.1 bit 14, COMTEST TRA.
NOTE: In the superior controller the received bit should be sent directly to the drive
again without inverting and without delay (recommended updating time maximum
100 ms).
PLC Drive
Transmit
The DCS800 standard application sends information on the main status word (MSW)
and several other signals to the crane logic. A new status word is created in a
module of the crane logic.
This module is used to transmit signals from the drive to a supervisory controller via
high-speed serial bus in the form of a Fieldbus, e.g. Advant Module bus (max 30
words/dir), Profibus (max 10 words/dir) and ModbusPlus. The module includes
elements for packing 16 Boolean signals to word signals.
MSW
8.01 8.15 Fieldbus
Crane
Logic group 51
group 70
Transmit DataSets 11, 13, 15, 17, 19, and 21 (alt. 2, 4, 6, 8, 10, and 12)
Example: DS11.2 = DataSet 11, Word 2
DataSet.Word Signal Range Description Dset
(set in group 92) corresp. to address
+/- 32767
DS11.1 (DS2.1) FB StatusWord (8.15) Fieldbus status word 92.01=815
DS11.2 (DS2.2) MotSpeed (1.04) -163.84– Speed actual, rmp 92.02=104
+163.84
DS11.3 (DS2.3) MotTorque (1.08) -327.67– Torque actual, %Tn 92.03=108
+327.67
DS13.1 (DS4.1) SpeedRef3 (2.02) -163.84– Speed reference 3, 92.04=202
+163.84 % of parameter 50.1
DS13.2 (DS4.2) PosActPPU (1.54) -32767– Position actual value 92.05=154
+32767
DS13.3 (DS4.3) PowOpSpeedRef (1.52) -163.84– Power optimization speed 92.06=152
+163.84 ref, %
DS15.1 (DS6.1) MotCur (1.06) -327.67– Motor current, 92.07=106
+327.67 % of parameter 99.03
DS15.2 (DS6.2) Mot1FldCurRel (1.29) -327.67– Field current Motor 1, 92.08=129
+327.67 % of parameter 99.11
DS15.3 (DS6.3) Mot2FldCurRel (1.31) -327.67– Field current Motor 2, 92.09=131
+327.67 % of parameter 49.05
DS17.1 (DS8.1) ArmVoltActRel (1.13) -327.67– Armature voltage, 92.10=113
+327.67 % of parameter 99.02
DS17.2 (DS8.2) FBAuxStatusWord (8.16) Auxiliary status word 92.11=816
DS17.3 (DS8.3) “free”
DS19.1 (DS10.1) FaultWord1 (9.01) Motor control faults 92.13=901
Scalings:
MotTorque: Integer 10000 = 100 % of motor nominal torque.
Tnom(Nm) = 9550 * Pnom(kW)/n = signal MotTorqNom (4.23))
MotCur: Integer 10000 = 100 % of parameter 99.02
MotxFldCurRel: Integer 10000 = 100 % of parameter 99.11 or 49.05, respectively
Overview
This chapter explains the function of, and valid selections for, each DCC800 signal
and parameter.
Signal groups
Parameter groups
The DCC800 parameters are arranged into groups by their function. Chapter
DCS800 Control Panel operation in DCS800 Firmware manual explains how to
select and set the parameters. Some parameters that are not in use in the current
application are hidden to simplify programming.
60.02 Zero Pos Sel NOT USED; DI2; DI5; DI6; Zero position digital input
EXT DI9 ... EXT DI14 (Stand alone)
60.03 SlowDown-N Sel NOT USED; DI2; DI5; DI6; Slowdown digital input
EXT DI9 ... EXT DI14; DI2_5; (Stand alone)
EXT DI9_DI10; EXT
DI11_DI12; EXT DI13_DI14
60.04 FastStop-N Sel See parameter 60.02 Fast stop digital input
(Stand alone)
60.06 Sync Sel NOT USED; DI2; DI5; DI6; DI7; Synchronisation digital input
DI8; EXT DI9 … EXT DI14
60.08 Step Ref2 Sel See parameter 60.02 Step reference 2 digital input
(Stand alone)
60.09 Step Ref3 Sel See parameter 60.02 Step reference 3 digital input
(Stand alone)
60.10 Step Ref4 Sel See parameter 60.02 Step reference 4 digital input
(Stand alone)
60.11 High Speed Sel See parameter 60.02 High speed digital input
(Stand alone)
60.12 Snag Load-N Sel See parameter 60.02 Snag load digital input
60.14 Step Ref5 Sel See parameter 60.02 Step reference 5 digital input
(Stand alone)
60.15 Shared Motion Sel See parameter 60.02 Shared motion selection
(Stand alone)
61.01 PosMeasEnable
True
Position measurement according to the ACC800 crane control is active.
False
Position measurement according to the standard ACS800 is active.
63.01 FastStop Type 11 NOT USED; FAST STOP 1; FAST STOP 2; Fast stop type 11
FAST STOP 3
63.02 FastStop Type 12 NOT USED; FAST STOP 1; FAST STOP 2; Fast stop type 12
FAST STOP 3
Group 64 Crane
The Range/unit column in the table below shows the allowed parameter values. The
text following the table explains the parameters in detail.
Parameter Range/unit Description
64.18 Speed/Torq Ctrl Speed; Torque; AI1 AND 2 LEVEL Speed or torque control
selection
64.19 Slow Down Mode SINGLE DIR; DUAL DIR Selection of slow down
direction
64.03 HighSpeedLevel 1
Joystick output (e.g. AI1) speed reference signal level to give HIGH SPEED signal
(see page 33) for power optimization.
64.07 SlowDownsSpeedRef
Maximum speed reference level (limitation) when the slow down function is activated
(e.g. Ext DI9=0).
Scaling: 100% = parameter 50.01 (motor 1) or 49.22 (motor 2) level.
64.08 ZeroPosOk TD
Time delay for the joystick to stay in zero position before a new start order can be
given after a stop from: trip, fast stop or joystick warning.
65.01 Continuous On
Contactors will remain on without time limit after the motor is stopped, if parameter
Continuous On = True.
66.04 Regen Test Sel True; False Regenerative bridge test select
68.03 PowOpAutotuneSel
TRUE
Activates the tuning.
Note: Parameter is reset to False after each calculated total inertia value.
The value of the inertia can be read in signal Total Inertia (1.51).
An average value after running 2–3 times in each direction should then be entered to
parameters InertiaTotalUp (68.04) and InertiaTotalDown (68.05) respectively.
FALSE
Autotune mode not active.
68.04 InertiaTotalUp
Total inertia measured in upward direction.
68.05 InertiaTotalDown
Total inertia measured in downward direction.
68.06 TorqLimUp
Maximum load torque allowed upwards (=field weakening power limit).
68.07 TorqLimDown
Maximum load torque allowed downwards (=field weakening power limit).
68.08 PowOpResetLevel
Speed level (in % of base speed) where the calculated power optimization reference
will be reset to be prepared for a new calculation during the next acceleration.
68.09 LoadTorqueFiltTC
Filter time constant for calculated signal LoadTorque (1.53) (see the alternative
commissioning instruction for power optimization in page 35).
68.10 SlackRopeTorqLev
Detection level for "slack rope", (see Power optimization (68) on page 33 for more
details on the "Slack rope" function). The signal LoadTorque (1.53) dropping below
this level is considered a "slack rope", making a Fast stop type 1 to the drive. Setting
of -300% (default) will disable the Fast stop.
Group 72 Master/Follower
Group 72 handles the Master/Follower configuration for communication via the DCS
link. (Group 94)
The range/unit column in the table below shows the allowed parameter values.
NOTE! Several of the parameters in this group also appears in other parameter
groups. However, they are gathered in this group (72) in order to simplify the settings
for Master/Follower mode. The setting of these parameters is written to – and
overwirtes any other value on – the corresponding parameter according to the table
below.
Parameter Range/unit Description
72.02 Torque Selector Zero; Speed; Torque; Minimum; Maximum; Torque selector setting
(writes to 26.01) Add; Limitation
72.05 Window Width Pos -10000 – +10000 rpm Window width, positive
(Writes to 23.08)
72.06 Window Width Neg -10000 – +10000 rpm Window width,, negative
(writes to 23.09)
72.08 Torq Ref A FTC 0 ... 32767 ms (Visible only if M/F CTRL Torque reference A, filter time constant
(writes to 25.02) macro is selected.)
72.09 M/F Fault TD 0 ... 32767 ms (Visible only if M/F CTRL Master/Follower fault time delay
macro is selected.)
72.10 M/F Comm Err TD 0 ... 32767 ms (Visible only if M/F CTRL Master/Follower communication error
macro is selected.) time delay
72.6 W IN DOW
Speed Reference W IDTH NEG
72.5 W IN DOW
W IDTH POS
e Actual Speed
Torque Reference
Speed Decrease =
Drooping Speed Controller Output Max. Speed
No Drooping
Speed Controller
Output (%)
100%
At 100 % speed controller output, drooping is at its maximum level i.e. equal to the
value of the DROOP RATE. The drooping effect decreases linearly to zero along
with the decreasing load.
80.10 Sync Sel 2 NOT USED; DI2; DI5; Selection of input sync signal, motor 2
DI6; DI7; DI8;
EXT DI9 … EXT DI14
80.11 Slow Down Mode 2 SINGLE DIR; Selection of slow down direction, motor
DUAL DIR 2
80.20 Sp Der Blk Lev 2 0 …100 s Speed derivative blocking level, motor 2
80.25 Acc Time Fwd 2 0.1 …60.0 s Acceleration time forward, motor 2
80.26 Acc Time Rev2 0.1 …60.0 s Acceleration time reverse, motor 2
80.27 Dec Time Fwd 2 0.1 …60.0 s Deceleration time forward, motor 2
80.28 Dec Time Rev 2 0.1 …60.0 s Deceleration time reverse, motor 2
80.19 TorqueFault TD 2
If a speed error higher than Speed DevLev 2 occurs for motor 2, and if it lasts longer
than the time TorqueFault TD 2, the drive will trip, indicating torque fault (code F610).
Fault tracing
Fault signals
The fault signals will be shown on the seven segment display of the control board
SDCS-CON-2 as codes (F ..) as well as on the LCD of the control panel CDP 312 as
numbers with text. Moreover there are fault signals which will only be shown on the
LCD of the control panel.
All fault signals – with the exception of F 17, F 18 and F 20 – can be reset (after
elimination of the faults).
For resetting (RESET) fault signals, the following steps are required:
• Switching off the commands ON/OFF and RUN
• Elimination of the faults
• Fault acknowledgement, i.e. resetting (RESET) through input of the command
RESET with APC or in "LOCAL" mode with control panel CDP 312/DRIVES
WINDOW.
• Depending on the application conditions, generate the commands ON/OFF and
RUN once more.
•
The fault signals will result in tripping the drive (installation-dependent).
If a fault occurs, there will be three different possibilities of reaction (see column
"Remark" in the fault list):
1. Fault will switch off the signals energizing the main contactor, the field contactor
and the fan contactor.
2. Fault will switch off the signals energizing the main contactor and the field
contactor.
3. Fault will switch off the signal energizing the main contactor.
See also DCS800 Firmware manual for fault and warning message descriptions.
Fault signals
Code Text on LCD of control Definition/Action Status signal Remark
seven panel CDP 312 (or (FAULT_WORD_
segm. DRIVES WINDOW) 1/2/3/4)
display
F610 TorqueFault If SPEED ERROR during constant speed 9.05 bit 0 (1)
is higher than Speed Dev Lev (62.02) for
a time longer than Torque Fault TD
(62.03), the drive will trip for
TorqueFault.
Check:
• Ramp times
• Torque and Current limit settings
• Torque monitoring (Group 62)
parameter settings
• Motor and motor cables
• Pulse encoder connections (A and B)
F611 MasterOscFlt If "next edge" of the communication test 9.05 bit 1 (1)
bit is not received within a certain time
(parameter 70.04), the drive will trip.
Check:
• Fieldbus adapter and its connection to
board SDCS-COM-8x channel 0.
• PLC program connection of comm. test
bit from input to output.
• Fieldbus wiring.
Alarm signals
The alarm signals will be shown on the seven segment display of the control board
SDCS-CON-2 as codes A .. . On the LCD of the control panel CDP 312, the alarm
signals will be shown as numbers (without the leading digit "1") with text.
Alarm signal
Code Text on LCD of control Definition / Possible source Signal number Remark
seven panel CDP 312 (ALARM_WORD
segm. (or DRIVES WINDOW) _1/2)
display
The tables in this appendix list all the actual signals, parameters, and alternative
settings for the CraneDrive. Use these tables as reference when you are
customizing macros for your CraneDrive application.
Also see the DCS800 Firmware manual for signal and parameter description.
Information (group 4)
Signal name Range/unit Description
INFORMATION (Group 4) See DCS800 Firmware manual
4.01 FirmwareVer –
4.03 ApplicName –
4.04 ConvNomVolt V
4.05 ConvNomCur A
4.06 Mot1FexType NotUsed; OnBoard; FEX-425-Int;
DCF803-0035; DCF803-0050;
DCF804-0050; DCF803-0060;
DCF804-0060; DCS800-S01;
DCS800-S02; FEX-4-Term5A
4.07 Mot2FexType NotUsed; OnBoard; FEX-425-Int;
DCF803-0035; DCF803-0050;
DCF804-0050; DCF803-0060;
DCF804-0060; DCS800-S01;
DCS800-S02; FEX-4-Term5A
4.08 Mot1FexSwVer –
4.09 Mot2FexSwVer –
4.11 Com8SwVer –
4.12 ApplicVer –
4.13 DriveLibVer –
4.14 ConvType None; D1; D2; D3; D4; D5; D6; D7;
ManualSet
4.15 QuadrantType Auto; BlockedBridge2; RelBridge2
4.16 ConvOvrCur A
4.17 MaxBridgeTemp ºC
4.18 DCS Link Stat1 0-65535 See DCS800 Firmware manual for bit
information
4.19 DCS Link Stat2 0-65535 See DCS800 Firmware manual for bit
information
4.20 Ext IO Stat 0-65535 See DCS800 Firmware manual for bit
information
4.21 CPU Load %
4.22 ApplLoad %
4.23 MotTorqNom Nm
4.24 ProgressSignal %
4.25 TachoTerminal –
4.26 IaActScaling A
Some signals and parameters in the DCS800 firmware are overwritten by the crane
drive application (DCC800). The table below tells which signals that are overwritten,
and under which conditons.
Overwritten signal Condition
The figures in this appendix shows typical signal connections at the RMIO board I/O
for the different control modes.
Connections at the I/O boards in Stand alone mode, Joystick control
Terminal Function
IOB-21 &
CON-4
X6:1 DI 1 Converter Fan ackn.
X6:2 DI 2 Zero Pos
X6:3 DI 3 Main Contactor Ackn.
X6:4 DI 4 Electrical disconnect
X6:5 DI 5 Programmable
X6:6 DI 6 Brake ackn. (def.)
X6:7 DI 7 Start Dir A
X6:8 DI 8 Start Dir B
X7:3,4 +48 V IOB-21: 48 Vdc, max 50 mA
X6:9 +48 V CON-4: 48 Vdc, max 50 mA
Connections at the I/O boards in Stand alone mode, Joystick control (continued)
Terminal Terminal
IOB-3 CON-4 Function
X4:7 X4:4 Vref. Reference voltage 10 VDC
Forward max 5 mA
X4:8 X4:3 GND
X3:4 X3:6 AI 1+ Speed reference
Reverse 0…10V <-> 0 …100%
X3:3 X3:5 AI 1-
TE
X3:6 X3:8 AI 2+ Torque reference
0…10V <-> 0 …Tmax
X3:5 X3:7 AI 2-
X3:8 X3:10 AI3+ Speed Correction
+/-10V <-> +/- 100%
X3:7 X3:9 AI3-
rpm X4:1 X4:7 AO1+ Speed
-10V … +10V <-> -100 …100%
X4:2 X4:6 AO1-
Nm X4:3 X4:8 AO2+ Torque
-10V …+10V <-> -Tn…+Tn
X4:4 X4:6 AO2-
TE
Connections at the RMIO board in Stand alone mode, Motor pot control
Terminal Function
IOB-21 &
CON-4
X6:1 DI 1 Converter Fan ackn.
X6:2 DI 2 Accelerate
X6:3 DI 3 Main Contactor Ackn.
X6:4 DI 4 Electrical disconnect
X6:5 DI 5 Programmable
X6:6 DI 6 Brake ackn. (def.)
X6:7 DI 7 Start Dir A
X6:8 DI 8 Start Dir B
X7:3,4 +48 V IOB-21: 48 Vdc, max 50 mA
X6:9 +48 V CON-4: 48 Vdc, max 50 mA
Terminal Terminal
IOB-3 CON-4 Function
X4:7 X4:4 Vref. Reference voltage 10 VDC
max 5 mA
X4:8 X4:3 GND
X3:4 X3:6 AI 1+
X3:3 X3:5 AI 1-
X3:6 X3:8 AI 2+
X3:5 X3:7 AI 2-
X3:8 X3:10 AI3+ Speed Correction
+/-10V <-> +/- 100%
X3:7 X3:9 AI3-
rpm X4:1 X4:7 AO1+ Speed
-10V … +10V <-> -100 …100%
X4:2 X4:6 AO1-
Nm X4:3 X4:8 AO2+ Torque
-10V …+10V <-> -Tn…+Tn
X4:4 X4:6 AO2-
TE
Terminal Function
IOB-21 &
CON-4
X6:1 DI 1 Converter Fan ackn.
X6:2 DI 2
X6:3 DI 3 Main Contactor Ackn.
X6:4 DI 4 Electrical disconnect
X6:5 DI 5 Programmable
X6:6 DI 6 Brake ackn. (def.)
X6:7 DI 7 Start Dir A
X6:8 DI 8 Start Dir B
X7:3,4 +48 V IOB-21: 48 Vdc, max 50 mA
X6:9 +48 V CON-4: 48 Vdc, max 50 mA
Terminal Terminal
IOB-3 CON-4 Function
X4:7 X4:4 Vref. Reference voltage 10 VDC
Forward max 5 mA
X4:8 X4:3 GND
X3:4 X3:6 AI 1+ Speed reference
Reverse 0…10V <-> 0 …100%
X3:3 X3:5 AI 1-
TE
X3:6 X3:8 AI 2+ Torque reference
0…10V <-> 0 …Tmax
X3:5 X3:7 AI 2-
X3:8 X3:10 AI3+ Speed Correction
+/-10V <-> +/- 100%
X3:7 X3:9 AI3-
rpm X4:1 X4:7 AO1+ Speed
-10V … +10V <-> -100 …100%
X4:2 X4:6 AO1-
Nm X4:3 X4:8 AO2+ Torque
-10V …+10V <-> -Tn…+Tn
X4:4 X4:6 AO2-
TE
Terminal Function
IOB-21 &
CON-4
X6:1 DI 1 Converter Fan ackn.
X6:2 DI 2 SnagLoad-N
X6:3 DI 3 Main Contactor Ackn.
X6:4 DI 4 Electrical disconnect
X6:5 DI 5 “programmable”
X6:6 DI 6 Brake ackn. 1 (def.)
X6:7 DI 7 Sync
X6:8 DI 8
X7:3,4 +48 V IOB-21: 48 Vdc, max 50 mA
X6:9 +48 V CON-4: 48 Vdc, max 50 mA
Terminal Terminal
IOB-3 CON-4 Function
X4:7 X4:4 Vref. Reference voltage 10 VDC
max 5 mA
X4:8 X4:3 GND
X3:4 X3:6 AI 1+
X3:3 X3:5 AI 1-
X3:6 X3:8 AI 2+
X3:5 X3:7 AI 2-
X3:8 X3:10 AI3+
X3:7 X3:9 AI3-
rpm X4:1 X4:7 AO1+ Speed
-10V … +10V <-> -100 …100%
X4:2 X4:6 AO1-
Nm X4:3 X4:8 AO2+ Torque
-10V …+10V <-> -Tn…+Tn
X4:4 X4:6 AO2-
TE
ABB AB
Crane Systems
SE-721 59 Västerås
SWEDEN
Telephone +46 21 34 00 00
Telefax +46 21 34 02 90
Internet http://www.abb.com/cranes