Sei sulla pagina 1di 27

Technical Proposal

Mini TP48300B-N04C1 & L04C1 Power System

HUAWEI TECHNOLOGIES CO., LTD.


TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal Contents

Contents

1 Overview ................................................................................................................................... 1
2 XX Company Mini Indoor Power System ............................................................................. 2
2.1 Design Rules ......................................................................................................................................................... 2
2.2 Specifications ........................................................................................................................................................ 2

3 Huawei Mini Power Solution ................................................................................................. 4


3.1 Introduction ........................................................................................................................................................... 4
3.2 Configurations....................................................................................................................................................... 5

4 Combined Indoor Power Solution Features ......................................................................... 6


5 TP48300B-N04C1 and TP48300B-L04C1................................................................................. 7
5.1 Introduction ........................................................................................................................................................... 7
5.2 Features................................................................................................................................................................. 8
5.2.1 AC-DC Conversion............................................................................................................................................. 8
5.2.2 Efficient Rectification ......................................................................................................................................... 9
5.2.3 Power Supply Management ................................................................................................................................ 9
5.2.4 Battery Management ........................................................................................................................................... 9
5.2.5 Environment Monitoring..................................................................................................................................... 9
5.2.6 Human-Machine Interface and Remote Communication ...................................................................................... 9
5.2.7 Maintenance from the Front ...............................................................................................................................10
5.2.8 D.G. Management .............................................................................................................................................10
5.2.9 Abundant Installation Modes..............................................................................................................................10
5.3 Specifications .......................................................................................................................................................10
5.4 Composition .........................................................................................................................................................12
5.4.1 Power Cabinet ...................................................................................................................................................12
5.4.2 Rectifier ............................................................................................................................................................12
5.4.3 Monitoring Unit.................................................................................................................................................15
5.4.4 Battery Rack ......................................................................................................................................................22

Disclaimer .................................................................................................................................. 25

Issue 01 (2013-09-14) Huawei Proprietary and Confidential i


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 1 Overview

1 Overview

The power system converts AC input into –48 V DC output to power communications
equipment. Equipped with batteries, the power system serves as an uninterruptible power
system (UPS). The power system consists of the power cabinet, rectifier, monitoring unit, AC
power distribution unit (PDU), and DC PDU.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 1


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 2 XX Company Mini Indoor Power System

2 XX Company Mini Indoor Power System

2.1 Design Rules


 Security: The power system is secure for users and communications systems.
 Reliability: The power system supplies reliable power to communications equipment,
preventing single-point failures.
 Cost-effectiveness: The power system is efficient and energy-saving.
 Operability: The power system is easy to manage, maintain, and configure. The power
system supports centralized monitoring, remote management, and fault diagnosis.
 Scalability: The power system meets predictable site or monitoring expansion
requirements, helping the customer maximize the return on investment (ROI) during
system upgrade.

2.2 Specifications
Table 2-1 Specifications

Category Item Specifications


AC input AC input system 220/380 V AC three-phase, four-wire
(TP48300B-N04C1)
110 V, dual–live wire: 100–120
VAC/200–240 V AC (TP48300B-L04C1)
Voltage 85–300 V AC
Surge protection 20 kA (nominal); 40 kA (maximum)
DC output Maximum load power *W
Average load power *W
DC power Load low voltage LLVD: one 1-pole 100 A circuit breaker and
distribution disconnection (LLVD) two 1-pole 80 A circuit breakers (10P
mandatory; 12P optional, MCB)
Battery low voltage BLVD: one 1-pole 63 A circuit breaker, one
disconnection (BLVD) 1-pole 32 A circuit breaker, and two 1-pole

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 2


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 2 XX Company Mini Indoor Power System

Category Item Specifications


16 A circuit breakers (6P mandatory, MCB)
Battery power Fuses: 2*160 A
distribution
Rectifier Power range 3000 W (176–300 V AC) or 2000
W(176–300 V AC)
Efficiency > 96% (maximum)
Monitoring User port RS232/RS485
Liquid crystal display Required
(LCD)

Reserved Boolean Six


values

Sensor ports One channel of door switch, One flooding


sensor , One smoke sensor, one battery
temperature sensor, and one ambient
temperature and humidity sensor
Dry contact outputs Eight
Protocol Master/Slave protocol, BIN protocol, SNMP
protocol.
Others Dimensions (H x W x 480 mm x 442 mm x 360 mm
D)
Operating temperature –10°C to +50°C
Weight ≤ 30 kg
Backup time Six hours
Protection level IP20 (with a cover)
Maintenance Front maintenance; cables routed from the
top
Heat dissipation Cools as the ambient temperature drops.
Certification CE

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 3


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 3 Huawei Mini Power Solution

3 Huawei Mini Power Solution

3.1 Introduction
[Select the following solution based on XX company's requirements.]
TP48300B-N04C1& L04C1 (TP48300B for short) provides a site power solution by working
with the AC power source, AC transfer switch (ATS), and batteries. Figure 3-1 shows a
typical solution.

Figure 3-1 Typical site power solution

Air conditioner

AC lighting

D.G. Transmission
Communications
power supply equipment

Other DC
equipment

Mains

AC
DC
Battery string 1 Battery string 2

Figure 3-2 shows the TP48300B (300 A) interior.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 4


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 3 Huawei Mini Power Solution

Figure 3-2 TP48300B interior


(9) (8)

(1)

(2)
(7)

(3)
(4)

(5)

(6)

(1) Cabinet (2) Battery fuses (3) DC circuit breakers (extended)


(4) AC distribution (extended) (5) AC input ports and surge protective device (SPD) (6) Rectifiers
(7) Monitoring unit (8) LLVD circuit breakers (9) BLVD circuit breakers

3.2 Configurations
Determine configurations including the product model and quantity based on project
requirements.
This section is applicable only to customer-constructed projects.
This project uses Huawei Mini power system TP48300B-N04C1 (including the monitoring
unit) and rectifier R4850G2. The basic configurations are as follows:

No. Device Type Model Quantity Remarks


1 Combined TP48300B-N04C1 * The model may change.
indoor power Power distribution is
systems described.
TP48300B-L04C1 /
2 Rectifiers R4850G2 * Configured based on the
customer's power and
R4850N2 / efficiency requirements
R4830G2 /
3

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 5


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 4 Combined Indoor Power Solution Features

4 Combined Indoor Power Solution


Features

[Analyze based on the selected solution.]


 High security
The system is CE certified. The high reliability and redundancy design and low voltage
disconnection (LLD) ensure the system security.
 High reliability
The power system equipped with batteries serves as a UPS. The mean time between
failures (MTBF) exceeds 200,000 hours.
 High efficiency and energy saving
The rectifier has a maximum efficiency of more than 96% and keeps an efficiency of
more than 95% in a wide load range. The rectifier supports intelligent hibernation.
 Operability
The intelligent monitoring system centrally manages and monitors the site, reducing the
operational expenditure (OPEX).
 Scalability
Rectifiers are hot-swappable, which allows you to insert new rectifiers online.
Expandable load routes are reserved.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 6


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

5 TP48300B-N04C1 and TP48300B-L04C1

5.1 Introduction
The TP48300B is a new generation indoor Mini power system. It converts AC input into
stable –48 V DC for communications equipment. The TP48300B equipped with batteries
serve as a UPS. The TP48300B consists of the power cabinet, rectifier, monitoring unit, AC
PDU, and DC PDU.
 The TP48300B-N04C1 provides BLVD and LLVD and supports three-phase AC input
systems (compatible with single-phase AC input systems). It has a maximum capacity of
300 A.
 The TP48300B-L04C1 provides BLVD and LLVD and supports 110 V dual–live wire
input systems (compatible with single-phase input systems). It has a maximum capacity
of 300 A.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 7


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Figure 5-1 TP48300B

5.2 Features
5.2.1 AC-DC Conversion
The TP48300B-N04C1 supports 220/380 V AC three-phase, four-wire input systems
(compatible with single-phase, three-wire input systems):
 220/380 V AC three-phase, four-wire
 Rated voltage: 200–240 V AC or 346–415 V AC
 Operating voltage: 85–300 V AC or 147–519 V AC
The TP48300B-L04C1 supports 110 V AC dual–live wire, two-wire input systems
(compatible with single-phase, three-wire input systems):
 Rated voltage: 100–120 V AC or 200–240 V AC
 Operating voltage: 85–300 V AC
 DC output: –42 V DC to –58 V DC (default value: –53.5 V DC)
Highlights:
 Flexible support for power grid systems
 Wide AC input range: 85–300 V AC
The TP48300B can withstand root mean square (RMS) 320 V AC input voltage.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 8


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

5.2.2 Efficient Rectification


 1 U 30 A or 50 A high- or standard-efficiency rectifier
 Maximum efficiency: 96% or higher
 Wide AC input range: 85–300 V AC
The TP48300B can withstand RMS 320 V AC input voltage.
 DC output: –42 V DC to –58 V DC (default value: –53.5 V DC)
 Wide operating temperature: –40°C to +75°C
Highlights:
 High efficiency
 Energy saving
 Less OPEX

5.2.3 Power Supply Management


The intelligent hibernation function shuts down redundant rectifiers so that the other rectifiers
work efficiently. This maximizes the power supply efficiency.
Highlights:
 Reduces power consumption costs.
 Extends the service life of rectifiers.

5.2.4 Battery Management


 Supports equalized and float charging management, charge current limit, temperature
compensation, battery test, and capacity calculation.
 Supports battery balance detection and battery cell management (using a BMU). BMU is
short for battery management unit.
 Supports BLVD and intelligent battery hibernation.
Highlights: This feature maximizes battery utilization, which extends the battery lifespan and
reduces the OPEX.

5.2.5 Environment Monitoring


 Temperatures, humidity, water immersion, smoke generation, and door status monitoring
 One AC SPD alarm input, one DC SPD alarm inputs, six reserved alarm inputs
(DIN1–DIN3: indoor protection)
 Alarm outputs: eight (ALM1–ALM4: outdoor protection)
Highlight: This feature reduces costs for purchasing environment monitoring components
The monitoring unit reports the monitoring information to the EMS over dry contacts and
third-party equipment.

5.2.6 Human-Machine Interface and Remote Communication


RS485/RS232 port (BIN protocol supported); SNMP (PSNU01 required); Network
Ecosystem (NetEco)/M2000 supported

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 9


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

The monitoring unit communicates with rectifiers over the CAN bus and communications
with the host over the COM port or RS485/RS232 port. It supports NetEco protocol and
master/slave protocol and supports remote management and online upgrade. It monitors and
controls the TP48300B and reports alarms in a timely manner. Equipped with the PSNU01,
the TP48300B provides extended FE ports to support web access, which allows the
TP48300B to be managed by the NetEco remotely.
The TP48300B supports local and remote maintenance and provides a local keyboard and
LCD.
Highlight: Less OPEX

5.2.7 Maintenance from the Front


All AC input and output cables, DC load cables, battery cables, ground cables, and signal
cables can be operated from the front, which greatly facilitates product maintenance.
Highlights: This feature improves product maintainability.

5.2.8 D.G. Management


 The D.G., mains, and batteries work alternately.
If the mains fails, the D.G. starts based on the remaining battery capacity. When the
battery charge current is below the specified threshold, the D.G. shuts down. This
improves the D.G. efficiency.
 Small-D.G. output power limit management
The monitoring unit monitors D.G. startup signals. After the D.G. starts, the monitoring
unit limits the rectifier output power. The D.G. breaks down if the power exceeds the
upper threshold.
 User-defined time period, during which D.G. startup is prohibited to prevent disturbing
residents.
Highlights:
 Improves D.G. and battery utilization.
 Extends the battery lifespan.
 Prevents disturbing residents.
 Minimizes the OPEX.

5.2.9 Abundant Installation Modes


The TP48300B is compact and is easy to install. The TP48300B can be mounted on a floor,
on a 19-, 21-, or 23-inch standard rack, against a wall (at least 100 mm away from the wall),
or stacked on a wireless medium-sized cabinet BTS3900 (compatible with the TP48300/A).
Highlight:
 The installation modes are abundant.
 The installation is flexible and compatible with TP48300/A installation.

5.3 Specifications
The following table lists TP48300B-N04C1 specifications.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 10


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Category Item Specifications


Environmental Operating –10°C to +50°C
specifications temperature
Storage temperature –40°C to+70°C
Transportation –40°C to+70°C
temperature
Operating humidity 5%–95% RH (non-condensing)
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m
When the altitude is 2000–4000 m, the
operating temperature decreases by 1ºC for
each additional 200 m.
AC input Input system 220/380 V AC three-phase, four-wire input
system (compatible with single-phase input
systems)
Input voltage 85–300 V AC (phase voltage)
Input frequency 45–66 Hz (rated frequency: 50 Hz or 60 Hz)
Power factor ≥ 0.99 (at rated load)
DC output Output voltage –42 V to –58 V
range
Default output –53.5 V
voltage
Maximum output Number of rectifiers multiplied by the
power output power of a single rectifier
Regulated voltage ≤ ±0.6%
precision
Structure Dimensions (H x W 480 mm x 442 mm x 360 mm
x D)
Weight ≤ 30 kg (excluding rectifiers)
Protection level IP20 (with a cover)
Installation mode Floor mounted, wall mounted,
19/21/23-inch rack mounted; battery rack
mounted, and medium-sized cabinet
mounted
Maintenance mode Maintained from the front; cables routed
from the top
Cooling mode Cools as the ambient temperature drops.
The rectifier provides fans.
Surge protection AC input surge Class C

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 11


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Category Item Specifications


protection Standard surge discharge current: 20 kA
(8/20 µs)
Maximum surge discharge current: 40 kA
(8/20 µs)

5.4 Composition
5.4.1 Power Cabinet
A power cabinet consists of the rectifier, monitoring unit, AC PDU, and DC PDU.

Item TP48300B-N04C1 TP48300B-L04C1


Input system 220/380 V AC three-phase, 110 V, dual–live wire: 100–120 V
four-wire (L1, L2, L3, and N) AC or 200–240 V AC
AC input circuit One 3-pole 63 A circuit breaker One 2-pole 125 A circuit breaker
breaker
SPD Level C
Battery route Two 160 A fuses Two 160 A fuses
Load route LLVD: one 1-pole 100 A circuit LLVD: one 1-pole 100 A circuit
breaker and two 1-pole 80 A breaker and two 1-pole 80 A circuit
circuit breakers (5P reservered) breakers (5P reservered)
BLVD: one 1-pole 63 A circuit BLVD: one 1-pole 63 A circuit
breaker, one 1-pole 32 A circuit breaker, one 1-pole 32 A circuit
breaker, and two 1-pole 16 A breaker, and two 1-pole 16 A
circuit breakers (4P reservered) circuit breakers (4P reservered)

DC distribution description:
Power distribution solutions can be quickly customized.
 28P (maximum): reserved for DC power distribution
 Recommendation: BLVD + LLVD = 6P + 10P or BLVD + LLVD = 10P + 6P
 Allowed extended configuration: 12P 18 mm LLVD circuit breakers
 Standard battery power distribution: two fuses , and four circuit breakers could be
customized by AI+EC.

5.4.2 Rectifier
The rectifier converts AC input into stable –48 V DC output. Figure 5-2 shows a rectifier.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 12


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Figure 5-2 Rectifier

The rectifier panel has a Run indicator, a Protection indicator, and a Fault indicator. Figure 5-3
shows the rectifier panel.

Figure 5-3 Rectifier panel

(1) Run indicator (2) Protection indicator (3) Fault indicator

Indicator description:

Indicator Color Abnormal Exception Cause Measure


Run Green Off No AC input Check that the AC
indicator input voltage is
normal.
Rectifier fault Replace the rectifier.
Protection Yellow Steady on Overtemperature or Ensure that the
indicator undertemperature rectifier vent is
unblocked.
AC input overvoltage or -
undervoltage
Hibernation shutdown (The -
Protection indicator is
steady on and the rectifier
does not report any alarms.)
Fault Red Steady on Output overvoltage Hot-swap the
indicator protection rectifier once. If the
fault persists, replace
the rectifier.
Fan fault Replace the rectifier.
Overtemperature power-off Ensure that the
protection rectifier vent is
unblocked.
No output due to internal Replace the rectifier.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 13


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

faults

The rectifier has the following features:


 Works reliably and efficiently.
 Supports hot swap.
 Protects against input overvoltage and undervoltage, input and output overvoltage,
output short circuits, output current limiting, and overtemperature.
The following table lists the rectifier specifications.

Item Specifications
Input Input Single-phase, three-wire
features system
Input 85–300 V AC (rated voltage: 220 V AC)
voltage
Frequency 45–66 Hz (rated frequency: 50 Hz or 60 Hz)
Output Output –42 V DC to –58 V DC (rated voltage: –53.5 V DC)
features voltage
Output R4830G2: 2000 W (input voltage: 176–300 V AC)
power 840 W (input voltage: 85–175 V AC, linearly derated)
R4850N2: 2900 W (input voltage: 176–300 V AC)
1200 W (input voltage: 85–175 V AC, linearly derated)
R4850G2: 3000 W (input voltage: 176–300 V AC)
1250 W (input voltage: 85–175 V AC, linearly derated)
Regulated voltage precision ≤ ±0.6%
Efficiency R4830G2: ≥ 96% or 95% (230 V AC and 20%–90% load)
R4850N2: ≥ 92.5% or 91.5% (230 V AC and 35%–80%
load)
R4850G2: ≥ 96% or 95% (230 V AC and 30%–100% load)
Power factor ≥ 0.99 (220 V AC; rated output voltage; rated load)
Cooling mode Fan-cooled. The rectifier provides fans (temperature control
and speed adjustment).
Mechanical Dimensions R4830G2: 1 U x 105 mm x 281 mm
specification (H x W x D) R4850G2/N22: 1 U x 105 mm x 281 mm
s
Weight R4830G2: 2.0 kg
R4850G2/N2: 2.0 kg
Environment Operating –40°C to +75°C. When the temperature ranges from –40ºC
al temperature to –33ºC, the rectifier can start properly.
requirements R4830G2: When the temperature is 55ºC–65ºC, the load is
linearly derated to 80%.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 14


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Item Specifications
R4850N2: When the temperature is 50ºC–60ºC, the load is
derated linearly to 80%.
R4850G2: When the temperature is 55ºC–65ºC, the load is
linearly derated to 80%.
Storage –40ºC to 70ºC
temperature
Relative 5%–95% RH (non-condensing)
humidity

5.4.3 Monitoring Unit


The monitoring unit provides the monitoring CPU, power-on and power off drivers,
communications ports, and digital parameter and analog parameter monitoring.

Figure 5-4 Monitoring unit

Port Positions
Door-mounted SMU06C ports

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 15


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

(1) Battery temperature sensor port (2) Dry contact inputs (3) Dry contact outputs
(4) RS485/RS232 port (5) COM port

Communications Ports
The SMU06C provides two communications ports, which are described in Table 5-1.

Table 5-1 SMU06C communications ports

Port Communications Communications Protocol


Parameters
COM port Baud rate: 9600 bit/s Modbus protocol
RS485/RS232 port Baud rate: 9600 bit/s NetEco protocol and Modbus protocol

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 16


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Figure 5-5 Pins in a communications port

Table 5-2 Pins in a communications port

Pin Signal Description


1 COM_R+ Receives data.
2 COM_R-
3 NC -
4 COM_T+ Sends data.
5 COM_T-
6 GND Signal ground
7 NC -
8 NC -
9 RS485_T+ Sends data.
10 RS485_T-
11 RS232_R Receives data.
12 RS485_R+ Receives data.
13 RS485_R-
14 GND Signal ground
15 RS232_T Sends data.
16 NC -

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 17


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Sensors and Dry Contacts

Figure 5-6 Sensors and dry contacts

Table 5-3 Sensor and dry contact description

Port Type Silk Screen Description


Sensor port TEM-HUM Temperature and humidity
sensor
WATER Water sensor
GATE Door status sensor
SMOKE Smoke sensor
BTEMP Battery temperature sensor
Dry contact inputs DIN1 Dry contact input 1
NOTE DIN2 Dry contact input 2
For details about the alarms
associated with dry contact DIN3 Dry contact input 3
inputs, see the power system
user manual. DIN4 Dry contact input 4
DIN5 Dry contact input 5
DIN6 Dry contact input 6
Dry contact outputs ALM1 Dry contact output 1

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 18


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Port Type Silk Screen Description


NOTE ALM2 Dry contact output 2
For details about the alarms
associated with dry contact ALM3 Dry contact output 3
outputs, see the power system
user manual. ALM4 Dry contact output 4
ALM5 Dry contact output 5
ALM6 Dry contact output 6
ALM7 Dry contact output 7
ALM8 Dry contact output 8

Table 5-4 Sensor pin definitions

Silk Screen No. Pin Definition


TEM-HUM 1 12 V
2 ENV_TEMP
3 12 V
4 ENV_HUM
WATER 1 12 V
2 WATER
3 GND
4 -
GATE 1 GATE+
2 GATE-
SMOKE 1 SMOKE
2 12 V
BTEMP 1 BTEM1
2 GND

The monitoring system has the following functions:

Type Function
Monitors the power  Monitors AC and DC information.
system in real time.  Monitors rectifier information.
 Monitors battery information.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 19


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Type Function
 Monitors temperature control information.
 Monitors ambient temperatures, battery temperatures, ambient
humidity, door status, smoke generation, and water intrusion.
 Monitors six input dry contacts.
Detects and reports  Alarms can be associated with dry contact outputs. A maximum
alarms in real time. of eight dry contact outputs are supported.
 There are four alarm severities: critical, major, minor, and
warning.
 Indicators and alarm sounds (mutable) inform users of alarms.
 2000 historical alarms can be recorded.
Supports multiple  RS485 protocol and BIN protocol
remote management  SNMP: implemented by installing the PSNU01.
modes.
 Supports the NetEco and M2000.
Supports flexible  Controls rectifier output voltages.
rectifier  Controls rectifier output currents.
management.
 Starts or shuts down each rectifier.
Supports effective Intelligent rectifier hibernation management
energy saving
management.
Supports  Battery charging management
comprehensive  Battery temperature compensation
battery management.
 High and low battery temperature alarm reports and protection
 Battery test management
 Battery current limiting management
 BLVD protection
 Battery imbalance detection
 Intelligent battery hibernation
Supports intelligent  Switches between the D.G. and batteries to save energy.
diesel generator  Limits rectifier output power based on the D.G. capacity and
(D.G.) management. loading percentage of the power system to ensure normal load
operation.

Panel:
The panel provides indicators, buttons, and an LCD. The panel is on the front door of the
cabinet and is connected to the monitoring board over a flat cable. Figure 6 shows the panel.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 20


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

Figure 5-7 Panel

(1) Alarm indicator (2) Run indicator (3) LCD


(4) Back button (5) Down button (6) Enter button
(5) Up button

Indicator description

Name Color Meaning Status Description


Run Green Run Off The SMU is faulty or has no
indicator indicator DC input.
Blinking at 0.5 The SMU is running properly
Hz and communicating with the
host properly.
Blinking at 4 Hz The SMU is running properly
but is not communicating with
the host properly.
ALM Red Alarm Off No critical or major alarm is
indicator indicator generated.
Steady on A critical or major alarm is
generated.

Button description

Button Description
▲ or ▼ Turns to the previous or next menu and sets parameter
values.

Cancel Returns to the previous menu.


Enter Enters the main menu from the standby screen, enters a
submenu from the main menu, or saves the settings of a
submenu item.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 21


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

SNMP module (optional):


An SNMP module converts RS485 into TCP/IP. It provides an FE port for the power system
that does not have the Ethernet communication function. The power system can communicate
with the NetEco over the FE port. Figure 5-8 shows the network diagram of the SNMP
module.
The SNMP module is optional and can be installed on the power cabinet door interior.

Figure 5-8 SNMP networking

SNMP module NetEco

Power system
DC
Signal

5.4.4 Battery Rack


Figure 5-9 Battery rack specification

Item Basic Battery Extended Assembled battery


Frame battery Frame Frame
External 750 mm x 600 750 mm x 600 1500 mm x 600 mm x 600
dimensions (H x mm x 600 mm mm x 600 mm mm
W x D)

Internal 338 mm x 552 338 mm x 552 338 mm x 552 mm x 600


dimensions for mm x 600 mm mm x 600 mm mm
battery (H x W x
D)
shelf load 250 kg/layer 250 kg/layer 250 kg/layer
capability
Fixing method Floor-mounted Extending unit Floor-mounted
Rack weight 11 kg 10 kg 21 kg

The following figure shows an installed battery rack.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 22


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

A basic battery rack can house two 48 V battery strings. If you require four battery strings,
install an extended battery rack.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 23


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal 5 TP48300B-N04C1 and TP48300B-L04C1

By using the installation fittings suitable for the TP48300/A battery rack, TP48300B
installation is compatible with TP48300/A installation

Figure 5-10 TP48300B installation using TP48300/A battery rack installation fittings

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 24


Copyright © Huawei Technologies Co., Ltd.
TP48300B-N04C1 and TP48300B-L04C1
Technical Proposal Disclaimer

Disclaimer

The information in this document may contain predictive statements including, but not limited to, statements
regarding future financial and operating results, future product portfolios, and new technologies. There are a
number of factors in practice that cause actual results and developments to materially differ from those expressed
or implied in the predictive statements. Such information is provided for reference only and constitutes neither an
offer nor an acceptance. Huawei may change the information at any time without notice.
Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved.

Issue 01 (2013-09-14) Huawei Proprietary and Confidential 25


Copyright © Huawei Technologies Co., Ltd.

Potrebbero piacerti anche