Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Contents
1 Overview ................................................................................................................................... 1
2 XX Company Mini Indoor Power System ............................................................................. 2
2.1 Design Rules ......................................................................................................................................................... 2
2.2 Specifications ........................................................................................................................................................ 2
Disclaimer .................................................................................................................................. 25
1 Overview
The power system converts AC input into –48 V DC output to power communications
equipment. Equipped with batteries, the power system serves as an uninterruptible power
system (UPS). The power system consists of the power cabinet, rectifier, monitoring unit, AC
power distribution unit (PDU), and DC PDU.
2.2 Specifications
Table 2-1 Specifications
3.1 Introduction
[Select the following solution based on XX company's requirements.]
TP48300B-N04C1& L04C1 (TP48300B for short) provides a site power solution by working
with the AC power source, AC transfer switch (ATS), and batteries. Figure 3-1 shows a
typical solution.
Air conditioner
AC lighting
D.G. Transmission
Communications
power supply equipment
Other DC
equipment
Mains
AC
DC
Battery string 1 Battery string 2
(1)
(2)
(7)
(3)
(4)
(5)
(6)
3.2 Configurations
Determine configurations including the product model and quantity based on project
requirements.
This section is applicable only to customer-constructed projects.
This project uses Huawei Mini power system TP48300B-N04C1 (including the monitoring
unit) and rectifier R4850G2. The basic configurations are as follows:
5.1 Introduction
The TP48300B is a new generation indoor Mini power system. It converts AC input into
stable –48 V DC for communications equipment. The TP48300B equipped with batteries
serve as a UPS. The TP48300B consists of the power cabinet, rectifier, monitoring unit, AC
PDU, and DC PDU.
The TP48300B-N04C1 provides BLVD and LLVD and supports three-phase AC input
systems (compatible with single-phase AC input systems). It has a maximum capacity of
300 A.
The TP48300B-L04C1 provides BLVD and LLVD and supports 110 V dual–live wire
input systems (compatible with single-phase input systems). It has a maximum capacity
of 300 A.
5.2 Features
5.2.1 AC-DC Conversion
The TP48300B-N04C1 supports 220/380 V AC three-phase, four-wire input systems
(compatible with single-phase, three-wire input systems):
220/380 V AC three-phase, four-wire
Rated voltage: 200–240 V AC or 346–415 V AC
Operating voltage: 85–300 V AC or 147–519 V AC
The TP48300B-L04C1 supports 110 V AC dual–live wire, two-wire input systems
(compatible with single-phase, three-wire input systems):
Rated voltage: 100–120 V AC or 200–240 V AC
Operating voltage: 85–300 V AC
DC output: –42 V DC to –58 V DC (default value: –53.5 V DC)
Highlights:
Flexible support for power grid systems
Wide AC input range: 85–300 V AC
The TP48300B can withstand root mean square (RMS) 320 V AC input voltage.
The monitoring unit communicates with rectifiers over the CAN bus and communications
with the host over the COM port or RS485/RS232 port. It supports NetEco protocol and
master/slave protocol and supports remote management and online upgrade. It monitors and
controls the TP48300B and reports alarms in a timely manner. Equipped with the PSNU01,
the TP48300B provides extended FE ports to support web access, which allows the
TP48300B to be managed by the NetEco remotely.
The TP48300B supports local and remote maintenance and provides a local keyboard and
LCD.
Highlight: Less OPEX
5.3 Specifications
The following table lists TP48300B-N04C1 specifications.
5.4 Composition
5.4.1 Power Cabinet
A power cabinet consists of the rectifier, monitoring unit, AC PDU, and DC PDU.
DC distribution description:
Power distribution solutions can be quickly customized.
28P (maximum): reserved for DC power distribution
Recommendation: BLVD + LLVD = 6P + 10P or BLVD + LLVD = 10P + 6P
Allowed extended configuration: 12P 18 mm LLVD circuit breakers
Standard battery power distribution: two fuses , and four circuit breakers could be
customized by AI+EC.
5.4.2 Rectifier
The rectifier converts AC input into stable –48 V DC output. Figure 5-2 shows a rectifier.
The rectifier panel has a Run indicator, a Protection indicator, and a Fault indicator. Figure 5-3
shows the rectifier panel.
Indicator description:
faults
Item Specifications
Input Input Single-phase, three-wire
features system
Input 85–300 V AC (rated voltage: 220 V AC)
voltage
Frequency 45–66 Hz (rated frequency: 50 Hz or 60 Hz)
Output Output –42 V DC to –58 V DC (rated voltage: –53.5 V DC)
features voltage
Output R4830G2: 2000 W (input voltage: 176–300 V AC)
power 840 W (input voltage: 85–175 V AC, linearly derated)
R4850N2: 2900 W (input voltage: 176–300 V AC)
1200 W (input voltage: 85–175 V AC, linearly derated)
R4850G2: 3000 W (input voltage: 176–300 V AC)
1250 W (input voltage: 85–175 V AC, linearly derated)
Regulated voltage precision ≤ ±0.6%
Efficiency R4830G2: ≥ 96% or 95% (230 V AC and 20%–90% load)
R4850N2: ≥ 92.5% or 91.5% (230 V AC and 35%–80%
load)
R4850G2: ≥ 96% or 95% (230 V AC and 30%–100% load)
Power factor ≥ 0.99 (220 V AC; rated output voltage; rated load)
Cooling mode Fan-cooled. The rectifier provides fans (temperature control
and speed adjustment).
Mechanical Dimensions R4830G2: 1 U x 105 mm x 281 mm
specification (H x W x D) R4850G2/N22: 1 U x 105 mm x 281 mm
s
Weight R4830G2: 2.0 kg
R4850G2/N2: 2.0 kg
Environment Operating –40°C to +75°C. When the temperature ranges from –40ºC
al temperature to –33ºC, the rectifier can start properly.
requirements R4830G2: When the temperature is 55ºC–65ºC, the load is
linearly derated to 80%.
Item Specifications
R4850N2: When the temperature is 50ºC–60ºC, the load is
derated linearly to 80%.
R4850G2: When the temperature is 55ºC–65ºC, the load is
linearly derated to 80%.
Storage –40ºC to 70ºC
temperature
Relative 5%–95% RH (non-condensing)
humidity
Port Positions
Door-mounted SMU06C ports
(1) Battery temperature sensor port (2) Dry contact inputs (3) Dry contact outputs
(4) RS485/RS232 port (5) COM port
Communications Ports
The SMU06C provides two communications ports, which are described in Table 5-1.
Type Function
Monitors the power Monitors AC and DC information.
system in real time. Monitors rectifier information.
Monitors battery information.
Type Function
Monitors temperature control information.
Monitors ambient temperatures, battery temperatures, ambient
humidity, door status, smoke generation, and water intrusion.
Monitors six input dry contacts.
Detects and reports Alarms can be associated with dry contact outputs. A maximum
alarms in real time. of eight dry contact outputs are supported.
There are four alarm severities: critical, major, minor, and
warning.
Indicators and alarm sounds (mutable) inform users of alarms.
2000 historical alarms can be recorded.
Supports multiple RS485 protocol and BIN protocol
remote management SNMP: implemented by installing the PSNU01.
modes.
Supports the NetEco and M2000.
Supports flexible Controls rectifier output voltages.
rectifier Controls rectifier output currents.
management.
Starts or shuts down each rectifier.
Supports effective Intelligent rectifier hibernation management
energy saving
management.
Supports Battery charging management
comprehensive Battery temperature compensation
battery management.
High and low battery temperature alarm reports and protection
Battery test management
Battery current limiting management
BLVD protection
Battery imbalance detection
Intelligent battery hibernation
Supports intelligent Switches between the D.G. and batteries to save energy.
diesel generator Limits rectifier output power based on the D.G. capacity and
(D.G.) management. loading percentage of the power system to ensure normal load
operation.
Panel:
The panel provides indicators, buttons, and an LCD. The panel is on the front door of the
cabinet and is connected to the monitoring board over a flat cable. Figure 6 shows the panel.
Indicator description
Button description
Button Description
▲ or ▼ Turns to the previous or next menu and sets parameter
values.
Power system
DC
Signal
A basic battery rack can house two 48 V battery strings. If you require four battery strings,
install an extended battery rack.
By using the installation fittings suitable for the TP48300/A battery rack, TP48300B
installation is compatible with TP48300/A installation
Figure 5-10 TP48300B installation using TP48300/A battery rack installation fittings
Disclaimer
The information in this document may contain predictive statements including, but not limited to, statements
regarding future financial and operating results, future product portfolios, and new technologies. There are a
number of factors in practice that cause actual results and developments to materially differ from those expressed
or implied in the predictive statements. Such information is provided for reference only and constitutes neither an
offer nor an acceptance. Huawei may change the information at any time without notice.
Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved.