Sei sulla pagina 1di 2

PDS1-400K

Features

 Bi-direction DC-DC converter


 PV / Battery input available
 Flexible derating available
 High power density
 Field-replaceable modular design
 Shared or separated DC bus

Specification

PDS1-400K
LV PV input mode
HV DC bus voltage LV voltage+40V ~ 850V
HV DC bus current 0~100A×8
LV PV input voltage 250~840V
LV PV input current 0~120A×8
Power rating 50kW×8
LV battery dis-/charge mode
HV DC bus voltage LV voltage+40V ~ 850V
HV DC bus current 0~100A×8
LV battery voltage 250~840V
LV battery current 0~120A×8
Power rating 50kW×8
Physical
Cooling Forced air cooling
Noise 70dB
Enclosure IP20/NEMA1
Max elevation 3000m/10000feet (> 2000m/6500feet derating)
Operating ambient
-20°C to 50°C (De-rating over 45°C)
temperature
Humidity 0~95% (No condensing)
Size (W×H×D) 1100×2060×800mm
Weight 600kg
Installation Floor standing
Other
Peak efficiency 98.60%

Protection OTP, OVP/UVP, EPO, Fan/Relay Failure, OLP

Configurable protection
Upper/Lower Voltage, Battery EOD voltage.
limits
Display Touch Screen
Communication RS485,CAN,Ethernet
Isolation Non-isolation
CE LVD IEC 62109/62477,
Compliant CE EMC IEC 61000
UL1741

Volt-Ampere Curve (LV port)

LV current

ABCD:DC BUS voltage 700V


EFCD:DC BUS voltage 850V
A J G B
120A
E F
100A
H
C 70kW

50kW
I

D
LV voltage
0
250V 500V 583V 700V 840V

Applications
 DC coupled PV+Energy Storage System
 Low voltage battery adaption in energy storage system

Potrebbero piacerti anche