B SERIES
R-410A or R-22 - Multi-Position - 50HZ/60HZ (Export Only)
E N G I N E E R I N G D ATA Bulletin No. 490137
September 2009
FEATURES
CABINET
Enhanced grommets - secure & tight.
Multi-position available from factory and field
convertible.
Side return right- or left-hand capable on 12 to 30 and
36 size models.
All air handlers are basiloid packaged with bar coding
and full description on label.
Magnetic filter rack door makes for easy filter
replacement and a tight seal for less air leakage.
Fiberglass air filter comes with every air handler and
filter racks accepts readily available size filters.
Rigid beige painted cabinets constructed of heavy
gauge steel to prevent corrosion and are lined with high
quality
9.5 mm (5/8 in.) foil faced insulation to prevent
sweating.
EVAPORATOR COIL
Patented lanced fin design and internally enhanced
copper tubing.
Suitable for use with R-22 and R-410A.
Dual 19 mm (3/4 in.) FPT left and right condensate
drain connections.
Drain pans are molded of corrosion proof high
temperature engineering polymer.
Coils are air pressure tested at 72 kPa (500 PSI), 3.5 to 17.6 kW (1 to 5 Tons)
pressure tested with Helium, sealed and then charged
with dry air. Optional Electric Heat - 2.5 to 25 kW
Optional Hot Water Heat -
Florator, non-bleed A/C or HP TXV’s available factory 2.6 to 36.3 kW (9,000 to 124,000 Btuh)
installed. Screw-on TXV’s also available for field
installation.
HOT WATER HEAT
Suitable for potable water systems.
Hot Water Heat Kits available both factory and field
installed. 1. Pump timer activates pump for 1 minute every 6
hours eliminating stagnant water in hot water coil.
Easy to replace hot water coil. Remove one screw and
slide out. 2. 24 VAC isolation valve control-allows for zoning
control.
Optional factory installed circulating pump fully encased
in cabinet. 3. Auxiliary contacts for water heater or boiler
activation.
Purge valve on hot water coil allows for manual release
of any air trapped in coil during installation or servicing. 4. Freeze protection- standard factory installed,
activates at 4°C (40°F) and deactivates at 21°C (70°F).
Water connections 7/8 in. ODF (for 3/4 in. water pipe)
on 12 to 30, and 36 size models and 1-1/8 in. ODF (for 5. Thermostat connections.
1 in. water pipe) on 31, and 37 - 60 size models.
6. Time delay for blower activation:
Control board comes standard factory installed on all
Air Handlers and includes the following features: • 60 seconds (tap in OFF position)
Features are compatible with both factory and field • 54°C (130°F) Aquastat (tap in ON position)
installed circulating pumps. Note: Aquastat tap only included if ordered
FEATURES
Choose your own cooling/heating airflow settings, by Factory installed fan time delay postpones blower
selecting taps A-D on the variable-speed control board. shutoff 30 seconds in heating mode and 45 seconds in
cooling mode.
Fine tune your airflow setting by selecting (+) tap to
increase airflow by 10% and (-) tap to decrease airflow
by 12%.
Soft start feature runs airflow at 82% of cooling airflow
for first 7.5 minutes of operation.
Time Delay- 1.5 minute blower off delay at the end of a
call for cooling.
B C R M A1 2 24 S 2P 3
MOTOR TYPE 2 = 208/240 V, 60 Hz, 1 ph. w/ time delay & 130°F Aquastat
Horizontal Drain Pan Position* speed blower options and 2N, 3N, & 4N Heat options)
L = Left-Hand
R = Right-Hand HEAT
2 = 3 Kw ELEC.**
V = Vertical Only
2 = Piston R-22
UNIT SIZE
Connections Suction line (o.d.) - mm (in.) sweat 19 (3/4) 19 (3/4) 19 (3/4) 19 (3/4) 19 (3/4) 26 (7/8)
Liquid line (o.d.) - mm (in.) sweat 9.5 (3/8) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8)
Condensate - in. fpt (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4
Circulating pump connection size - in. 7/8 7/8 7/8 7/8 7/8 7/8
Three Wheel nominal diameter x width - mm (in.) 229 x 152 (9 x 6) 254 x 203 (10 x 8)
Speed
Blower Blower motor output - W (hp) 149 (1/5) 187 (1/4) 224 (1/3)
Nominal air volume - L/s (cfm) 190 (400) 285 (600) 380 (800) 380 (800) 470 (1000) 470 (1000)
Variable Wheel nominal diameter x width - mm (in.) --- --- --- 229 x 152 254 x 203 254 x 203
Speed (9 x 6) (10 x 8) (10 x 8)
Blower
Blower motor output - W (hp) --- --- --- 224 (1/3) 373 (1/2) 373 (1/2)
Cooling range - L/s (cfm) --- --- --- 285 - 470 285 - 565 285 - 565
(600 - 1000) (600 - 1200) (600 - 1200)
Heating range L/s (cfm) --- --- --- 285 - 470 520 - 565 520 - 565
(600 - 1000) (1100 - 1200) (1100 - 1200)
Filters Size of filter - mm (in.) 305 x 508 305 x 508 305 x 508 406 x 508 406 x 508 406 x 635
(12 x 20) (12 x 20) (12 x 20) (16 x 20) (16 x 20) (16 x 25)
Shipping Data -1 package - kg (lbs.) less hot water coil 54 (120) 54 (120) 54 (120) 59 (130) 64 (140) 68 (150)
ELECTRICAL DATA
Available Voltage (three speed) 1
120V or 208/240V, 60Hz, 1 ph or 220V, 50Hz, 1 ph
Full load amps at 120V 2.0 3.2 3.2 5.3 5.3 7.1
Full load amps at 240V 1.4 1.4 1.8 2.2 2.2 2.6
Full load amps at 120V --- --- --- 4.8 5.4 5.4
Full load amps at 240V --- --- --- 2.4 2.7 2.7
Amps 0.52
1
Electric heat models not available in 120 V, 60 Hz.
Connections Suction (vapor) line (o.d.) - mm (in.) sweat 19 (3/4) 26 (7/8) 26 (7/8) 26 (7/8) 26 (7/8)
Liquid line (o.d.) - mm (in.) sweat 9.5 (3/8) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8)
Condensate - in. fpt (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4
Circulating pump connection size - in. 7/8 7/8 7/8 7/8 7/8
Three Wheel nominal diameter x width - mm (in.) 254 x 203 254 x 254
Blower (10 x 8) (10 x 10)
Blower
Blower motor output - W (hp) 224 (1/3) 224 (1/3) 373 (1/2) 560 (3/4) 560 (3/4)
Nominal L/s (cfm) 565(1200) 565 (1200) 660 (1400) 755 (1600) 945 (2000)
Variable Wheel nominal diameter x width - mm (in.) --- 254 x 203 254 x 203 254 x 203 254 x 254
Speed (10 x 8) (10 x 8) (10 x 8) (10 x 10)
Blower
Blower motor output - W (hp) --- 373 (1/2) 373 (1/2) 560 (3/4) 746 (1)
Cooling range - L/s (cfm) --- 285 - 565 470 - 710 660 - 850 800 - 895
(600 - 1200) (1000 - 1500) (1400 - 1800) (1700 - 1900)
Heating range L/s (cfm) --- 520 - 565 565 - 710 755 - 850 800 - 895
(1100 - 1200) (1200 - 1500) (1600 - 1800) (1700 - 1900)
Filters Size of filter - mm (in.) 406 x 508 406 x 635 406 x 635 406 x 635 457 x 635
(16 x 20) (16 x 25) (16 x 25) (16 x 25) (18 x 25)
Shipping Data -1 package - kg (lbs.) less hot water coil 64 (140) 68 (150) 95 (210) 104 (230) 109 (240)
ELECTRICAL DATA
Available Voltage (three speed) 1
120V or 208/240V, 60Hz, 1 ph or 220V, 50Hz, 1 ph
Amps 0.52
1
Electric heat models not available in 120 V, 60 Hz.
42 and 48
11.1 LPM (3 GPM) 14.8 LPM (4 GPM) 18.5 LPM (5 GPM)
Coil Entering
Water Water Water
Size Water
Pressure L/s cfm L/s cfm L/s cfm Pressure L/s cfm L/s cfm L/s cfm Pressure L/s cfm L/s cfm L/s cfm
No.of Temp.
Drop Drop Drop
rows
°C °F Pa in. ft. 661 1400 708 1500 755 1600 Pa in. ft. 661 1400 708 1500 755 1600 Pa in. ft. 661 1400 708 1500 755 1600
49 120 199 0.8 9.64 32,883 9.87 33,695 10.09 34,441 348 1.4 10.61 36,190 10.91 37,221 11.19 38,173 497 2.0 11.27 38,464 11.62 39,660 11.93 40,722
60 140 199 0.8 13.64 46,541 13.98 47,701 14.29 48,766 323 1.3 15.00 51,167 15.44 52,686 15.82 53,996 497 2.0 15.92 54,329 16.42 56,032 16.89 57,617
3
71 160 199 0.8 17.69 60,372 18.14 61,888 18.55 63,279 323 1.3 19.43 66,310 20.00 68,229 20.52 70,004 472 1.9 20.62 70,350 21.27 72,572 21.87 74,640
82 180 224 0.9 21.78 74,330 22.33 76,209 22.84 77,933 323 1.3 23.91 81,575 24.60 83,951 25.25 86,149 472 1.9 25.35 86,486 26.15 89,234 26.90 91,792
49 120 249 1.0 11.32 38,636 11.61 39,631 11.88 40,540 423 1.7 12.52 42,707 12.90 44,006 13.25 45,204 646 2.6 13.32 45,457 13.77 46,988 14.19 48,409
60 140 249 1.0 16.00 54,582 16.41 55,996 16.79 57,288 423 1.7 17.67 60,284 18.21 62,131 18.71 63,834 646 2.6 18.79 64,115 19.43 66,290 20.02 68,310
4
71 160 249 1.0 20.72 70,692 21.26 72,535 21.75 74,216 423 1.7 22.87 78,023 23.57 80,428 24.22 82,647 622 2.5 24.30 82,925 25.13 85,756 25.90 88,386
82 180 249 1.0 25.47 86,924 26.14 89,200 26.75 91,276 398 1.6 28.10 95,879 28.97 98,851 29.77 101,592 597 2.4 29.85 101,845 30.87 105,340 31.82 108,588
60
11.1 LPM (3 GPM) 14.8 LPM (4 GPM) 18.5 LPM (5 GPM)
Coil Entering
Water Water Water
Size Water
Pressure L/s cfm L/s cfm L/s cfm Pressure L/s cfm L/s cfm L/s cfm Pressure L/s cfm L/s cfm L/s cfm
No.of Temp.
Drop Drop Drop
rows
°C °F Pa in. ft. 849 1800 897 1900 944 2000 Pa in. ft. 849 1800 897 1900 944 2000 Pa in. ft. 849 1800 897 1900 944 2000
49 120 298 1.2 10.93 37,308 11.12 37,936 11.29 38,521 522 2.1 12.20 41,636 12.44 42,459 12.67 43,229 796 3.2 13.09 44,672 13.38 45,650 13.65 46,570
60 140 298 1.2 15.47 52,797 15.74 53,693 15.98 54,526 522 2.1 17.25 58,874 17.60 60,047 17.92 61,145 796 3.2 18.50 63,115 15.97 54,508 19.29 65,818
3
71 160 298 1.2 20.07 68,481 20.41 69,650 20.73 70,737 497 2.0 22.36 76,308 22.81 77,839 23.23 79,273 771 3.1 23.96 81,747 24.49 83,564 24.99 85,273
82 180 298 1.2 24.71 84,309 25.13 85,756 25.53 87,101 497 2.0 27.52 93,886 28.07 95,781 28.59 97,555 771 3.1 29.46 100,517 30.12 102,764 30.74 104,879
49 120 274 1.1 12.80 43,662 13.01 44,406 13.22 45,095 472 1.9 14.39 49,104 14.69 50,118 14.97 51,065 721 2.9 15.50 52,882 15.86 54,114 16.20 55,271
60 140 274 1.1 18.07 61,666 18.38 62,721 18.67 63,698 472 1.9 20.32 69,318 20.74 70,759 21.13 72,104 696 2.8 21.86 74,605 22.38 76,356 22.86 77,999
4
71 160 274 1.1 23.40 79,853 23.80 81,224 24.18 82,492 448 1.8 26.30 89,723 26.84 91,598 27.36 93,347 696 2.8 28.29 96,514 23.09 78,793 29.58 100,931
82 180 274 1.1 28.77 98,172 29.27 99,863 29.73 101,427 448 1.8 32.32 110,265 32.99 112,579 33.63 114,739 671 2.7 34.75 118,557 35.57 121,369 36.34 124,009
All capacities are based on 21°C (70°F) entering air temperature.
For entering air temperatures other than 21°C (70°F) use the following capacity correction factors:
22.2°C (72°F) x 0.982, 20°C (68°F) x 1.02, 18.8°C (66°F) x 1.04.
Glycol correction factors: (10% X 0.98), (20% X 0.95), (30% X 0.92), (40% X 0.88)
(1) From the 10.5 kW heating capacity tables select a hot water coil that supplies at least 17.6 kW at 565 L/s, 82°C water temperature
The 3 row coil supplies 20.2 kW @ 14.8 LPM, 0.5 kPa pressure drop 20.2
Correct capacity for 40% glycol (correction factors found below capacity chart) X 0.88
Corrected coil heating capacity (kW) = 17.7
(4) Now select a pump that supplies 14.8 LPM with at least 2.0 m head capability.
Note: If desired, recalculation can be done with another line size to vary pump requirement.
Upflow Upflow
As shipped from factory As shipped from factory
(return in bottom or left side) (return in bottom or right side)
Liquid Liquid
Suction
Suction Suction
Drains Drains
Bottom/Filter Frame
Horizontal Right
Factory ready if ordered as multi-position
or field converted with horizontal drain pan kit
Bottom/Filter Frame
Suction
Liquid
Drains
Horizontal Left
Factory ready if ordered as multi-position
or field converted with horizontal drain pan kit Bottom/Filter Frame
Liquid
Suction
Drains
Suction
Liquid
Drains Either set Drains
may be used
Bottom/Filter
Frame Horizontal Right
Factory ready if ordered as multi-position
or field converted with horizontal drain pan kit
Suction
Liquid
Drains
Horizontal Left
Factory ready if ordered as multi-position
or field converted with horizontal drain pan kit Bottom/Filter
Frame
Liquid
Suction
Drains
Line voltage
24 V
Right hand side
Optional field
installed filter
Liquid Optional field
rack installed filter
rack
Suction Suction
B C
Line voltage
Right, Left, and Top Side
24 V
Right hand side
Suction
Liquid
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. ©2009 Lennox Industries, Inc.