ControlNet Network Access Cable

(Cat. No. 1786-CP)

Installation Instructions

Use the ControlNet Network Access cable (1786-CP) to connect


a programming device to any intelligent device (i.e. workstation,
PLC processor, scanner or adapter) on ControlNet through the
network access port ( ).

1786CP

programing device end device


trunkline A

20139

Connections
shield shield
GND REF GND REF
8 1
+24V DC +24V DC
7 2
6 PTRx_H PTTx_H
3
PTRx_L PTTx_L
3.05m 5 4
(10') PTTx_L PTRx_L
4 5
3 PTTx_H PTRx_H 6
+24V DC +24V DC
2 7
GND REF GND REF
1 8
This cable is not a straightthrough cable.
Installation Instructions
ControlNet Network Access Cable
1786CP

ATTENTION: Do not use the1786-CP cable to provide more


than one connection to your ControlNet cable system;
this connection could result in possible network failures.
1786CP
do not use the 1786CP cable to connect
your programming device to ControlNet
two ways simultaneously

1786CP

do not use the 1786CP cable


to connect a scanner or adapter
module to a PLC processor

1786CP
do not use the 1786CP cable to
connect two separate ControlNet
segments

20140

For additional information on making connections to ControlNet,


see the ControlNet Cable System Planning and Installation Manual
(publication 1786-6.2.1).
ControlNet is a trademark; PLC is a registered trademark of Allen-Bradley, Inc.

With offices in major cities worldwide


Publication 17862.6 March 1994 PN 95511679
Copyright 1994 AllenBradley Company, Inc. Printed in USA