MEMORIAS DE CALCULO

CUADRO DE CALCULO REGULACION Y PERDIDAS EN CONDUCTORES


Carga I Corriente Id Proteccion Distancia Momento Acometida en Regulación % Pérdidas
SISTEMA DE
Tramo
TENSION
Factor K Resistencia Ω
kVA Amperios In*1,25 Amperios Metros Kva-m AWG Parcial Total R<3% I2XR(W) %

ACOMETIDA TABLERO 30.00 83.27 104.09 100 20 600.00 3x2 F+1x4N+1x8 T CU 3Ø 208/120V 0.0015 0.9000 1.9000 0.6230 2.16 0.01

CIRCUITO ILUMINACION 1.00 8.3 10.4 1X20 20 20.00 1x12 F+1x12n+1#12 T CU 1Ø 120V 0.087 1.7400 2.7400 6.5600 0.22778 0.02278
REFLECTORES 0.90 7.5 9.4 1X20 50 45.00 1x12 F+1x12n+1#12 T CU 1Ø 120V 0.087 3.9150 4.9150 6.5600 0.07380 0.00820
TOMAS 2 0.50 4.2 5.2 1X20 40 20.00 1x12 F+1x12n+1#12 T CU 1Ø 120V 0.087 1.7400 2.7400 6.5600 0.02847 0.00569
CONGELADOR 2.00 9.6 12.0 2X30 30 60.00 2x10 F+1x10N+1#10 T CU 2Ø 208V 0.0075 0.4500 1.4500 3.9400 0.12143 0.00607
MANEJADORA AIRE 1 4.80 13.3 16.7 3X40 40 192.00 3x8 F+1x8 N+1x10 T CU 3Ø 208/120V 0.0055 1.0560 2.0560 2.5600 0.11362 0.00237
MANEJADORA AIRE 2 6.00 16.7 20.9 3X40 40 240.00 3x8 F+1x8 N+1x10 T CU 3Ø 208/120V 0.0055 1.3200 2.3200 2.5600 0.17753 0.00296
TOMAS TRIFASICAS 3.00 8.3 10.4 3X40 30 90.00 3x8 F+1x8 N+1x10 T CU 3Ø 208/120V 0.0055 0.4950 1.4950 2.5600 0.05918 0.00197

ILUMINACION EMERGENCIA 0.50 4.2 5.2 1X20 50 25.00 1x12 F+1x12n+1#12 T CU 1Ø 120V 0.087 2.1750 3.1750 4.5300 0.01573 0.00315
TABLERO REGULADO 2.00 9.6 12.0 1x30 30 60.00 1x10 F+1x10N+1#10 T CU 1Ø 120V 0.0505 3.0300 4.0300 2.9700 0.09153 0.00458
MANEJADORA NEVERAS 01 4.00 11.1 13.9 3X40 46 184.00 3x10 F+1x10 N+1x10 T CU 3Ø 208/120V 0.008 1.4720 2.4720 2.9700 0.07960 0.00199
MANEJADORA NEVERAS 2 3.00 8.3 10.4 3x30 46 138.00 3x10 F+1x10 N+1x10 T CU 3Ø 208/120V 0.008 1.1040 2.1040 2.9700 0.04477 0.00149

( r  cos   x  sen ) V (%)  (kVA  m)  k


k 
5  kV 2

CALCULOS ECONÓMICO DE CONDUCTORES EN BT "ALIMENTADOR PRINCIPAL"


PRECIO DISTANCIA PRECIO I PÉRDIDAS VALOR KW/H VALOR DE PERDIDAS COSTO TOTAL
ACOMETIDA KVA-M
METRO METROS TOTAL AMP I2XR(KW) PROMEDIO 20 AÑOS 8 HORAS/DIA PRECIO + PERDIDAS
3#2 F+1x4N+1x8 T CU 12.0 360.0 83.3
$ 58,021.43 $ 696,257.10 2.16 $ 460.00 $34,817,697 $35,513,954
Resistencia eléctrica c.a. y reactancia inductiva para Cables de Cobre,
instalación trifásica para 600V a 60Hz y 75oC. Tres conductores sencillos en tubo conduit (Tabla 9
De La NTC 2050)

Resistencia en c.a. Resistencia en c.a.


alambres de cobre alambres de aluminio
Reactancia (XL) descubiertos descubiertos

Calibra AWG Conduit de Conduit de Conduit de Conduit de Conduit de Conduit de


o Kcmil PVC y Al acero PVC acero PVC acero
14 0.19 0.24 10.17 10.17
12 0.177 0.223 6.56 6.56 10.49 10.49
10 0.164 0.207 3.94 3.94 6.56 6.56
8 0.171 0.213 2.56 2.56 4.27 4.27
6 0.167 0.21 1.61 1.61 2.66 2.66
4 0.157 0.197 1.02 1.02 1.67 1.67
3 0.154 0.194 0.82 0.82 1.31 1.31
2 0.148 0.187 0.623 0.623 1.05 1.05
1 0.151 0.187 0.525 0.525 0.82 0.82
1/0 0.144 0.18 0.394 0.394 0.656 0.656
2/0 0.141 0.177 0.328 0.328 0.525 0.525
3/0 0.138 0.171 0.253 0.259 0.427 0.427
4/0 0.135 0.167 0.203 0.207 0.328 0.328 𝑘=((𝑟×cos⁡𝜃+
250 0.135 0.171 0.171 0.177 0.279 0.282
300 0.135 0.167 0.144 0.148 0.233 0.236
350 0.131 0.164 0.125 0.128 0.2 0.206
400 0.131 0.161 0.108 0.115 0.177 0.18
500 0.128 0.157 0.089 0.095 0.141 0.148
600 0.129 0.157 0.075 0.082 0.118 0.125
750 0.125 0.157 0.065 0.069 0.095 0.102
1000 0.121 0.151 0.049 0.059 0.075 0.082
CALCULO DEL VALOR DE K TRIFASICO 208 CALCULO DEL VALOR DE K

Tension de Factor de SEN Tension de


K ARCOSFP
Linea (VL) Potencia (ARCOSFP) Linea (VL)

208 0.95 0.0146 0.3122 0.3176 120


208 0.9 0.0084 0.4359 0.4510 120
208 0.9 0.0055 0.4359 0.4510 220
208 0.9 0.0036 0.4359 0.4510
208 0.9 0.0023 0.4359 0.4510
208 0.9 0.0019 0.4359 0.4510
208 0.9 0.0015 0.4359 0.4510

𝑘=((𝑟×cos⁡𝜃+𝑥×𝑠𝑒𝑛𝜃))/(10×𝑘𝑉^2 )
CALCULO DEL VALOR DE K MONOFASICO 110V

Factor de SEN
K ARCOSFP
Potencia (ARCOSFP)

0.95 0.08752 0.3122 0.3176


0.9 0.05050 0.4359 0.4510
0.9 0.00990 0.4359 0.4510
CALCULO POR CAPACIDAD DE CORRIENTE
(AMP)
Datos de la Carga
Tipo de Lampara 100 KVA
Factor de Demanda 1
Carga nominal: 100000 VA
Tension del sistema: 440 V
Fp: 0.9
Eff: 100 %
Factor de diseño: 125 %
Corriente: 131.22 A
Corriente de Diseño 164.02
Datos del Conductor
Calibre: 2 AWG/MCM
Capacidad nominal: #VALUE! A
Factor correcion Temp: 0.91
Conductores por fase: 2
Capacidad Total: #VALUE! A
CALIBRE TEMP. MATERIAL COR. Temp.
8 75°C COBRE 36-40

Cap. Nominal 50 A
Factor Correc. 0.88
Capacidad 44 A

Tabla 310.16 CEN 1999

Ampacidades admisibles de los conductores aislados para tensiones nominales de 0 a 2000 V


y 60°c a 90°c con no mas de tres conductores portadores de corriente en una canalización,
cable o directamente enterrados, basadas en una temperatura ambiente de 30°c

Calibre COBRE ALUMINIO


60°C 75°C 90°C 60°C 75°C 90°C
TBS, SA,
SIS, FEP*, TBS, SA,
FEPB*, MI, SIS, THHN*,
RHH*, THHW*,
FEPW*,
RHW-2, RH*, RHW*, THW-2,
RH*, RHW*,
THHN*, THHW*, THWN-2,
THHW*,
THHW*, THW*, RHH*,
AWG/kcmil TW*, UF* THW*, TW*, UF*
THW-2*, THWN*, RHW-2,
THWN*,
THWN-2*, XHHW*, USE-2,
XHHW*,
USE-2, USE* XHH,
USE*, ZW*
XHH, XHHW,
XHHW*, XHHW-2,
XHHW-2, ZW-2
ZW-2
18 0 0 14 0 0 0
16 0 0 18 0 0 0
14 20 20 25 0 0 0
12 25 25 30 0 20 25
10 30 35 40 25 30 35
8 40 50 55 30 40 45
6 55 65 75 40 50 60
4 70 85 95 55 65 75
3 85 100 110 65 75 85
2 95 115 130 75 90 100
1 110 130 150 85 100 115
1/0 125 150 170 100 120 135
2/0 145 175 195 115 135 150
3/0 165 200 225 130 155 175
4/0 195 230 260 150 180 205
250 215 255 290 170 205 230
300 240 285 320 190 230 255
350 260 310 350 210 250 280
400 280 335 380 225 270 305
500 320 380 430 260 310 350
600 355 420 475 285 340 385
700 385 460 520 310 375 420
750 400 475 535 320 385 435
800 410 490 555 330 395 450
900 435 520 585 355 425 480
1000 455 545 615 375 445 500
1250 495 590 665 405 485 545
1500 520 625 705 435 520 585
1750 545 650 735 455 545 615
2000 560 665 750 470 560 630

TEMP AMB.
21-25 1.08 1.05 1.04 1.08 1.05 1.04
26-30 1 1 1 1 1 1
31-35 0.91 0.94 0.96 0.91 0.94 0.96
36-40 0.82 0.88 0.91 0.82 0.88 0.91
41-45 0.71 0.82 0.87 0.71 0.82 0.87
46-50 0.58 0.75 0.82 0.58 0.75 0.82
51-55 0.41 0.67 0.76 0.41 0.67 0.76
56-60 0.58 0.71 0.58 0.71
61-70 0.33 0.58 0.33 0.58
71-80 0.41 0.41
CALIBRE TEMP. Tension
2 90°C 2001-5000 V

Cap. Nominal 130 A

Capacidad 130 A

Tabla 310.73 CEN 1999


Ampacidades de cables triples aislados o de tres conductores de
cobre sencillos, en un conducto físicamente aislado, al aire libre,
basadas en temperaturas de conductor de 90°C en una temperatura
ambiente de 40°C

Calibre 2001-5000 V 5001-35000 V


AWG/kcmil 90°C 105°C 90°C 105°C
8 55 61
6 75 84 83 93
4 97 110 110 120
2 130 145 150 165
1 155 175 170 190
1/0 180 200 195 215
2/0 205 225 225 255
3/0 240 270 260 290
4/0 280 305 295 330
250 315 355 330 365
350 385 430 395 440
500 475 530 480 535
750 600 665 585 655
1000 690 770 675 755