GRZ100

Command protection signalling for tripping during a


FEATURES power swing.
Fully numerical distance protection relay Command protection for 2- or 3-terminal applications.
High speed operation typically 20ms Phase-segregated transfer trip (intertripping).
Time-stepped distance protection with four forward Transmission of binary signals for user-configurable
zones, two reverse zones, and one non-directional applications.
zone Transmission of measured values to be displayed at
Zone 1 extension protection the remote terminals.
Command protection distance schemes (PUP, POP, Synchronisation of the clocks at the various terminals.
BOP and UOP with week infeed and current reversal Enhanced fault-location accuracy by use of remote- end
logic) data in the case of 3-terminal applications.
Command protection DEF schemes (POP, BOP and Continuous monitoring of the communication channels,
UOP) with capability to provide dual-redundant channels in
Single- and/or three-phase trip the case of a 2-ended system, and automatic
High-resistance earth fault protection re-routing of signals in the event of a communi-
cation channel failure in a 3-ended system.
Overcurrent backup protection
Thermal overload protection APPLICATION
Overvoltage and undervoltage protection
GRZ100 is a full-scheme high-speed numerical distance
Switch-on-to-fault (SOTF) and stub protection relay for application to transmission lines in solidly earthed
Broken conductor detection networks, and further can be applied to resistance earthed
Breaker failure protection networks using directional earth fault protection for an earth
fault.
Out-of-step trip protection
Power swing blocking GRZ100 provides the following protection schemes.
VT failure detection Time-stepped distance protection
Single-shot (single/three/single+three phase) or Zone 1 extension protection
multi-shot (three phase) autoreclose Command protection (distance protection using
Fault location telecommunication)
Configurable binary inputs and outputs Overcurrent protection for SOTF and stub fault
Programmable logic for I/O configuration, alarms, Out-of-step trip protection
indications, recording, etc. Breaker failure protection
Automatic supervision
As a backup protection for high-resistance earth faults,
Metering and recording functions
GRZ100 provides the following four functions.
Menu-driven user interfaces
Directional earth fault protection
Front-mounted RS232C port for communication to a
Directional earth fault protection using
local PC and rear-mounted RS485, Fibre optic or
telecommunication
Ethernet LAN serial ports for communication to a
remote PC Directional or non-directional inverse time overcurrent
and earth fault protection
IRIG-B port for external clock
Definite time overcurrent and earth fault protection
Data communication with substation control and
automation systems is supported according to the GRZ100 can initiate high-speed single-shot autoreclose or
IEC 61850 and IEC 60870-5-103 standards. multi-shot autoreclose.
GRZ100 can be provided with integral digital communi-
cation channels for teleprotection signalling. Either one or GRZ100 provides the following metering and recording
two communication channels can be provided, suitable for functions.
relay-to-relay connection via fibre-optic links, or via Metering
electrical interfaces to a digital communication network. Fault recording
GRZ100 can be configured using the integral communi-
Event recording
cation channels to support the following functions:
Disturbance recording
Phase-segregated command protection distance
schemes (PUP, POP, BOP and UOP with week GRZ100 provides the following user interfaces for relay
infeed and current reversal logic). setting or viewing of stored data.
Phase-segregated command protection DEF Relay front panel; LCD, LED display and operation keys
schemes (POP, BOP and UOP).
Local PC

2
GRZ100
Remote PC

A local PC can be connected to the relay via the RS232C Ch1 Ch1

port on the front fascia of the relay. Either one or two rear RELAY A RELAY B
ports (RS485 or fibre optic) are provided for connection to a
(a) Two-ended system, single channel
remote PC and for IEC 60870-5-103 communication with a
substation control and automation system. Further, an Ch1 Ch1
Ethernet LAN port (TCP/IP) can be provided and
communication according to the IEC 61850 standard is also Ch2 Ch2
supported. RELAY A RELAY B

GRZ100 has four models which differ depending on (b) Two-ended system, dual redundant channels
whether or not the autoreclose or fault detector provided
with independent MPU and trip contact for fail-safe Ch2 Ch1
function have been included.
RELAY A

Model 200 - With autoreclose for single


series breaker scheme
Ch1 Ch2
Model 300 - With autoreclose for one-and-a- Ch2
Ch1
series half breaker scheme RELAY C RELAY B

(c) Three-ended system, chain topology


Model 400 - With autoreclose for single
series breaker scheme
- With fault detector Ch2 Ch1
Model 500 - With autoreclose for one-and-a- RELAY A
series half breaker scheme
-With fault detector

Ch1 Ch2
The following GRZ100 models provide integral digital Ch2
Ch1
communication channels for protection signalling. These RELAY C RELAY B
models can also be applied using standard, external
teleprotection equipment. (d) Three-ended system, ring topology

Model - 2-terminal line application


Figure 1 Communication System Topologies
211B, (one communication channel)
214B, - With autoreclose for single breaker RELAY FUNCTIONS
216B scheme Time-Stepped Distance Protection
Model - 2-terminal line application
311B (one communication channel) GRZ100 provides maximum four-zone distance protection
- With autoreclose for (Z1, Z2, Z3, ZF) for forward faults, two-zone distance
one-and-a-half breaker scheme protection (ZR1, ZR2) for reverse faults and one non-
Model - 2- / 3-terminal line application directional distance protection (ZND) for both forward and
221B, (two communication channels) reverse faults.
224B, - With autoreclose for single breaker GRZ100 provides individual phase-fault measuring elements
226B scheme and earth-fault measuring elements for all types of fault.
Model - 2- / 3-terminal line application Direction measurement in GRZ100 is based on cross
321B, (two communication channels) polarization with voltage memory to ensure dependable
323B - With autoreclose for fault detection. GRZ100 uses an advanced distance
one-and-a-half breaker scheme measurement algorithm which achieves accurate fault
impedance measurement over a wide range of frequencies.
This superior algorithm also minimizes the effect of CT
In the GRZ100 models provided with an integral digital
saturation and gives stable performance with CVT
communication channel for protection signaling, four
transients.
communication topologies are available depending on the
model. Models 211/214/216/311B support configuration (a) The GRZ100 provides measuring zones with mho-based
only in Figure 1. Models 221/224/226/321/323B can support characteristics or quadrilateral characteristics, as shown in
all configurations. Configuration (b) and (d) offer security Figures 2 and 3.
against failure of a communication link. As shown in Figure 2, mho-based characteristics are
composed of mho element, offset mho element, reactance
element, and blinder element for phase fault protection and
earth fault protection.

3
GRZ100

(a) Phase fault measuring element (a) Phase fault measuring element

(b) Earth fault measuring element


(b) Earth fault measuring element Figure 3 Quadrilateral Characteristics
Figure 2 Mho-based Characteristics
ZR1 and ZR2 are reverse looking elements applied to
As shown in Figure 3, quadrilateral characteristics are Reverse Zone 1 and Zone 2, and used for local back-up
composed of reactance element, directional element and protection for busbar faults or transformer faults.
blinder element. Reverse zones for phase fault use the Z4 is used for detection of reverse faults in command
offset directional element to ensure reverse close-up fault protection.
detection. Z4S has an offset characteristic in order to assure detection
Z1 is applied to Zone 1 protection. The reactance line of Z1 of close-up phase faults.
can be configured to take a negative gradient when the
terminal is sending power, which prevents Z1 from Zone 1 Extension
overreaching for remote end faults. When telecommunications cannot be applied, a Zone 1
To ensure that GRZ100 can provide reliable time-delayed extension (Z1X) protection is provided for high-speed
tripping for close-up three-phase faults, the phase fault protection of any fault along the whole length of the
elements are reverse offset following Z1 operation. protected line.
Z2 is applied to Zone 2 which provides protection for the The reactance line of Zone 1 extension can take a negative
rest of the protected line not covered by Zone1 and backup gradient when the terminal is sending power, which
protection for the remote end busbar. prevents Zone 1 extension from overreaching.
Z3 is applied to Zone 3 which provides remote back-up
Command protection
protection for adjacent lines. Z3 is also used for detection of
forward faults in command protection. If Z3 is dedicated to The following four schemes are available for distance
command protection, then ZF can be used for Zone 3 protection using telecommunication.
instead of Z3 in time-stepped distance protection.

4
GRZ100
- Permissive Underreach Protection (PUP) Switch-on-to-fault Protection and Stub
- Permissive Overreach Protection (POP) Protection
- Unblocking Overreach Protection (UOP) Switch-on-to-fault (SOTF) protection is provided in order to
- Blocking Overreach Protection (BOP) detect faults that are present when a line or busbar is
energized.
POP and UOP are equipped with echo logic and weak
For 500 ms following circuit breaker closure, this function is
infeed tripping functions and can be used in the protection of
effective to protect against any switch-on-to-fault. A
lines with weak infeed or no infeed terminals. An
non-directional overcurrent element or distance measuring
undervoltage element is incorporated for the weak infeed
elements perform the SOTF protection.
tripping function.
Stub protection operates for a fault in a stub zone using an
Earth Return and Mutual Coupling overcurrent element.
Compensation
Voltage Transformer Failure Supervision
Z1G, Z2G, Z1XG and ZR1G for earth fault protection adopt
vectorial zero sequence current compensation to eliminate Failure in the voltage transformer (VT) secondary circuit
distance measuring errors due to the earth return of zero may cause false tripping by voltage dependent measuring
sequence current. When the GRZ100 is applied to a double elements. Therefore, the following voltage dependent
circuit line, in order to eliminate the influences of zero protections are blocked instantaneously when VT failure is
sequence mutual coupling, the zero sequence current for detected.
the parallel line can be introduced. ZR1G is not provided - Distance protection
with zero sequence mutual coupling compensation for the
- Directional earth fault protection
parallel line.
- Protection using telecommunications
Application to long and short lines - Out of step protection
The large capacitance of a long transmission line can VT failure is detected in any of the following cases.
adversely affect the measurement of fault impedance. GRZ100
employs an advanced charging current compensation technique - If residual voltage is detected when residual current is not
which gives significant improvement in impedance detected.
measurement for long transmission lines. - If undervoltage is detected when a current change is not
The suitability of a distance relay for application to short detected.
lines is not determined by its minimum setting but rather by
Power Swing Blocking
its measuring accuracy for high SIR conditions. GRZ100
provides highly accurate measuring elements suitable to be The relay provides a power swing blocking (PSB) function to
applied to short lines. prevent false tripping by distance measuring elements
during a power swing.
Fault Phase Selection
When a power swing is detected, all distance protection
GRZ100 provides single- and/or three-phase tripping zones and protection using telecommunications can be
functions. blocked independently. The non-directional zone, ZND, is
In order to perform extremely reliable single-phase tripping, an not blocked.
undervoltage element with current compensation is used for A power swing condition is detected using two PSB
fault phase selection. elements with quadrilateral characteristics shown in Figure 5.
The undervoltage element with current compensation can The outer PSB element PSBOUT encloses the inner
operate correctly even for a fault with a strong power source element PSBIN, the two elements being separated by a
and small voltage drop at the relay installation point. width of PSBZ. Further, GRZ100 provides PSBSZ and
PSBGZ for phase fault measuring elements and earth fault
The characteristics of the phase selection element are as
measuring elements respectively. Their functions and
shown in Figure 4.
characteristics are identical. PSBGZ provides
phase-segregated characteristics.
IZc I: Fault current
V: Fault voltage
If the impedance locus enters the PSBZ zone for more than
V Zc: Impedance setting a predetermined time (20 to 60ms), the PSB function will
Vk: Undervoltage setting
block the selected zones. The PSB function is reset after
500 ms when the impedance locus has moved outside the
I
PSB elements.
Vk
GRZ100 can provide high speed tripping for faults which
occur during a power swing condition, by utilising a
Figure 4 Phase selection element well-proven, dedicated negative sequence directional
element and any of the PUP, POP, UOP and BOP
command schemes.

5
GRZ100
X
The IDMT element has a reset feature with definite time reset.
PSBZ
If the reset time is set to instantaneous, then no intentional
delay is added. As soon as the energising current falls
PSBIN PSBOUT below the reset threshold, the element returns to its reset
condition.
0 R If the reset time is set to some value in seconds, then an
PSBZ PSBZ
intentional delay is added to the reset period. If the
energising current exceeds the setting for a transient period
without causing tripping, then resetting is delayed for a
PSBZ user-definable period. When the energising current falls
below the reset threshold, the integral state (the point
PSBZ: Impedance setting of PSB element
towards operation that it has travelled) of the timing function
Figure 5 Characteristics of power swing blocking element (IDMT) is held for that period.
This does not apply following a trip operation, in which case
Out-of-step Trip Protection resetting is always instantaneous.
The out-of-step tripping function is used to execute power
system separation at the optimum point when an out-of-step
Definite time overcurrent protection
occurs. Definite time overcurrent protection is enabled by the
An out-of-step is detected by using two distance measuring instantaneous overcurrent element and pick-up delay timer.
elements with quadrilateral characteristics as shown in
Figure 5. The element operates when the out-of-step locus
Broken Conductor Detection
passes from Zone A Zone B Zone C (or Zone C The unbalance condition caused by an open circuited
Zone B Zone A) and remains in Zones A and C for the conductor is detected by the broken conductor
detection time (TOST). detection function. An unbalance threshold with
X programmable definite time delay is provided.
OSTXF
High-resistance Earth Fault Protection
Impedance
locus
This protection provides high-resistance earth fault protection
Zone C Zone B Zone A
using the directional earth fault (DEF) element and the earth
fault overcurrent element as follows.

OSTR2 OSTR1 R Directional Earth Fault Protection

OSTXB
DEF element is used for time-delayed backup protection for
high-resistance faults.
Figure 6 Characteristics of out of step trip element
Directional Earth Fault Protection using
Breaker Failure Protection Telecommunication
When an overcurrent element remains in operation longer High-speed DEF protection using telecommunications is
than a pre-determined length of time following the output of provided by using a forward looking DEF element and a
a trip signal the associated circuit breaker is judged to have reverse looking DEF element. POP, UOP, and BOP
failed and adjacent circuit breakers can be tripped as a schemes can be selected with DEF protection using
back-up measure. telecommunications.
Two independent timers are available, one of which can be To enable single phase tripping for a high impedance earth
used to control the RETRIP of the original circuit breaker(s). The fault, GRZ100, when equipped with the optional integral
second timer is used to control the backtripping of adjacent communication channels, is provided with phase selection
circuit breakers. logic to obtain phase segregated trip permission signals.
For high-speed protection, an overcurrent element with The characteristics of the forward and reverse looking DEF
high-speed reset time is used to prevent a spurious re-trip elements are as shown in Figure 7.
or backtrip following a successful trip or re-trip action.
Backward DEF
Overcurrent Backup Protection
The IDMT(inverse definite minimum time) overcurrent
element is provided for non-directional inverse time -3V0
overcurrent protection. The IDMT element is available in
conformity with either of three IEC Standard characteristics 3I0
Forward DEF
(Standard inverse, Very inverse, Extremely inverse) or a
Long-time inverse.
The characteristics of each IDMT are shown in Figure 8. Figure 7 Characteristics of directional earth fault element

6
GRZ100
Inverse Time Overcurrent Earth Fault Thermal Overload Protection
Protection
The thermal overload feature provides protection for cables
Directional or non-directional inverse time overcurrent earth and other plant against the effects of prolonged operation
fault protection is provided using a combination of the IDMT under excess load conditions. A thermal replica algorithm is
(inverse definite minimum time) overcurrent earth fault applied to create a model for the thermal characteristics of
element and DEF element. The IDMT element is available the protected plant. Tripping times depend not only on the
in conformity with either of three IEC Standard level of overload current, but also on the level of prior load
characteristics (Standard inverse, Very inverse, and current, the thermal replica providing ‘memory’ of previous
Extremely inverse) or a Long-time inverse. conditions.
The characteristics of each IDMT are shown in Figure 8. The thermal characteristics of the system are defined by
entering settings for full load current and thermal time
The IDMT element for earth fault also has a reset feature
constant. The GRZ100 issues a trip according to the ‘cold’ and
with definite time reset.
‘hot’ curves specified in IEC60255-8 (see Figure 9), to
prevent the protected system from exceeding its thermal
capacity. The cold curve tripping times are applicable when
the system is first energised, while the hot curves are
relevant when the system has already been carrying some
prior load for a period of time. An alarm output is also
available to give early warning of high load current, set as a
percentage of thermal capacity.
Thermal overload protection is not provided with GRZ100-400
series and -500 series.
IEC60255-8 Thermal Characteristics

Thermal Curves (Cold Curve - no Thermal Curves (Hot Curve - 90%


prior load) prior load)

1000 1000

100
100

10

Operate Time (minutes)


Operate Time (minutes)

10

1
τ=100
τ=100
1
τ=50
τ=50
0.1
τ=20 τ=20

τ=10 τ=10
0.1
τ=5 0.01 τ=5
τ=2
τ=2
τ=1
τ=1
0.01 0.001
1 10 1 10
Ove rload Curre nt (M ultiple of k .IFLC) Ove rload Curre nt (M ultiple of k .IFLC)

 I2   I 2 − I P2 
t = τ .Ln  2 2  ;
t = τ .Ln  2 2 
 I − (k .I FLC )   I − (k .I FLC ) 
IEC60255-8 ‘Cold’ Curve IEC60255-8 ‘Hot’ Curve

t = time to trip for constant overload current I (seconds)


I = overload current (largest phase current) (pu)
IP = previous load current (pu)
k.IFLC (or Iθ) = thermal overload current setting (pu)
τ = thermal time constant (seconds)
Ln = natural logarithm

Figure 9 IEC60255-8 thermal characteristics

Overvoltage and Undervoltage Protection


Figure 8 IDMT operating time characteristics
GRZ100 provides two-stage overvoltage protections for
both phase-to-phase voltage input and phase-to-neutral
Definite Time Overcurrent Earth Fault
voltage input. The first stage can be set for inverse time or
Protection
definite time operation, and the second stage set for definite
Definite time overcurrent earth fault protection is provided time operation. In total, therefore, GRZ100 provides four
using the instantaneous overcurrent element and pickup- independent overvoltage thresholds.
delay timer. GRZ100 also provides four independent undervoltage
The definite time earth fault (EF) can be configured to issue thresholds with two-stage undervoltage protection for
either an alarm and/or trip signal. phase-to-phase voltage input and two-stage undervoltage
protection for phase-to-neutral voltage input. The
undervoltage protection is provided with an undervoltage

7
GRZ100
blocking function to prevent undervoltage tripping in the Synchronism Check
case of a dead line.
For the correct operation of three-phase autoreclose, voltage
Overvoltage Inverse Time Curves
Undervoltage Inverse Time Curves
and synchronism check are necessary. Characteristics of
1000.000 1000.000
the synchronism check element are shown in Figure 11.
VL: Line voltage
VB: Busbar voltage
100.000 θ: Synchronism
VL check angle
100.000

Operating Time (secs)


Operating Time (secs)

θ
10.000 0 deg
TMS =10
θ VB
TMS =5 TMS = 10

10.000
TMS =2 TMS = 5
θ
1.000
TMS =1
OV
TMS = 2
θ Operating zone

TMS = 1
UV
0.100 1.000 Figure 11 Synchronism check element
1 1.5 2 2.5 3 0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs) Applied Voltage (x Vs)

1 1
A detected slip cycle is determined by the following equation:
t=
(VVs)−1 xTMS t=
1− V ( Vs) xTMS θ
f=
Figure 10 Inverse time characteristics 180°ХTSYN
where,
Autoreclose f: slip cycle
Most faults on HV and EHV overhead transmission lines are θ: synchronism check angle setting
transient faults, which are removed following line TSYN: synchronism check timer setting
de-energization. After a short time, the hot gases disperse
and the air de-ionizes. After clearing the fault and deionizing One-and-a-half Breaker Scheme (Models 300
the fault arc, reclosing can be performed. GRZ100 provides and 500)
two autoreclose schemes, single-shot autoreclose and
GRZ100 performs two-breaker autoreclose in a one-and-
multi-shot autoreclose.
a-half breaker scheme.
The GRZ100 autoreclose function can be initiated by any of Only single-shot autoreclose is available in Models 300 and
the following high-speed protections. 500. Single-phase autoreclose, three-phase autoreclose or
- Protection using telecommunication single and three-phase autoreclose can be applied to the
two circuit breakers.
- Zone1 extension protection
Single-shot autoreclose Fault Detector (Models 400 through 500)
Single-shot reclosing can provide any of three auto- For ultra-critical applications, where security is the over-
reclose modes; single-phase autoreclose, three-phase riding concern and a two-out-of-two tripping philosophy is
autoreclose, and single-and three-phase autoreclose. specified, GRZ100 can be provided with an independent
fault detector. This fault detector contains its own main
In the single-phase autoreclose mode, only a faulted
processing unit (MPU) and trip contacts. The trip contacts
phase is tripped, and then reclosed if a single-phase
of the main protection are connected in series with the fault
earth fault occurs.
detector trip contacts to ensure completely fail-safe operation.
In the three-phase autoreclose mode, all three phases
The fault detector incorporates the following six fault
are tripped, and then reclosed regardless of the fault
detection elements.
mode, whether a single-phase fault or a multi-phase
fault has occurred. - Multi-level overcurrent element
In the single- and three-phase autoreclose mode, the - Current change detection element
single-phase is reclosed if a single-phase is tripped and - Earth fault overcurrent element
the three phases are reclosed if three phases are - Undervoltage element for earth fault detection
tripped. - Undervoltage element for phase fault detection
Multi-shot autoreclose - Undervoltage change detection element
In a multi-shot autoreclose, two- to four-shot reclosing Interfaces for Integral Communication
can be selected. The first shot is selected from any of
the four autoreclose modes available in the single-shot GRZ100 can be provided with the following interface(s) and
autoreclose scheme. linked to a dedicated optical fibre communication circuit or
multiplexed communication circuit (multiplexer) shown in
If reclosing by the first shot fails, three-phase tripping Figure 12.
and reclosing is applied for the second to fourth shots.
The electrical interface supports CCITT G703-1.2.1, -1.2.2,

8
GRZ100
-1.2.3, X.21(RS530) and RS422. Twisted pair cable with Event Record
shield is used for connecting the relay and multiplexer. In
The most recent 480 time-tagged events are stored with
the case of an optical link via a multiplexer, the optical
1ms resolution. 1024 events are available in the case of the
interface unit G1IF1 (optical to electrical converter) is
GRZ100-∗∗∗D series.
required for connecting to the multiplexer. The electrical
interface between the converter and the multiplexer The event recorder can be triggered by a Trip signal, by
supports CCITT G703 -1.2.1, -1.2.2, -1.2.3, and Overcurrent trigger elements (OC) and by Undervoltage
X.21(RS530). trigger elements (UV). In case of 'Trip', the trigger is
performed whenever tripping occurs. In case of OC/UV,
On(used) or Off(not used) is selectable.
GRZ100 Opt.
I/F Event trigger is freely selectable by using PLC.

Optical Fibre Events recorded are as follows.


64kbps - Tripping and reclosing
a) Optical interface
- Alarms
Optical - Change of binary input signal
GRZ100 Opt. I/F Multi-
I/F Unit plexer
- Change of relay setting
G1IF1
- Relay failure
(Option)
GI Opt. Fibre
< 2km Fault Record
SWL, 64kbps
A relay trip initiates fault recording. Time-tagged fault
CCITT-G703. data can be stored for the 8 most recent faults. Fault
ITUT-X.21
Bit rate: 64kbps record items are as follows.
b) Optical interface using multiplexer - Date and time
- Faulted phase
GRZ100 Elec. Multi- - Phases tripped
I/F plexer
- Tripping mode
Twisted pair cable - Fault location
CCITT-G703.
- Pre-fault and post-fault current and voltage data (phase,
ITUT-X.21
RS422 phase to phase, symmetrical components)
Bit rate: 64kbps
- Autoreclose operation
c) Electrical interface using multiplexer

Figure 12 Telecommunication system Fault Location


Fault location is initiated by relay tripping signals excluding
METERING AND RECORDING breaker failure, overcurrent backup and out-of-step tipping. It
can also be started on receipt of a start signal from external
Metering and Monitoring relays.
The following power system data is measured continuously Fault location is indicated in km and % for the whole length of
and can be displayed on the LCD on the relay fascia, at the the protected line. The fault location is highly accurate for
local PC, and the remote PC when connected. parallel lines due to the implementation of zero-sequence
- Voltages (phase, phase to phase, symmetrical mutual impedance compensation.
components) The result of the fault location is stored as fault record data.
- Currents (phase, phase to phase, symmetrical In GRZ100 with integral communication, improved fault
components) location accuracy is achieved for 3-ended applications by
- Active power and reactive power use of data received from the remote terminals.

- Frequency Disturbance Record


Currents and voltages can be indicated as primary or The relay can record 8 analog and 32 binary signals. The
secondary values. Active power and reactive power are disturbance recorder is initiated by operation of the overcurrent
indicated as primary values. element, undervoltage element and/or relay tripping.
The user can monitor the following output and status on the In respect to analog data, phase voltage and current,
LCD and at local/remote PCs. residual voltage and current, and the residual current of the
- Relay element output parallel line are recorded. The data can be transformed into
- Binary input/output the COMTRADE format.

- CB status Pre-fault recording time is fixed at 300ms, post-fault


recording time can be set from 100 ms to 3 s. The maximum

9
GRZ100
number of stored records depends on the post-fault can be monitored by pressing the VIEW key. The VIEW key
recording time. In the case of a post-fault recording time of can be pressed without removing the relay front cover.
500ms, up to 20 disturbance records can be stored. The Arbitrary signals can be assigned to the four user
record number of the recorded data is displayed on the configurable LEDs.
LCD.
Two monitoring jacks are operable when the test mode is
Calendar and Time selected in the LCD window. An oscilloscope can be
connected to the relay through these jacks. Selection of
The calendar and time are provided for the time-tagging of output signals on the monitoring jacks can be set from the
recorded data. Synchronisation with GPS (Global menu.
Positioning System) is achieved via the IRIG-B port.
Local PC
USER INTERFACE The user can communicate with the GRZ100 from a local
PC via the RS232C port on the relay fascia. The following data
Relay Front Panel can be viewed or analysed on the local PC with RSM100
The relay front panel incorporates the following user software.
interfaces. Setting the relay and viewing stored data are - Setting
possible using the Liquid Crystal Display (LCD) and - Metering
operation keys.
- Event records
- 40 character, four line LCD with back light
- Fault records
- Eight Light Emitting Diodes (LED) including four that are
- Disturbance records
configurable
- Fault location
- Operation keys
- RS232C port Relay Setting and Monitoring (RSM)
- Monitoring jacks GRZ100 can be connected to the RSM system via the
Figure 13 shows the relay front panel. RS485 interface at the rear of the relay. The user can
operate the relay from a remote PC in the same way as
from a local PC.
Figure 14 shows the configuration of the RSM system via
the protocol converter G1PR2 (option). The G1PR2 can be
provided with maximum 8 ports and each port supports 32
relays addressing.
A maximum of 32 x 8 relays can be connected to the
remote PC in multi-drop mode, via the protocol converter.
The RSM100 software is also used to communicate with the
relay and to view or analyze disturbance records on the
remote PC.
The data transmission rate between relays and the protocol
converter is 64kbps.
Figure 13 Relay front panel

The following items can be displayed on the LCD.


- Setting
- Metering G1PR2

- Event records
- Fault records
- The number of disturbance records
- Fault location
- Any failure code detected by the automatic supervision

Password protection can be provided from the setting menu


on the LCD to provide security for relay setting changes.
After the password has been set, the password must be
entered to access the setting menu from a local or remote PC Figure 14 Relay setting and monitoring system
as well as on the LCD.

The contents of metering, fault records, and relay failures

10
GRZ100
IEC 60870-5-103 Communication and LEDs are programmed by the PLC function.
The relay can support the IEC 60870-5-103 communication
AUTOMATIC SUPERVISION
protocol. This protocol is mainly used when the relay
communicates with a control system and is used to transfer Automatic Monitoring Function
measurand data, status data and general commands
The automatic monitoring function will detect failures,
between the relay and the control system.
should they occur, that might cause unwanted operation.
IEC 61850 Communication The items monitored include the following:
- Analog input circuits
GRZ100-201D, -301D and -303D can also support data
communication according to the IEC 61850 standard. Station - Analog-to-digital converter
bus communication as specified in IEC 61850-8-1 facilitates - Watchdog Timer
integration of the relays within substation control and - Binary output circuits
automation systems via Ethernet LAN.
- DC power supply circuits
Figure 15 shows an example of a substation automation
- CPU
system using Ethernet-based IEC 61850 communication.
- Telecommunication circuit
- Relay address monitoring

Automatic Test Function for External


Communication
In the BOP scheme, a signal check-back test function is
provided to check the integrity of the signalling channels.

Alarms
In the unlikely event that a relay failure should occur, this
is detected by automatic monitoring and the LED
ALARM on the relay fascia is illuminated. A binary
“RELAY FAILURE” output is simultaneously operated
and the date/time of any such failure would be stored in
the event record.

Figure 15 IEC 61850 Communication Network


PC DISPLAY
Relay Setting
The user can input or change settings using the operation
keys on the relay fascia or via a local or remote PC with the
RSM system.
Password protection is provided to change settings.
Eight active setting groups are provided. This allows the
user to set one group for normal operating conditions while
other groups may be set to cover alternative operating
conditions.
Fault record
Configurable Binary Output Contacts
GRZ100 is provided with 13 to 41 user configurable
normally open output contacts used for indication and alarm.
The number of outputs varies according to the relay model.

Configurable Binary Inputs


GRZ100 is provided with 18 to 28 user configurable binary
inputs.
The number of inputs varies according to the relay model.

PLC Function
GRZ100 is provided with a PLC (Programmable Logic Waveform data analysis
Control) function allowing user-configurable sequence logics
on binary signals. Configurable binary inputs, binary outputs

11
GRZ100
TECHNICAL DATA

Ratings
AC current In: 1A or 5A
AC voltage Vn: 100V, 110V, 115V, 120V
Frequency: 50Hz or 60Hz
DC power supply: 110Vdc/125Vdc (Operative range: 88 - 150Vdc)
220Vdc/250Vdc (Operative range: 176 - 300Vdc)
48Vdc/54Vdc/60Vdc (Operative range: 38.4 - 72Vdc)
24Vdc/30Vdc (Operative range: 19.2 – 36Vdc)
AC ripple on DC supply IEC60255-11 maximum 12%
DC supply interruption IEC60255-11
Permissive duration of DC supply voltage
interruption to maintain normal operation: less than 50ms at 110V
Restart time: less than 10s
Binary input circuit DC voltage 110Vdc/125Vdc
220Vdc/250Vdc
48Vdc/54Vdc/60Vdc
24Vdc/30Vdc
Overload Ratings
AC current input 4 times rated continuous
100 times rated for 1s
AC voltage input 2 times rated continuous
2.5 times rated for 1s
Burden
AC current input 0.2VA per phase (at rated 5A)
0.4 VA at zero-sequence circuit (at rated 5A)
0.1VA per phase (at rated 1A)
0.3 VA at zero-sequence circuit (at rated 1A)
AC voltage input 0.1VA (at rated voltage)
DC power supply: less than15W (quiescent)
less than 25W (operation)
Binary input circuit: ≤ 0.5W/input at 110Vdc
CT Ratio Setting
CT ratio 1 to 20000 in 1 steps
Full Scale of Current for Measurement
Current 65 times rated current
Phase Fault Distance Measuring Element
Z1S, Z2S and Z1XS 0.10 to 250.00Ω in 0.01Ω steps (1A relay)
0.01 to 50.00Ω in 0.01Ω steps (5A relay)
Z1S θ1 0° to 45° in 1° steps
Z1S θ2 45° to 90° in 1° steps
ZFS, ZR1S and ZR2S 0.1 to 250.0Ω in 0.1Ω steps (1A relay)
0.01 to 50.00 in 0.01Ω steps (5A relay)
Z3S and Z4S 0.1 to 250.0Ω in 0.1Ω steps (1A relay)
0.01 to 50.00 in 0.01Ω steps (5A relay)
Characteristic angle 45° to 90° in 1° steps
Z1S, Z4S, ZR1S and ZR2S offset 7.5Ω fixed (1A relay)
1.5Ω fixed (5A relay)
ZNDS 0.1 to 250.0Ω in 0.1Ω steps (1A relay)
0.01 to 50.00 in 0.01Ω steps (5A relay)
Blinder (BFRS1, BFRS2, BFRS3, BRRS, BNDS) 0.5 to 100.0Ω in 0.1Ω steps (1A relay)
BRLS: Linked with BRRS 0.10 to 20.00Ω in 0.01Ω steps (5A relay)
Characteristic angle: (BFRS1, BFRS2, BFRS3, BRRS, BNDS) 75° fixed
Characteristic angle (BFLS) 90° to 135°

12
GRZ100
Earth Fault Distance Measuring Element
Z1G, Z2G and Z1XG 0.10 to 250.00Ω in 0.01Ω steps (1A relay)
0.01 to 50.00Ω in 0.01Ω steps (5A relay)
Z1G θ1 0° to 45° in 1° steps
Z1G θ2 45° to 90° in 1° steps
ZR1G 0.1 to 250.0Ω in 0.1Ω steps (1A relay)
0.01 to 50.00 in 0.01Ω steps (5A relay)
ZFG, Z3G, ZR2G and Z4G 0.1 to 500.0Ω in 0.1Ω steps (1A relay)
0.01 to 100.00 in 0.01Ω steps (5A relay)
Characteristic angle 45° to 90° in 1° steps
ZNDG 0.1 to 500.0Ω in 0.1Ω steps (1A relay)
0.01 to 100.00 in 0.01Ω steps (5A relay)
Blinder (BFRG1, BFRG2, BFRG3, BRRG, BNDG) 0.5 to 100.0Ω in 0.1Ω steps (1A relay)
BRLG: Linked with BRRG 0.10 to 20.00Ω in 0.01Ω steps (5A relay)
Characteristic angle (BFRG1, BFRG2, BFRG3, BRRG, BNDG) 75° fixed
Characteristic angle (BFLG) 90° to 135°
Time Setting for Zone Protection
Time setting of Z1S, Z2S, Z3S, ZFS, ZR1S, ZR2S, 0.00 to 10.00s in 0.01s steps
ZNDS, Z1G, Z2G, Z3G, ZFG, ZR1G, ZR2G, ZNDG
Command Protection
Coordination time for BOP scheme 0 to 50ms in 1ms steps
Operating and Resetting Time of Distance Measuring Element
Typical operating time 20ms
Operating time curve (SIR curve) Refer to Figure 13.
Resetting time for tripping output Typical 30ms (Adjustable by PLC function)
Accuracy of Distance Measuring Element
Static accuracy ±5% under SIR < 30, ±10% under 30 < SIR < 50
Static angle accuracy ±5°
Transient overreach +5%
Minimum Operating Current
Current 0.08A (1A relay)
0.4A (5A relay)
Residual Current Compensation
Residual current compensation for reactance element of Adjustable as follows:
Z1G, Z1XG, Z2G, ZFG, ZR1G
Earth return compensation 0 to 1000% in 1% steps
Mutual coupling compensation (ZR1G excluded) 0 to 1000% in 1% steps
Phase Selection Element
Undervoltage 10 to 60V in 1V steps
Impedance 0.0 to 250.0Ω in 0.1Ω steps (1A relay)
0.0 to 50.0Ω in 0.1Ω steps (5A relay)
Characteristic angle 45° to 90° in 1° steps
Residual current compensation Automatically set according to residual current
compensation setting of reactance element
Switch-on-to-fault and Stub protection
Overcurrent 0.4 to 3.0A in 0.1A steps (1A relay)
2.0 to 15.0A in 0.1A steps (5A relay)
Broken Conductor Detection
Broken conductor threshold (I2/I1): OFF, 0.10 to 1.00 in 0.01 steps
DTL delay: 0.00 to 300.00s in 0.01s steps
Accuracy of pick-up value ±5%

13
GRZ100
Voltage Transformer Failure Supervision
Undervoltage element (phase-to-phase) 50 to 100V in 1V steps
Undervoltage element (phase-to-earth) 10 to 60V in 1V steps
Current change detection element 0.1A fixed (1A relay)
0.5A fixed (5A relay)
Residual voltage element 20V fixed
Residual current element Common use with earth fault detection element
Power Swing Blocking
Detection zone (PSBZS, PSBZG) 2.5 to 75.0Ω in 0.1Ω steps (1A relay)
0.50 to 15.00 in 0.01Ω steps (5A relay)
Current change detection element 0.1 to 2.0A in 0.1A steps (1A relay)
0.5 to 10.0A in 0.1A steps (5A relay)
Detection time 30 to 60ms in 1ms steps
Resetting time 500ms fixed
Out-of-step Protection
Resistive reach (OSTR1) 15 to 150Ω in 1Ω steps (1A relay)
3.0 to 30.0Ω in 0.1Ω steps (5A relay)
Resistive reach (OSTR2) 5 to 50Ω in 1Ω steps (1A relay)
1.0 to 10.0Ω in 0.1Ω steps (5A relay)
Resistive reach (OSTXF) 5 to 250Ω in 1Ω steps (1A relay)
1.0 to 50.0Ω in 0.1Ω steps (5A relay)
Resistive reach (OSTXF) 1 to 50Ω in 1Ω steps (1A relay)
0.2 to 10.0Ω in 0.1Ω steps (5A relay)
Detection time (TOST) 0.01 to 1.00s in 0.01s steps
Breaker Failure (BF) Protection
Overcurrent element 0.1 to 2.0A in 0.1A steps (1A relay)
0.5 to 10.0A in 0.1A steps (5A relay)
BF timer for retry-trip of failed breaker 50 to 500ms in 1ms steps
BF timer for related breaker trip 50 to 500ms in 1ms steps
Operating time of overcurrent element less than 20ms at 50Hz or less than 17ms at 60Hz
Resetting time of overcurrent element less than 15ms at 50Hz or less than 13ms at 60Hz
Inverse Time Overcurrent Protection
Overcurrent 0.10 to 5.00A in 0.01A steps (1A relay)
0.5 to 25.0A in 0.1A steps (5A relay)
Time multiplier 0.05 to 1.00 in 0.01 steps
Characteristic Refer to Figure 8.
Accuracy of inverse time characteristics Standard, Very and Long-time: IEC60255-3 class 5
Extremely inverse: IEC60255-3 class 7.5
Reset definite time 0.0 to 10.0s in 0.1s steps
Definite Time Overcurrent Protection
Overcurrent 0.1 to 20.0A in 0.1A steps (1A relay)
0.5 to 100.0A in 0.1A steps (5A relay)
Time for delayed trip 0.00 to 10.00s in 0.01s steps
Operating time of overcurrent element less than 20ms
Accuracy of pick-up value ±5%
Directional Earth Fault Protection
Characteristic angle 0 to 90° in 1° steps (3I0 lags for −3V0)
Polarising voltage (3V0) 1.7 to 21.0V in 0.1V steps
Zero-sequence current (3I0) 0.10 to 1.00A in 0.01A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
Time for backup trip 0.00 to 10.00s in 0.01s steps
Accuracy of pick-up value ±5%

14
GRZ100
Directional Earth Fault Command Protection
Time for delayed trip 0.00 to 0.30s in 0.01s steps
Coordination time 0 to 50ms in 1ms steps
Inverse Time Earth Fault Protection
Earth fault 0.10 to 1.00A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
Time multiplier 0.05 to 1.00 in 0.01 steps
Characteristic Refer to Figure 8.
Accuracy of inverse time characteristics Standard, Very and Long-time: IEC60255-3 class 5
Extremely inverse: IEC60255-3 class 7.5
Reset definite time 0.0 to 10.0s in 0.1s steps
Definite Time Earth Fault Protection
Earth fault 0.10 to 1.00A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
Time for delayed trip 0.00 to 10.00s in 0.01s steps
Accuracy of pick-up value ±5%
Weak Infeed and Echo Protection
Phase-to-phase undervoltage element 50 to 100V in 1V steps
Phase-to-earth undervoltage element 10 to 60V in 1V steps
Thermal overload Protection
Thermal setting (THM = k.IFLC) OFF, 0.40 – 2.00A in 0.01A steps (1A rating)
OFF, 2.0 – 10.0A in 0.1A steps (5A rating)
Time constant (τ) 0.5 – 300.0mins in 0.1min steps
Thermal alarm OFF, 50% to 99% in 1% steps
Pre-load current setting 0.00 – 1.00A in 0.01A steps (1A rating)
0.0 – 5.0A in 0.1A steps (5A rating)
Overvoltage Protection
1st, 2nd Overvoltage thresholds: OFF, 5.0 – 150.0V in 0.1V steps (for both
phase-to-phase and phase-to-neutral voltage)
Delay type: DTL, IDMTL(1st threshold only)
IDMTL Time Multiplier Setting TMS: 0.05 – 100.00 in 0.01 steps
DTL delay: 0.00 – 300.00s in 0.01s steps
DO/PU ratio 10 – 98% in 1% steps
st
Reset Delay (1 threshold only): 0.0 – 300.0s in 0.1s steps
Accuracy of pick-up value ±5%
Undervoltage Protection
1st, 2nd Undervoltage thresholds: OFF, 5.0 – 150.0V in 0.1V steps (for both
phase-to-phase and phase-to-neutral voltage)
Delay type: DTL, IDMTL(1st threshold only)
IDMTL Time Multiplier Setting TMS: 0.05 – 100.00 in 0.01 steps
DTL delay: 0.00 – 300.00s in 0.01s steps
st
Reset Delay (1 threshold only): 0.0 – 300.0s in 0.1s steps
Accuracy of pick-up value ±5%
Fault Locator
Line reactance and resistance setting 0.0 to 999.9Ω in 0.1Ω steps (1A relay)
0.00 to 199.99Ω in 0.01Ω steps (5A relay)
Line length 0.0 to 399.9km in 0.1km steps
Correction factor of impedance between lines 80 to 120% in 1% steps
Correction factor of impedance between in each phase 80 to 120% in 1% steps
Accuracy ±2.5km (up to 100km)
±2.5% (up to 399.9km)
Minimum measuring cycles 2.5 cycles

15
GRZ100
Autoreclose Function
Number of shots 1 to 4 shots
Timer settings
Dead time for single-phase autoreclose 0.01 to 10.00s in 0.01s steps
Dead time for three-phase autoreclose 0.01 to 100.00s in 0.01s steps
Multi-shot dead line time 5.0 to 300.0s in 0.1s steps
Multi-shot reset time 5.0 to 300.0s in 0.1s steps
Reclaim time 5 to 300s in 1s steps
Pulse width of reclosing signal output 0.1 to 10.0s in 0.1s steps
Autoreclose reset time 0.01 to 100.00s in 0.01s steps
Reset time for developing fault 0.01 to 10.00s in 0.01s steps
One-and-a-half breaker scheme
Follower breaker autoreclose delay time 0.1 to 10.0s in 0.1s steps
Voltage and synchronism check element
Synchronism check angle 5 to 75° in 1° steps
UV element 10 to 150V in 1V steps
OV element 10 to 150V in 1V steps
Busbar or line dead check 10 to 150V in 1V steps
Busbar or line live check 10 to 150V in 1V steps
Synchronism check time 0.01 to 10.00s in 0.01s steps
Voltage check time 0.01 to 1.00s in 0.01s steps
Operating time of synchronism check element less than 50ms
Operating time of UV and OV elements less than 40ms
Integral Communication Interface (Protection Signalling)
Electrical interface (Telecomm. equipment link)
Applicable standard CCITT-G703-1.2.1
CCITT-G703-1.2.2 or 1.2.3
RS530 (RS485)
Connector type D-sub connector
Optical interface (2 km class)
Type of fibre Graded-index multi-mode 50/125µm or 62.5/125µm
Connector type ST
Wave length 820nm
Optical transmitter LED, more than −19dBm(50/125µm),
−16dBm(62.5/125µm)
Optical receiver PIN diode, less than −24dBm
Optical interface (30 km class)
Type of fibre Single mode 10/125µm
Connector type Duplex LC
Wave length 1310nm
Optical transmitter Laser, more than −13dBm
Optical receiver PIN diode, less than −30dBm
Optical interface (80 km class)
Type of fibre Dispersion shifted optical fibre (DSF)
Connector type Duplex LC
Wave length 1550nm
Optical transmitter Laser, more than −5dBm
Optical receiver PIN diode, less than −34dBm

16
GRZ100
Disturbance Record Initiation
Overcurrent element 0.1 to 50.0A in 0.1A steps (1A relay)
0.5 to 250.0A in 0.1A steps (5A relay)
Undervoltage element 0 to 132V in 1V steps (for phase fault)
0 to 76V in 1V steps (for earth fault)
Pre-fault time 0.3s fixed
Post-fault time 0.1 to 3.0s in 0.1s steps
Communication Port
Front communication port (local PC)
Connection Point to point
Cable type Multi-core (straight)
Cable length 15m (max.)
Connector RS232C 9-pin D-subminiature connector female
Rear communication port (remote PC)
RS485 I/F:
Transmission data rate for RSM system 57.6kbps (max.)
Connection Multidrop mode (max. 32 relays)
Connector Screw terminals
Cable and length Twisted pair cable with shield, max. 1200m
Isolation 2kVac for 1min.
Fibre optic I/F: ST connector, graded-index multi-mode 50/125µm or
62.5/125µm type optical fibres
Ethernet LAN I/F: 10BASE-T: RJ-45 connector
100BASE-TX: RJ-45 connector
100BASE-FX: SC connector
IRIG-B Port
Connection BNC connector
Cable type 50 ohm coaxial cable
Binary Inputs
Operating voltage Typical 74Vdc(min.70Vdc) for 110V/125Vdc rating
Typical 138Vdc(min.125Vdc) for 220V/250Vdc rating
Typical 32Vdc(min.30Vdc) for 48V/54V/60Vdc rating
Typical 16Vdc(min.15Vdc) for 24V/30Vdc rating
Contact Ratings
Trip contacts
Make and carry 5A continuously,
30A, 290Vdc for 0.5s (L/R=10ms)
Break 0.15A, 290Vdc (L/R=40ms)
Auxiliary contacts
Make and carry 4A continuously,
10A, 220Vdc for 0.5s (L/R≧5ms)
Break 0.1A, 220Vdc (L/R=40ms)
Durability
Make and carry 10,000 operations minimum
Break 100,000 operations minimum
Mechanical design
Weight 10kg (Type-A), 13kg (Type-B)
Case colour Munsell No. 10YR8/0.5
Installation Flush mounting or rack mounting

17
GRZ100

a) Minimum operating time (50Hz) b) Maximum operating time (50Hz)


Phase to phase fault

a) Minimum operating time (50Hz) b) Maximum operating time (50Hz)


Phase to earth fault
Note: In the case of a 60Hz relay the operate time is reduced by approximately 15% to 20%.

Figure 16 Operating time curve

18
GRZ100
ENVIRONMENTAL PERFORMANCE
Test Standards Details
Atmospheric Environment
Temperature IEC60068-2-1/2 Operating range: -10°C to +55°C.
Storage / Transit: -25°C to +70°C.
Humidity IEC60068-2-78 56 days at 40°C and 93% relative humidity.
Enclosure IEC60529 IP51 (Rear: IP20)
Protection
Mechanical Environment
Vibration IEC60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC60255-5 2kVrms for 1 minute between all terminals and earth.
2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
High Voltage IEC60255-5 Three positive and three negative impulses of 5kV(peak),
Impulse 1.2/50µs, 0.5J between all terminals and between all
terminals and earth.
Electromagnetic Environment
High Frequency IEC60255-22-1 Class 3, 1MHz 2.5kV applied to all ports in common mode.
Disturbance / IEC61000-4-12 / 1MHz 1.0kV applied to all ports in differential mode.
Damped Oscillatory EN61000-4-12
Wave
Electrostatic IEC60255-22-2 Class 3, 6kV contact discharge, 8kV air discharge.
Discharge IEC61000-4-2 /
EN61000-4-2
Radiated RF IEC60255-22-3 Class 3, Field strength 10V/m for frequency sweeps of 80MHz to
Electromagnetic IEC61000-4-3 / 1GHz and 1.7GHz to 2.2GHz. Additional spot tests at 80,
Disturbance EN61000-4-3 160, 450, 900 and 1890MHz.
Fast Transient IEC60255-22-4, 4kV, 2.5kHz, 5/50ns applied to all inputs.
Disturbance IEC61000-4-4 /
EN61000-4-4
Surge Immunity IEC60255-22-5 1.2/50µs surge in common/differential modes:
HV ports: 2kV/1kV (peak)
PSU and I/O ports: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted RF IEC60255-22-6 Class 3, 10Vrms applied over frequency range 150kHz to 100MHz.
Electromagnetic IEC61000-4-6 / Additional spot tests at 27 and 68MHz.
Disturbance EN61000-4-6
Power Frequency IEC60255-22-7, 300V 50Hz for 10s applied to ports in common mode.
Disturbance IEC61000-4-16 / 150V 50Hz for 10s applied to ports in differential mode.
EN61000-4-16 Not applicable to AC inputs.
Conducted and IEC60255-25, Conducted emissions:
Radiated Emissions EN55022 Class A, 0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
IEC61000-6-4 / 0.50 to 30MHz: <73dB (peak) or <60dB (mean)
EN61000-6-4 Radiated emissions (at 30m):
30 to 230MHz: <30dB
230 to 1000MHz: <37dB
European Commission Directives
89/336/EEC Compliance with the European Commission Electromagnetic
Compatibility Directive is demonstrated according to EN
61000-6-2 and EN 61000-6-4.
73/23/EEC Compliance with the European Commission Low Voltage
Directive is demonstrated according to EN 50178 and EN
60255-5.

19
GRZ100
Optical Interface Unit G1IF1 (Option)
Ratings
Power supply: 110Vdc/125Vdc (Operative range: 88 - 150Vdc)
220Vdc/250Vdc (Operative range: 176 - 300Vdc)
48Vdc (Operative range: 38.4 - 72Vdc)
Burden: less than 8W
Interface
Communication interface: CCITT-G703-1.2.1
CCITT-G703-1.2.2 or 1.2.3
X.21
Optical transmitter LED, more than −19dbm(50/125µm), −16dBm(62.5/125µm)

Optical receiver PIN diode, less than −24dBm


Wavelength: 820nm
Connector type: ST
Fibre type: Graded-index multi-mode 50/125µm or 62.5/125µm
Atmospheric Environment
Temperature IEC60068-2-1/2 Operating range: -10°C to +55°C.
Storage / Transit: -25°C to +70°C.
Humidity IEC60068-2-78 56 days at 40°C and 93% relative humidity.
Enclosure Protection IEC60529 IP40 (without outer-case, excluding terminal parts)
IP50 (with outer-case, excluding cable exit)

Protocol Converter G1PR2 (Option)


Ratings
Power supply: 110Vdc/100Vac Operative range: 88 - 150Vdc of 110Vdc rated voltage
80 - 120Vac of 100Vac rated voltage
220Vdc/200Vac Operative range: 170 - 300Vdc of 220Vdc rated voltage
200 - 240Vac of 200Vac rated voltage
48Vdc Operative range: 38.4 - 72Vdc
Burden: less than 20W
Communication port
RS232C interface
Connector type RS232C 9-pin D-subminiature connector female
Cable type Multi-core (straight)
RS485 interface
Connector Screw terminals (Phoenix Contact, FRONT type)
Cable type Twisted pair cable
Optical interface
Operative Range: less than 1.2km with 62.5/125µm GI fibre (3dB/km)
Wavelength: 820nm
Connector type: ST
Fibre type: 62.5/125µm glass fibre
IRIG-B
Connector Screw terminals (Phoenix Contact, FRONT-MSTB type)
Mechanical design
Enclosure Protection IEC60529, IP20
Weight 5 kg
Installation Flush mounting
Atmospheric Environment
Temperature IEC60068-2-1/2 Operating range: -10°C to +55°C.
Storage / Transit: -25°C to +70°C.
Humidity IEC60068-2-78 56 days at 40°C and 93% relative humidity.

20
GRZ100

21
GRZ100
ORDERING

1. Distance Relay
GRZ100 − B− 0− 0

Relay Type:
Distance protection relay GRZ100
Relay Model:
-Model 200: With autoreclose for single breaker scheme
18 BIs, 23 BOs, 6 trip BOs 201
24 BIs, 41 BOs, 6 trip BOs 203
22 BIs (12-independent), 19 BOs, 3 trip BOs 204
28 BIs (12-independent), 37 BOs, 3 trip BOs 206
-Model 300: With autoreclose for one and a half breaker scheme
18 BIs, 23 BOs, 6 trip BOs 301
21 BIs, 27 BOs, 6 trip BOs 302
24 BIs, 41 BOs, 6 trip BOs 303
-Model 400: With autoreclose for single breaker and redundant fault
detector scheme
21 BIs, 35 BOs, 6 trip Bos 401
-Model 500: With autoreclose for one and a half breaker and
redundant fault detector scheme
21 BIs, 35 BOs, 6 trip BOs 501
Ratings:
1A, 50Hz, 110V/125Vdc 1
1A, 60Hz, 110V/125Vdc 2
5A, 50Hz, 110V/125Vdc 3
5A, 60Hz, 110V/125Vdc 4
1A, 50Hz, 220V/250Vdc 5
1A, 60Hz, 220V/250Vdc 6
5A, 50Hz, 220V/250Vdc 7
5A, 60Hz, 220V/250Vdc 8
1A, 50Hz, 48V/54V/60Vdc A
1A, 60Hz, 48V/54V/60Vdc B
5A, 50Hz, 48V/54V/60Vdc C
5A, 60Hz, 48V/54V/60Vdc D
1A, 50Hz, 24V/30Vdc E
1A, 60Hz, 24V/30Vdc F
5A, 50Hz, 24V/30Vdc G
5A, 60Hz, 24V/30Vdc H
Communications:
RS485 1
Fibre optic 2
Dual RS485 3
Dual fibre optic 4
RS485 + fibre optic 9
Note:
Fibre optic is available for model 203,204,206,302,303,401,501.
10BASE-T option is available for specific configuration.
Miscellaneous:
None 0
Note: Please inform us which is ordered flush mount type or 19-inch rack mount type.
In 19 inch rack mount type, please order optional attachment kit.
- for relay case Type-A attachment kit: EP101
- for relay case Type-B attachment kit: EP102

22
GRZ100
2. Distance Relay with integral communications
GRZ100 − B− − 0
Relay type:
Distance relay GRZ100
Relay Model:
Model 210: For 2-terminal line application (one communication channel)
/ with autoreclose for single breaker scheme
18 BIs, 23 BOs, 6 trip BOs 211
22 BIs (12-independent), 19 BOs, 3 trip BOs 214
28 BIs (12-independent), 37 BOs, 3 trip BOs 216
Model 310: For 2-terminal line application (one communication channel)
/ with autoreclose for one-and-a-half breaker scheme
18 BIs, 23 BOs, 6 trip BOs 311
Model 220: For 2- / 3-terminal line application (two communication
channels) / with autoreclose for single breaker scheme
18 BIs, 23 BOs, 6 trip BOs 221
22 BIs (12-independent), 19 BOs, 3 trip BOs 224
28 BIs (12-independent), 37 BOs, 3 trip BOs 226
Model 320: For 2- / 3-terminal line application (two communication
channels) / with autoreclose for one-and-a-half breaker scheme
18 BIs, 23 BOs, 6 trip BOs 321
18 BIs, 41 BOs, 6 trip BOs 323
Ratings:
1A, 50Hz, 110V/125Vdc 1
1A, 60Hz, 110V/125Vdc 2
5A, 50Hz, 110V/125Vdc 3
5A, 60Hz, 110V/125Vdc 4
1A, 50Hz, 220V/250Vdc 5
1A, 60Hz, 220V/250Vdc 6
5A, 50Hz, 220V/250Vdc 7
5A, 60Hz, 220V/250Vdc 8
1A, 50Hz, 48V/54V/60Vdc A
1A, 60Hz, 48V/54V/60Vdc B
5A, 50Hz, 48V/54V/60Vdc C
5A, 60Hz, 48V/54V/60Vdc D
1A, 50Hz, 24V/30Vdc E
1A, 60Hz, 24V/30Vdc F
5A, 50Hz, 24V/30Vdc G
5A, 60Hz, 24V/30Vdc H
Integral communication interface (Protection signaling):
Electrical interface (CCITT-G703-1.2.1) 1
Electrical interface (CCITT-G703-1.2.2 or 1.2.3) 2
Optical interface (Short wavelength light: GI: 2km class) 3
Optical interface (Long wavelength light: SM: 30km class) 6
Optical interface (Long wavelength light: SM: 80km class) 7
Electrical interface (RS530, X.21) 9
Communications (User data):
RS485 1
Fibre optic 2
Dual RS485 3
Dual fibre optic 4
RS485 + fibre optic 9
Note:
Fibre optic is available for model 214, 216, 226, and 323
10BASE-T option is available for specific configuration
Miscellaneous:
None 0
Note: Please inform us which is ordered flush mount type or 19-inch rack mount type.
In 19 inch rack mount type, please order optional attachment kit.
- for relay case Type-A attachment kit: EP101
- for relay case Type-B attachment kit: EP102

23
GRZ100
3. Optical Interface Unit (Option)
G1IF1 − −
Type:
Communication interface box G1IF1
Model:
For X.21 with outer case 01
For CCITT-G703-1.2.1 contradirectional 02
For CCITT-G703-1.2.2 or 1.2.3 contradirectional 03
For X.21 04
Auxiliary power supply:
DC 48V / 54V / 60V 01
DC 110V / 125V 02
DC 220V / 250V 03

4. Protocol Converter (Option)


G1PR2 − A− −

Type:
Protocol converter G1PR2
Model:
1 port, Electrical signal (RS485) 101
4 ports, Electrical signal (RS485) 104
8 ports, Electrical signal (RS485) 108
8 ports, Electrical signal (RS485): Max. 8, Optical signal: Max. 1 118
8 ports, Electrical signal (RS485): Max. 8, Optical signal: Max. 4 148
8 ports, Electrical signal (RS485): Max. 4, Optical signal: Max. 8 184
1 port, Electrical signal (RS485) or Optical signal 111
1 port, Optical signal 110
4 ports, Optical signal 140
8 ports, Optical signal 180
Auxiliary power supply rating:
AC 100 / DC 110V 10
AC 200 / DC 220V 50
DC 48V A0
External time synchronisation:
None. 00
IRIG-B port 10

24
GRZ100
RELAY OUTLINE

Flush Mount

M3.5 Ring terminal

M3.5 Ring terminal

65(∗ )

Note (∗): This dimension shows in the case of model 201D and 301D.

Figure 17 Relay case Type-A outline(for models 201, 204, 211, 214, 221, 224, 301, 311, 321)

M3.5 Ring terminal

M3.5 Ring terminal

65(∗ )

Figure 18 Relay case Type-B outline(for models 203, 206, 216, 226, 302, 303, 323, 401, 501)

25
GRZ100
19-inch Rack Mount

DISTANCE PROTECTION

V W

Figure 19 Relay case Type-A outline(for models 201, 204, 211, 214, 221, 224, 301, 311, 321)

DISTANCE PROTECTION

V W

Figure 20 Relay case Type-B outline(for models 203, 206, 216, 226, 302, 303, 323, 401, 501)

26
GRZ100
Outline of Optical interface unit
2- Φ5

TB1

130 195

Power
TX from COM 156
TX from RELAY
CLK from COM

SPARE
RX TX CLK
12
66
2-5x9

168

180

Figure 21 Outline of optical interface unit G1IF1 (without outer case)

Outline of Protocol Converter


88-150Vdc/80-120Vac RS232C
POWER

OFF ON
P FG N
1 2
IRIG-B

OPT1 OPT2 OPT3 OPT4 OPT5 OPT6 OPT7 OPT8


RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

TB2

TB1 RS485-1 RS485-2 RS485-3 RS485-4 RS485-5 RS485-6 RS485-7 RS485-8 SG FG


(Note) IRIG-B: Option

356
339.3
316 200

TX POWER
1 2 3 4 5 6 7 8 ALARM
IRIG-B
PROTOCOL CONVERTER
57.1 115 108.3
φ7.1 1 2 3 4 5 6 7 8 Type G1PR2
Model 180A-10-∗∗
RX Power 110Vdc/100Vac
Made in Japan

10.3 Note: IRIG-B (Option)

Figure 22 Outline of protocol converter G1PR2

27
GRZ100
EXTERNAL CONNECTION DIAGRAM

BUS
TB2-A1
BO1
TB3- A2 B1
BUS VT
BO1
A1 A2
TB1 -1
CT 2 BO2 BO2
3 B1 B2
4 BO3
5 A3
B2
6 BO3
7 B3
8
A3
9 A4
Io from 10 BO4
B3 BO4
Adjacent Line CT B4
CB
A4
11 A5
VT BO5
B4 BO5
12
B5
A5
13
14 A6
BO6
B5
15 BO6
B6
BUS VT 16 A6
20 BO7 A7
B6
BO7
B7
A7
BO8 A8
B7
BO8
[Default setting] (+) A8 B8
CB1-A TB4 -A4 BO9
B8 A9
BI1
CB auxiliary contacts BO9
CB1-B A9 B9
(Closed when bus CB main B4
contact closed.) BI2 BO10
B9 A10
CB1-C A5 BO10
BI3 A10 B10
BO11
B10
Signal receive (CH1) B5
BI4
A11
IO#3
Signal receive (CH2) A6 BO12
or Z1-EXT initiation B11
BI5

External VT failure (EXT VTF) B6 TB3-A13


BI6 SIGNAL SEND
IO#1 BO13
B13 (HIGH SPEED RELAY)
Disconnector N/O contact A7
FAIL A12
BI7
RELAY FAILURE
B7 B12
Disconnector N/C contact
BI8

Carrier protection block A8 TB3-A18


BI9 COM-A TB2-A18
COM2-A
B18 COM2-B A17
CB ready condition B8 A17
BI10 COM-B COM2-0V A16
RS485 I/F Dual RS485 I/F ports
B17 B18
A9 COM1-A
(Single port)
A16 COM1-B B17
BI11 COM-0V
B16 COM1-0V B16
Autoreclose block (REC BLOCK) B9
BI12
Ethernet LAN I/F
Indication reset A10 T (option)
BI13

Main protection trip B10


BI14

Main protection ON A11


B11 BI15
(-) CN1
EXT trip-A IRIG-B CN1
TB3 -A14 TB4 TB3 TB2
A1 B1 A1 B1
BI16
External trip signals EXT trip-B TB4- A3
B14 (+)
(CBF Initiation) BI17
IO#2 B3 AB E

EXT trip-C TP-A1 A1


A15 TRIP-A 11
B15 BI18
(-) T
B10
TB1
TP-B1 A2 IO#3
RELAY FAIL. TRIP-B BUS CB 1 2
≧1
DD FAIL. TP-C1 B2
TRIP-C 1
TB4-A16 +5Vdc TB4-A14 A18 B18 A18 B18
DC (+) B16 DC-DC B14 (+) IO#1 IO#2 19 20
SUPPLY A17
0V VCT
(-) B17 TP-A2 A12
A18 TRIP-A Terminal Block Arrangement (Rear view)
B18
(∗1)These connections are connected (∗1) A15 TP-B2 A13
TRIP-B CENTER CB
by wire link before shipment. B15
TP-C2 B13
CASE EARTH TRIP-C
E

Figure 23 Typical external connection of Model 201B

28
GRZ100
BUS

BUS VT TB2- A2 TB5- A2 TB3- A2


BO1 BO1 BO1
TB1 -1 A1 A1 A1
CT 2
3 BO2 BO2 BO2
4 B1 B1 B1
5 BO3 BO3 BO3
6 B2 B2 B2
7
8
9 A3 A3 A3
Io from 10
BO4 BO4
Adjacent Line CT BO4 B3 B3 B3
CB
11 A4 A4 A4
VT
BO5 BO5
12 BO5 B4 B4 B4

13 A5 A5 A5
14
BO6 BO6
BO6 B5 B5 B5
15
BUS VT 16 A6 A6 A6
BO7 BO7
20 BO7 B6 B6 B6

- A7 A7 A7
[Default setting] (+)
BO8 BO8
BO8 B7 B7 B7
CB1-A TB4 -A4
BI1 A8 A8 A8
CB auxiliary contacts
CB1-B BO9 BO9
(Closed when bus CB main B4 BO9 B8 B8 B8
contact closed.) BI2
A9 A9 A9
CB1-C A5
BO10 BO10
BI3 BO10 B9 B9 B9

Signal receive (CH1) B5 A10 A10 A10


BI4
BO11 BO11
BO11 B10 B10 B10
Signal receive (CH2) A6
or Z1-EXT initiation BI5 A11 A11 A11
BO12 BO12
External VT failure (EXT VTF) B6 BO12 B11 B11 B11
BI6
A12 A12
Disconnector N/O contact A7
BO13 BO13
BI7 B12 B12

Disconnector N/C contact B7


A13 A13
BI8
BO14 BO14
IO#1 B13 B13
Carrier protection block A8
BI9
B8 IO#3 IO#4
CB ready condition
BI10
TB2-A13
A9 SIGNAL SEND
BO13 B13 (HIGH SPEED RELAY)
BI11
A12
Autoreclose block (REC BLOCK) B9 FAIL
RELAY FAILURE
BI12 B12
TB2-A18
A10 COM2-A
Indication reset TB2-A18 A17
BI13 COM-A COM2-B
B18 COM2-0V A16
Main protection trip B10 Dual RS485 I/F ports
A17 B18
BI14 COM-B COM1-A
B17 RS485 I/F COM1-B B17
Main protection ON A11 (Single port)
BI15 A16 COM1-0V B16
(-) B11 COM-0V
EXT trip-A B16
TB2 -A14
BI16
External trip signals EXT trip-B Ethernet LAN I/F
(CBF Initiation) B14 IO#2
BI17 T (option)
EXT trip-C A15
T Fibre optic I/F
(-) B15 BI18 OP (option)
R
TB5 -A14
(+) BI19
TB5 TB4 TB3 TB2 CN1
B14 IO#3 A1 B1
BI20
CN1 OP
IRIG-B
A15 AB AB AB AB E
B15 BI21
(-)
TB4- A3
TB3 -A14 (+) 11 TB1
B3 11 11 11
(+) BI34
1 2

T
B14 IO#4 TP-A1 A1
TRIP-A
1 2
BI35 A18 B18
19 20
TP-B1 A2 IO#3 IO#1 IO#4 IO#2
TRIP-B BUS CB VCT
A15
B15 BI36
(-) TP-C1 B2 Terminal Block Arrangement (Rear view)
TRIP-C
RELAY FAIL. TB4-A14
≧1 B14 (+)
DD FAIL.

TB4-A16 +5Vdc TP-A2 A12


TRIP-A
DC (+) B16 DC-DC
SUPPLY A17 TP-B2 A13
0V TRIP-B
(-) B17
A18
B18 TP-C2 B13
TRIP-C
(∗1)These connections are connected (∗1) A15
by wire link before shipment. B15

CASE EARTH
E

Figure 24 Typical external connection of Model 203B

29
GRZ100
BUS

TB2-A1

BUS VT BO1
TB3- A2 B1
BO1
TB1 -1 A1 A2
CT 2
3 BO2 BO2
B2
4 B1
5 BO3 A3
6 B2
7 BO3
B3
8
9 A3 A4
Io from 10
BO4 BO4
Adjacent Line CT B3 B4
CB
11 A4 A5
VT
12 BO5 BO5
B4 B5

13 A5 A6
14
BO6 BO6
B5 B6
15
BUS VT 16 A6

20
BO7
B6
IO#3
A7
[Default setting] (+) BO8
B7
CB1-A TB4 -B4
CB1 contacts A4 BI1 A8
(Closed when CB main CB1-B B5 BO9
BI2 B8
contact closed.) A5
CB1-C B6 A9
A6 BI3
BO10
B7 B9
Signal receive (CH1)
A7 BI4
Signal receive (CH2) A10
B8
or Z1-EXT initiation A8 BI5 BO11
B10
B9
External VT failure (EXT VTF) BI6
A9 A11
B10 IO#1 (HIGH SPEED RELAY)
Disconnector N/O contact BO12
A10 BI7 B11
B11
Disconnector N/C contact BI8 TB3-A13
A11
B12 SIGNAL SEND
Carrier block BO13
BI9 B13 (HIGH SPEED RELAY)
A12
B13 A12
Indication reset BI10
FAIL
RELAY FAILURE
A13
B12
B14
Protection block BI11
A14
B15
Z1X initiation BI12 TB3-A18 TB3-A18
A15 COM-A COM2-A
(-)
EXT trip-A TB3 –A14 B18 COM2-B A17
BI16 A17 COM2-0V A16
COM-B Dual RS485 I/F ports
External trip signals EXT trip-B B14 B17 RS485 I/F B18
COM1-A
BI17 IO#2 (Single port)
(CBF Initiation) A16 COM1-B B17
EXT trip-C A15 COM-0V
B16 COM1-0V B16
BI18
(-) B15
TB2 –A7
OCI block BI19 Ethernet LAN I/F
B7 T (option)
EFI block BI20
A8 T Fibre optic I/F
OC block OP (option)
BI21 R
DEF block B8
BI22 IO#3
A9 CN1
EXTTP block IRIG-B TB4 TB3 TB2 CN1
BI23 A1 B1
STUB block B9 OP
BI24 TB4- A3
(+) AB AB E
SOTF block A10 B3
BI25
(-) B10
TP-A1 A1 11 11
TRIP-A
B10
TP-B1 T TB1
A2 IO#3
RELAY FAIL. TRIP-B 1 2
≧1
DD FAIL. A1 B1
TP-C1 B2
TRIP-C 1
TB4 -A16 +5Vdc A18 B18
DC (+) B16 DC-DC 0 0
IO#1 IO#2 19 20
SUPPLY A17 VCT
0V
(-) B17
A18 Terminal Block Arrangement (Rear view)
(∗1)These connections are connected by (∗1) B18
wire link before shipment.
CASE EARTH 19 20
E

Figure 25 Typical external connection of Model 204B

30
GRZ100
BUS

TB5- A1 TB3- A2
BUS VT BO1
BO1
TB2- A2 B1 A1
TB1 -1 BO1 BO2
CT 2 A1 A2
B1
3 BO2 BO2 BO3
4 B2
B1
5 B2
BO3 A3
6
7 B2
BO3
8 B3 A3
9 BO4
Io from 10 A3 A4 B3
adjacent Line CT BO4 BO4
CB B3 B4 A4
11 BO5
VT A4 A5 B4
12 BO5 BO5
B4 B5 A5
13 BO6
14 A5 A6 B5
BO6 BO6
15 B5 B6 A6
BUS VT 16 BO7
A6 A7 B6
20 BO7 BO7
B6 B7 A7
BO8
A7 A8 B7
[Default setting] (+)
BO8 BO8
CB1-A TB4 -B4 B7 B8 A8
CB1 contacts A4 BI1 BO9
A8 A9 B8
(Closed when CB main CB1-B B5
BI2 BO9 BO9
contact closed.) A5 B8 B9 A9
CB1-C B6
A9 A10 BO10
A6 BI3 B9
B7 BO10 BO10
Signal receive (CH1) B9 B10 A10
A7 BI4
Signal receive (CH2) B8 A10 BO11
B10
or Z1-EXT initiation A8 BI5 IO#3
BO11
B9 B10 A11
External VT failure (EXT VTF) BI6
A9 BO12
A11 B11
B10 IO#1 (HIGH SPEED RELAY)
Disconnector N/O contact BI7 BO12
A10 B11 A12
B11
Disconnector N/C contact BI8 BO13
A11 TB2-A13 B12
B12 SIGNAL SEND
Carrier block BI9 BO13 A13
A12 B13 (HIGH SPEED RELAY)
B13 A12 BO14
Indication reset BI10 FAIL
B13
A13 RELAY FAILURE
B14 B12
Protection block BI11 IO#4
A14
B15
Z1X initiation BI12
A15
(-)
EXT trip-A TB2 –A14
BI16 TB2-A18
COM-A TB2-A18
External trip signals EXT trip-B B14 B18 COM2-A
BI17 IO#2 A17
(CBF Initiation) A17
COM2-B
EXT trip-C A15 COM-B A16
RS485 I/F COM2-0V
BI18 B17 Dual RS485 I/F ports
(-) B15 (Single port) COM1-A B18
A16
TB5 -A12 COM-0V COM1-B B17
OCI block BI19 B16
COM1-0V B16
B12
EFI block BI20
Ethernet LAN I/F
A13
OC block T (option)
BI21
DEF block B13
BI22 IO#3 T Fibre optic I/F
OP IEC103 (option)
A14 R
EXTTP block
BI23

STUB block B14


BI24 CN1
IRIG-B
SOTF block A15
BI25 TB5 TB4 TB3 TB2 CN1
A1 B1
B15 TB4- A3
ARC block (+)
BI26 B3 OP
AB AB AB AB E
CB1 ready A16
BI27 TP-A1 A1
TRIP-A
TB1
B16 11 11 11 11
CBF block TP-B1 A2 1 2
BI28 TRIP-B
(-) A18
T
TB3 -A14 TP-C1 B2 1 2
(+) BI34 TRIP-C A18 B18 19 20
IO#3 IO#1 IO#4 IO#2
B14 VCT
BI35 IO#4
(∗2) Terminal Block Arrangement (Rear view)
A15
BI36
(-) B15
RELAY FAIL.
≧1
DD FAIL.

TB4 -A16 +5Vdc


DC (+) B16 DC-DC
SUPPLY A17
0V
(-) B17
A18
(∗1)These connections are connected B18
(∗1)
by wire link before shipment.
CASE EARTH
E

Figure 26 Typical external connection of Model 206B

31
GRZ100
BUS

BUS VT TB2-A1
TB1 -1 BO1
TB3- A2 B1
2
CT 3 BO1
A1 A2
4
5 BO2 BO2
CB B2
6 B1
7
BO3 A3
8
B2
9 BO3 B3
Io from 10
CB Adjacent Line CT A3 A4
11 BO4 BO4
CT B3 B4
VT 12
A4 A5
13 BO5 BO5
B4 B5
14

15 A5 A6
CB
BUS VT 16
BO6 B5 BO6 B6
BUS ADJACENT LINE VT 17
A6 A7
18
20 BO7 B6 BO7 B7

A7 A8

BO8 B7 BO8 B8
[Default setting] (+)
CB1-A A8 A9
TB4 -A4
(+) BI1 BO9 BO9
B8 B9
CB auxiliary contacts
(Closed when bus CB main CB1-B B4
A9 A10
contact closed.) BI2
BO10 B9 BO10 B10
CB1-C A5
BI3
A10
B5 BO11
IO#3
Signal receive (CH1) B10
BI4
A11
Signal receive (CH2) A6
or Z1-EXT initiation BI5 BO12 B11

External VT failure (EXT VTF) B6


BI6 TB3-A13
IO#1 SIGNAL SEND
BO13
A7 B13 (HIGH SPEED RELAY)
Disconnector N/O contact
BI7
A12
FAIL
B7 RELAY FAILURE
Disconnector N/C contact B12
BI8

Carrier protection block A8


BI9 TB3-A18 TB3-A18
COM-A COM2-A
CB1 ready condition B8 B18 COM2-B A17
BI10 A16
A17 COM2-0V
COM-B Dual RS485 I/F ports
A9 B17 RS485 I/F
CB2 ready condition COM1-A B18
BI11 (Single port)
A16 COM1-B B17
COM-0V
Autoreclose block (REC BLOCK) B9 B16 COM1-0V B16
BI12

Indication reset A10 Ethernet LAN I/F


BI13 T (option)

Main protection trip B10


BI14

Main protection ON A11


B11 BI15
(-)
EXT trip-A CN1
TB3 -A14 IRIG-B
BI16 TB4 TB3 TB2 CN1
A1 B1 A1 B1
External trip signals EXT trip-B
(CBF Initiation) B14 IO#2 TB4- A3
BI17 (+)
B3 AB A E
EXT trip-C
A15
B15 BI18 TP-A1 A1
(-) TRIP-A 1 1
B10
TP-B1 A2 T TB1
RELAY FAIL. TRIP-B BUS CB IO#3 1 2
≧1
DD FAIL. TP-C1 B2
TRIP-C
TB4 -A16 +5Vdc TB4-A14 1
A18 B18 A18 B18
DC (+) B16 DC-DC B14 (+)
IO#1 IO#2
SUPPLY A17 19 20
0V
(-) B17 TP-A2 A12
A18 TRIP-A
B18 Terminal Block Arrangement (Rear View)
(∗1)These connections are connected (∗1) A15 TP-B2 A13
TRIP-B CENTER CB
by wire link before shipment. B15
TP-C2 B13
CASE EARTH TRIP-C
E

Figure 27 Typical external connection of Model 301B

32
GRZ100
BUS BUS VT
TB1 -1
2
CT 3 TB5- A2 TB3- A2
TB2- A2 BO1 BO1
5 BO1 A1 A1
CB 6 A1
BO2 BO2
7 BO2 B1 B1
8 B1 BO3 BO3
Io from 9
BO3 B2 B2
Adjacent Line CT 10
B2
CB 11
A3 A3
CT VT 12 A3
BO4 BO4
B3 B3
13 BO4 B3
14 A4 A4
A4
15 BO5 BO5
B4 B4
BUS VT 16 BO5 B4
CB
Adjacent Line VT 17 A5 A5
A5
18 BO6 BO6
BUS 20 B5 B5
BO6 B5
A6 A6
(+) A6
BO7 BO7
[Default setting] B6 B6
CB1-A TB4- A4 BO7 B6
BI1 A7 A7
CB auxiliary contacts A7
(Closed when bus CB main CB1-B B4 BO8 BO8
B7 B7
contact closed.) BI2 BO8 B7
A8 A8
CB1-C A5
A8
BI3 BO9 BO9
B8 B8
BO9 B8
B5
Signal receive (CH1) A9 A9
BI4 A9
BO10 BO10
Signal receive (CH2) B9 B9
A6 BO10 B9
or Z1-EXT initiation BI5
A10 A10
A10
External VT failure (EXT VTF) B6 BO11 BO11
B10 B10
BI6 BO11 B10
A11 A11
A7
Disconnector N/O contact A11
BI7 BO12 BO12
B11 B11
BO12 B11
Disconnector N/C contact B7
A12 A12
BI8
BO13 BO13
A8 B12 B12
Carrier protection block IO#1
BI9
A13 A13
CB1 ready condition B8
BO14 B13 BO14 B13
BI10

CB2 ready condition A9


BI11 IO#3 IO#4
Autoreclose block (REC BLOCK) B9
TB2-A13 (∗2)
BI12
SIGNAL SEND
BO13
Indication reset A10 B13 (HIGH SPEED RELAY)
BI13
FAIL A12
B10 RELAY FAILURE TB2-A18
Main protection trip COM2-A
B12
BI14 A17
COM2-B
Main protection ON A11 TB2-A18
COM2-0V A16
COM-A
(-) B11 BI15
B18
Dual RS485 I/F ports
COM1-A B18
EXT trip-A
TB2 -A14 A17 COM1-B B17
COM-B
BI16 B17 RS485 I/F COM1-0V B16
External trip signals EXT trip-B B14
(Single port)
(CBF Initiation) IO#2 A16
COM-0V
BI17
B16
EXT trip-C A15
Ethernet LAN I/F
(-) B15 BI18
T (option)
CB2-A TB5 -A14
BI19
T Optical I/F
CB auxiliary contacts CB2-B OP IEC103 (option)
(Closed when bus CB main B14 IO#3 R
contact closed.) BI20
CN1 TB5 TB4 TB3 TB2 CN1
CB2-C A15 (IRIG-B)
B15 BI21 IRIG-B A1 B1
(-) OP
TB3- A14 TB4-A3
E
(+) BI34 B3
B14 TP-A1 A1 TB1
BI35 IO#4 TRIP-A 1 2

TP-B1 A2 T
A15 TRIP-B BUS CB
B15 BI36
A18 B18
(-) IO#3 IO#1 IO#4 19 20
TP-C1 B2 IO#2
VCT
TRIP-C
RELAY FAIL. TB4-A14
≥1
DD FAIL. B14 Terminal Block Arrangement (Rear view)

TB4 -A16 +5Vdc TP-A2 A12 (∗2) Model 302 is not provided with IO#4.
DC (+) TRIP-A
B16 DC-DC
SUPPLY A17
0V TP-B2 A13
(-) B17 TRIP-B CENTER CB
A18
B18 TP-C2 B13
TRIP-C
(∗1)These connections are connected (∗1) A15
by wire link before shipment. B15

CASE EARTH
E

Figure 28 Typical external connection of Model 302B/303B

33
GRZ100
BUS
TB3-A1
BO1
BUS VT TB2- A2 B1 TB5- A2
BO1 A2 BO1
TB1 -1 A1 A1
CT 2 BO2
BO2 B2 BO2
3
4 B1 B1
A3
5 BO3 BO3
6 BO3
B2 B3 B2
7
8 A4
9 A3 A3
BO4
Io from 10 B4 BO4
Adjacent Line CT BO4 B3 B3
CB A10
11 A4 BO5 A4
VT B10
BO5
12 BO5 B4 B4
A11
13 A5 BO6 A5
14 B11
BO6
BO6 B5 B5
A12
15
BUS VT 16 BO7
A6 B12 A6
BO7
BO7 B6 A13 B6
20
BO8
- A7 B13 A7
(+)
BO8
[Default setting] BO8 B7 B7
CB1-A TB4 -A4
BI1 A8 A8
CB auxiliary contacts
(Closed when bus CB main CB1-B B4 BO9
BO9 B8 B8
contact closed.) BI2
A9 A9
CB1-C A5
BI3 BO10
BO10 B9 B9

Signal receive (CH1) B5


A10 A10
BI4 A17
(+) BO11
BO11 B10 FD2 B17 B10
Signal receive (CH2) A6 (∗1)
or Z1-EXT initiation BI5 A18
A11 A11
B18 (∗1)
B6 BO12
External VT failure (EXT VTF) BO12 B11 B11
BI6 A15
(+)
FD1 B15 (∗1) A12
Disconnector N/O contact A7
BO13
BI7 A16 B12
B16 (∗1)
Disconnector N/C contact B7
A13
BI8
BO14
A8
IO#1 IO#4 B13
Carrier protection block
BI9

CB ready condition B8 IO#3


BI10
TB2-A13
A9 SIGNAL SEND
BI11 BO13 B13 (HIGH SPEED RELAY) Caution
A12 Connect FD output contact with A- to
Autoreclose block (REC BLOCK) B9 FAIL
BI12
RELAY FAILURE C-phase tripping output contacts in
B12
A10
series.
Indication reset TB2-A18
BI13 TB2-A18
COM-A COM2-A
B18 COM2-B A17
Main protection trip B10
A17 COM2-0V A16
BI14 COM-B Dual RS485 I/F ports
A11 B17 RS485 I/F B18
Main protection ON COM1-A
B11 (Single port)
BI15 A16 COM1-B B17
(-) COM-0V
EXT trip-A B16 COM1-0V B16
TB2 -A14
BI16 Ethernet LAN I/F
T (option)
External trip signals EXT trip-B B14
(CBF Initiation) IO#2
BI17 Optical I/F
T
EXT trip-C OP IEC103(option)
A15 R
(-) B15 BI18
CN1
TB5 -A14 IRIG-B
(+) BI19
TB4- A3
(+) TB5 TB4 TB3 TB2 CN1
B14 IO#3 B3 A1 B1
BI20
TP-A1 A1 OP
A15 TRIP-A E
AB AB AB AB
B15 BI21
(-) TP-B1 A2
TRIP-B BUS CB TB1
11 11 11 11
RELAY FAIL. 1 2
≧1 TP-C1 B2
DD FAIL. TRIP-C T
TB4-A14
TB4 -A16 +5Vdc A18 B18 1 2
B14
DC (+) B16 DC-DC (+) IO#3 IO#1 IO#4 IO#2
19 20
A17 VCT
SUPPLY 0V TP-A2 A12
(-) B17 TRIP-A
A18 Terminal Block Arrangement (Rear view)
B18 TP-B2 A13
(∗1)These connections are connected (∗1) TRIP-B
A15
by wire link before shipment. B15 TP-C2 B13
TRIP-C
CASE EARTH
E

Figure 29 Typical external connection of Model 401B

34
GRZ100
BUS BUS VT
TB1 -1
2 TB3-A1 TB5- A2
CT 3 BO1
4 TB2- A2 B1 A1
5 BO1 BO1
CB 6 A1 A2
B1
7 BO2 BO2
BO2 B2
8 B1
9 B2
Io from BO3 A3 BO3
10
Adjacent Line CT B2 BO3
CB 11 A3
B3
CT BO4
VT 12 A3 A4 B3
BO4
13 BO4 B3 B4 A4
14
BO5
A4 A10 B4
15 BO5
BUS VT 16 BO5 B4 B10 A5
CB
ADJACENT LINE VT 17 BO6
A5 A11 B5
18
BUS 20 BO6
BO6 B5 B11 A6
BO7
A6 A12 B6
BO7
BO7 B6 B12 A7
(+)
[Default setting] CB1-A TB4 -A4 BO8
A7 A13 B7
BI1 BO8
CB auxiliary contacts BO8 B7 B13 A8
(Closed when bus CB main CB1-B B4
contact closed.) BI2 BO9
A8 B8
CB1-C A5 BO9 B8 A9
BI3
BO10
Signal receive (CH1) B5 A9 B9
BI4
BO10 B9 A17 A10
(+)
Signal receive (CH2) A6 FD2 B17
or Z1-EXT initiation BI5 (*) BO11
A10 B10
A18
External VT failure (EXT VTF) B6 BO11 (*)
B10 B18 (*) A11
BI6
BO12
A7 A11 A15 B11
Disconnector N/O contact (+)
BI7 FD1 B15
BO12 B11 A12
Disconnector N/C contact B7 (*)
A16 BO13
BI8 B12
IO#1 B16 (*)
Carrier protection block A8
BI9
A13

CB ready condition B8 IO#4 BO14


B13
BI10 TB2-A13
A9 SIGNAL SEND
BO13
BI11 B13 (HIGH SPEED RELAY) IO#3
B9 A12
Autoreclose block (REC BLOCK) FAIL
BI12 RELAY FAILURE
B12 TB2-A18
Indication reset A10 COM2-A
BI13 TB2-A18 COM2-B A17
COM-A A16
B10 B18 COM2-0V
Main protection trip Dual RS485 I/F ports
BI14 COM1-A B18
A17
Main protection ON A11 COM-B COM1-B B17
RS485 I/F
B11 BI15
B17
(-) (Single port) COM1-0V B16
EXT trip-A A16
TB2 -A14 COM-0V
BI16 B16
External trip signals EXT trip-B Ethernet LAN I/F
B14 IO#2
(CBF Initiation)
BI17 T (option) Caution
EXT trip-C A15 Connect FD output contact with A- to
T Optical I/F
(-) B15 BI18 OP
R IEC103 (option) C-phase tripping output contacts in series.
TB5 -A14
(+) BI19
CN1
B14 IO#3 IRIG-B
BI20
TB4-A3
A15
B15 BI21
B3
(-)
TP-A1 A1
TRIP-A TB5 TB4 TB3 TB2 CN1
A1 B1
RELAY FAIL.
≥1 TP-B1 A2
TRIP-B BUS CB OP
DD FAIL.
E
TB4 -A16 +5Vdc TP-C1 B2
TRIP-C
DC (+) B16 DC-DC TB4-A14 TB1
SUPPLY A17
0V B14 1 2
(-) B17 T
A18
B18 TP-A2 A12
TRIP-A
(∗1) A15 IO#3 IO#1 IO#4
A18 B18 19
IO#2
20

(∗1)These connections are connected B15 TP-B2 A13 VCT


TRIP-B CENTER CB
by wire link before shipment.
CASE EARTH Terminal Block Arrangement (Rear view)
E TP-C2 B13
TRIP-C

Figure 30 Typical external connection of Model 501B

35
GRZ100
BUS
TB3- A2
BO1 TB2-A1
A1
BUS VT BO1
BO2 B1
B1
TB1 -1 A2
CT 2 BO3
3 B2 BO2
B2
4
5 A3 A3
6
BO4 BO3
7 B3 B3
8
9 A4 A4
Io from 10
BO5 BO4
Adjacent Line CT B4 B4
CB
11 A5 A5
VT
BO6 BO5
12 B5 B5

13 A6 A6
14
BO7 BO6
B6 B6
15
BUS VT 16 A7 A7
BO8 BO7
B7 B7
20
A8 A8
BO9 BO8
B8 B8
(+)
[Default setting]
A9 A9
CB1-A TB4 -A4
BI1 BO10 BO9
B9 B9
CB auxiliary contacts
CB1-B B4
(Closed when bus CB main A10 A10
contact closed.) BI2
BO11 BO10
B10 B10
CB1-C A5
BI3 A11

B5 BO12 IO#3
B11
Transfer trip 1 BI4

TB3-A13
Transfer trip 2 A6
BI5 BO13 (HIGH SPEED RELAY)
B13
B6 A12
External VT failure (EXT VTF) BI6
FAIL
RELAY FAILURE
IO#1
B12
A7 TB3-A18
Disconnector N/O contact COM2-A
BI7 TB3-A18
COM-A COM2-B A17
B7 B18 A16
Disconnector N/C contact COM2-0V
Dual RS485 I/F ports
BI8 A17
COM-B RS485 I/F COM1-A B18
(Single port) B17
A8 B17 COM1-B
Carrier protection block
BI9 A16 COM1-0V B16
COM-0V
B8 B16
CB ready condition BI10
T Ethernet LAN I/F
A9 (option)
BI11

Autoreclose block (REC BLOCK) B9


BI12
CN1
IRIG-B
Indication reset A10
BI13 TB4 TB3 TB2 CN1
A1 B1 A1 B1
TX1 CH1
Main protection trip B10 CH1 RX1
BI14 CK1 Electrical E
A11 TX2 Interface
Main protection ON (*)CH2 RX2
B11 BI15 CK2 Communication
(-) or B10 TB1
EXT trip-A TX1 Links 1 2
CH1 IO#3
TB3 -A14 RX1 Optical
BI16 Interface T
A18 B18 A18 B18
External trip signals EXT trip-B TX2
B14 (*) CH2 IO#1 IO#2 19 20
(CBF Initiation) IO#2 RX2 VCT
BI17
EXT trip-C For electrical interface
A15 TB4- A3
B15 BI18 (+)
(-) B3 CN1
TB4 TB3 TB2
A1 B1 A1 B1
TP-A1 A1
RELAY FAIL. TRIP-A TX1
≧1
RX1
DD FAIL. E
TP-B1 A2
TRIP-B BUS CB (*)
TB4-A16 +5Vdc TX2
DC (+) B16 DC-DC B10 TB1
TP-C1 B2 RX2
1 2
SUPPLY A17 TRIP-C IO#3
0V TB4-A14
(-) B17
A18 B14 (+) T
A18 B18 A18 B18
B18 19 20
(∗1) IO#1 IO#2
A15 TP-A2 A12 VCT
B15 TRIP-A
(∗1)These connections are connected For optical interface
by wire link before shipment. TP-B2 A13
CASE EARTH TRIP-B
E Terminal Block Arrangement (Rear view)
TP-C2 B13 (Note) GRZ100-211: 2 terminal system, not provided
TRIP-C
with terminals marked with (*).
GRZ100-221: 3 terminal system

Figure 31 Typical external connection of Models 211B/221B

36
GRZ100

BUS

TB3- A2 TB2-A1
BO1
BUS VT A1 BO1
B1
BO2
TB1 -1 A2
B1
CT 2
3 BO3 BO2
B2
4 B2
5 A3
6
7 A3 BO3
B3
8
BO4
9 B3 A4
Io from 10
A4 BO4
adjacent Line CT B4
CB
BO5
11 B4 A5
VT
12 A5 BO5
B5
BO6
13 B5 A6
14
A6 BO6
B6
15
BO7
BUS VT 16 B6

20 A7 IO#3
BO8
B7

[Default setting] (+) A8


BO9
CB1-A TB4 -B4 B8
CB1 contacts A4 BI1
(Closed when CB main CB1-B A9
B5
contact closed.) A5 BI2 BO10
B9
CB1-C B6
A6 BI3 A10
B7
Transfer trip 1 BO11
B10
A7 BI4
B8
Transfer trip 2 BI5
A11
A8
B9 BO12
B11
External VT failure (EXT VTF) BI6
A9
B10 IO#1 TB3-A13
Disconnector N/O contact BI7
A10
BO13 (HIGH SPEED RELAY)
B11 B13
Disconnector N/C contact BI8
A11 A12
FAIL
B12 RELAY FAILURE
Carrier block BI9
A12 B12 TB3-A18
B13 COM2-A
Indication reset BI10
TB3-A18 A17
A13 COM-A COM2-B
B14 B18 COM2-0V A16
Protection block BI11 Dual RS485 I/F ports
A14 A17 B18
COM-B RS485 I/F COM1-A
B15 (Single port)
Z1X initiation B17 COM1-B B17
A15 BI12
(-) A16 COM1-0V
COM-0V B16
EXT trip-A TB3 –A14
B16
BI16
External trip signals EXT trip-B B14
BI17 IO#2 Ethernet LAN I/F
(CBF Initiation) T
EXT trip-C A15 (option)
TB4 TB3 TB2 CN1
BI18 A1 B1 CH1 A1
T
(-) B15
B1
Fibre optic I/F
OP
TB2 –A7 R IEC103(option)
OCI block BI19
OP E
CN1
B7 IRIG-B
EFI block BI20 B6 TB1
1 2
A8 IO#3
OC block TX1
BI21 CH1 RX1 T

DEF block B8 CK1 Electrical A18 B18 A18 B18


BI22 IO#3 TX2 Interface IO#1 IO#2 19 20
(*)CH2 RX2 VCT
EXTTP block A9 CK2 Communication
or
BI23 Links For electrical interface
TX1
CH1 Optical
STUB block B9 RX1
BI24 Interface TB4 TB3 TB2 CN1
A1 B1 A1 B1
SOTF block A10 TX2
(*) CH2
BI25 RX2 TX1

(-) B10 RX1 OP


E
(*)
RELAY FAIL. TX2
TB1
≧1 RX2 B6
DD FAIL. TB4- A3 IO#3
1 2
(+)
B3
TB4 -A16 +5Vdc T
DC (+) B16 DC-DC TP-A1 A1 A18 B18 A18 B18
SUPPLY A17 TRIP-A IO#1 IO#2 19 20
0V VCT
(-) B17
A18 TP-B1 A2 For optical interface
TRIP-B
B18
(∗1) A15 Terminal Block Arrangement (Rear view)
TP-C1 B2
B15 TRIP-C
(∗1)These connections are connected (Note) GRZ100-214: 2 terminal system, not provided
by wire link before shipment. with terminals marked with (*).
CASE EARTH
E GRZ100-224: 3 terminal system

Figure 32 Typical external connection of Models 214B/224B

37
GRZ100
BUS

TB2- A2 TB5- A1 TB3- A2


BO1 BO1
BUS VT A1 BO1
B1 A1
BO2 BO2
TB1 -1 A2
B1 B1
CT 2
3 BO3 BO2 BO3
B2
4 B2 B2
5 A3
6 A3
7 BO3
B3 A3
BO4
8 B3
9 BO4
A4 B3
Io from 10 A4
BO4
adjacent Line CT BO5 B4 A4
CB B4
11 BO5
A5 B4
VT A5
12 BO5
BO6 B5 A5
B5
13 BO6
A6 B5
14 A6
BO6
BO7 B6 A6
15 B6
BUS VT 16 BO7
A7 B6
A7
BO7
20 BO8 B7 A7
B7
BO8
A8 B7
[Default setting] (+) A8
BO8
BO9 B8 A8
CB1-A TB4 -B4 B8
CB1 contacts BI1 A9 BO9
A4 B8
(Closed when CB main CB1-B A9
B5 BO9
BI2 B9 A9
contact closed.) A5 BO10
B9
CB1-C B6 BO10
A10 B9
A6 BI3 A10
BO10
B7 B10 A10
Transfer trip 1 BO11
B10
A7 BI4
BO11
B10
Transfer trip 2 B8
A11 IO#3
A8 BI5
BO12 A11
B9 B11
External VT failure (EXT VTF) BI6 BO12
A9 B11
B10 IO#1 TB2-A13
Disconnector N/O contact BI7
A10 A12
BO13 (HIGH SPEED RELAY)
B11 B13 BO13
Disconnector N/C contact BI8 B12
A11 A12
FAIL
B12 RELAY FAILURE
Carrier block A13
A12 BI9 B12
BO14
B13 B13
Indication reset BI10 TB3-A18
A13 COM-A
B14
Protection block BI11
B18
IO#4
A14 A17
COM-B RS485 I/F
B15 (Single port)
Z1X initiation BI12 B17
A15
(-) A16
EXT trip-A TB2 –A14 COM-0V
BI16 B16 TB3-A18
COM2-A
External trip signals EXT trip-B B14 Ethernet LAN I/F
T COM2-B A17
BI17 IO#2 (option)
(CBF Initiation) A16
COM2-0V
EXT trip-C A15 Dual RS485 I/F ports
BI18 T Fibre optic I/F COM1-A B18
B15 OP IEC103(option)
(-) R B17
COM1-B
TB5 –A12
OCI block BI19
CN1 COM1-0V B16
IRIG-B
B12
EFI block BI20
A13 TX1 Electrical Communication
OC block CH1 RX1
BI21 CK1 Interface Links
DEF block B13 TX2
BI22 IO#3 (*)CH2 RX2
CK2 or TB5 TB4 TB3 TB2 CN1
A14 CN2
EXTTP block TX1 CH1
A1 B1
BI23 CH1 Optical
RX1
STUB block B14 Interface
OP E
BI24
TX2
A15 (*) CH2
SOTF block RX2
TB1
BI25
1 2
ARC block B15
BI26 T

CB1 ready A16 A18 B18


BI27 IO#3 IO#1 IO#4 IO#2
19 20
VCT
CBF block B16
BI28 For electrical interface
(-) A18
TB3 –A14 TB5 TB4 TB3 TB2 CN1
(+) BI34 A1 B1
TB4- A3
B14 (+) TX1
BI35 IO#4 B3 RX1 OP E
A15 TP-A1 A1
TRIP-A (*)
BI36 TX2
TB1
(-) B15 RX2 2
1
TP-B1 A2
RELAY FAIL. TRIP-B
≧1
T
DD FAIL. TP-C1 B2
TRIP-C A18 B18
19 20
TB4 -A16 +5Vdc IO#3 IO#1 IO#4 IO#2
VCT
DC (+) B16 DC-DC
A17 For optical interface
SUPPLY 0V
(-) B17
Terminal Block Arrangement (Rear view)
A18
(∗1)These connections are connected (∗1) B18 (Note) GRZ100-216: 2 terminal system, not provided
by wire link before shipment. with terminals marked with (*).
CASE EARTH
E GRZ100-226: 3 terminal system

Figure 33 Typical external connection of Models 216B/226B

38
GRZ100
BUS BUS VT
TB1 -1 TB3- A2
TB2-A1
2 BO1
CT 3 A1 BO1
B1
4
BO2
5 B1 A2
CB 6
7 BO3 BO2
B2
8 B2
Io from 9 A3
adjacent Line CT 10 A3
BO3
CB B3
11 BO4 B3
CT A4
VT 12
A4
BO4
B4
13 BO5 B4
14 A5
A5 BO5
15 B5
BUS VT 16 BO6
CB B5
ADJACENT LINE VT 17 A6
18 A6 BO6
BUS 20 B6
BO7 B6
A7
A7 BO7
B7
BO8 B7
(+) A8
[Default setting]
CB1-A TB4 -A4 A8 BO8
B8
BI1
BO9 B8
CB auxiliary contacts A9
CB1-B B4
(Closed when bus CB main
BI2 A9 BO9
contact closed.) B9
CB1-C BO10 B9
A5 A10
BI3
A10 BO10
B10
B5
Transfer trip 1 BI4 BO11 B10

A6 A11
IO#3
Transfer trip 2
BI5
BO12 B11
B6
External VT failure (EXT VTF) BI6
IO#1 TB3- A13

A7 BO13
Disconnector N/O contact B13 (HIGH SPEED RELAY)
BI7
A12
B7 FAIL
Disconnector N/C contact RELAY FAILURE
BI8 B12

A8 TB3-A18
Carrier protection block TB3-A18 COM2-A
BI9 COM-A
COM2-B A17
B18
B8 A16
CB1 ready condition BI10 A17 COM2-0V
Dual RS485 I/F ports
COM-B
RS485 I/F COM1-A B18
CB2 ready condition A9 B17
(Single port) COM1-B B17
BI11 A16
COM-0V COM1-0V B16
B9 B16
Autoreclose block (REC BLOCK)
BI12
T Ethernet LAN I/F
(option)
Indication reset A10
BI13

Main protection trip B10


BI14 CN1
IRIG-B CN1
Main protection ON A11 A1
TB4 TB3 TB2
B1 B1
B11 BI15 Communication CH1
A1
(-) TX1 Links
EXT trip-A CH1 RX1
TB3 -A14 CK1 Electrical E
(+) BI16 TX2 Interface
(*)CH2 RX2
External trip signals EXT trip-B B14 CK2 B10 TB1
IO#2 or
(CBF Initiation) BI17 TX1 IO#3 1 2
CH1 Optical
EXT trip-C RX1 T
A15 Interface
A18 B18 A18 B18
B15 BI18 19 20
(-) TX2 IO#1 IO#2
(*) CH2 VCT
RX2
For electrical interface
TB4-A3
B3 TB4 TB3 TB2 CN1
A1 B1 B1
A1
TP-A1 A1 TX1
TRIP-A
RX1
RELAY FAIL. E
≥1 TP-B1 A2 BUS CB
DD FAIL. TRIP-B (*)
TX2

RX2 B10 TB1


TB4 -A16 +5Vdc TP-C1 B2 IO#3 1 2
DC (+) TRIP-C
B16 DC-DC
SUPPLY A17 TB4-A14 T
0V
(-) B17 B14 A18 B18 A18 B18
19 20
A18 IO#1 IO#2
VCT
B18 TP-A2 A12
TRIP-A CENTER CB For optical interface
(∗1)These connections are connected (∗1) A15
by wire link before shipment. B15
TP-B2 A13 Terminal Block Arrangement (Rear view)
TRIP-B
CASE EARTH (Note) GRZ100-311: 2 terminal system, not provided
E TP-C2 B13
TRIP-C with terminals marked with (*).
GRZ100-321: 3 terminal system

Figure 34 Typical external connection of Model 311B/321B

39
GRZ100
BUS BUS VT
TB1 -1 TB2- A2 BO1 TB5- A2 TB3- A2
BO1
2 BO1
CT 3 A1 A1 A1
4 BO2 BO2
BO2
5 B1
CB BO3 B1 B1
6 BO3
BO3
7
8 B2 B2 B2
Io from 9
adjacent Line CT 10 A3 A3 A3
CB 11 BO4 BO4 BO4
B3 B3 B3
CT VT 12 A4 A4 A4
13 BO5 BO5 BO5
B4 B4 B4
14
A5 A5 A5
15
BUS VT 16 BO6 B5 BO6 BO6
CB B5 B5
ADJACENT LINE VT 17
18 A6 A6 A6
BUS 20
BO7 B6 BO7 BO7
B6 B6
(+)
A7 A7 A7
[Default setting] CB1-A TB4- A4
BO8 B7 BO8 BO8
BI1 B7 B7
CB auxiliary contacts
(Closed when bus CB main CB1-B B4 A8 A8 A8
contact closed.) BI2
BO9 B8 BO9 BO9
B8 B8
CB1-C A5
BI3 A9 A9 A9

B5 BO10 B9 BO10 BO10


Transfer trip 1 B9 B9
BI4
A10 A10 A10
Transfer trip 2 A6
BO11 B10 BO11 BO11
BI5 B10 B10

B6 A11 A11 A11


External VT failure (EXT VTF)
BI6
BO12 B11 BO12 BO12
B11 B11
A7
Disconnector N/O contact
BI7 TB2-A13 A12 A12
BO13 BO13
Disconnector N/C contact B7 B13 (HIGH SPEED RELAY) B12 BO13
B12
BI8
FAIL A12 A13 A13
Carrier protection block A8 IO#1 RELAY FAILURE
BI9 B12 BO14 B13 BO14 B13

CB1 ready condition B8 TB3-A18


BI10 COM-A
B18 IO#3 IO#4
CB2 ready condition A9
A17
BI11 COM-B
B17 RS485 I/F
B9 (Single port)
Autoreclose block (REC BLOCK)
A16
BI12 COM-0V
B16 TB3-A18
A10 COM2-A
Indication reset
COM2-B A17
BI13 T Ethernet LAN I/F
(option) COM2-0V A16
Main protection trip B10 Dual RS485 I/F ports
COM1-A B18
BI14 T Fibre optic I/F
OP IEC103(option) COM1-B B17
Main protection ON A11 R
COM1-0V B16
(-) B11 BI15 CN1
EXT trip-A TB2 -A14 IRIG-B

BI16
External trip signals EXT trip-B B14
TX1 Electrical Communication
(CBF Initiation) IO#2 CH1 RX1
CK1 Interface Links
BI17
TX2
EXT trip-C A15 CH2 RX2
CK2 or TB5 TB4 TB3 TB2
(-) B15 BI18
TX1 CH1 A1 B1 CN1
CB2-A CH1 Optical
TB5 -A14 RX1
(+) Interface
BI19 OP E
CB auxiliary contacts
(Closed when bus CB main CB2-B CH2 TX2
B14 IO#3 RX2
contact closed.) BI20 TB1
1 2
CB2-C A15
BI21 T
B15
(-)
A18 B18
TB3- A14 IO#3 IO#1 IO#4 IO#2 19 20
TB4- A3
(+) BI34
B3
For electrical interface
B14
BI35 IO#4 TP-A1 A1
TRIP-A TB5 TB4 TB3 TB2
A15 A1 B1 CN1
TP-B1 A2 BUS CB
B15 BI36 TRIP-B TX1
(-) RX1
OP E
TP-C1 B2
RELAY FAIL. TRIP-C
≥1 TB4- A14 TX2
DD FAIL. TB1
B14 RX2
1 2
TB4 -A16 +5Vdc
DC (+) TP-A2 A12 T
B16 DC-DC TRIP-A
SUPPLY A17 A18 B18
0V IO#4
(-) B17 TP-B2 A13 IO#3 IO#1 IO#2 19 20
TRIP-B CENTER CB
A18
B18 For optical interface
(∗1)These connections are connected (∗1) TP-C2 B13
A15 TRIP-C
B15
Terminal Block Arrangement (Rear view)
by wire link before shipment.

CASE EARTH
E

Figure 35 Typical external connection of Model 323B

40
||
||
------
------
------
-----
------
------
------
------
------
------
------
------
-----聞
・・・・岡
・・・・・・
・・・・・・
・・・・・・
・・・・・・
・・・・・
・・・・同
------
------
I
-------
------
------ l
Il
------
li
-----
li li
------
------
------
------
------
------
------
------
- ------
-----E
I l
- 劃E・E・
l
-E・E・- i ----------
-EEEE・
l l
l
-----
Z------
EE・E・- E・---
- - -