In this article, will demonstrate some of the basics for carrying out fire sprinkler
calculations by the long hand method with just the aid of a scientific calculator or
our own hydraulic calculator - Hcal2 which you can freely download from our
website.
We will for this example use simple three sprinklers and three pipes which would of
course be part of a much larger fire sprinkler system. These basic procedures can
also be used for calculating many other types of systems such as fire hydrant,
hose reel or the discharge from a water cannon or monitor we can also use the
same principal for almost all other water-based fire protection systems if we have a
k-factor for the output device (fire sprinkler, water mist nozzle and so on).
In this example, will we use a very simple system with just three sprinklers and
three pipes this is often called a range pipe or branch pipe, which is part of a larger
'tree system'. A tree system is 'end feed', that is water is only fed from one direction
as opposed to a grid or loop system when water may arrive at the sprinkler head
from more than one direction.
Below is a diagram of the three sprinklers and three pipes which we will calculate.
We have dimensioned the pipe lengths and given each junction point a unique
node reference number which we use throughout the calculations.
For each pipe, we need to know the pipe length, internal diameter (ID) of the pipe
and the pipe material so we can determine the pipes c-factor, the table below
summarises the pipe data which we will need for the calculation for this example:
We will also we will need some additional information such as the type sprinkler
The first step is to calculate the minimum flow which will be required at the most
remote sprinkler which in this case is at node [130], this is a two-step process as
will need to calculate the minimum flow required to satisfy the 7.50 mm/min design
density and then find the flow rate from the sprinkler given the sprinklers minimum
pressure requirement, whichever is the greater flow will become our initial flow
from the first sprinkler at node [130].
We will first calculate the flow given the design density of 7.50 mm/min and the
area the head is covering, we do this by multiplying the design density by the head
area:
Equation 1:
q1 = (design density) x (area per sprinkler)
In this example, this gives:
q1 = 7.50 mm/min x 10.20 m2 = 76.50 L/min
The second step is to calculate the minimum flow from the sprinkler given the K-
Factor and the minimum head pressure by using the standard K-Factor formula:
Equation 2:
q = kp0.5
Where
p = pressure loss in bar per meter
Q = flow through the pipe in L/min
C = friction loss coefficient
d = internal diameter of the pipe in mm
We know that the flow rate from the sprinkler at node [130] is 76.50 L/min and this
will be the flow rate in the first pipe between nodes [130]-[120]. As the pipe has an
internal diameter of 27.30 mm and has a C value of 120 this will give us:
This gives 70 x 1.2800.5 = 79.20 L/min from the sprinkler head at node [120] which
we now add to the flow in the first pipe node [130]-[120] to find the total flow in the
second pipe [120]-[110] to find the total flow in the seconded pipe which is 155.70
L/min.
Having found the total flow in the seconded pipe [120]-[110] we can now find the
pressure loss in, to do this we will use the Hazen-Williams pressure loss, formula 4
which we used above this gives us:
We now add the pressure loss 0.317 bar to the pressure at node [120] to find the
pressure at node [110] this give us: 0.317 + 1.280 = 1.597 bar
The last step is to find the pressure loss in the third pipe [110]-[100] and again we
will use the Hazen-Williams pressure loss formula given is formula 4 above.
However, the last pipe has an internal diameter of 36.0 mm so this gives us:
We now add the pressure loss in this pipe to the pressure at node [110] to find the
pressure at node [100] this will be 0.189 + 1.597 = 1.786 bar. We have now
completed the calculation for all three sprinkler heads and have found the source
pressure and flow required for this system is:
244.20 L/min @ 1.786 Bar
This pressure and flow is often referred to as the source requirement for the
system and is the minimum pressure and flow required for the system for it to be
able to provide the required design density (in this example 7.50 mm/min) at the
most remote head [MRH] at node [130].
You should also be able to see that only the Most Remote Head has the minimum
requirement of 7.50 mm/min design density and all the other sprinklers will have a
higher pressure as they are hydraulically closer to the water source so they will
1. Calculate minimum flow from the MRH with the sprinkler minimum pressure
and k-factor
2. Calculate the minimum flow given the system design density and sprinkler
head area.
3. If the calculation in step 2 is the highest flow demand, then calculate the
required head pressure otherwise we can use the minimum sprinkler
pressure in step 1.
4. Calculate the pressure loss in the pipe.
5. Add the head pressure to the pressure loss in step 4 to determine the
pressure at the next sprinkler.
6. Use the k-factor formula to determine the flow from the sprinkler head.
7. Repeat step 4 to 6 until you do not have any more sprinklers or pipes