Sei sulla pagina 1di 8

Engineering Structures 26 (2004) 1931–1938

www.elsevier.com/locate/engstruct

Reliability based assessment of the effectiveness of metallic dampers


in buildings under seismic excitations
Raúl Oscar Curadelli a,, Jorge Daniel Riera b
a
Federal University of Rio Grande do Sul, Porto Alegre, Brazil
b
Laboratory of structural Dynamic and Reliability, Federal University of Rio Grande do Sul, Sao Simao 385, Casa 1,
91420-560 Porto Alegre, RS, Brazil

Received 25 April 2003; received in revised form 14 June 2004; accepted 7 July 2004

Abstract

Both for purposes of seismic retrofitting and in new designs of building frames, external energy dissipation systems may be
advantageously used. In this paper, the improvement of the system reliability achieved through use of external passive metallic or
viscous dampers is assessed by simulation. The effect of the dissipation system is numerically evaluated using the properties of a
prototype lead-rings damper developed at LDEC, UFRGS in conjunction with methods for nonlinear structural dynamic analy-
sis. To obtain robust estimators of the reliability, a database including acceleration records with markedly different characteristics
was used in the simulation study. On the premise that the efficiency of a dampers system can best be assessed on a reliability
basis, full reliability analyses of typical steel and reinforced concrete frame buildings are performed, showing that a five-fold
reduction in the probability of failure may be achieved by introducing external metallic or similar dampers systems.
# 2004 Elsevier Ltd. All rights reserved.

Keywords: Reliability in structures; Metallic dampers; Fragility curves; Energy dissipation

1. Introduction damage, which is clearly undesirable. Moreover, the


task of restoring a structure damaged by an earth-
In general, the traditional approach for structural quake to its original condition is still cumbersome
design of buildings under seismic loads reduces the and costly. This resulted in the search for alter-
original dynamic problem to an equivalent static prob- natives, such as seismic isolation or the incorporation
lem. The dynamic excitation is modelled as a set of lat- of energy dissipators external to the structure, both
eral static loads, which for a low-intensity earthquake of which have received increasing attention in the last
may be resisted by the structure within its elastic range. two decades [1,2]. This paper discusses an application
Meanwhile, in case of a moderate or strong earth- of the second approach: by the incorporation of ele-
quake, the structure is allowed to deform into the ments specifically designed to dissipate energy, the
inelastic range, which may give rise to structural and deformations of the structure during an earthquake
non-structural damage, but should not result in failure. may be significantly reduced. Hence, the structure
This philosophy has been generally adopted in codes may remain elastic or at least see the ductility
and design recommendations, meeting considerable demand on its members greatly reduced.
success, in terms of preservation of life, i.e. of avoiding A large variety of passive devices for energy dissi-
failure. pation are available [2]. In this paper, the increment of
However, the approach presents some obvious defi- the system reliability achieved through use of passive
ciencies: energy dissipation is achieved through structural metallic or viscous dampers is assessed by simulation.
The effect of the external dissipation system is numeri-

Corresponding author. Fax: +55-54-3316-3000. cally evaluated using the properties of a metallic dam-
E-mail address: ocuradelli@yahoo.com (R. O. Curadelli). per developed at LDEC, UFRGS [3] in conjunction
0141-0296/$ - see front matter # 2004 Elsevier Ltd. All rights reserved.
doi:10.1016/j.engstruct.2004.07.004
1932 R.O. Curadelli, J.D. Riera / Engineering Structures 26 (2004) 1931–1938

Fig. 1. View of tested energy dissipator device.

with methods for nonlinear structural dynamic analy-


sis, applied to enhance the seismic worthiness of exist-
ing steel and reinforced concrete structures. To obtain
robust estimators of the reliability, a database includ-
ing acceleration records with markedly different char-
acteristics was used in the simulation study.

2. Metallic energy dissipators

The inelastic strain of metallic elements with large


hysteretic cycles is one of the most effective mechan-
isms available to dissipate energy in vibrating struc-
tures. The first proposals to use this type of damper to
dissipate part of the seismic energy in structures sub-
jected to earthquake excitation are attributed to Kelly
et al. [4] and Skinner et al. [5]. In those devices, the Fig. 2. Force–displacement curves of metallic damper
(frequency ¼ 0:5 Hz).
inelastic strains were produced in steel beams by tor-
sion and bending. More recently, steel plate dampers
have received considerable attention. Bergman and
Goel [6] reported cyclic tests with ‘‘X’’ and ‘‘V’’ plate
dampers manufactured by Bechtel Corporation. At the
University of California, Berkeley, Wittaker et al. [7]
developed another program, jointly sponsored by
Bechtel Power Corporation and Counter Quake Cor-
poration, focused on the analysis of a device with ‘‘X’’
plates called Added Stiffness and Damping (ADAS).
Another type of metallic damper, based on lead
extrusion, was developed by Robinson and Greenbank
[8]. Monti and Robinson [9] describe a lead commercial
damper that works under shear deformations.
A device for energy dissipation, using the defor-
mation capacity of lead, was developed at LDEC,
UFRGS [3] (Fig. 1). When a relative displacement
between both steel coaxial cylinders is applied, a plastic
deformation in a set of lead rings occurs, due to com- Fig. 3. Damper force–displacement curves for different frequencies.
bined compression and shear stresses. If this process is
repeated in both directions, a hysteretic cycle is
developed (Figs. 2 and 3). nearly rectangular force–displacement curve. In conse-
The most important characteristics of a device of this quence, the absorbed energy oscillates between 80%
type are its force–displacement curve. As the elastic and 90% of the total strain energy corresponding to a
energy involved in a cycle is relatively small compared given capacity and displacement.
with the plastic energy, and the post-yielding hardening To study the mechanical properties at different strain
is negligible, this device acts as rigid-plastic with a levels, tests with displacement amplitudes from 1 to 12
R.O. Curadelli, J.D. Riera / Engineering Structures 26 (2004) 1931–1938 1933

mm were performed. Fig. 2 shows a sample curve for 4. Reliability assessment of externally damped
cyclic excitation at 0.5 Hz. To study the influence of structures
the strain rate on the load vs. strain curve of the dam-
per, cyclic tests for frequencies ranging between 0.1 and In order to account for the uncertainties involved in
the frequency content, duration and other features of
3 Hz were carried out. Fig. 3 shows typical results for a
the excitation, the most appropriate approach to assess
displacement amplitude of 9 (mm) and frequencies
the effectiveness of a structural damper arrangement is
equal to 0.1, 0.3, 0.5 and 1 Hz. In the frequency range
through a reliability analysis. Thus, in this paper the
studied, which covers most buildings and Civil Engin-
failure probability of the structure prior to and after
eering structures, the damper constitutive relation can
the installation of the external metallic dampers is eval-
be considered independent on the excitation frequency. uated. The efficiency of the damping system is mea-
The device was subjected to 500 cycles, from 0.1 to sured by the computed decrease of the failure
3 Hz and displacement amplitudes between 1 and 12 mm probability of the structure.
to assess the risk of shake-down or early weakening. No The procedure is basically the following: (a) samples
change in the mechanical properties was observed, even of the excitation are obtained, as described below and
under conditions considered more severe than expected normalized by the peak ground acceleration (PGA), (b)
in service. fragility curves are built by simulation, counting the
relative number of failures for each PGA level, and (c)
the fragility curves are used to estimate, in a second
3. Methods of analysis of structures with external stage, the failure probability for an N-years period at
dampers any specific location, as discussed in Section 6.
In step (a), either acceleration time-histories obtained
To consider the presence of damping devices in struc- as samples of earthquakes defined as stationary or
tural design, it is necessary to define their non-linear evolutionary random processes or actual earthquake
stress–strain law. For such purpose, Ozdemir [10] pro- records may be used. In order to draw general conclu-
posed a model using analogies with existing elastoplastic sions about the expected seismic performance of build-
and viscoelastic constitutive laws used earlier for met- ing structures provided with external metallic dampers,
allic elements under time dependent loads. Afterwards, applicable in any location, a set of 10 widely different
Bhatti et al. [11] used the methodology to determine the acceleration time-histories, corresponding to strong
response of structures with torsional dampers and a earthquakes recorded in Asia and North and South
seismic isolation system. An extension of Ozdemir’s America, was employed in the study. The records are
model for multiaxial loads is due to Graesser and the following:
Cozzarelli [12]. Zienkiewicz and Taylor [13] discuss a
more complete and complex finite element model in 1. Caucete, San Juan, Argentina, 1977.
plasticity of metals. Recently, Dargush and Soong [14] 2. Chichi, CHY010 E, N, Taiwan, 1999.
and Tsai and Tsai [15] proposed triangular and ‘‘X’’ 3. Imperial Valley, El Centro, 000, USA, 1979.
metallic damper models on the basis of classical mech- 4. Kobe, JMA, NS, Japan, 1995.
anics, but without verification by means of experimental 5. Landers, Josuha Tree, 000, USA, 1992.
6. Llollelo, 010, Chile, 1985.
testing or more advanced theoretical models.
7. Loma Prieta, Halls Valley, 000, USA, 1989.
Non-linear structural analyses of elastic structures
8. Northridge, Brentwood V.A. Hospital, 195, CA,
provided with metallic dampers using the finite element
USA, 1994.
program DRAIN-2D [16] are found in the works of
9. San Fernando, Pasadena, Cit Athenaeum, 000,
Tsai et al. [17] and Xia and Hanson [18], who employ
USA, 1971.
steel plate triangular and ‘‘X’’ dampers, respectively. 10. Taft, CA, N21E, USA, 1952.
In several previous contributions, the seismic per-
formance of externally damped structures was assessed The accelerograms were normalized to 10 specified
by the storey drift method, as shown by Pall et al. [19], levels of PGAs, as required by the probabilistic seismic
Filiatrault and Cherry [20] and Aiken et al. [21], who analysis discussed in Section 5. It is important to note
were concerned with friction dampers. Similarly, Tsai that different scaling procedures are possible, such as
et al. [22] and Martinez-Romero [23] considered met- response-spectrum intensity, but the inferences on dam-
allic dampers, while Chang et al. [24,25] applied the per performance are not expected to be affected by this
approach to viscoelastic dampers. Alternatively, Nims choice.
et al. [26] and Filiatrault and Cherry [27] assess the per- In order to assess whether a given sample fails (step
formance by estimating the acceleration reduction at b above), it is necessary to monitor the response of the
different levels of the building. system up to failure. Since for such purpose a robust
1934 R.O. Curadelli, J.D. Riera / Engineering Structures 26 (2004) 1931–1938

same time, simple failure criterion was adopted. Eq. (1)


defines the damage vector as:
D ¼ ½d1 =xc1 ;d2 =xc2 ; . . . ;dn =xcn T ð1Þ
in which D is the damage vector; di is the maximum
story-drift during seismic event; and xci is the ith story-
drift that results in failure.
The xci values can be determined as follows: by
means of a pushover analysis, the global failure dis-
placement Xc was defined as the roof displacement
when the base shear drops 20% of its peak value. A
pushover analysis is frequently used in seismic design to
check the structural performance. For additional
Fig. 4. Typical moment–rotation relationship. details see for instance works of Mwafy and Elnashai
[33], Krawinkler and Seneviratna [34] or Tso and
Moghadam [35]. Because the structures present a linear
non-linear structural model is needed, a plane frame stiffness distribution through their height, the xci values
model was resorted to, reducing the range of case stu- were assumed constant and determined as the ratio
dies discussed in this paper to symmetrical buildings between Xc and the story height. For illustration pur-
without torsional effects. The hysteretic moment– poses, Fig. 5 shows the base shear–roof displacement
rotation relationship is represented by a bilinear plastic relationship of the structures described in Section 7,
hinge with a limited rotation capacity at each element assuming ductility 6. The curves show sudden drops
end, as indicated in Fig. 4. In order to reduce the num- due to the exhaustion of the rotation capacity of sev-
ber of random variables in the description of the struc- eral plastic hinges. Structural failure will be reached
ture, the ductility was assumed constant. However, to when one or more damage vector elements become
assess the relevance of this factor, both a high ductility,
equal to, or larger than one. Therefore, it is possible to
namely 6, and a low ductility, assumed equal to 3, were
define a failure variable C, as:
considered in the analysis. In columns, the combined  S S
effect of axial force and bending moment was taken ¼ 1; if ðDi  1Þ ¼ ðdi =xci  1ÞðfailureÞ
C ð2Þ
into account using interaction surfaces. More details ¼ 0; otherwise ðno failureÞ
can be found in FEMA 273 [28]. S
where denotes the union of elements in the set.
The likelihood of structural damage caused by
5. Failure criterion increasing intensity levels of the ground motion is
described by earthquake motion intensity vs. damage
To build the fragility curves needed for the reliability relationship usually known as fragility curve. Once the
assessment, a failure criterion for buildings subjected to seismic events set, the structural model and the failure
seismic excitation must be available. Several such cri- criterion are defined, fragility curves for the structures
teria have been proposed in the technical literature. under consideration, with and without external dam-
Murotsu et al. [29] consider that the structure reaches pers may be built, using the relative frequency of the
failure when the ratio between the module of the deter- variable C as estimator of failure probability, that is:
minants of the stiffness matrices of the damaged and
undamaged structures becomes smaller than a specified PC ¼ P½C ¼ 1 ¼ P½[ðdi =xci  1Þ ð3Þ
value. Park et al. [30] define a damage index for rein-
forced concrete elements, as a combination between 6. Determination of failure probability
maximum structural deformation and absorbed hyster-
etic energy, adjusted with experimental data. This para- If the conditional failure probability function pC, in
meter has a log-normal distribution with unit mean terms of the PGA, is modelled by a log-normal density
and a coefficient of variation equal to 0.54. Esteva and function:
Ruiz [31] obtained estimates of the seismic hazard of
1 2
multistory buildings under seismic loads. As failure cri- PC ðlnPGAÞ ¼ pffiffiffiffiffiffi e
ðlnPGA
lC Þ =2rC ð4Þ
terion, a relationship between the maximum story-drift rC 2p
and the specified ductile strain capacity of the structure The probability distribution function of C, that defines
was adopted. It is clear that the definition of a failure the failure state, i.e. the actual fragility, is given by:
criterion to rigorously quantify the damage level of a ð lnPGA
structure subjected to seismic excitation is still an open PC ðlnPGAÞ ¼ PC ðlnPGAÞdðlnPGAÞ ð5Þ
question [32]. Hence, in this study a robust and at the 0
R.O. Curadelli, J.D. Riera / Engineering Structures 26 (2004) 1931–1938 1935

Fig. 5. Base shear–roof displacement relationship. Structure 1 (left); Structure 2 (right).

in which lC and rC denote the expected value and the metrical and mechanical properties are indicated
standard deviation of C, respectively. The values of the below.
latter parameters were determined, in each case, by a
log-normal approximation of the fragility curves 7.1.1. Example 1
obtained by numerical simulation. This example consists of the three bays, 10-stories
Moreover, the probability density function of the high steel frame, in a building with two planes of sym-
PGA, which defines the excitation A of each seismic metry [39]. The structure was designed for a PGA of
area, is also represented by a log-normal function, fol- 0.5 g (value from seismic hazard curve, that has a 10%
lowing Lee et al. [36]. chance of exceedance in 50 years) in accordance with
1 2 the provisions of the Uniform Building Code [40] and
PA ðlnPGAÞ ¼ pffiffiffiffiffiffi e
ðlnPGA
lA Þ =2rA ð6Þ
rA 2p as reported in the reference. The total mass per floor is
47 t and Young’s modulus of steel E ¼ 2 1011 N=m2 ,
in which lA and rA denote the expected value and the
resulting in a fundamental period for low amplitude
standard deviation of A, respectively. In this analysis,
vibration equal to T1 ¼ 1:67 s. The nominal yield stress
the parameters used in Eq. (6) were based on the
attenuation relationships for the two seismic scenarios of steel was assumed to be fy ¼ 2:48 108 N=m2 and
assumed in the examples. For more details on this the internal damping in the frame defined by a 1% of
topic, see works of Field [37] and Lee et al. [36] and, critical damping ratio. Frame and members dimensions
for a complete probabilistic seismic hazard analysis in are indicated in Fig. 6.
order to determine the seismic hazard curve, see
SSHAC [38]. Finally, the failure probability P may be 7.1.2. Example 2
obtained by numerically integrating the convolution The second example is a three bays, six-stories high
integral: reinforced concrete frame, in a building designed for
ð1 PGA of 0.17 g (value from seismic hazard curve, that
P¼ PC ðlnPGAÞPA ðlnPGAÞdðlnPGAÞ ð7Þ has a 10% chance of exceedance in 50 years), in accord-
0 ance with the provisions of the Argentine Code
INPRES-CIRSOC 103 [41] or ACI, which in this case
result in similar designs. The total mass per floor is 100
7. Evaluation of the metallic dampers effectiveness t, Young’s modulus of concrete E ¼ 2:48 1010 N=m2
which lead to a fundamental period T1 ¼ 1 s. The
7.1. Description of example structures internal damping was assumed equal to 5% of critical
Two plane frames were analyzed in order to assess damping ratio. In the non-linear constitutive relations,
their original reliability and the up-dated reliability the yield strength of reinforcing steel and the com-
after installation of dampers. Both may be considered pressive strength of concrete were assumed equal
typical of steel and concrete frame buildings without to fy ¼ 4:13 108 N=m2 and fc ¼ 2:76 107 N=m2 ,
shear walls in seismic areas, for which reason they were respectively. Fig. 7 shows the geometric characteristics
selected from the technical literature. The relevant geo- of the structure.
1936 R.O. Curadelli, J.D. Riera / Engineering Structures 26 (2004) 1931–1938

Fig. 8. Dampers location. Structure 1 (left); Structure 2 (right).

Table 1
Dampers capacity distribution

Floor Dampers capacity distribution (N)


Structure 1 Structure 2
1 2:0 105 4:08 105
Fig. 6. Steel structure (Structure 1). Bertero et al. [39].
2 1:9 105 3:96 105
3 1:85 105 3:61 105
4 1:75 105 3:01 105
5 1:62 105 2:18 105
6 1:44 105 1:16 105
7 1:23 105 –
8 9:7 104 –
9 6:74 104 –
10 3:5 104 –
Total 1:38 106 (30% 1:8 106 (30%
of total weight) of total weight)

In every case, the energy dissipation system was


quite effective, leading to a reduction of the probability
of structural failure between 70% and 80%. The effect
is more pronounced for fragile structures (ductility 3),
suggesting that the use of external dampers may also
Fig. 7. Reinforcement concrete structure. (Structure 2).
be a feasible alternative to enhance the seismic
reliability of non-complying structures, cases in which a
The dampers location in both structures may be seen five-fold reduction of the failure probability may be
in Fig. 8. The distribution in height of the dampers expected.
capacity is finally indicated in Table 1. It should be mentioned that the distribution of struc-
tural damage with height, that is, the floors in which
7.2. Reliability analysis and discussion of results damage begins or most damage occurs, vary signifi-
cantly with the earthquake type. An optimum distri-
Fig. 9 shows the form of Eqs. (5) and (6) for both bution of the dampers capacity would be valid only for
examples, with and without dampers, for ductility 6. specific types of motion, and thus would not be rel-
Similar information for ductility 3, i.e. for a fragile evant in the development of a robust energy dissipation
behavior, is presented in Fig. 10. Table 2 shows the esti- system.
mated failure probabilities, obtained by applying Eq. (7),
at sites in CA, USA, for Example 1, and Tucumán,
Argentina, for Example 2, for the structures without 8. Conclusions
and with external damping system. The analysis was
conducted both for a fragile behavior (ductility 3) and Both for purposes of seismic retrofitting and in new
for ductile or normal behavior (ductility 6). designs of frame building structures, external energy
R.O. Curadelli, J.D. Riera / Engineering Structures 26 (2004) 1931–1938 1937

Fig. 9. Fragility curve with and without dissipation system and peak ground acceleration probability density function (excitation). Structure 1
(left); Structure 2 (right), for ductility 6.

Fig. 10. Fragility curve with and without dissipation system and peak ground acceleration probability density function (excitation). Structure 1
(left); Structure 2 (right), for ductility 3.

Table 2
Probability of failure of example structures with and without dampers

Structure Failure probability


Ductility 6 Ductility 3
Without dampers With dampers Ratio Without dampers With dampers Ratio
1 (Steel) 0.014 0.004 3.5 0.152 0.038 4
2 (Concrete) 0.01 0.002 5 0.134 0.027 5

dissipation systems may be advantageously used. The Acknowledgements


effectiveness of an energy dissipation system based on
metallic dampers is examined in the paper, including The authors wish to thank the financial support of
the experimental determination of the mechanical CNPq and CAPES, Brazil. The tests were conducted at
properties of a prototype lead-rings damper. On the the Laboratory of Physical Metallurgy, School of
premise that the efficiency of a dampers system can Engineering, UFRGS, Brazil.
best be assessed on a reliability basis, full reliability
analyses of typical steel and reinforced concrete frame
buildings are performed, showing that a five-fold References
reduction in the probability of failure may be achieved
by introducing external metallic or similar dampers [1] Kelly JM. Aseismic base isolation: review and bibliography. Soil
systems. Dynamics and Earthquake Engineering 1986;5(4):202–16.
1938 R.O. Curadelli, J.D. Riera / Engineering Structures 26 (2004) 1931–1938

[2] Soong TT, Dargush GF. Passive energy dissipation systems in UCB/EERC-88/17, University of California, Berkeley, CA;
structural engineering. John Wiley & Sons; 1997. 1988.
[3] Curadelli RO, Riera JD. Design and testing of a lead damper for [22] Tsai KC, Chen HW, Hong CP, Su YF. Design of steel triangu-
seismic applications. Engineering Structures; 2003 (submitted for lar plate energy absorber for seismic-resistant construction.
publication). Earthquake Spectra 1993;9(3):505–28.
[4] Kelly JM, Skinner RI, Heine AJ. Mechanisms of energy absorp- [23] Martinez-Romero E. Experiences on the use of supplemental
tion in special devices for use in earthquake resistant structures. energy dissipators on building structures. Earthquake Spectra
Bulletin of New Zealand Society for Earthquake Engineering 1993;9(3):581–625.
1972;5(3):63–88. [24] Chang KC, Soong TT, Oh ST, Lai ML. Seismic behavior of
[5] Skinner RJ, Kelly JM, Heine AJ. Hysteresis dampers for earth- steel frame with added viscoelastic dampers. Journal of Structur-
quake-resistant structures. Earthquake Engineering and Struc- al Engineering 1995;121(10):1418–26.
tural Dynamics 1975;3:287–96. [25] Chang KC, Soong TT, Oh ST, Lai ML. Effect of ambient tem-
[6] Bergman DM, Goel SC. Evaluation of cyclic testing of steel- perature on a viscoelastically damped structure. Journal of
plate device for added damping and stiffness. Report no. UMCE Structural Engineering 1992;118(7):1955–73.
87-10, The University of Michigan, Ann Arbor, MI; 1987. [26] Nims DK, Richter PJ, Bachman RE. The use of energy dissipat-
[7] Wittaker AS, Bertero VV, Thompson CL, Alonso LJ. Seismic ing restraint for seismic hazard mitigation. Eathquake Spectra
testing of steel plate energy dissipation devices. Earthquake 1993;9(3):467–89.
Spectra 1991;7(4):563–604. [27] Filiatrault A, Cherry S. Performance evaluation of friction
[8] Robinson WH, Greenbank LR. An extrusion energy absorber damped braced frames under simulated earthquake loads. Earth-
suitable for the protection of structures during an earthquake. quake Spectra 1987;3(1):57–78.
Earthquake Engineering and Structural Dynamics 1976;4:251–9. [28] FEMA. NEHRP. Guidelines for seismic rehabilitation of build-
[9] Monti MD, Robinson WH. A lead damper suitable for reducing ings. FEMA 273, Federal Emergency Management Agency; 1996.
the motion induced by wind and earthquake. Proceedings, XI [29] Murotsu Y, Okada H, Shao S. Reliability-based design of trans-
WCEE, Acapulco, México. 1996. mission lines structures under extreme wind loads. In: Schüeller
[10] Ozdemir H. Nonlinear transient dynamic analysis of yielding GI, Shinozuka M, Yao JTP, editors. Structural safety and
structures. PhD dissertation, University of California, Berkeley, reliability, ICOSSAR, vol. 3. 1993, p. 1675–81.
CA; 1976. [30] Park Y, Ang A. Seismic damage analysis of reinforced concrete
[11] Bhatti MA, Pister KS, Polek E. Optimal design of an earth- buildings. Journal of Structural Engineering 1985;111(4):740–57.
quake isolation system. Report no. UBC/EERC-78/22. Univer- [31] Esteva L, Ruiz S. Seismic failure rates of multistory frames.
sity of California, Berkeley, CA; 1978. Journal of Structural Engineering 1989;115(2):268–84.
[12] Graesser EJ, Cozzarelli FA. A multidimensional hysteretic [32] Esteva L, Dı́az-López O, Garcı́a-Pérez J. Reliability functions
model for plastically deforming metals in energy absorbing devi- for earthquake resistant design. Reliability Engineering and Sys-
ces. Technical report NCEER-91-0006, National Center for tem Safety 2001;73:239–62.
Earthquake Engineering Research, Buffalo, NY; 1991. [33] Mwafy AM, Elnashai AS. Static pushover versus dynamic col-
[13] Zienkiewicz OC, Taylor RL. The finite element method. London lapse analysis of RC buildings. Engineering Structures
(UK): McGraw-Hill; 1989. 2001;23:407–24.
[14] Dargush GF, Soong TT. Behavior of metallic plate damper in [34] Krawinkler H, Seneviratna GD. Pros and Cons of a pushover
seismic passive energy dissipation systems. Earthquake Spectra analysis of seismic performance evaluation. Engineering Struc-
1995;11(4):545–68. tures 1998;20(4–6):452–64.
[15] Tsai CS, Tsai KC. TPEA device as seismic damper for high-rise [35] Tso WK, Moghadam AS. Pushover procedure for seismic ana-
building. Journal of Engineering Mechanics, ASCE lisys of buildings. Progress in Structural Engineering and Materi-
1995;121(10):1075–81. als 1998;1(3):337–44.
[16] Kanaan AE, Powel GH. DRAIN-2D a general-purpose com- [36] Lee Y, Anderson JG, Zeng Y. Evaluation of empirical ground
puter program for dynamic analysis of inelastic plane structures. motion relations in Southern California. Bulletin of Seismic
Technical report no. UCB/EERC 73-06, University of Cali- Society of America 2000;90:6B.
fornia, Berkeley, CA; 1973. [37] Field EH. Accounting for site effects in probabilistic seismic haz-
[17] Tsai KC, Chen HQ, Hon CP, Su YF. Design of steel triangular ard analysis of southern California. Overview of the SCEC
plate energy absorbers for seismic-resistant construction. Earth- phase III report. Bulletin of Seismic Society of America
quake Spectra 1993;9(3):505–28. 2000;90:6B [Available from: http://www.scec.org/phase3/
[18] Xia C, Hanson RD. Influence of ADAS element parameters on index.html, http://www.scec.org/resources/catalog/seismicha-
building seismic response. Journal of Structural Engineering, zards.html].
ASCE 1992;118(7):1903–18. [38] SSHAC (Senior Seismic Hazard Analysis Committee). Recom-
[19] Pall A, Venzina S, Proulx P, Pall R. Friction dampers for seis- mendations for probabilistic seismic hazard analysis: guidance
mic control of Canadian Space Agency Headquarters. Earth- on uncertainty and use of experts. US Nuclear Regulatory Com-
quake Spectra 1993;9(3):547–57. mission report CR-6372, 1997, Washington (DC).
[20] Filiatrault A, Cherry S. Comparative performance of friction- [39] Bertero V, Mahin S, Herrera R. Aseismic design implications of
damped systems and based isolation systems for earthquake ret- near-fault San Fernando earthquake records. Earthquake Engin-
rofit and aseismic design. Earthquake Engineering and Structur- eering and Structural Dynamics 1978;6:31–42.
al Dynamic 1988;16:389–416. [40] U.B.C. Uniform building code. vol. 1–3; 1997.
[21] Aiken ID, Kelly J, Pall AS. Seismic response of a nine-story steel [41] INPRES-CIRSOC 103. Normas Argentinas para Construcciones
frame with friction damped cross-bracing. Technical report no. Sismo-resistentes; 1970.

Potrebbero piacerti anche