Sei sulla pagina 1di 52

Title of Document : DATA SHEET FOR PRESSURE TRANSMITTERS

Project Name : LPG4 Project

Project / PO No. : SGMF01133

DCAF Control ID : 1245.6.31

Assai Issue Code : IFC

Issue Date : 12 May 2020

Document Status : Issued For Construction

Document Type : Specification

Equipment Tag ID : N/A

Page :
1 OF 32

WOOD REVISION HISTORY

Digitally signed by
roger.tan2
DN: CN=roger.tan2
Reason: I am
roger.tan2
approving this
document
Date: 2020.05.13
16:57:43+08'00'

F2 Re-Issued for Construction 12-May-20 LHK RT RT

F1 Issued for Construction 30-Jan-20 LHK VV RT -

O1 Issued for Comment 26-Sep-19 VV LHK RT -


Issue Prepared Checked Approved Quality
Rev No. Enquiry Rev No. Reason For Issue
Date By By By Review By
WOOD DOCUMENT NO.: 0591-8550-DS-03-0011
DSN NO.: 1257
INSPECTION LEVEL:
SGMF SUBGROUP PLANT / UNIT / GRID
01133 34 LPG4 PU2

DRAWING NUMBER REV


SHELL EASTERN PETROLEUM (PTE) LTD
PULAU BUKOM SKI-01133-630 2
REVISION CONTROL PAGE

REVISION
DESCRIPTION DATE ORIGINATOR REVIEWER APPROVER
NO.
1A ISSUED FOR COMMENT 26-Sep-19 VV LHK RT

1 ISSUED FOR CONSTRUCTION 30-Jan-20 LHK VV RT

2 RE-ISSUED FOR CONSTRUCTION 12-May-20 LHK RT RT


DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE 0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.


4530684342 /
1 12 May 20 2 3
VENDOR : EMERSON P.O. NO.: 4531633540
4 5 6

REVISION
SHEET DESCRIPTION TOTAL PAGE
O1 F1 F2
1 COVER SHEET 1 PAGE X X X
2 REVISION CONTROL PAGE 1 PAGE X X X
3 INDEX SHEET 1 PAGE X X X
4 NOTES SHEET 1 1 PAGE X X X
5 NOTES SHEET 2 1 PAGE X X X
6 NOTES SHEET 3 1 PAGE X X X
7 27PIA-503-TX 1 PAGE X X
8 27PIA-510-TX 1 PAGE X X
9 27PICA-508-TX 1 PAGE X X
10 27PI-509-TX 1 PAGE X X X
11 27PICA-514-TX 1 PAGE X X
12 27PI-520-TX 1 PAGE X X
13 27PIA-521-TX 1 PAGE X X
14 27PI-524-TX 1 PAGE X X
15 27PICA-531-TX 1 PAGE X X
16 27PSA-534-TX 1 PAGE X X X
17 27PZA-532-TX 1 PAGE X X X
18 83PICA-038-TX 1 PAGE X X
19 27PI-553-TX 1 PAGE X X
20 27PIA-554-TX 1 PAGE X X
21 27PIA-526-TX 1 PAGE X
22 27PIA-527-TX 1 PAGE X
23 27PZA-538-TX 1 PAGE X
24 27PZA-539-TX 1 PAGE X
25 27PZA-540-TX 1 PAGE X
26 27PZA-541-TX 1 PAGE X
27 27PZA-542-TX 1 PAGE X
28 27PZA-543-TX 1 PAGE X
29 SUPPLIER DOCUMENTATION REQUIREMENT 1 1 PAGE X X X
30 SUPPLIER DOCUMENTATION REQUIREMENT 2 1 PAGE X X X
31 DEVIATION LIST 1 PAGE X X X
32 ATTACHMENT 1: PRESSURE TRANSMITTER 1 PAGE X X X
PROCESS SPECIFICATION, Rev.F1

Page 3 of 32
DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE 0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.


4530684342 /
1 12 May 20 2 3
VENDOR : EMERSON P.O. NO.: 4531633540
4 5 6
GENERAL NOTES
1) TBA = TO BE ADVISE, VTA = VENDOR TO ADVISE, N/A = NOT APPLICABLE, AMB = AMBIENT,
ATM = ATMOSPHERIC, G.NOTE = REFER PROCESS SPECS. NOTES, FV = FULL VACUUM
2) Transmitter diaphragms shall be "gold plated" for the following services:a.) Hydrogen services ;b.) All sour
and wet H2S services as per section 9, DEP 32.31.00.32 Gen. Vendor to advice suitability of materials.
3) Field instruments shall be protected from lightning with built-in lightning surge arrestor.
4) Transmitter range shall be suitably sized to ensure no IOP ( input open) alarm during normal operating condition.
5) Galvanic isolation is mandatory requirement to all field electronic transmitters
6) All electrical equipments shall be suitable for installation in classified area Zone 2, Gr IIA,IIB T3 (IEC Code)
and certification is required to install in the classified area.
7) All field electronic instruments shall have an RFI immunity circuit to suppress RF signals.
8) Materials and all electrical components shall be suitable for corrosive atmosphere and tropical climate.
9) Vendor calibration certificate for all instruments and instrument system shall be checked and documented
in accordance with the quality plan. Calibration equipment shall be provided by calibration certificate and
traceable to accredited laboratory.Refer to section 6, DEP 62.10.08.11
10) Instrument accuracy shall be maintained all throughout the instrument range to cater the abnormal process
condition such as: start-up, commissioning, regeneration and emergency operation.
11) All transmitter output mode and display mode shall be "Linear".
12) Local indicator shall be configured to read in "Engineering Units" not by percentage output.
13) Vendor shall supply L type 304SST mounting bracket that is suitable for 2" pipe mounting and instrument manifold
valve, SS316, 2-Valve, suitable for 3/8" OD tube.
14) Transmitter housing shall be low copper aluminium type, with epoxy paint suitable for marine environment.
15) Field transmitter shall be EMC compatabiltiy as per Section 2.13 of DEP 32.31.00.32
16) Vendor to provide model decoding or nomenclature for each product model offered.
17) Vendor to include the recommended spare parts on the quotation.
18) All Transmitters shall have Hermetically sealed electronics.
19) All HART Transmitters shall have following settings.

Settings Value in mA Description


Transmitter Burnout HI setting 21.6 Transmitter Hardware failure
Transmitter Burnout LO setting 3.2 Transmitter Hardware failure
Transmitter Saturation HI current 20.5 Process Alarm
Transmitter Saturation LO current 3.8 Process Alarm
Sens AI HI (PLC) 21 Transmitter Fault Alarm
Sens AI LO (PLC) 3.5 Transmitter Fault Alarm
DCS IOP + 21
DCS IOP - 3.5

20) Sunshade with bracket: SS316 shall be provided by vendor


21) Cable entry shall be M20x1.5. Vendor to provide certified adaptor where it's required.
22) Spare electrical connection entries shall be equipped with 316SS Ex'd' plugs, any going to be used electrical
connection shall be equipped with temporary plastic cap.
23) Vendor shall confirm the suitability of materials for all wetted components including seals gaskets & O-rings
with the process fluid & conditions indicated on the attached data sheets.
24) NACE MR0103 requirements shall be in accordance with MESC 77/303.
25) Foundation Fieldbus device shall be a H1 Field Device that is connected on fieldbus network operating at
at 31.25kbit/sec. FF transmitter data - MAC address & ID to be clearly indicated.
DD files to be supplied & transmitter to be pre configured.

Page 4 of 32
DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE 0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.


4530684342 /
1 12 May 20 2 3
VENDOR : EMERSON P.O. NO.: 4531633540
4 5 6
GENERAL NOTES
26) Other requirement for Pressure Transmitter
i) 2 VALVE MANIFOLD: MI, MP21H.SG.BP01.ISO.YP, 1PC
ii) MOUNTING PLATE: M.I. no.: S0200040, 1PC
iii) SUNSHADE SS316: M.I. no.: 20161000, 1PC
iv) ASSEMBLY & LEAK TEST

Model no. specified for item 26 are indicative, vendor to verify wetted part material is suitable for process conditions.

HOLDS

Page 5 of 32
DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.


4530684342 /
1 12 May 20 2 3
VENDOR : EMERSON P.O. NO.: 4531633540
4 5 6

REFERENCE DOCUMENTS: PEFS

1 ISBL PEFS:
Wood Dwg No Shell PEFS No.: Rev.
0591-8110-25-0014 T-1.477.150 R2
0591-8110-25-0016 B-4.042.891 R2
0591-8110-25-0017 B-4.042.892 R2
0591-8110-25-0018 B-4.042.893 R2
0591-8110-25-0019 B-4.042.894 R2
0591-8110-25-0034 B-4.042.921 R2
0591-8140-25-0001 B-4.042.951 S2

2 APPLICABLE DEPS:
DEP No Ver. Description
32.31.00.32 Feb.2018 INSTRUMENTS FOR MEASUREMENT AND CONTROL
62.10.08.11 Feb.2018 INSPECTION AND FUNCTIONAL TESTING OF INSTRUMENTS
37.001 B INSTRUMENT IMPULSE LINES

TAG NO. SUFFIX:


-CV Control valve
-E Element
-S Switch
-SV Solenoid Valve
-TW Thermowell
-TX Transmitter
-VO On-off Valve

Page 6 of 32
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PIA-503-TX 61 Plant '--- LPG 4

62
3 Service --- LEAN ADIP Location/Unit '--- H2S EXTRACT/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0016 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
EPOXY COATED
ALUMINIUM
72
POLYURETHANE
13 Fill fluid --- SILICONE Housing material --- COATED
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 16
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LEAN ADIP / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 5.8 11 93 MAC- value '---
35 Temperature °C - 45 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 15.1 (G.NOTE3) 101
43 Design Temperature min/ max °C 80 (G.NOTE3) 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 1 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Req.no. Req.rev:
Page 7 of 32
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PIA-510-TX 61 Plant '--- LPG 4

62
3 Service --- C-2751 Location/Unit '--- H2S EXTRACT/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0016 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 25
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LPG / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 17.8 - 93 MAC- value '---
35 Temperature °C - 43.8 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 42 / FV (G.NOTE1) 101
43 Design Temperature min/ max °C -29/120 (G.NOTE1,2) 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG5A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 2 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 8 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PICA-508-TX 61 Plant '--- LPG 4
CAUSTIC WASH&LPG
62
3 Service --- TREATED LPG TO P-2756A/B Location/Unit '--- FACILITIES/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0017 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 25
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- TREATED LPG / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 17 - 93 MAC- value '---
35 Temperature °C - 43.8 - 94 Advise chemical requirements '---
36 95 NACE requirements '--- YES
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 28 101
43 Design Temperature min/ max °C -29 / 65 (G.NOTE2) 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG5A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1D5DOQ15 ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 3 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 9 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PI-509-TX 61 Plant '--- LPG 4
CAUSTIC WASH&LPG
62
3 Service --- OFFSPEC LPG TO VAPOURIZER Location/Unit '--- FACILITIES/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0017 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 16
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- OFFSPEC LPG / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg 5 8.52 8.87 8 93 MAC- value '---
35 Temperature °C - 43.8 - 94 Advise chemical requirements '---
36 95 NACE requirements '--- YES
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 28.8 101
43 Design Temperature min/ max °C -29 / 120 (G.NOTE2) 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG5A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1D5DOQ15 ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 4 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 10 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PICA-514-TX 61 Plant '--- LPG 4
CAUSTIC WASH&LPG
62
3 Service --- V-2752 Location/Unit '--- FACILITIES/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0017 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 40
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LIGHT HYDROCARBON / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 20.5 - 93 MAC- value '---
35 Temperature °C - 46.3 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 28.8 / FV (G.NOTE1) 101
43 Design Temperature min/ max °C -29/120 (G.NOTE1,2) 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG5A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 5 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 11 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PI-520-TX 61 Plant '--- LPG 4
CAUSTIC WASH&LPG
62
3 Service --- C-2753 bottom Location/Unit '--- FACILITIES/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0017 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 40
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- TREATED LPG / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 20.9 - 93 MAC- value '---
35 Temperature °C - 101.6 104.4 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 28.8 / FV (G.NOTE1) 101
43 Design Temperature min/ max °C -29/120 (G.NOTE1,2) 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG5A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 6 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 12 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PIA-521-TX 61 Plant '--- LPG 4
SECURED INSTRUMENT AIR LPG HG
62
3 Service --- VESSEL Location/Unit '--- ABSORBER/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0018 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 10
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- INSTRUMENT AIR / GAS 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg 4.2 6.5 7.5 93 MAC- value '---
35 Temperature °C - 38 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 10.5 101
43 Design Temperature min/ max °C 65 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 7 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 13 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PI-524-TX 61 Plant '--- LPG 4
LPG HG
62
3 Service --- V-2751 Location/Unit '--- ABSORBER/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0018 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 40
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LPG / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 27 - 93 MAC- value '---
35 Temperature °C - 44 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 41 / FV (G.NOTE1) 101
43 Design Temperature min/ max °C -29/ 65 (G.NOTE1,2) 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG5A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 8 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 14 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PICA-531-TX 61 Plant '--- LPG 4
CONDENSATE
62
3 Service --- LP STEAM FROM A-2751 Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0019 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 4
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 2.46 2.2 - 3.8 93 MAC- value '---
35 Temperature °C - 155 135 - 170 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 6.5 / FV 101
43 Design Temperature min/ max °C 300 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03B1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 9 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 15 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PSA-534-TX 61 Plant '--- LPG 4
CONDENSATE
62
3 Service --- LP STEAM Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0019 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg -1 / 9
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 0 - 93 MAC- value '---
35 Temperature °C - 100 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 6.2 / FV 101
43 Design Temperature min/ max °C 360 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03B1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 10 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 16 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PZA-532-TX 61 Plant '--- LPG 4
CONDENSATE
62
3 Service --- LP STEAM FROM A-2751 Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0019 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 6
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure (HOLD 6) barg - 2.46 2.2 4.9 93 MAC- value '---
35 Temperature (HOLD 6) °C - 155 135 - 170 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99 9
41 100
42 Design pressure barg 6.5 / FV 101
43 Design Temperature min/ max °C 300 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03B1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 11 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 17 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 83PICA-038-TX 61 Plant '--- LPG 4
CONDENSATE
62
3 Service --- LP PRODUCT FROM C-2753 Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591-8110-25-0014 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
Digital / Foundation
71
12 Body material --- AL W/ LOW CU CONTENT Output Signal mA Fieldbus (FF)
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 40
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LPG PRODUCT / LIQUID 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 20.7 - 93 MAC- value '---
35 Temperature °C - 99.7 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 28.8 / FV 101
43 Design Temperature min/ max °C -29/ 120 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG5F03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4T1P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 12 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 18 of 32 Req.no. barg
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PI-553-TX 61 Plant '--- LPG 4
UTILITY STATION
62
3 Service --- LP STEAM SUPPLY TO LPG-04 Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591A-8140-25-0034 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 6
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg -3 4 3.5 -4 93 MAC- value '---
35 Temperature °C - 167 270 230 - 270 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 6.5 / FV 101
43 Design Temperature min/ max °C 300 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03B1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 13 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 19 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PIA-554-TX 61 Plant '--- LPG 4
UTILITY STATION
62
3 Service --- NITROGEN SUPPLY TO LPG-04 Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591A-8140-25-0034 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 /10
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- NITROGEN / GAS 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 8 - 13.5 93 MAC- value '---
35 Temperature °C - 30 - 30 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 16.7 101
43 Design Temperature min/ max °C 100 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 14 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 20 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PIA-526-TX 61 Plant '--- LPG 4
UTILITY STATION
62
3 Service --- 27UZV-511 SIA Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591A-8110-25-0016 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 /10
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- INSTRUMENT AIR / GAS 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg 4.2 6.5 7.5 93 MAC- value '---
35 Temperature °C - 38 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 10.5 101
43 Design Temperature min/ max °C 65 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 15 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 21 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PIA-527-TX 61 Plant '--- LPG 4
UTILITY STATION
62
3 Service --- 27UZV-601 SIA Location/Unit '--- SYSTEM/2750
4 P.E.F.S darws. Number --- 0591A-8110-25-0017 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- C/W REMOTE MANIFOLD 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GLASS-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 /10
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- INSTRUMENT AIR / GAS 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg 4.2 6.5 7.5 93 MAC- value '---
35 Temperature °C - 38 - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A EN 10204-3.1B
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 10.5 101
43 Design Temperature min/ max °C 65 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. 2-Way valve manifold, G1/4 with 3/8" tube fitting
3051CG4A03A1BH2SJE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO ½" NPT Female x 3/8" NPT, provide
58 Serial number '--- N/A 117 necessary adaptor compression fitting (if required) to
59 Item number '--- 16 118 connect to 3/8" SS tubing

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F1
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 22 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PZA-538-TX 61 Plant '--- LPG 4
3 Service --- ADP SYS 2 62 Location/Unit '--- DELUGE SYSTEM
4 P.E.F.S darws. Number --- 0591-8140-25-0001 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- INTEGRAL 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 2
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 1.5 2 93 MAC- value '---
35 Temperature °C - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 7 101
43 Design Temperature min/ max °C 38 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 1. Burnout and Saturation Value as per NAMUR NE 43
114
56 Supplier '--- EMERSON 2. Process connection shall be with 1/4" NPTF.
115
3051CG4A03B1BH2BCE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO 3. Vendor to provide SS 2" pipe mounting bracket.
58 Serial number '--- N/A 117
59 Item number '--- 118

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 23 of 32 Req.no. Req.rev:
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PZA-539-TX 61 Plant '--- LPG 4
3 Service --- ADP SYS 2 62 Location/Unit '--- DELUGE SYSTEM
4 P.E.F.S darws. Number --- 0591-8140-25-0001 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- INTEGRAL 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 2
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 1.5 2 93 MAC- value '---
35 Temperature °C - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 7 101
43 Design Temperature min/ max °C 38 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 1. Burnout and Saturation Value as per NAMUR NE 43
114
56 Supplier '--- EMERSON 2. Process connection shall be with 1/4" NPTF.
115
3051CG4A03B1BH2BCE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO 3. Vendor to provide SS 2" pipe mounting bracket.
58 Serial number '--- N/A 117
59 Item number '--- 118

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Req.no. Req.rev:
Page 24 of 32
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PZA-540-TX 61 Plant '--- LPG 4
3 Service --- ADP SYS 1 62 Location/Unit '--- DELUGE SYSTEM
4 P.E.F.S darws. Number --- 0591-8140-25-0001 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- INTEGRAL 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 2
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 1.5 2 93 MAC- value '---
35 Temperature °C - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 7 101
43 Design Temperature min/ max °C 38 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 1. Burnout and Saturation Value as per NAMUR NE 43
114
56 Supplier '--- EMERSON 2. Process connection shall be with 1/4" NPTF.
115
3051CG4A03B1BH2BCE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO 3. Vendor to provide SS 2" pipe mounting bracket.
58 Serial number '--- N/A 117
59 Item number '--- 118

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Req.no. Req.rev:
Page 25 of 32
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PZA-541-TX 61 Plant '--- LPG 4
3 Service --- ADP SYS 1 62 Location/Unit '--- DELUGE SYSTEM
4 P.E.F.S darws. Number --- 0591-8140-25-0001 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- INTEGRAL 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 2
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 1.5 2 93 MAC- value '---
35 Temperature °C - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 7 101
43 Design Temperature min/ max °C 38 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 1. Burnout and Saturation Value as per NAMUR NE 43
114
56 Supplier '--- EMERSON 2. Process connection shall be with 1/4" NPTF.
115
3051CG4A03B1BH2BCE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO 3. Vendor to provide SS 2" pipe mounting bracket.
58 Serial number '--- N/A 117
59 Item number '--- 118

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Req.no. Req.rev:
Page 26 of 32
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PZA-542-TX 61 Plant '--- LPG 4
3 Service --- ADP SYS 3 62 Location/Unit '--- DELUGE SYSTEM
4 P.E.F.S darws. Number --- 0591-8140-25-0001 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- INTEGRAL 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 2
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 1.5 2 93 MAC- value '---
35 Temperature °C - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 7 101
43 Design Temperature min/ max °C 38 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 1. Burnout and Saturation Value as per NAMUR NE 43
114
56 Supplier '--- EMERSON 2. Process connection shall be with 1/4" NPTF.
115
3051CG4A03B1BH2BCE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO 3. Vendor to provide SS 2" pipe mounting bracket.
58 Serial number '--- N/A 117
59 Item number '--- 118

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Req.no. Req.rev:
Page 27 of 32
DATA SHEET FOR PRESSURE TRANSMITTERS contr.job no:1-PD-0591E
Rev Units Units
1 GENERAL: --- 60 GENERAL
2 Tag number --- 27PZA-543-TX 61 Plant '--- LPG 4
3 Service --- ADP SYS 3 62 Location/Unit '--- DELUGE SYSTEM
4 P.E.F.S darws. Number --- 0591-8140-25-0001 63 Zone '--- ZONE 2
5 64 Gas group '--- IIA/IIB
6 Intermediate revison - 65 Temp category '--- T3
7 66
8 BODY: 67 ELECTRONICS:
9 Meter type --- INTEGRAL 68 Type '--- INTEGRATED
10 Measuring function --- GAUGE 69 Transmission type '--- 2-WIRE
11 Measuring method --- CAPACITANCE 70 Supply VDC 24
12 Body material --- AL W/ LOW CU CONTENT 71 Output Signal mA 4-20, HART
ALUMINIUM
72
13 Fill fluid --- SILICONE Housing material --- POLYURETHANE
14 Diaphragm material --- HASTELLOY C276 73 Electrical connections --- SCREW TERMINALS
15 Gasket material --- GRAPHITE-FILLED PTFE 74 Cable entry '--- M20 x 1.5
16 Gold coating --- N/A 75 Explosion prot. Cert.transmitter '--- Ex d IIC, T5/T6
17 Bolt --- 316 SST 76 Weather protection '--- IP66
18 Nuts --- 316 SST 77 Mounting brackets '--- YES
19 Over pressure 78
20 Range limits 79
21 80
22 81
23 82 RANGE
24 83 Calibrated range barg 0 / 2
25 84 Output form LINEAR
BETTER THAN 0.25%
85
26 Accuracy % OF ADJUSTED SPAN
27 86 Burnout value min/max mA NOTE 1
28 87 Saturation value min/max mA NOTE 1
29 88
30 PROCES DATA 89 SPECIAL REQUIREMENTS
31 Medium/Phase '--- LP STEAM / VAPOUR 90
32 91 Test requirements
33 Operating conditions Min Norm Max 92 Validation '---
34 pressure barg - 1.5 2 93 MAC- value '---
35 Temperature °C - 94 Advise chemical requirements '---
36 95 NACE requirements '---
37 96 Material certificate '--- N/A
38 Corrosive '--- 97 Mati. Cert. file no. '---
39 Toxic '--- 98 Oxyen service '---
40 Pulsation '--- 99
41 100
42 Design pressure barg 7 101
43 Design Temperature min/ max °C 38 102
44 103
45 104
46 105
47 106 NON-VENDOR RELATED INFO
48 107
49 108 Winterizing heating
50 109 Grid position '---
51 110 Design code '---
52 111 Shell registration no. '---
53 112 Mesc number '---
54 PURCHASE DATA 113 REMARKS
55 Manufacturer '--- EMERSON 114 1. Burnout and Saturation Value as per NAMUR NE 43
56 Supplier '--- EMERSON 115 2. Process connection shall be with 1/4" NPTF.
3051CG4A03B1BH2BCE7Y2L4M
116
57 Model number '--- 5Q4D4T1C4P1DO 3. Vendor to provide SS 2" pipe mounting bracket.
58 Serial number '--- N/A 117
59 Item number '--- 118

Eng. By: WOOD Sheet no. REVISION


Data sheet rev: F2
Principal:SHELL EASTERN PETROLEUM (PTE) LTD PULAU BUKOM Page 28 of 32 Req.no. Req.rev:
DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE 0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.

VENDOR : EMERSON P.O. NO.: 4530684342 1 12 May 20 2 3

4 5 6

This Supplier Documentation Requirements is in conjunction with the FW Standard “General Notes for
Requisitions”, document no. 0605-8820-GN-00-0001, defines the scope of documentation for all Supplier Documents

SUPPLIER shall include the supply of all Documentation to define the Equipment supplied for the purposes of:
•Integration into the Plant Design
•Design Code Compliance
•Regulatory Authority Approval
•Installation, Operation and Maintenance

DOC. DUE DOCUMENT QUANTITIES


DATA
DOCUMENT TITLE TYPE DATE WITH FOR CERT.
BOOK
CODE CODE QUOTE REVIEW FINAL
SUPPLIER Document Index (SDI) L01 A2 - NOTE 1 - -
Production Program K85 A3 - NOTE 1 - -
Inspection and Test Procedures P80 A6 - NOTE 1 1 VDB
Inspection and Test Plan Q93 A3 - NOTE 1 1 VDB
CE Declaration Z98 E - NOTE 1 - -
Certificate of Conformity Z98 E - NOTE 1 1 VDB
Hazardous Area Certificates Z98 A3 - NOTE 1 1 VDB
QA Manual Index Q93 A6 - NOTE 1 1 VDB
Quality Plans Q93 A6 - NOTE 1 1 VDB
Instrument Data Sheets and Sizing Calcs (Valve and A60
Actuator)
Q/A3 1 NOTE 1 1 VDB
Schematic Wiring Diagrams D62 A3 1 NOTE 1 1 VDB
G.A. Drawing (including mounting details and hook-ups)
G61 A3 - NOTE 1 1 VDB
Installation /Maintenance Instructions I94 F - NOTE 1 1 VDB
Operating Instruction Manual O94 F 1 NOTE 1 1 VDB
Part List M69 Q/A3 1 NOTE 1 1 VDB
Spare Parts Lists M95 Q/F 1 NOTE 1 1 VDB
Suborders and index J95 E - - - -
Concession Requests (if required) E93 E - NOTE 1 1 VDB
NDE / NDT Procedures / Pressure Test Procedures P80 A6 - NOTE 1 1 VDB
Calibration and Test Procedures P80 A3 - NOTE 1 1 VDB
Insulation/Painting Procedures P82 A6 - NOTE 1 - VDB
Inspection Reports Z98 E - NOTE 1 1 VDB
Calibration and Test Certificates Z98 E - NOTE 1 1 VDB
Material Test Certificates, including PMI and Shop Test
Z98Certificates
E - NOTE 1 1 VDB
Hydrostatic/Pneumatic Certificate Z98 E - NOTE 1 1 VDB
Leak Test Certificate Z98 E - NOTE 1 1 VDB
Vendor Data book Index X99 A6 - NOTE 1 1 VDB
Vendor Data Book W99 G - NOTE 1 A 2.1.3 -
Vendor Data Book-CD W98 G - NOTE 1 A 2.1.3 -

Page 29 of 32
DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE 0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.

VENDOR : EMERSON P.O. NO.: 4530684342 1 12 May 20 2 3

4 5 6
NOTES FOR SUPPLIER DOCUMENT SUBMISSION TABLE
1) Documents for review shall be submitted via e-procurement process. No hard copy is required to be submitted
2) Documents shall be submitted in accordance with a DUE DATE CODE as follows
A2 DOCUMENT TIMING
A2.1.1 WITH QUOTE
Q Documents shall be submitted with the Quotation.
A2.1.2 FOR REVIEW
Documents shall be submitted in accordance with a DUE DATE CODE as follows
An : n weeks after order placement (normally n=3)
Bn=3 : n weeks after receipt of PURCHASER information (normally n=3)
Dn : n weeks after equipment dispatch (normally n=2)
E : As information becomes available
F : 1 month prior to equipment dispatch and one copy with equipment
G : at Final Inspection
A2.1.3 DATA BOOKS
VDB : n weeks after order placement (normally n=3)

Supplier may specifically note that the MR has total 3nos of WBS as listed at below:
WBS01= ISBL
WBS02= OSBL
WBS03= COMMON AREAS
Each WBS represents different unit/sections of the plant.

During document approval process supplier may combine documents of similar category (i.e Sizing
/ GAD /Reports etc), mentioned above, for all WBS (01 to 03) as single set / document
for XXXX/FWAPL approval

Approved documents/Certified Final documents are to be inserted in the Vendor Data Books as per
VDB index. These documents must be stamped and signed by the WOOD responsible engineer as
Code 4 or 5, as defined in the General Notes

Project requires that supplier provides separate VDB & CD for each WBS (01 to 03).
CD shall be structured for easy navigation to all documents listed in VDB index via use of bookmarks
/ links

The data book shall include 4 sets of hardcopy and 2 sets of electronics copy (CD ROM) for each
WBS (01 to 03).

Page 30 of 32
DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE 0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.

VENDOR : EMERSON P.O. NO.: 4530684342 1 12 May 2020 2 3

4 5 6
DEVIATIONS LIST
SUPPLIER shall list all deviations to the Material Requisition and reference documents that are included in the
requisition. SUPPLIER’s quotation is deemed to comply with all requirements except those are brought out
in the deviation list

SUPPLIER’s scope of work and supply shall fully comply with the requirements of this requisition except for the
deviations listed in the following table

Note, SUPPLIER shall propose alternatives and/or the impact, cost and delivery, to comply with the
requirements of the material requisition and associated documents for each deviation tabled

Document Rev Reference Deviation Impact

Page 31 of 32
DATA SHEET NO.:
DATE
CLIENT: SHELL EASTERN PETROLEUM PTE LTD. SITE: PULAU BUKOM, SINGAPORE 0591-8550-DS-03-0011

WOOD CONTRACT : 1-PD-0591E UNIT: 2750 30-Jan-20

MATERIAL : PRESSURE TRANSMITTERS NO REQ.: 22 SUPERSEDED BY CHANGE NO.

VENDOR : EMERSON P.O. NO.: 4530684342 1 12 May 20 2 3

4 5 6
ATTACHMENT 1: PRESSURE TRANSMITTER PROCESS SPECIFICATIONS, Rev.F1 (20 PAGES)

Page 32 of 32

Potrebbero piacerti anche