Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Feeder Management
Relays
T&D
Protection & Control
MiCOM P140 Series
Feeder Management Relays
Introduction Control
The MiCOM Feeder Management • Multi-shot autoreclose with check
Relays provide flexible and reliable synchronising
integration of protection, control, • Circuit breaker control
monitoring and measurement
functions. Extensive functionality is • Programmable scheme logic
able to provide complete protection • Programmable allocation of
and control for a wide range of optically isolated inputs and relay
overhead lines and underground outputs
cables from distribution to • Multiple settings groups
transmission voltage levels.
Measurements
Protection
• Comprehensive measurement
• Directional/non-directional phase values Figure 1: MiCOM P141
overcurrent
• Instantaneous
• Directional/non-directional earth User Friendly Interface
• Integrated
fault
• Liquid crystal display with
• Sensitive directional/non- Post Fault Analysis backlight
directional earth fault
• Fault location • Programmable LED indications
• Wattmetric earth fault
• Event and fault records • Password protection
• Restricted earth fault
• Disturbance records • Optional secondary protective
• Blocked overcurrent logic
cover
• Selective overcurrent logic Monitoring
• Fully programmable menu text
• Cold load pick-up logic • Trip circuit supervision
• Voltage controlled overcurrent • Breaker state monitoring
Software Support
• Directional/non-directional • Breaker condition monitoring Available in conjunction with
negative sequence overcurrent MiCOM S1 support software:
• Thermal overload Communications • Settings editor
• Under/overvoltage • A choice of protocols • Programmable scheme logic
• Residual overvoltage • Front and rear communication editor
• Negative sequence overvoltage ports • Viewing of fault diagnostics and
measurements
• Under/overfrequency
Diagnostics • Menu text editor
• Broken conductor
• Power-up diagnostics • Disturbance recorder viewer
• Circuit breaker failure
• Continuous self monitoring
• Voltage transformer supervision Models Available
• Test facilities
• Current transformer supervision • P141 Feeder Management Relay
• P142 with autoreclose
• P143 with autoreclose and check
synchronising
2
Application
The MiCOM P140 series is suitable
for all applications where
overcurrent protection is required.
The integration of many functions
provides complete protection for a
wide range of overhead lines and
underground cables, from P141
M
51P 64N
distribution to transmission voltage 51N 27
levels. It is suitable for solid earthed, 67P 47
impedance earthed, Petersen coil 67N 50BF
3
Protection Functions Both earth fault elements may be blocked overcurrent busbar
enabled at the same time providing protection scheme.
Three phase tripping with faulted discriminative directional earth fault
phase indication is provided for all protection and back-up standby Selective overcurrent logic
protection functions. earth fault protection in the same Selective overcurrent logic assists
Phase overcurrent device. The directionality of the with relay co-ordination by allowing
earth fault elements is provided by the time delay settings of the
Four independent stages are either residual voltage or negative overcurrent elements to be
available for each phase sequence voltage. temporarily modified by
overcurrent element. Each stage energisation of an optically isolated
may be selected as non-directional Sensitive earth fault input.
or directional (forward/reverse). A core balance CT should be used
All stages have definite time to drive the sensitive earth fault Cold load pick-up logic
delayed characteristics, two of the function. The directionality of the Cold load pick-up temporarily raises
stages may also be independently sensitive earth fault elements is the overcurrent settings following
set to one of nine IDMT curves provided by the residual voltage. closure of the circuit breaker,
(IEC and IEEE). The IDMT stages
allowing the protection settings to
have a programmable reset timer Wattmetric be set closer to the load profile.
for grading with electromechanical
As an alternative to the directional
relays, to reduce autoreclose dead Voltage controlled overcurrent
wattmetric characteristic a
times and to reduce clearance times
directional I cos (φ) characteristic Voltage controlled overcurrent
where intermittent faults occur.
can be used for Petersen coil earth provides back-up protection for
The phase fault directional elements fault protection using the sensitive remote phase faults whilst remaining
are internally polarised by earth fault input. This protection insensitive to load conditions.
quadrature phase-phase voltages, provides discrimination as faulted
and will make a correct directional feeders will have a large component Negative sequence overcurrent
decision down to: of residual current whilst healthy Negative sequence overcurrent
0.5V (Vn = 100 – 120V) or feeders will have a small value. protection can be set as either non-
2.0V (Vn = 380 – 480V). A directional I sin (φ) characteristic directional or directional (forward/
A synchronous polarising signal is is also available for protection of reverse), and can operate for
maintained for 3.2s after voltage insulated feeders. remote phase-phase and phase-
collapse to ensure that the earth faults even with delta-star
instantaneous and time delayed Neutral admittance protection transformers present.
overcurrent elements operate Neutral admittance protection is
correctly for close-up three phase provided for the Polish market for Thermal overload
faults. earth fault protection. Three single Thermal characteristics suitable for
stage elements are provided for cables and transformers are
Standard earth fault non-directional overadmittance, available providing both alarm and
There are two standard earth fault non-directional/directional trip stages. The thermal element may
elements, each with four overconductance and be set with either a single time
independent stages. non-directional/directional constant characteristic for the
oversusceptance. protection of cables or dry
• The first element operates from
measured quantities: transformers, or a dual time constant
Restricted earth fault characteristic to protect oil filled
– earth fault current which is The restricted earth fault protection transformers. In the event of loss of
directly measured using a may be configured as either high auxiliary supply, the thermal state is
separate CT impedance or low impedance stored in non-volatile memory.
– residual connection of the biased differential.
three line CTs Under/overvoltage
Blocked overcurrent logic Under/overvoltage protection may
• The second standard earth fault
Each stage of overcurrent and earth be configured to operate from either
element operates from a residual
fault protection can be blocked by phase-phase or phase-neutral
current that is derived internally
an optically isolated input. quantities. Two independent stages
from the summation of the three
This enables overcurrent and earth with definite time elements are
phase currents.
fault protection to integrate into a available, one of the stages can
All earth fault elements have the also be configured to an inverse
same directionality and IDMT characteristic.
characteristics as the phase
overcurrent element.
4
Neutral displacement/residual transformer supervision alarm and Programmable scheme logic
overvoltage blocking when used with MCBs or Programmable scheme logic allows
Residual overvoltage protection is other external forms of voltage the user to customise the protection
available for detecting earth faults transformer supervision. and control functions. It is also used
in high impedance earthed or Current transformer to programme the functionality of
isolated systems. The neutral voltage supervision the optically isolated inputs, relay
is derived from the three phase outputs and LED indications.
voltage inputs. Two independent Current transformer supervision is
provided to detect loss of phase CT The programmable scheme logic
measuring elements with definite
signals and inhibit the operation of comprises gate logic and general
time characteristics are available,
current dependent protection purpose timers. The gate logic
one of the elements can also be
elements. includes OR, AND and majority
configured to have an inverse
gate functions, with the ability to
characteristic.
Control invert the inputs and outputs, and
Negative sequence overvoltage provide feedback. The system is
Circuit breaker control optimised to evaluate changes to the
Negative sequence overvoltage scheme logic signals and thus avoid
protection provides either a tripping Circuit breaker control is available
unnecessary signal processing.
or an interlocking function, upon from the front panel user interface,
detection of unbalanced supply optically isolated inputs and The programmable scheme logic is
voltages. remotely via the substation configured using the graphical
communications. MiCOM S1 PC based support
Under/overfrequency software, as illustrated in Figure 3.
Autoreclose with check
Two independent stages of The required logic is drawn as
synchronising
overfrequency and four of shown and is then downloaded
underfrequency are provided. The P142 provides three pole multi- directly into the relay. The logic may
Each stage functions as a definite shot autoreclose. The user may also be uploaded from the relay
time element. select a single, two, three or four and then modified using
shot autoreclose cycle, with MiCOM S1 support software.
Broken conductor independently settable dead times
The broken conductor protection and reclaim time. Autoreclose can Independent protection
detects unbalanced conditions be initiated from the internal settings groups
caused by broken conductors, mal- protection elements or from external
The settings are divided into two
operation of single phase protection via an opto input.
categories; protection settings, and
switchgear or by single phasing More advanced features of the control and support settings. Four
conditions. P143 include check synchronising, setting groups are provided for the
live line working and sequence protection settings to allow for
Supervisory Functions co-ordination (co-ordination with different operating conditions and
downstream reclosing equipment). adaptive relaying. All settings are
Circuit breaker failure stored in E2PROM.
protection
Two stage circuit breaker failure
protection may be used for tripping
upstream circuit breakers and
retripping of the local circuit breaker
if required. The circuit breaker
failure logic may also be initiated
externally from other protection
devices if required.
Voltage transformer
supervision
Voltage transformer supervision is
provided to detect loss of one, two
or three VT signals, providing
indication and inhibition of voltage
dependent protection elements.
An optically isolated input may also
be configured to initiate the voltage
5
Measurement and Integrated values Plant Supervision
Recording Facilities Wh VArh Trip circuit supervision
The P140 series is capable of Peak, average and rolling demand: Supervision of the trip circuit in both
measuring and storing the values of • Ia Ib Ic circuit breaker open and closed
a wide range of quantities. states can be realised using the
• W VAr optically isolated inputs and
All events, fault and disturbance
records are time tagged to a The P143 provides an additional programmable scheme logic.
resolution of 1ms using an internal voltage input for synchronisation
and additional measurements: Circuit breaker state
real time clock. An optional IRIG-B
monitoring
port is also provided for accurate • Check synchronising voltage
time synchronisation. An alarm will be generated if there
• Slip frequency is a discrepancy between the open
A lithium battery provides a back-up
and closed auxiliary contacts of the
for the real time clock and all Post Fault Analysis circuit breaker.
records in the event of supply
failure. This battery is supervised Fault location Circuit breaker condition
and easily replaced from the front of A fault location algorithm provides monitoring
the relay. distance to fault in miles, kilometres, The circuit breaker condition
ohms or percentage of line length. monitoring features include:
Measurements
The measurements provided, which Event records • monitoring the number of breaker
may be viewed in primary or Up to 250 time-tagged event trip operations
secondary values, can be accessed records are stored in battery backed • recording the sum of the broken
by the back-lit liquid crystal display, memory, and can be extracted current quantity ∑ Ix, 1.0≤ x ≤2.0
or the communications ports. Phase using the communication ports or • monitoring the breaker operating
notation is user definable using the viewed on the front panel display. time
MiCOM S1 text editor.
Fault records • fault frequency counter
Instantaneous measurements
Records of the last 5 faults are
Phase voltages Van Vbn Vcn stored in battery backed memory.
Line voltages Vab Vbc Vca The information provided in the fault
record includes:
Neutral voltage Vn
• Indication of faulted phase
Phase current Ia Ib Ic
• Protection operation
Neutral currents In ISEF
• Active setting group
Sequence currents and voltages
• Date and time
Frequency
• Fault location
Thermal state
• Relay and CB operating time
Single and three phase power factor
• Currents, voltages and frequency
Active power Wa Wb Wc
Wtotal Disturbance records
Reactive power VAra VArb VArc The internal disturbance recorder
VArtotal has 8 analogue channels, 32 digital
and 1 time channel. Data is
Apparent power VAa VAb VAc
sampled 12 times a cycle and
VAtotal
typically 20 disturbance records,
Phase currents and phase to neutral each of up to 10.5 seconds
voltages are available in true rms duration are stored in battery
and fundamental quantities. backed memory. All channels and
the trigger source are user
configurable. Disturbance records
can be extracted from the relay via
the remote communications and
saved in the COMTRADE format.
These records may be examined
using MiCOM S1 or any suitable
software program.
6
Local and Remote DNP 3.0 Hardware Description
Communications The DNP 3.0 protocol is defined All models within the MiCOM P140
and administered by the DNP User series include:
Two communication ports are Group. The relay operates as a
available; a rear port providing DNP 3.0 slave and supports subset • A back-lit liquid crystal display
remote communications and a front level 2 of the protocol plus some of • 12 LEDs
port providing local the features from level 3. • An optional IRIG-B port
communications.
Local communications • An RS232 port
Remote communications • An RS485 port
The front serial communications port
The remote communications are has been designed for use with • A download/monitor port
based on RS485 voltage levels. MiCOM S1, which fully supports • A battery (supervised)
Any of the protocols listed below functions within the relay by
can be chosen at the time of • N/O and N/C watchdog
providing the ability to programme contacts
ordering. the settings off-line, configure the
• Supervised +48V field voltage
Courier/K-Bus programmable scheme logic, extract
and view event, disturbance and • 1A/5A dual rated CTs
The Courier language is a protocol fault records, view the measurement The hardware variations between
which has been developed information dynamically and the MiCOM P140 series models
specifically for the purpose of perform control functions. PAS&T are:
developing generic PC programmes support software can also be used
that will, without modification, with the local communications port. P141 P142 P143
communicate with any device using 100 – 120V or
the Courier language. 3 3 4
Diagnostics 380 – 480V VTs
7
C23 J11
Relay failed
N
C
c
V synch J12
P143 Watchdog
b
check J13
C24 Relay healthy
a
J14
+ J7
C1 5A 48V field voltage
J9
IA C2
kA, kV, Hz
C3 50P 50N 51P 1 4 0 0 kW, kVA, kVArs + J8
1A 48V field voltage
kWh, kVArh J10
C4 5A
Sequence components + J2
IB C5 51N 64 37P Measurements Thermal state Auxiliary voltage
C6
1A J1
See note 2 C7 5A 37N 46 49 IN > 1 Start ON
IC C8 250 See note 4
00:12:00 01/01/99
C9
Event
Trip A B C ON IRIG-B
1A 79 50BF records
C10 5A 00:12:01 01/01/99
IN C11 RS232 MiCOM S1
C12
BC CTS
J17
1A
20 RS485 Courier
C13 5A J18
IN Disturbance Modbus
Sensitive C14 IEC60870-5-103
C15
records LEDs
1A
59 67 67W
See note 1 User programmable
See note 3 5 Fault A-B-C 15ms
C19 47 27 VTS Fault Ia = 1000 A
reports Ib = 1000 A
VA 81U 81O Ic = 1000 A
51V
C20 H1
RL1
H2
In>/ISEF> start
VB 1 RL2
H3
I> start
C21 & 1 & H4
H5
RL3 Protection trip
Programmable scheme logic H6
N
C
VC H7
B
C22
RL4
H8 General alarm
H9 User
A
52
H13
RL6
H14 Control CB close
H15
D2 H16
Setting group RL7 H17 Control CB trip
D1 H18
D4
Setting group
D3
D6
Block In1>3&4 D5
D8
Block I>3&4
D7
D10
Reset LEDs
D9
D12
G1
External trip RL8 Any start
D11 G2
D14 G3
52A RL9 A/R successful
D13 G4
D16 G5
52B RL10
G6
Non auto mode
D15
G7
F2 RL11 G8 A/R in progress User
Select auto mode G9
programmable
F1
G10
F4
G11 A/R prot. lockout See note 2
Select telecontrol mode RL12
F3 G12
F6 G13
Select live line mode G14 A/R in service
F5 RL13
G15
F8
CB healthy G16
F7 G17 Live line mode
F10 RL14 G18
Block A/R
F9
F12
Reset lockout F11
F14
User F13
programmable F16
See note 2 F15
ANSI Numbers
Note 1: All CT connectors have integral shorting. These contacts are made before the internal CT circuits are disconnected.
Note 2: Additional hardware for P143 only.
Note 3: 5A CT connections shown, 1A CT connections available on the terminal blocks.
Note 4: The bridge rectifier is not present on the 24 – 48V dc version.
8
Protection Setting Ranges
1
6 Phase fault
IDMT/definite time
stages 0.08 to 4.0In
9
IEC/UK curves IEEE/US curves
TMS = 1 TD = 7
1000 100
100
Operating
10
time (s)
Operating
time (s)
10
UK LTI
IEC SI 1
IEEE MI
1
IEEE VI
IEC VI
US CO2
IEC EI US CO8
IEEE EI
0.1 0.1
1 10 100 1 10 100
Current (Multiples of Is) Current (Multiples of Is)
0.14
IEC Standard inverse t = TMS x IEEE Moderately inverse
0.02
()I
Is
-1 t=
TD
x
0.0515
0.02
+ 0.114
7
()
I
Is
-1
13.5
IEC Very inverse t = TMS x IEEE Very inverse
( ) -1
I
Is t=
TD
x
19.61
2
+ 0.491
7
( ) -1
I
Is
80
IEC Extremely inverse t = TMS x IEEE Extremely inverse
2
( )-1I
Is t=
TD
x
28.2
2 + 0.1217
7
( ) -1
I
Is
10
Restricted earth fault Residual overvoltage
Voltage settings, Vs
I DIFF
Operate 1 to 80V (100 – 120V)
K1 0% to 20%
K2 K2 0% to 150% 4 to 320V (380 – 480V)
I s1 0.08 to 1.0I n
Time settings
Restrain I s2 0.10 to 1.5I n
K1 Definite time 0 to 100s
I s1
IDMT t = TMS(V/Vs – 1)
I s2 I BIAS
TMS 0.5 to 100
Negative sequence
Undercurrent Dual time constant
overvoltage
Phase and neutral characteristic
Voltage settings, Vs
0.02 to 3.2In –t –t
0.4 e τ1 + 0.6 eτ2 1 to 110V (100 – 120V)
ISEF 0.001 to 0.8In
4 to 440V (380 – 480V)
I2 – (k.IFLC)2
Voltage controlled overcurrent =
I2 – IP2 Time settings
Voltage control threshold Definite time 0 to 100s
Where:
20 to 120V (100 – 120V)
τ1, τ2 = plant heating and cooling Under/overfrequency
80 to 480V (380 – 480V) time constants (1 to 200 Frequency settings 45 to 65Hz
Overcurrent sensitivity factor minutes)
Definite time 0 to 100s
0.25 to 1.0 Thermal trip current setting
Broken conductor
Negative sequence 0.08 to 3.2In
I2/I1 0.2 to 1.0
overcurrent Undervoltage
Definite time 0 to 100s
Threshold 0.08 to 4.0In Voltage settings, Vs
Definite time 0 to 100s Autoreclose and check
10 to 120V (100 – 120V) synchronising (where
Thermal overload 40 to 480V (380 – 480V) appropriate
Thermal alarm 50% to 100% Time settings Main shots 1 to 4
Single time constant Definite time 0 to 100s Dead times (1, 2) 0.01 to 300s
characteristic IDMT t = TMS/(1 – V/Vs) Dead times (3, 4) 0.01 to 9999s
I2 – (kIFLC)2 TMS 0.5 to 100 Check
I2 – IP2 synchronising 5° to 90°
Overvoltage
Where: Slip frequency 0.02 to 1.00Hz
Voltage settings, Vs
t= time to trip, following 60 to 185V (100 – 120V) Neutral admittance
application of the overload
240 to 680V (380 – 480V) Voltage threshold Vn
current, I
Time settings 1 to 40V (100 – 120V)
τ= plant heating and cooling
time constant (1 to 200 Definite time 0 to 100s 4 to 160V (380 – 480V)
minutes) IDMT t = TMS/(V/Vs – 1) Correction angle
I = largest phase current TMS 0.5 to 100 –30° to +30°
IFLC = thermal trip setting Overadmittance settings
k= 1.05 constant YN>/Overconductance settings
GN>/Oversusceptance settings
IP = Steady state pre-load current
BN>
25µs to 2.5ms (SEF input)
250µs to 25ms (EF input)
Time settings (definite time)
Operating time 0.05 to 100s
Reset time 0 to 100s
11
Accuracy/operating times Technical Data Current transformer
(typically) requirements
Ratings The following CT requirements are
Phase and earth fault ±5% or 50ms
Inputs: based on a maximum prospective
Wattmetric ±5% or 40ms
fault current of 50In and the relay
• AC current (In)
Restricted earth fault ±5% or 45ms having a maximum high set setting
1A/5A dual rated ac rms of 25In. The CT requirements are
Negative sequence
overcurrent ±2% or 60ms • AC voltage (Vn) designed to provide operation of:
Undervoltage ±2% or 50ms 100 – 120V or 380 – 480V rms • Phase and standard earth fault
nominal phase-phase elements
Overvoltage ±2% or 50ms
Rated frequency 50/60Hz 1A rated currrent circuits
Measurements
Operative range 45Hz to 65Hz 2.5VA 10P 20
Voltage and amperes <1%
Auxiliary voltage (Vx) 5A rated current circuits
0.2 – 3.0In ±0.5%
7.5VA 10P 20
0.2 – 2.0In ±0.5% Nominal
Operative range (V)
Derived value <2% (V)
Digital inputs
dc dc ac
Optically isolated inputs may be
24 – 48 19 to 65 –
energised from the supervised 48V
48 – 110 37 to 150 24 to 110
field voltage provided or an
110 – 250 87 to 300 80 to 265
external battery.
Burdens Contacts
• DC auxiliary voltage • Contact ratings:
10W typical (P141 and P142) Make: 30A and carry for 3s
12W typical (P143) Carry: 5A continuous
• AC auxiliary voltage Break: dc 50W resistive
25W inductive
10W typical (P141 and P142)
(L/R = 40ms)
12W typical (P143)
ac 1250VA resistive
• Optically isolated inputs
ac 1250VA inductive
0.24W per input at 48V (P.F. = 0.5)
• Nominal voltage circuit Subject to maxima of 5A and
Vn 100 – 120V <0.02VA at 300V
110V • Watchdog contact ratings
Vn 380 – 480V <0.1VA at 440V dc 30W resistive
• Nominal current circuit dc 15W inductive
Phase and neutral (L/R = 40ms)
<0.1Ω at 1A ac 375VA inductive
(P.F. = 0.7)
<0.02Ω at 5A
• Durability:
Thermal withstand Loaded contact
• AC current inputs
10,000 operations minimum
4.0In continuous Unloaded contact
30In for 10s
100,000 operations minimum
100In for 1s
• AC voltage inputs
2 Vn continuous
2.6 Vn for10s
12
Rear communications port Download/monitor port Electrical environment
• Connection This is a 25 pin D-type female • DC supply interruption
Multidrop (32 units) connector located on the front user IEC 60255-11: 1979
interface and is specifically
• Cable type The unit will withstand a 20ms
designed for test purposes and
Screened twisted pair software download. interruption in the auxiliary
supply, in its quiescent state,
• Cable length 1000m max • Isolation ELV without de-energising.
• Connector Screw • Local access • AC ripple on dc supply
terminals
IEC 60255-11: 1979
• Signal levels RS485 High voltage withstand
This is not applicable to the RS232 The unit will withstand a 12% ac
• Isolation SELV
and download/monitor ports. ripple on the dc supply.
• Remote access
• AC voltage dips and short
• Dielectric withstand
interruptions
Protocols supported IEC 60255-5: 1977
• Courier IEC 61000-4-11: 1994
2kV rms for 1 minute between all
• Modbus 20ms interruptions/dips.
case terminals connected together
• IEC 60870-5-103 and the case earth. • High frequency disturbance
• DNP 3.0 2kV rms for 1 minute between all IEC 60255-22-1: 1988 Class III
terminals of independent circuits At 1MHz, for 2s with 200Ω
Note: An interface to an optical
with terminals on each source impedance:
fibre, type 850nm, BFOC 2.5
independent circuit
connector is available for 2.5kV peak between independent
connected together.
IEC 60870-5-103. circuits and independent circuits
ANSI/IEEE C37.90-1989 and case earth.
Front communications port (r1994)
1.0kV peak across terminals of
• Connection Point to point 1kV rms for 1 minute across the the same circuit.
• Cable type Multi-core open contacts of the watchdog
This is not applicable to the
relays.
• Cable length 15m max RS232 and download/monitor
1kV rms for 1 minute across open ports.
• Connector RS232 DTE contacts of changeover output
9 pin D-type female relays. • Fast transient disturbance
• Protocol Courier 1.5kV rms for 1 minute across IEC 60255-22-4 : 1992 Class IV
• Isolation ELV open contacts of normally open 4kV, 2.5kHz applied directly to
output relays. auxiliary supply
• Local access
• High voltage impulse 4kV, 2.5kHz applied to all inputs.
IRIG-B Port IEC 60255-5: 1977 This is not applicable to the
• Carrier signal Three positive and three negative RS232 and download/monitor
impulses of 5kV peak, 1.2/50µs, ports.
Amplitude modulated
0.5J between all terminals and all • Surge withstand capability
• Cable type
terminals and case earth. IEEE/ANSI C37.90.1 (1989)
50 ohm coaxial cable
• Connection BNC 4kV fast transient and 2.5kV
oscillatory applied directly across
• Isolation SELV each output contact, optically
isolated input and power supply
Internal battery circuit.
Battery type: 1/ AA, 3.6V
2
• Radiated immunity
C37.90.2: 1995
25MHz to 1000MHz, zero and
100% square wave modulated.
Field strength of 35V/m.
13
• Electrostatic discharge Atmospheric environment Cases
IEC 60255-22-2: 1996 Class 4 • Temperature • P141 & P142 MiCOM 40TE
15kV discharge in air to user IEC 60255-6:1988 • P143 MiCOM 60TE
interface, display and exposed Operating –25°C to +55°C • Weight
metal work.
Storage and transit –25°C to P141/P142 c.7.3 kg
IEC 60255-22-2: 1996 Class 3 +70°C
P143 c.9.2 kg
8kV discharge in air to all IEC 60068-2-1: 1990/A2:1994
communication ports. 6kV point
Cold Additional Information
contact discharge to any part of
the front of the product. IEC 60068-2-2: 1974/A2:1994 MiCOM P140 Series
• Surge immunity Dry heat Technical Guide TG8612
IEC 61000-4-5: 1995 Level 4 • Humidity Operation Guide OG8612
4kV peak, 1.2/50µs between all IEC 60068-2-3: 1969
Courier Communications R4113
groups and case earth. 56 days at 93% RH and +40°C
MiCOM S1 User Manual R8610
2kV peak, 1.2/50µs between • Enclosure protection
terminals of each group. Midos Parts Catalogue
IEC 60529: 1989 and Assembly Instructions R7012
This is not applicable to the
IP52 Protection (front panel)
RS232 and download/monitor PAS&T R8514
against dust and dripping water
ports.
at 15° to the vertical.
• EMC compliance
14
Case
The MiCOM P140 series relays are 23.30 155.40 8 off holes Dia. 3.4
housed in a specially designed case A B BA
providing a high density of Sealing strip
177.0
functionality within the product, a 159.00 168.00 (4U)
customisable user interface, AB BA
additional functions and information 181.30
10.35 483 (19” rack)
concealed by upper and lower 202.00
covers. Physical protection of the A = Clearance holes
Flush mounting panel
front panel user interface and Panel cut-out detail
B = Mounting holes
prevention of casual access is
provided by an optional transparent 200.00 Note: If mounting plate
is required use flush
front cover, which can be fitted or mounting cut out dimensions
omitted according to choice, since
the front panel has been designed All dimensions in mm
to IP52 protection against dust and
water. The case is suitable for either
rack or panel mounting as shown in Secondary cover (when fitted)
Figures 7 and 8. 240.00
Front view
Incl. wiring
Side view
206.00 30.00
177.0
159.00 (4U)
AB B A BA
All dimensions in mm
Side view
309.60 30.00
15
MiCOM P140 Series Four independent stages of Programmable scheme logic for
underfrequency protection and two configuring custom logic schemes
Specification
of overfrequency protection shall be shall be uploadable from relay to
An integrated feeder protection and provided. PC or PC to relay. The relay shall
autoreclose scheme shall provide store factory default protection and
The device shall be responsive to
3 phase overcurrent and earth fault scheme logic settings for restoration
unbalanced conditions providing
protection with faulted phase or upload to a PC.
alarm and tripping signals. Back-up
indication. An integral three pole
protection for remote phase-phase Time-tagged event, fault and
multi-shot autorecloser shall support
and phase-ground faults shall also disturbance records shall be stored
check synchronising, live line
be available. in battery backed memory.
working and sequence
The internal disturbance recorder
co-ordination. Thermal protection with single and
shall have a capacity to store 20
dual time constant characteristics
Five dual rated 1/5A CT inputs records, each record shall store
suitable for cables and transformers
shall be available for connection to sampled data from 8 analogue and
shall be provided. The thermal state
3 phase and 2 earth CTs. 32 digital channels over a period of
shall be stored in non-volatile
10 seconds.
Four stages of directional phase memory.
overcurrent and earth fault The vendor shall be able to provide
Programming of the device shall be
protection shall be provided, with a software support for local and
possible using a front panel user
selection of nine IDMT remote programming, and
interface, local and remote
characteristics for two of the stages. extraction of records from the
communications ports.
Cold load pick-up logic shall device.
A configuration feature shall be
provide co-ordination with upstream
provided to enable selection of A comprehensive range of
devices and allow protection
required functions. This shall allow instantaneous and integrated
settings to be set closer to the load
menu customisation removing measurement values shall be
profile during short term overload
unwanted functions and setting available for viewing on the user
conditions. An additional CT shall
groups from the settings display. interface and the communications
be provided for sensitive and
The front panel user interface shall ports.
restricted earth fault protection.
provide independent keys for the
viewing and acknowledgement of
alarms. Fixed and programmable
scheme logic shall be provided.
16
Information Required with Order
Version
Standard version 1
With integral autoreclose 2
With integral autoreclose and check synchronising 3
Vx aux rating
24 – 48V dc 1
48 – 110V dc (30 – 100V ac) 2
110 – 250V dc (100 – 240V ac) 3
Vn rating
100 – 120V ac 1
380 – 480V ac 2
Hardware options
Standard version 1
IRIG-B input 2
Fibre optic converter (IEC 60870-5-103) 3
IRIG-B input & fibre optic converter (IEC 60870-5-103) 4
Protocol options
K-Bus 1
Modbus 2
IEC 60870-5-103 (VDEW) 3
DNP 3.0 4
17
ALSTOM T&D Protection & Control Business contact addresses
18
Your contact:
19
TRANSMISSION & DISTRIBUTION Protection & Control, HQ, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex, France
Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: pcs.enquiries@tde.alstom.com Internet: www.alstom.com
©2000 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
Other names mentioned, registered or not, are the property of their respective companies.
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.