Date GE Tag Description Learning

8-28-17 18VGG-1B/1A Seismic Charge Amplifier 1. Signal terminal is generated 0 mv ac once healthy even without sensor.
(PGT25) Power Turbine 2. Signal terminal is generated 10 v ac (faulty) once the extension cable is faulty
(note. Not tried if the sensor is faulty).
VSV 1. Servo coil : 31.8 ohms
(PGT25) 2. Excitation coil: 94.9 ohms
3. Feedback A: 71.8 ohms and Feeback B: 71.8 ohms so total of 140 ohms.
Key Phasor 1. Can simulate using frequency generator (i.e. Fluke 754)
2. 7000 RPM is the maximum speed of Power turbine. 1 RPM = 1/60 Hz
3. so 7000 RPM/60 = 116 Hz.
4. Amplitude is set to 5 V ac sinewave and the Frequency may varies.
5. Set up using series of 9V to Fluke 754.
Radial Vibration Alarm 1. Vibration accumulated ‘Alarm” once will receive high vibration while “Fault”
once any of the sensor or proximitor are broken.
2. To simulate the H and HH alarm of the Radial without TK-3, use Fluke 754
series with 9V battery and bypass the proximitor.
3. Connect the negative probe of the Fluke 754 to “common” and positive probe of
the battery to “output” of the proximitor.
4. 2.78 mV ac per microns.
5. Calibration range 0 to 140 microns.
6. Set the Fluke 754 fixed to 100 hz, and simulate the amplitude from 0 to 400 mV
ac sinewave.
Axial Vibration 1. Can simulate directly using volts source output.
Seismic Vibration 1. Simulate using TSU 109 (set to 100 Hz and Adjust the amplitude to 4 vac)
2. Can check the Seismic vibration actual in BN PLC on “band pass” but cannot
check in MarkVie HMI if without gg speed (i.e ST).
3. if no GG speed the 1X Ampl is invalid.
4. Hook-up the TSU 109 on charge amplifier, remove the seismic sensor.

Bently Nevada To connect from engg Laptop to BN PLC, use “NETWORK” then type the
corresponding IP address for using RJ45.
If direct connection use the dedicated cable to connect direct into rack select the
channel, com port and baud rate.
VT-2201 and VT- Proximitor Model: Calibration range is 0 to 200 mm/sec.
2202 1. Using 6 V battery series with Fluke 754.
86517-01-01-01-02 2. Apply 10 Hz or (100 hz to become stable voltage) frequency Fluke 754 the
Acceleration Interface simulate the signal. 1 v = 20 mm/s
moduel 100 mv/in/sec (3.94 3. Take note the lower and upper limit voltage inside verification in BN rack.
mv/mm/s
(GG seismic vibration will not activate the reading in 1X Amplitude if not enough
the signal). Unlike Power turbine the band pass reading directly to 1X Amplitude.
Magnetic pick up hilliard 1. correct sensing distance let say 0.8 to 1.5 mm the ohms is 118.
starting clutch 2. if the distance too far and too near the ohms is 2.9 kilo-ohms

June 23, Gas Metering CANBUS SIGNAL 1. Ensure 2 resistor 120 ohms are installed each end of the loop, put in CANH &
2019 LM2500 CANL.
2. If healthy voltage Between GRND to CANH is about 2.75 Volts DC, while
GRND to CANL is about 2.5 Volts DC, hence voltage difference between CANH
and CANL is 0.25 VDC.
3. Ensure that correct node ID put inside gas metering correspond the device ID in
MARKVei example. FCV-103 is NodeID 1 and FCV-104 is Node ID 2, Baud rate
of 250 kbs.
Calibration accelerometer 86517 Bently Nevada

How to calibrate Accelerometer 86517 Bently Nevada,


To perform these procedures, Firstly prepare the following tools:
 Function Generator (50 ohm output)
 DC power supply -24 Vdc
 Multimeter
 Small screw driver
 Capacitor 0.01 microfarad 1% capacitor, (BNC conector P/N 00448308)

Step to calibrate:
1. Connect power supply  to the - 24 Vdc and COM terminals on the accelerometer, and adjust the
output of power supply to -24Vdc, connect multimeter to the +ACCEL terminal, connect capacitor 0.01
microfarad to function generator, the input should connect to terminal C and leave pins A and B not
connected. Don't forged to connect the interface module case to common through the case sheild
terminal. Make sure the interface module case is netral
2. Adjust the function generator to null output level and measure the acceleration signal with the
multimeter, if the reading is more than a few milivolts rms then setup is probably injecting power line noise
into the charge amplifier, this noise must be eliminated, reduce lead lengths and changing lead routing
3. Adjust the function generator output to 0.3535 Vrms sine wave at 100 Hz for a transducer
sensitivity of 50 pC/g, or 0.707 Vrms for tranducer sensitivity of 100pC/g
4. Measure the acceleration output with the multimeter. If the output reads 0.3535+/-7.0 mV rms go
to step 8, If the output does not read 0.3535 V rms +/- 7.0 mV rms continue with step 5
5. Unscrew the four screws at each corner of the lid
6. Open the lid and fold it back
7. Adjust the potentiometer until the multimeter reads 0.3535 +/- 7.0 V rms, close and tighten the lid
and verify thet the multimeter still reads 0.3535 V rms, if it does not repeat step 6 and 7, be aware when
the lid is open the circuit is unshielded and the charge amp can pick up noise.
8. Disconnect the input from pin C and connect it to pin A and leave pin C and B unconnected, verify
that the multimeter still reads 0.3535 Vrms +/- 7.0 mVrms. If it does not then check your test setup as step
2 and repeat this step. If the test is not passed, replace the interface module.