20-05-19, PLC Programme, ROC D3,D5,D7 and F7MKII-Tophammer units

PLC-PROGRAMME EXPLANATION

PLC TYPE: MITSUBISHI MELSEC FXON


PLC PART NUMBER: 3222 3058 37
E-EPROM PART NUMBER: 3222 3104 03

DRILLRIG TYPE: D3/D5/D7 AND F7MK2 - TOPHAMMER UNITS.

TABLE OF CONTENTS PAGE

1. GENERAL FUNCTIONS 2
1.1 Power Supply 2
1.2 Pump Unload 2
1.3 Indication light for hydraulic jack 2
1.4.a Engine rpm, Manually controlled full speed drilling mode 2
1.4.b Engine rpm, Automatically controlled full speed drilling mode 2
2. DRILLING FUNCTIONS 2
2.1 Dustcollector 2
2.2 ECL-pump 3
2.3 ECG-pump 3
2.4 Anti jamming, activated by high rotation pressure 3
2.5 Anti jamming, activated by flushing 3
2.6.a Low feedpressure setting, pump 1 3
2.6.b Low impact activation 3
2.6.c High impact activation 4
2.7 Impact hour counter 4
3. RAPID FEED STOP FUNCTIONS 4
3.1.a Forward stop, at drill steel support 4
3.1.b Backward stop, at uncoupling 4
3.1.c Backward stop, at magazine 4
3.1.d Backward, max stop 4
4. RODHANDLING FUNCTIONS 5
4.1.a Open gripper 5
4.1.b Loose grip 5
4.1.c Hard grip 5
4.2.a Sleeve retainer activation 5
4.2.b Sleeve retainer de-activation 5
4.3.a RHS arm towards drillcentre 6
4.3.b RHS arm towards carousel 6
4.4.a RHS carousel rotation clockwise 6
4.4.b RHS carousel rotation counter clockwise 6

1(6)
20-05-19, PLC Programme, ROC D3,D5,D7 and F7MKII-Tophammer units

1. GENERAL FUNCTIONS

Function Signal from/position PLC input/status PLC output Valve

1.1 Power supply


S139/Ignition ON K4A
Fuse F13/ON + 24V and COM1 to COM7
X1/100 - earth connection*

-When ignition key S139 is in position 1, ignition ON, relay K4A is activated and allows power supply
to fuse F13.
*Earth connection also bridged to connection S/S and 0V.
1.2 Pump unload
S130/Tramming pos. X24/OFF
S139/Engine start X34/ON Y26/OFF
S139/Ignition X34/OFF Y26/ON Y123

Note ! When the ignition switch (S139) is released from starting position and respringed back to ignition
position, the output Y26 is ON again.
1.3 Indication light for hydraulic jack. ( not in use on Roc D5,D7 )
S130/Tramming pos. X24/OFF
B184/Dis-ACTIVE X33/OFF Y25/ON H127

Note ! The indication light only inform about the position of the hydraulic jack. The tramming is
possible in both active and disactive position.
1.4.a Engine rpm, manually controlled full speed drilling mode.
S189/ON X32/ON Y24/ON Y217

1.4.b Engine rpm, automatically controlled full speed drilling mode.


S130/Drilling pos. X24/ON
S100/Flush air pos. X25/ON or X26/ON
*S446/Flushing pos. X27/ON or X30/ON Y24/ON Y217

*To start flushing and DCT, press the impact switch (S446) for maximum 0,3 sec. To start low impact,
press the switch (S446) longer then 0,8 sec.

2.DRILLING FUNCTIONS

Function Signal from/position PLC input/status PLC output Valve


2.1 Dustcollector
S130/Drilling pos. X24/ON
S100/Flush air pos. X25/ON or X26/ON
S181/Suction pos. X2/ON
*S446/Flushing pos. X27/ON Y21/ON Y253

*To start flushing and DCT, press the impact switch (S446) for maximum 0,3 sec. To start low impact,
press the switch (S446) longer then 0,8 sec.

2(6)
20-05-19, PLC Programme, ROC D3,D5,D7 and F7MKII-Tophammer units

2.DRILLING FUNCTIONS

Function Signal from/position PLC input/status PLC output Valve

2.2 ECL-pump
S130/Drilling pos. X24/ON
S100/Flush air pos. X25/ON or X26/ON
*S446/Flushing pos. X27/ON Y0/ON Y106

*To start flushing and DCT, press the impact switch (S446) for maximum 0,3 sec. To start low impact,
press the switch (S446) longer then 0,8 sec.
Note !The ECL-Pump (Y106) works with an extended time of 60 seconds when the flush air switch S100
or impact switch S446 have been shut-off after drilling. This time is set on the external ECL-relay and is
not affected by a lost in output signal Y0.
2.3 ECG-pump
S130/Drilling pos. X24/ON
S100/Flush air pos. X25/ON or X26/ON
*S446/Flushing pos. X27/ON Y1/ON Y107

*To start flushing and DCT, press the impact switch (S446) for maximum 0,3 sec. To start low impact,
press the switch (S446) longer then 0,8 sec.
Note !The ECG-pump (Y107) does not work with an extended time. But it is possible to adjust
on the external ECG-relay if needed.
2.4 Anti-jamming activated by high rotation pressure
S130/Drilling pos. X24/ON
B134/ACTIVE X0/ON Y2/ON Y109

The minimum activating time for output Y2 is set by the PLC internally to 0,8sec.
2.5 Anti-jamming activated by flushing
S130/Drilling pos. X24/ON
*S100/Full flush air pos. X26/ON
S446/Flushing pos.
B142/Active X1/ON Y2/ON Y109

*The flow switch is only functioning during full flushing. The minimum activating time is set by the
PLC internally to 0,8sec.
2.6.a *Low feedpressure setting pump1.
S130/Drilling pos. X24/ON Y17/ON Y101B

*When switch (S130) is in drilling position, valve 101B for low feed and impact pressure is activated.
2.6.b Low impact activation.
S130/Drilling pos. X24/ON Y17/ON Y101B
S100/Flush air pos. X25/ON or X26/ON
B118/RHS-arm in carousel X3/ON
*S446/Low impact. X27/ON Y20/ON Y101A

*Switch S446 for low impact position must be pressed more then 0.8 seconds to obtain a self holding
circuit, Impact will be shut-off if switch S446 is released within 0,8 seconds (Y20/OFF). Pressing the
button under 0,3 sec, only starts the flushing.

3(6)
20-05-19, PLC Programme, ROC D3,D5,D7 and F7MKII-Tophammer units

2. DRILLING FUNCTIONS

Function Signal from/position PLC input/status PLC output Valve

2.6.c High impact activation.


S130/Drilling pos. X24/ON Y17/ON Y101B
S100/Flush air pos. X25/ON or X26/ON
S446/Low impact. X27/ON Y20 Y101A
 
*S446/High impact. X30/ON Y17/OFF
Y20/ON Y101A

*Switch S446 for high impact position must be pressed more then 0.3 seconds to obtain a self holding
circuit, Impact will be shut-off if switch S446 is released within 0,3 seconds (Y20/OFF).
To press the high impact position button on switch (S446) directly without first starting the low impact
will result in no self holding curcuit or flushing.
Note ! When changing back to low impact, press the low impact pressure button on switch (S446) longer
then 0,3 sec, otherwise the impact will stop.
2.7 Impact hour counter
S130/Drilling pos. X24/ON
S446/Impact. pos. X27/ON or X30/ON Y27 P108

3. RAPID FEED STOP FUNCTIONS

Function Signal from/position PLC input/status PLC output Valve

3.1.a Forward stop at drillsteel support


S130/Drilling pos. X24/ON
B122/Active X12/ON Y4/ON Y150
3.1.b Backward stop, at uncoupling
S130/Drilling pos. X24/ON
S113/Take up rod string X22/ON
B126/Active X13/ON Y3/ON Y149
3.1.c Backward stop, at intake magazine
S130/Drilling pos. X24/ON
S113/Take up rod string X22/ON
B126/Active X13/ON Y3/ON Y149
3.1.d Backward, max, stop
S130/Drilling pos. X24/ON
B127/Active X14/ON Y3/ON Y149

If sleeve retainer switch (S182), X23/ON is activated then rapid feed stop backward (Y149), Y3/ON and
rapid feed stop forward (Y150), Y4/ON will be automatically activated.

4(6)
20-05-19, PLC Programme, ROC D3,D5,D7 and F7MKII-Tophammer units

4. RODHANDLING FUNCTIONS

Function Signal from/position PLC inputs/status PLC output Valve

4.1.a Open Gripper


S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
B379/Operator seat active X31/ON
S111/Top button pushed X21/ON Y6/ON Y300

*Flushing is deactivated automatically when switching impact off, this enables rodhandling.
4.1.b Loose grip
S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
B379/Operator seat active X31/ON
S111/Neutral pos. All functions OFF
B118/Dis-ACTIVE X3/OFF Y7/ON Y306

*Flushing is deactivated automatically when switching impact off, this enables rodhandling.
4.1.c Hard grip
S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
B379/Operator seat active X31/ON
S111/Pos, backwards. X16/ON Y6andY7/OFF
Y10/ON Y301B

*Flushing is deactivated automatically when switching impact off, this enables rodhandling.
4.2.a Sleeve retainer activation
S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
B379/Operator seat active X31/ON
S111/Pos, backwards. X16/ON
**S182/Sleeve retainer X23/ON Y5/ON Y309

*Flushing is deactivated automatically when switching impact off, this enables rodhandling.
** Sleeve retainer activation is time delayed in PLC, to secure that the rodgrippers are out in drill centre
before activation.
4.2.b Sleeve retainer deactivation
S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
**S182/Sleeve retainer X23/OFF Y5/OFF

*Flushing is deactivated automatically when switching impact off, this enables rodhandling.
**Rod gripper transportation to carousel is time delayed in PLC, to secure that the sleeve retainer is back
in neutral position.

5(6)
20-05-19, PLC Programme, ROC D3,D5,D7 and F7MKII-Tophammer units

4. RODHANDLING FUNCTIONS

Function Signal from/position PLC inputs/status PLC output Valve

4.3.a RHS, arm towards drillcenter


S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
B379/ACTIVE X31/ON
S111/Pos backwards. X16/ON Y6andY7/OFF
Y10/ON Y301B

*Flushing is deactivated automatically by switching of the impact which enables rodhandling.


4.3.b RHS, arm towards carousel
S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
B379/ACTIVE X31/ON
S111/Pos, forward. X15/ON Y11/ON Y301A

*Flushing is deactivated automatically by switching of the impact which enables rodhandling.


4.4.a RHS, carousel rotation, clockwise.
S130/Drilling pos. X24/ON
*S446/Impact switch X27 and X30/OFF
B379/Operator seat active X31/ON
S111/Top button pushed. X21/ON
S111/Pos, to the left. X17/ON
B118/ACTIVE X3/ON
START B183/ACTIVE X7/ON Y13/ON Y303A
 B183/Dis-ACTIVE X7/OFF
STOP B183/ACTIVE X7/ON Y13/OFF

*Flushing is deactivated automatically when switching impact off, this enables rodhandling.
4.4.b RHS, carousel rotation, counter clockwise.
S130/Drilling pos. X 24/ON
*S446/Impact switch X27 and X30/OFF
B379/Operator seat active X31/ON
S111/Top button pushed. X21/ON
S111/Pos, to the right. X20/ON
B118/ACTIVE X3/ON
START B182/ACTIVE X6/ON Y12/ON Y303B
 B182/Dis-ACTIVE X6/OFF
STOP B182/ACTIVE X6/ON Y12/OFF

*Flushing is deactivated automatically by switching of the impact which enables rodhandling.

6(6)