installation systems:
fire protection classification.
-
Verifications
 Fireproof ins t allations for individual pipes and pipe routes of R30 – R120 and F30 – F120.
 P r o o f o f c o m p l i a n c e w i t h t h e c r i t e r i a a c c o r d i n g M L A R ( G e r m a n s t a n d a r d p i p e s y s t e m d i r e c t i ve )
for installation in escape and rescue routes.

 Fire protection – protection goals:  Fire inspection reports for the installation of
pipe clamps and channels:
Firstly, fire protection serves to protect people and is regulated by The fire safety inspection reports described in this brochure meet
the building laws in the respective countries (or regional states). the requirements for fire protection according to the building regula-
Secondly, fire protection serves to protect property. This is regulated tions of the countries and, especially for Germany, according to the
by the insurance associations, such as VdS and FM. These require- nationwide homonymic German pipe systems directive (LAR), based
ments partially go beyond the building legislation. This is particularly on the standard pipe systems directive of 2005 (MLAR 2005).
evident in the installation of fire protection systems, such as sprink- Personal protection is defined in the MLAR Directive through clear
lers, etc.. In these cases approved or recognised components must rules for escape routes, such as corridors, stairwells, hallways
be used (see the fischer catalogues for further details on this). between stairwells and the exit. The key message is to ensure the
safety of the escape route by ensuring the functioning of the fire-

a c c o rd i n g to M L A R i s re q u i re d b e t w e e n i n s t a l l a t i o n s a n d u n d e r -
lying suspended fire-proof F30 sub-ceilings (fire resistance of 30
minutes). Based on the fire inspections, load information for a fire re-
sistance of 30 minutes was determined in relation to the maximum
Reduction factors kθ p e r m i s s i b l e d e fo r m a t i o n o f c h a n n e l s o r p i p e c l a m p s . T h e n e c e s s i t y
1.0 for these considerations arises from the properties of steel, which is
0.9 Yield strength s u b j e c t e d to a t e m p e r a t u re o f > 8 0 0 ° C a c c o rd i n g to t h e s t a n d a rd

fischer
0.8
0.7
0.6
kγ,θ = fγ,θ / fγ

Elasticity module
temperature curve (ISO curve).
Additionally, the same information is documented in inspection reports
for a fire resistance rating of R30, R60, R90 and R120

Fireproof pipe installation


0.5
0.4
0.3
kΕ,θ = Εа,θ / Εа according to EN1363-1 and DIN4102-2 (see load tables).

 Fire inspection reports for installation systems -


0.2 Proportional limit pipe clamps, sliding elements, channel and cantilever
Certified fire protection for safe fixings.
0.1 kρ,θ = fρ,θ / fρ
arm:
0.0
0 200 400 600 800 1000 1200 Following “supplementary sheets to inspection reports” from MPA
Steel temperature [°C] Braunschweig are available:

Dependency of the yield strength, proportional limit and elasticity module  FRS (Document no. GS 3.2/14-175-2)
MLAR3).
on the temperature (basis: EN1993-1-2:2012-12 Eurocode MLAR
German standard regulations for
fire safety requirements

German standard regulations for
fire safety requirements
for piping systems (11/2005) for piping systems (11/2005)
F 30 R 30 F R S - L U n i ve r s a l ( D o c u m e n t n o . G S 3 . 2 / 1 5 - 1 4 1 - 3 )
Certificate of compliance of the Certificate of compliance of the
minimum distance ≤ 50 mm
 FLS / ALK (Document no. GS 3.2/15-141-4)
minimum distance ≤ 50 mm

Fire resistance Fire resistance


classification Additional
classification available “fire inspection reports” from MPA NRW, similar
Test preparation F 120 Rto120
the above criteria are:
according according
DIN 4102-2  SB push bar (F120) inspection report no. 2100051097
DIN EN 1363-1

 SB sliding carriage (F120) inspection report no. 2100051094


 PDH-K pendulum hangers (F120) inspection report no.
2100051096

Download for free at www.fischer.de

Fire inspection before. Fire inspection after.


Productfioverview
scher with proof in
inspection reports and
installation advisory
systems:
opinions.
fire protection classification.
-
R30 - F30 - R30 - F30 -
Picture Product Verifications
Document no. MLAR Picture Product Document no. MLAR
R120 F120 R120 F120
 Fireproof ins t allations for individual pipes and pipe routes of R30 – R120 and F30 – F120.
 P roofLeipzig
MFPA of co–mpliance with the criteria according ML AR (GMFPA
ermaLeipzig
n s t a–ndard pipe sys tem directive
FRS-L
FLS 37 for installation in escape
GS 3.2/15-  and rescue routes. GS 3.2/15-  
Universal
141-4 141-3

 Fire protection – protection goals:  Fire inspection reports for the installation
pipe clamps and channels:
Firstly,MFPA
fire protection
Leipzig – serves to protect people and is regulated by The fire safety
MFPA inspection
Leipzig – reports described in this broc
FUS 41 GS 3.2/14-
the building   countries (or regional states).
laws in the respective FRS the require
GS 3.2/14-   according to the bu
ments for fire protection
175-4
Secondly, fire protection serves to protect property. This is regulated 175-2
tions of the countries and, especially for Germany, acco
by the insurance associations, such as VdS and FM. These require- nationwide homonymic German pipe systems directive
ments partially go beyond the building legislation. This is particularly on the standard pipe systems directive of 2005 (MLAR
evident in the installation of fire protection systems, such as sprink- Personal protection is defined in the MLAR Directive th
MFPA Leipzig –
lers, etc.. In these cases approved or recognised components must MPA-NRW
rules for –
escape routes, such as corridors,
FUS 62 GS 3.2/14-   SB  stairwells, ha
be used (see the fischer catalogues for further details on this). 210005109-7
175-4 between stairwells and the exit. The key message is to
safety of the escape route by ensuring the functioning

a c c o rd i n g to M L A R i s re q u i re d b e t w e e n i n s t a l l a t i o n s a n
MFPA Leipzig – lying suspended
MPA-NRW –fire-proof F30 sub-ceilings (fire resista
ALK 37 GS 3.2/15-   SBS  
minutes). Based on the fire
210005109-4 inspections, load informatio
141-4
sistance of 30 minutes was determined in relation to th
Reduction factors kθ p e r m i s s i b l e d e fo r m a t i o n o f c h a n n e l s o r p i p e c l a m p s . T h
1.0 for these considerations arises from the properties of s
0.9 MFPA Leipzig – Yield strength s u b j e c t e d to a t e m p e r a t u re o f > 8 0 0 ° C a c c o rd i n g to t h
MPA-NRW –
FCA 41 0.8 GS 3.2/14-   kγ,θ = fγ,θ / fγ PDH-Ktemperature curve (ISO curve).  
210005109-6
0.7 175-4 Additionally, the same information is documented in inspe
0.6 Elasticity module for a fire resistance rating of R30, R60, R90 and R120
0.5 kΕ,θ = Εа,θ / Εа according to EN1363-1 and DIN4102-2 (see load tables)
0.4
0.3 MFPA Leipzig –  Fire inspection reports for installation syst
FCA 62 0.2 GS 3.2/14-  
Proportional limit pipe clamps, sliding elements, channel and
175-4 k =f /f
0.1 ρ,θ ρ,θ ρ
arm:
0.0
0 200 400 600 800 1000 1200 Following “supplementary sheets to inspection reports
Steel temperature [°C] Braunschweig are available:

Dependency of the yield strength, proportional limit and elasticity module  FRS (Document no. GS 3.2/14-175-2)
on the temperature (basis: EN1993-1-2:2012-12 Eurocode 3).

 F R S - L U n i ve r s a l ( D o c u m e n t n o . G S 3 . 2 / 1 5 - 1 4 1 - 3 )
 FLS / ALK (Document no. GS 3.2/15-141-4)

Additional available “fire inspection reports” from MPA


Test preparation to the above criteria are:
 SB push bar (F120) inspection report no. 21000510
 SB sliding carriage (F120) inspection report no. 210
 PDH-K pendulum hangers (F120) inspection report n
2100051096

fischer channel washer Connection ceiling fischer FCN Clix M CombinationDownload


with fischer
for free channel
at www.fi washer
scher.de
HK 41 (≧ 10,5mm) or fischer anchor and or FSM Clix M FCN Clix P or HK 41 (≧ 10,5mm) or
HK 31 (≧ 8,5mm) fiFire
scher channel
inspection washer
before. (M8Fire
andinspection
M10) after. FSM Clix P and HK HK 31 (≧ 8,5mm)
HK 41 (≧ 10.5mm) or (M8 or M10)
HK 31 (≧ 8.5mm)
fischerProduct overview with proof in
Loadinstallation
tablesinspection reports and advisory
systems:
based onprotection
fire the advisory
opinions. opinions.
classification.
-
FRS-F pipe clamps –Verifi
loadcations
table based on the advisory opinion no. GS 3.2/14-175-2 R30 - F30 - R30 -
Picture Product Document no. MLAR Picture Product Document no. MLAR
MLAR Maximum loads
R120 F120 R120 F
 Fireproof ins t allations for individual pipes and pipe routes of R30 – R120 and F30 – F120.
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute]
Clamping range ha Proomin
f oaf complia30
nce with thmin
e cariteria MFPA
a30ccoLeipzig
rd60
ing –M90
L AR (G erman s t andard pipe sys tem directivMFPA
120 e) Leipzig –
for installation in FRS-L
[mm] [mm] [mm] [kN]escape and rescue
FLS
[mm] 37 routes.
GS
[kN]3.2/15-
[kN] [kN] 
[kN] GS 3.2/15-  
Universal
≤ 250 ≤ 50 0,56 51 141-4 141-3
≤ 500 ≤ 50 0,56 54
f 12 – 67 0,56 0,29 0,20 0,15inspection reports for the installation of
≤750Fire protection
≤ 50 – protection
0,56 goals:
57  Fire
≤ 1000 ≤ 50 0,51 60 pipe clamps and channels:
ure meet ≤Firstly,
250 fire protection
≤ 50 0,65
serves to protect people50 and is regulated by
MFPA Leipzig – The fire safety inspection reports described in this brochure meet –
MFPA Leipzig
≤ 500 ≤ 50 0,62 53
ding72 – 92
regula- the building laws in the respective countries (or41
FUS regional
GSstates).
0,79 0,49 0,36
3.2/14- 0,29
 require
the  ments for fire protection according FRS to the building
GS 3.2/14-
regula-  
≤ 750 ≤ 50 0,59 56
ding to the Secondly, fire protection serves to protect property. 175-4
This is regulated tions of the countries and, especially for Germany, 175-2 to the
according
≤ 1000 ≤ 50 0,57 59
LAR), based ≤by
250the insurance
≤ 50 associations,
0,48 such as VdS61 and FM. These require- nationwide homonymic German pipe systems directive (LAR), based
2005). ≤m500
ents partia≤ll50
y go beyond0,43
the building legi64 slation. This0,63
is parti0,39
cularly 0,29
on the standard pipe systems directive of 2005 (MLAR 2005).
108 – 116 0,23
ugh clear ≤e750
vident in th≤e50 0,39
installation o f fire protection 66systems, such as sprink- Personal protection is defined in the MLAR Directive through clear
≤ 1000 ≤ 50 0,35 69 MFPA Leipzig –
ways lers, etc.. In these
≤ 250 ≤ 50
cases approved
0,96
or recognised
61
components must rules for escape routes, such as corridors, stairwells, MPA-NRW –
hallways
FUS 62 GS 3.2/14-   SB
nsure the be
≤ 500used (see the
≤ 50 fi scher catalogues
0,89 for further
63 details on this). between stairwells and the exit. The key message is 210005109-7
to ensure the
121 – 168 175-4 0,51 0,34 0,25
1,00
the fire- ≤ 750 ≤ 50 0,82 66 safety of the escape route by ensuring the functioning of the fire-
≤ 1000 ≤ 50 0,75 69
This
unddata
er- are valid for all FRS pipe clamps, galvanized, hdg and stainless steel. a c c o rd i n g to M L A R i s re q u i re d b e t w e e n i n s t a l l a t i o n s a n d u n d e r -
e of 30 MFPA Leipzig – lying suspended fire-proof F30 sub-ceilings (fire resistance of 30
Pipe clamp FRS-L Universal - load table based on the advisory opinion MPA-NRW –
for a fire re- ALK 37no. GS
GS3.2/15-141-3
3.2/15- 
minutes).  Based on the fire inspections, load SBS information for a fire re- 
210005109-4
MLAR 141-4 loads
Maximum
maximum sistance of 30 minutes was determined in relation to the maximum
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute]
necessity p e r m i s s i b l e d e fo r m a t i o n o f c h a n n e l s o r p i p e c l a m p s . T h e n e c e s s i t y
Clamping range ha Reduction
minfactors
a kθ 30 min a 30 60 90 120
el, which is 1.0 for these considerations arises from the properties of steel, which is
[mm] [mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN]
s t a n d a rd 0.9 s u b j e c t e d to a t e m p e r a t u re o f > 8 0 0 ° C a c c o rd i n g to t h e s t a n d a rd
≤ 250 ≤ 50 0,27 Yield54
strength MFPA Leipzig –
= fγ,θ 41
kγ,θ 57 / fγ temperature curve (ISO curve). MPA-NRW –
≤ 500
0.8 ≤ 50 0,26 FCA GS 3.2/14-   PDH-K 
210005109-6
on r8
ep- o37
rts ≤ 750
0.7 ≤ 50 0,24 60
0,27 0,14 0,09 0,07
175-4 Additionally, the same information is documented in inspection reports
≤ 1000
0.6 ≤ 50 0,22 62
Elasticity module for a fire resistance rating of R30, R60, R90 and R120
≤ 250 ≤ 50 0,17 72
kΕ,θ = Εа,θ / Εа
0.5 according to EN1363-1 and DIN4102-2 (see load tables).
≤ 500 ≤ 50 0,16 75
38 - 66 0.4 0,29 0,14 0,09 0,06
≤ 750 ≤ 50 0,15 78 Pict. 1
ms - 0.3 MFPA Leipzig –  Fire inspection reports for installation systems -
≤ 1000 ≤ 50 0,13 80
0.2 FCA 62 GS 3.2/14-  
cantilever ≤ 250 Proportional limit
≤ 50 0,53 75
175-4 pipe clamps, sliding elements, channel and cantilever
≤ 500
0.1 ≤ 50kρ,θ = fρ,θ / f0,53
ρ 78
67 - 119 0,53 0,35 0,27 arm: 0,22
≤ 750
0.0 ≤ 50 0,53 81
rom MPA ≤ 1000 0 ≤ 50200 4000,53 600 83
800 1000 1200 Following “supplementary sheets to inspection reports” from MPA
This data are valid for all for all FRS-L Universal pipe clamps, galvanized, hdg and stainless steel.
Steel temperature [°C] Braunschweig are available:

Dependency of the yield strength, proportional limit and elasticity module  FRS (Document no. GS 3.2/14-175-2)
on the temperature (basis: EN1993-1-2:2012-12 Eurocode 3). Pict. 2
MLAR - loads Max. Loads

Threaded rods ≥ 4.8 strain F-resistance Max. strain  F R S - L U n i ve r s a l ( D o c u m e n t n o . G S 3 . 2 / 1 5 - 1 4 1 - 3 )
Fire resistance time [minute]
ls min a 30 min a 30 60 90 FLS120 / ALK (Document no. GS 3.2/15-141-4)
Load case
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN]
≤ 400 1) ≤ 50 0,24 93 0,24 0,13 0,10 0,09
RW, similar Additional available “fire inspection reports” from MPA NRW, similar
Point load ≤ 400 2) ≤ 50 0,09 389 0,47 0,38 0,33 0,30
≤ 400Test
4) preparation
≤ 50 0,32 226 1,33 0,78 to the
0,53 above criteria are:
0,40
7 ≤ 400 1) ≤ 50 0,72 93 0,72 0,38 0,30
 SB0,27
push bar (F120) inspePict.
ctio3n report no. 2100051097
multiple
051load
094 3) ≤ 400 2) ≤ 50 0,26 289 1,42 1,13 0,99 0,90
 SB sliding carriage (F120) inspection report no. 2100051094
≤ 400 4) ≤ 50 0,81 226 1,33 0,78 0,53 0,40
.  PDH-K
Uniformly ≤ 400 1) ≤ 50 0,72 93 0,72 0,38 0,30 0,27 pendulum hangers (F120) inspection report no.
distributed ≤ 400 2) ≤ 50 0,35 308 1,37 1,19 1,06 21 00051096
0,95
load ≤ 50 0,81 226 1,33 0,78 0,53 0,40
fischer
These data are valid for all for FLS channels and channelarms,
ALK cantilever washer
galvanized, Connection ceiling
hdg and stainless steel. fischer
Download forFCN
freeClix M
at www.fi Combination with
scher.de fischer channel was
1) HK 412(≧ 10,5mm) or
Valid for a suspension height ha = 0 mm, s. picture fischer anchor and or FSM Clix M FCN Clix P or HK 41 (≧ 10,5mm)
2) Valid for a suspension height ha = 500mm, s. picture 1 (Expansion length of threaded rods in case of fire ~ 10mm/m)
3) Fire inspection HK
before. 31 (≧ 8,5mm)Fire inspection fi scher
after.
Given load values apply for multiple loads as summated point loads symmetrical allocated.channel washer (M8 and M10) FSM Clix P and HK HK 31 (≧ 8,5mm)
4) This values are valid for ALK 37-450 with additional support by threaded rod, s.HK 41 3(≧(ha
picture 10.5mm) or
= 500 mm). (M8 or M10)
HK 31 (≧ 8.5mm)
Product overview with proof in
Load tables
inspection reports and advisory Loa
based on the advisory opinions.
opinions. ba
0- R30 - F30
FRS-F pipe clamps – load table based on the advisory -
opinion no. GS 3.2/14-175-2 R30 - F30 - FRS-F pi
20 Picture Product Document no. MLAR Picture Product Document no. MLAR
R120 F120 R120 F120
MLAR Maximum loads
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute] Threa
Clamping range ha MFPAmin a
Leipzig – 30 min a 30 60 90 120
MFPA Leipzig – Clamping r
FRS-L
[mm] FLS 37
[mm] GS 3.2/15-
[mm] [kN]  [mm] [kN] [kN] [kN] GS 3.2/15-
[kN]   [mm]
Universal
≤ 250 141-4≤ 50 0,56 51 141-3
≤ 500 ≤ 50 0,56 54
12 – 67 0,56 0,29 0,20 0,15 12 – 6
≤ 750 ≤ 50 0,56 57
≤ 1000 ≤ 50 0,51 60
≤ 250 ≤ 50 0,65 50
MFPA Leipzig – MFPA Leipzig –
≤ 500 ≤ 50 0,62 53
72 – 92 FUS 41 GS 3.2/14-   0,79 0,49 FRS
0,36 GS 3.2/14-
0,29   72 – 9
≤ 750 ≤ 50 0,59 56
175-4 175-2
≤ 1000 ≤ 50 0,57 59
≤ 250 ≤ 50 0,48 61
≤ 500 ≤ 50 0,43 64
108 – 116 0,63 0,39 0,29 0,23 108 – 1
≤ 750 ≤ 50 0,39 66
≤ 1000 MFPA≤Leipzig
50 – 0,35 69
MPA-NRW –
FUS≤62250 ≤ 50
GS 3.2/14- 0,96 
 61 SB 
210005109-7
≤ 500 175-4≤ 50 0,89 63
121 – 168 1,00 0,51 0,34 0,25 121 – 1
≤ 750 ≤ 50 0,82 66
≤ 1000 ≤ 50 0,75 69
This data are valid for all FRS pipe clamps, galvanized, hdg and stainless steel. This data a
MFPA Leipzig –
Pipe clamp FRS-L Universal - load table basedon the MPA-NRW –
ALK 37 GS 3.2/15-  advisory opinion no. GS 3.2/15-141-3
SBS   Pipe clam
210005109-4
141-4 MLAR Maximum loads
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute] Threa
Clamping range ha min a 30 min a 30 60 90 120 Clamping r
[mm] [mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN] [mm]
≤ 250 MFPA≤Leipzig
50 – 0,27 54 MPA-NRW –
FCA≤41500 GS 3.2/14-
≤ 50 
0,26  57 PDH-K  
8 - 37 0,27 0,14 0,09 210005109-6
0,07 8 - 37
≤ 750 175-4≤ 50 0,24 60
≤ 1000 ≤ 50 0,22 62
≤ 250 ≤ 50 0,17 72
≤ 500 ≤ 50 0,16 75
38 - 66 0,29 0,14 0,09 0,06 38 - 6
≤ 750 ≤ 50 0,15 78 Pict. 1
MFPA Leipzig –
≤ 1000 ≤ 50 0,13 80
FCA 62 GS 3.2/14-  
≤ 250 ≤ 50 0,53 75
175-4
≤ 500 ≤ 50 0,53 78
67 - 119 0,53 0,35 0,27 0,22 67 - 11
≤ 750 ≤ 50 0,53 81
≤ 1000 ≤ 50 0,53 83
This data are valid for all for all FRS-L Universal pipe clamps, galvanized, hdg and stainless steel. This data a

Pict. 2
MLAR - loads Max. Loads
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute] Threa
ls min a 30 min a 30 60 90 120
Load case Load ca
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN]
≤ 400 1) ≤ 50 0,24 93 0,24 0,13 0,10 0,09
Point load ≤ 400 2) ≤ 50 0,09 389 0,47 0,38 0,33 0,30 Point lo
≤ 400 4) ≤ 50 0,32 226 1,33 0,78 0,53 0,40
≤ 400 1) ≤ 50 0,72 93 0,72 0,38 0,30 0,27 Pict. 3
multiple multip
≤ 400 2) ≤ 50 0,26 289 1,42 1,13 0,99 0,90
load 3) load 3
≤ 400 4) ≤ 50 0,81 226 1,33 0,78 0,53 0,40
Uniformly ≤ 400 1) ≤ 50 0,72 93 0,72 0,38 0,30 0,27 Uniform
distributed ≤ 400 2) ≤ 50 0,35 308 1,37 1,19 1,06 0,95 distribut
load ≤ 50 0,81 226 1,33 0,78 0,53 0,40 load
er fischer channel washer
These data are valid for Connection ceiling
all for FLS channels fischer
and ALK cantilever FCN
arms, galvanized, Combination
Clix M hdg and stainless steel. with fischer channel washer These data
HK 41 (≧ 10,5mm)
1) Valid for aor
suspensionfiheight
scherha anchor
= 0 mm,and
s. picture 2 or FSM Clix M FCN Clix P or HK 41 (≧ 10,5mm) or 1) Valid for
2) Valid for a suspension height ha = 500mm, s. picture 1 (Expansion length of threaded rods in case of fire ~ 10mm/m) 2) Valid for
HK 31 (≧ 8,5mm)
3) Given load values apply fischer channel washer (M8 and M10)
for multiple loads as summated point loads symmetrical allocated.
FSM Clix P and HK HK 31 (≧ 8,5mm) 3) Given loa
4) This values are valid forHKALK 4137-450
(≧ 10.5mm) or
with additional support by threaded rod, s. picture 3 (ha(M8 ormm).
= 500 M10) 4) This valu
HK 31 (≧ 8.5mm)
ad tables
Load tables
sed on based
the advisory
on the opinions.
advisory opinions.
clamps – load table based on the advisory opinion no. GS 3.2/14-175-2 Pict.
1
MLAR Maximum loads
d rods ≥ 4.8 strain FUS / FCA 41/2,5 (picture1-3)
F-resistance Max. strain MLAR - loads
Fire resistance time [minute] Max. Loads
ge ha min a Threaded30 rods ≥ 4.8 minstrain
a 30F-resistance
60 90Max. strain
120 Fire resistance time [minute]
ls min a 1) 30 min a 2) 30 60 90 120
[mm] [mm] Load case[kN] [mm] [kN] [kN] [kN] [kN]
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN]
≤ 250 ≤ 50 0,56 51
≤ 400 ≤ 50 0,90 278 2,40 1,33 0,92 0,72
≤ 500 ≤ 50 Point load0,56 54
≤ 700 ≤ 50 0,56 - 0,29 0,20 320 0,15 1,61 1,04 0,80 0,67
≤ 750 ≤ 50 0,56 57
multiple ≤ 400 ≤ 50 0,90 278 2,40 1,33 0,92 0,72
≤ 1000 ≤ 50 0,51 60
load 3) ≤ 700 ≤ 50 - 320 1,61 1,04 0,80 0,67
≤ 250 ≤ 50 0,65 50
Uniformly ≤ 400 ≤ 50 1,50 258 3,00 2,10 1,41 1,06
≤ 500 ≤ 50 0,62 53 Pict.
distributed ≤ 700 ≤ 50 0,79 0,60 0,49 0,36 2990,29 2,44 1,57 1,21 1,00
≤ 750 ≤ 50 0,59 56 2
load ≤ 1250 ≤ 50 - 468 3,29 1,81 1,27 0,98
≤ 1000 ≤ 50 0,57 59
FUS / FCA 62/2,5 (Pict. 1–3) MLAR Max. Loads
≤ 250 ≤ 50 0,48 61
Threaded rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute]
≤ 500 ≤ 50 0,43 64
6 ls min a1) 0,63 300,39 0,29min 0,23 a2) 30 60 90 120
≤ 750 ≤ 50 Load case0,39 66
[mm] [mm] [kN] [mm] [kN] [kN] [kN] [kN]
≤ 1000 ≤ 50 0,35 69
≤ 400 ≤ 50 1,76 25 1,76 1,06 0,78 0,62
≤ 250 ≤ 50 Point load0,96 61
≤ 1000 ≤ 50 - 460 2,27 1,31 0,93 0,72 Pict.
≤ 500 ≤ 50 0,89 63
8 ≤ 400 ≤ 50 1,00 1,76 0,51 0,34 250,25 1,76 1,06 0,78 0,62 3
≤ 750 ≤ 50 multiple0,82 66
≤ 9604) ≤ 50 4,30 550 4,30 2,14 1,39 1,01
≤ 1000 ≤ 50 load 3) 0,75 69
≤ 1000 ≤ 50 0,55 661 2,52 1,60 1,21 0,99
valid for all FRS pipe clamps, galvanized, hdg and stainless steel.
≤ 400 ≤ 50 1,76 25 1,76 1,06 0,78 0,62
Uniformly
≤ 9604) ≤ 50 4,30 550 4,30 2,14 1,39 1,01
distributed
FRS-L Universal - load table based on the advisory opinion
≤ 1000 ≤ 50 no. GS 3.2/15-141-3
0,55 661 2,52 1,60 1,21 0,99
load
MLAR ≤ 50 Maximum 0,50 loads 592 2,41 1,65 1,31 1,11
FUS 62/2,5 (picture 4) MLAR - loads Max. Loads
d rods ≥ 4.8 strain F-resistance Max. strain Fire resistance time [minute]
Vertical FUS 41/2,5 strain F-resistance Max. strain Fire resistance time [minute]
ge ha min a 30 min a 1) 30 60 90 120
ls min a 30 min a2) 30 60 90 120
[mm] [mm] Load case[kN] [mm] [mm][mm] [kN] [kN][kN] [kN] [mm][kN] [kN] [kN] [kN] [kN] Pict.
≤ 250 ≤ 50 Point load 0,27 ≤ 1000 54≤ 50 0,57 369 1,33 0,87 0,68 0,57 4
≤ 500 ≤ 50 multiple0,26 57
0,27 0,14 0,09 0,07
≤ 750 ≤ 50 load 3) 0,24 ≤ 1000 60≤ 50 0,62 649 1,92 1,34 1,08 0,92
≤ 1000 ≤ 50Uniformly dis-0,22 62
≤ 250 ≤ 50tributed load 0,17 ≤ 1000 72≤ 50 0,62 649 1,92 1,34 1,08 0,92
≤ 500 ≤ 50The following 0,16
figures are valid for75
FUS channels and FCA cantilever arms, galvanized, hdg and stainless steel.
0,29 0,14 0,09 0,06
≤ 750 ≤ 501) Valid for a0,15
suspension height ha 78≤ 500 mm Pict. 1
≤ 1000 ≤ 502) Based on suspension
0,13 height ha80 = 250mm, Expansion length of threaded rods in case of fire ~ 10mm/m
3) Given load values apply for multiple loads as summated point loads symmetrical allocated.
≤ 250 ≤ 50 0,53 75
4) This values are valid for FCA 62/2,5 with additional support by threaded rod.
≤ 500 ≤ 50 0,53 78
0,53 0,35 0,27 0,22
≤ 750 ≤ 50 0,53 81
≤ 1000 ≤ 50 0,53 83
valid for all for all FRS-L Universal pipe clamps, galvanized, hdg and stainless steel.

Application possibilities
Pict. 2
MLAR - loads Max. Loads
d rods ≥ 4.8 strain
Point load =
F-resistance Max. strain
Multiple load =
Fire resistance time [minute]
Uniformly distributed load =
ls min a Spot load,
30 min a 30 60 More90 than120one load Uniform distribution of load
[mm] [mm] e.g. a[kN]
pipe clamp [mm] [kN] [kN] point[kN] on the
[kN]rail, e.g. on the rails, e.g. bend-proof
≤ 400 1) ≤ 50 on the rail.
0,24 93 0,24 0,13 several
0,10 pipe clamps.
0,09 ventilation duct.
≤ 400 2) ≤ 50 0,09 389 0,47 0,38 0,33 0,30
≤ 400 4) ≤ 50 0,32 226 1,33 0,78 0,53 0,40
≤ 400 1) ≤ 50 0,72 93 0,72 0,38 0,30 0,27 Pict. 3 F = q xl
≤ 400 2) ≤ 50 0,26 289 1,42 1,13 0,99 0,90
Strichstärke 1
≤ 400 4) ≤ 50 0,81 226 1,33 0,78 0,53 0,40
≤ 400 1) ≤ 50 0,72 93 0,72 0,38 0,30 0,27
d ≤ 400 2) ≤ 50 0,35 308 1,37 1,19 1,06 0,95
≤ 50 0,81 226 1,33 0,78 0,53 0,40
e valid for all for FLS channels and ALK cantilever arms, galvanized, hdg and stainless steel.
suspension height ha = 0 mm, s. picture 2
suspension height ha = 500mm, s. picture 1 (Expansion length of threaded rods in case of fire ~ 10mm/m)
values apply for multiple loads as summated point loads symmetrical allocated. F = q xl
are valid for ALK 37-450 with additional support by threaded rod, s. picture 3 (ha = 500 mm).
Strichstärke 1,25
fischer FIXPERIENCE.
The design and information software suite.
 The modular design program includes engineering software and
REBAR
FIX
-
application modules.
RAIL-
FIX C-  The software is based on international design standards (ETAG 001 and
FIX
EC2, such as EC1, EC3 and EC5), including the national application docu-
LL -
INSTA
FIX ments. All common force and measurement units are available.
R-
MORTA
CE
FIX  Incorrect input will be recognized and the software gives tips to get a
ERIEN
-
WOOD
FIX FIXP correct result. This ensures a safe and reliable design every time.
 The graphical display can easily be rotated through 360°, panned, tilted
or zoomed as required.
 The 3D display gives a detailed and realistic image.
 The “live update” feature helps to keep the program up to date ensuring
you are always working with the latest version.
 Free download and updates at www.fischer.de/fixperience-en

Our service to you.


We are available to you at any time as a reliable partner to offer technical
support and advice:
 Our products range from chemical resin systems to steel anchors through
to nylon anchors.
 Competence and innovation through own research, development and
production.
 Global presence and active sales service in over 100 countries.
 Qualified technical consulting for economical and compliant fastening
solutions. Also on-site at the construction site if requested.
 Training sessions, some with accreditation, at your premises or at the
fischer ACADEMY.
 Design and construction software for demanding applications.

Regional Presence

U.A.E
State of Qatar Kingdom of Bahrain
fischer FZE (Regional Office) Tel: +974 4036 3100 Tel: +973 17408090
R/A 07, BA 01 - 04 Fax: +974 4471 0898 Fax: +973 17404323
Jebel Ali Free Zone Email: qatar@fischer.ae Email: bahrain@fischer.ae
Dubai, UAE
P. O. Box 261738 Kingdom of Saudi Arabia Sultanate of Oman
Tel: +971 4 883 7477 Tel: +966 13 8140866 Tel: +968 24445425/26/27/28/30
Fax: +971 4 883 7476 Fax: +966 13 8140855 Fax: +968 24445423
Email: enquiry@fischer.ae Email: saudi@fischer.ae Email: oman@fischer.ae

State of Kuwait Pakistan


Abu Dhabi Tel: +965 2481 8786, Tel: +923 01 8266216
Tel: +971 2 552 5777 +965 2482 5972 Email: pakistan@fischer.ae
Fax: +971 2 552 6566 Fax: +965 2481 8385
Email: enquiry@fischer.ae Email: kuwait@fischer.ae

Follow us:
www.fischer.ae

Potrebbero piacerti anche