DATE 4/30/2020 Day Shift Eng. Eng. M. Saied Night Shift Eng. Eng.

Ahmed Samir

Number of Number of Engineers Working


Location Job Activity / Task Description Job Type Starting Hour Ending Hours Engineers Tech. Hours
Tech. Working Hours Job Status Shift

1 MCB Normal Normal DAY

2 SS01 PM-1505B, PM-1506A, PM-1507A ---> Grease Motors CM 11:00 AM 1:00 PM 1 2 1 2 Finished DAY

3 SS01 TR-S1-03-01A, TR-S1-04-01A, TR-S1-04-02A, TR-S1-04-03A ---> Transformers Visual Inspection PM 10:00 AM 11:00 AM 1 1 1 1 Finished DAY

4 SS02 Normal DAY

install the new cable of the coke elevator after connecting the adjusted iron beam by static dep. and
adjust the new cable inside the cable roller
then test the elevator and found not ready because of land floor emergency switch and after check
5 SS03 found pit area emergency switch activated may be activated by lifting team within connecting the iron
CM 8:00 AM 6:00 PM 2 4 20 40 Finished DAY
beam so deactivated this switch and try the elevator at different level was ok and inspect the cable
roller found also ok and now in service

6 SS04 DAY

VFD-X3901-XM-01B1---> Reset the VFD, Operation checked the basin, didn't find sludge, and re-
7 SS05 flushed it CM 12:00 PM 2:00 PM 1 2 2 4 Follow Up DAY
Mech. team Checked the Mixer and Dehyd. And Found them normal too
8 RD Normal Finished DAY
9 SS06 DAY

10 LAB DAY

11 3 Bld sucking water under substation with submersible pump DAY

14

15 MCB Normal

16 SS01 Normal

17 EDG Normal

18 SS02 Tripping As A no of Start 66N X-8002-AM01

19 SS03

20 SS04 33KV BPT A Reading 32.625,31.610,33,427 KV

VFD-X3901-XM-01B1 Smooth Stopping without any Trip and current waveform is Normal during
Stopping

Noticed Voltage and Speed are Decreasing Smoothly and Stopping Done without any Problem
So After Flashing the Operation for Strating and Stopping for VFD is highly Smoothed
21 SS05
as may Be there was contaimented sludge during stopping as during stopping operation there is
Flashing valve is opened during stopping for about 5 min then main drive VFD-X3901-XM-01B1 Stop
So if the Flashing Operation is Not completed or Heavy Sludge Avaliable or malefunction it may cause
Same problem During Stopping

22 SS05 Tripping As A no of Start 66N X-3901-BLM02D , X-3901-BLM02D-2

22 RD Normal

23 SS06 Normal

24 LAB Normal

25 3 Bld Not visited

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48