Auto source change over with current limiter- ACCL

ACCL for Single phase and three phase application

FEATURES:
n While monitoring the Mains supply, it allows full load current.
n While monitoring the Generator supply, Allows only limited load and functions
as load limiter as per desired power and current.
n Current sealing (while monitoring the Generator) will be preset at factory.
n Whenever the load current exceeds the preset limit ,power is automatically
switched off instantaneously and reset automatically after 9 seconds and trips
again if the over load still exists, this cycle is(3Sec ON & 6Sec OFF) is
repeated every 9 seconds .ACCL enters Lock Out mode after five ON & OFF
cycles if over loading of the DG persists . The unit can be reset by switching
off the supply to the ACCL. However tailor made units i.e. field adaptable and
made as per customer requirements it is a micro controller based product.
n Display of each phase Voltages, Currents and power ( In three phase ACCL)
n Over voltage and Under Voltage cut off for both EB/DG(In three phase ACCL)
n On resumption of the mains supply it automatically changes over, and full load
can be drawn.

BENEFITS:
n Microprocessor based, hence precise and accurate.
n It measures the load current at which cut- off should take place .
n Over voltage & Under voltage cut off for EB & DG
n Simplifies electrical complexity
n Significant saving on wall space & wiring.
n Product guaranteed for 2 years
n In the event of change over from DG to EB the phase is first isolated, then the neutral is disconnected (Single
Phase ACCL)
n Tropicalized and rugged design.
n Three phase ACCL are enclosed in aesthetically made powder coated sheet metal enclosures.
n Single phase ACCL are enclosed ABS grade thermoplastic.
n LED indication of all operational status
n 2 line 16 character LCD display with back lit, displaying voltage, current
and power while monitoring the DG. (Three Phase ACCL)
n Mechanical inter lock between contactors in three phase models.
n Wiring connections- using insulated feed through terminal blocks.
If load current exceeds the rated current of contactor ACCL trips.

SPECIFICATIONS:
Single Phase ACCL.
n EB input: 220V AC 50Hz
n DG input: 220V AC 50Hz
n Red LED ON : load on EB
n Green LED ON; load on DG
n Green LED blinks: DG ON, load on EB
n Green LED turns Red: ACCL in lockout mode
n Relay Contact rating: 250V AC, 30

28 E-mail: prokdvs@blr.vsnl.net.in
Auto source change over with current limiter- ACCL
ACCL for Single phase and three phase application
SPECIFICATIONS:
Three Phase ACCL.
n EB input: 415V AC 50Hz 3ph 4wire
n DG input: 415V AC 50Hz 3ph 4wire
n LCD display : 2Line 16 character backlit LCD display
n LED (R,Y&B): Indicates presence of EB/DG
n Contactor rating: Depending on the model
SPECIFICATIONS:
SINGLE PHASE MODEL EB MAXIMUM LOAD CURRENT DG MAXIMUM LOAD CURRENT MOUNTING DIMENSION (mm)
ACCL 1 PHASE EB 1PHASE EG 30 AMPS 0.5-20 AMPS DIN 70X105X60
USER DEFINED
FACTORY SET
THREE PHASE MODELS EB LOAD DG LOAD
MAXIMUM PER PHASE MAXIMUM PER PHASE
AC1 DUTY
CONTRACTOR RATING
ACCL 3 PHASE EB 3 PHASE-DG 20 AMPS / PHASE 0-18 AMPS/PHASE SURFACE 153X137X200
4 WIRE 4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 3 PHASE DG 25 AMPS / PHASE 0-22 AMPS/PHASE SURFACE 153X137X200
4 WIRE 4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 3 PHASE DG 32 AMPS / PHASE 0-30 AMPS/PHASE SURFACE 153X137X200
4 WIRE 4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 3 PHASE DG 40 AMPS / PHASE 0-36 AMPS/PHASE SURFACE 153X137X200
4 WIRE 4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 3 PHASE DG 63 AMPS / PHASE 0-60 AMPS/PHASE SURFACE 280X175X193
4 WIRE 4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 1 PHASE DG 20 AMPS / PHASE 0-18 AMPS/PHASE SURFACE 153X137X200
4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 1 PHASE DG 25 AMPS / PHASE 0-22 AMPS/PHASE SURFACE 153X137X200
4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 1 PHASE DG 32 AMPS / PHASE 0-30 AMPS/PHASE SURFACE 153X137X200
4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 1 PHASE DG 40 AMPS / PHASE 0-36 AMPS/PHASE SURFACE 153X137X200
4 WIRE USER DEFINED
FACTORY SET
ACCL 3 PHASE EB 1 PHASE DG 63 AMPS / PHASE 0-60 AMPS/PHASE SURFACE 280X175X193
4 WIRE USER DEFINED
FACTORY SET
ALL 3 PHASE MODELS WITH DISPLAY 3 VOLTAGES, 3 CURRENTS & FREQUENCY IN EB & DG PRESENT THROUGH LCDS & TRIP INDICATION THROUGH LED &
MAGNITUDE ON LCD DISPLAY
Optional
1. InACCL 3 Phase 4 wire EB & 3 Phase 4 wire DG, accl isAvailable and also can be tailored to the customer specifications like, current setting on TheACCL DG only can be set
for arithmetic/cumulative sum of currents can be programmed based on the requirement and specific needs
2. OnlyACCL Module can be supplied base on the clients specification and request for higher current rating i.e. With out contactors, bus bars and CTs
3. EB Current Limiting is also possible as per client/customer needs.

http: www.prokdvs.com 29
MOUNTING: FLUSH
For : NUMERICAL OVER CURRENT & EARTH FAULT RELAY PNA Series

MOUNTING: FLUSH
For : NUMERICAL OVER VOLTAGE & UNDER VOLTAGE RELAY PNV NSP Series

For : AUTO SOURCE CHANGE OVER CUM CURRENT LIMITER [ ACCL ]