.1 General 23.1.1 Water chemistry of boiler feed water during normal
operation of the plant shall be maintained using combined water treatment (CWT) comprising of oxygen dosing and ammonia dosing in the condensate and feed water as per the guidelines of EPRI, USA/ VGB, Germany/ CEGB, UK/ relevant Japanese standard. The parameters of feed water proposed to be maintained in case of CWT are as below: i) Cation conductivity : ≤ 0.15 micro siemens/ cm ii) Hydrazine : Nil iii) pH value (250 C) : 8- 9.3 iv) Oxygen : 20- 200 ppb v) Iron : ≤ 5 ppb vi) Silica : ≤ 10 ppb
During startup or chemistry excursions, all volatile type of treatment (AVT)
using ammonia and hydrazine dosing shall be used. The following parameters shall be maintained in case of AVT: i) Cation conductivity : ≤ 0.25 micro siemens/ cm ii) Hydrazine : 10-15 ppb iii) pH value (250 C) : 9.0- 9.6 iv) Oxygen : ≤ 7 ppb v) Iron : ≤10 ppb vi) Silica : < 10 ppb The concentration of sodium and chloride in the condensate at the outlet of CPU shall be considered as 2 ppb each under normal operating conditions. During start-up condition, the sodium and chloride content at the outlet of CPU shall be considered as ≤ 5 and ≤ 10 ppb respectively. Oxygen Dosing System Oxygen shall be dosed in the condensate and in feed water circuit of each unit i.e. at outlet of condensate polishing unit and at the outlet of deaerator (suction line of boiler feed water pumps). Oxygen dosing at additional points shall also be provided, if required, as per manufacturer's standard practice. Standard Technical Features of BTG System for Supercritical 660/800 MW Thermal Units The dosing system shall be provided with set of oxygen cylinders alongwith required cylinder isolation/ check valves, cylinder manifolds, isolation valves in the common manifold, piping from manifold, dosing (automatic type) valves, check (non-return type) valves, associated control system and instruments etc. The dosing rate of oxygen shall be regulated automatically by control system based on the quality of condensate water and quality of feed water as the case may be. For each dosing location, system shall be designed for dosage rate of 200 ppb. The number of oxygen cylinders to supplied and installed shall cater for one month requirement of each unit. All Volatile Treatment (AVT) System Under AVT, ammonia and hydrazine shall be dosed in the feed water at suction lines to the boiler feed pumps as well as at the condensate pumps discharge after the condensate polishing unit. Ammonia shall be used as pH control agent and hydrazine as oxygen scavenger. Each unit shall be provided with skid mounted dosing systems for ammonia and hydrazine, each system comprising of 1x100% capacity measuring tank, 1x100% capacity preparation/ dosing tank and 2x100% metering pumps complete with strainers, piping, valves, fittings, instrumentation and control panel etc. Ammonia and hydrazine shall be received in containers/ barrels and hand pumps (drum pumps) shall be provided for transfer of ammonia and hydrazine to the respective measuring tanks. The flow of chemical from measuring tank to the preparation/ storage tank shall be by gravity. Space provision shall be kept in the main plant building for storage of ammonia and hydrazine containers/ barrels as per one month requirement of each unit. The measuring and preparation/ storage tanks for each chemical shall be sized for one day requirement of the unit. Metering pumps for each chemical shall be of horizontal positive displacement, reciprocating and variable stroke type. All the chemical measuring/ preparation/ storage tanks and metering pumps shall be of SS-316 construction. The provision shall be made for flushing of the metering pumps by the condensate/ DM water.