Installation Guide
Earthing
General considerations
• TT network
• TN-S network
• IT network
Earthing
The metal parts of the installations which are The customer must connect their earthing rod to the genset’s earthing installation
via an insulated copper conductor with a minimum section of 16 mm2 or with a bare
exposed to contact with people,because of an copper conductor with a minimum section of 25 mm2.
insulation fault or other accidental causes, could The materials, dimensions and depth of the earthing rod should be chosen so as to
withstand corrosion and have appropriate mechanical strength. It should be installed
become live. To ensure people protection, vertically into the ground. The resistance of the earthing rod depends on its size, its
Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology
International standard IEC 60364 distinguishes The second letter indicates the connection
three families of earthing arrangements, using the between earth or network and the electrical device
two-letter codes TN, TT, and IT: being supplied:
The first letter indicates the connection between • N: the neutral connection is supplied by the electricity
earth and the power-supply equipment: supply network, either separately to the protective earth
(PE) conductor or combined with the protective earth
• T: Direct connection of a point with earth .
(PEN) conductor.
Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology
TT network
Consumer
Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology
TN-S network
Separate protective earth (PE) and neutral (N) Generator Set Distribution network
Consumer
Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology
IT network
Consumer
Installation Guide < Previous Page Index Next Page > EARTHING
Standard earthing system in HIMOINSA’s generator sets
Installation Guide < Previous Page Index Next Page > EARTHING
Standard earthing system in HIMOINSA’s generator sets
SYSTEM DISTRIBUTION VOLTAGE EARTH POINT IN ALTERNATOR SYSTEM DISTRIBUTION VOLTAGE EARTH POINT IN ALTERNATOR
U U U
400/230V-50HZ U1 U1 U5
V5 W2 V1 W6
W6
V5
U1
230/132V-50HZ U2
V1
W5
U2 U6
V6
480/277V-60HZ U5 2Phases
W2
3Phases + N TN-S TN-S 230V-50HZ
U5
U6
U2 U6
W2 V6
440/254V-60HZ W2 V2 W6 V6 (12H) V6 W1 V2 W5
N W
W1
W5 V5 N U
V2
W1 V5
220/127V-60HZ W1 N V1
W1
W2 N V2
V1 U U1 U2 N U5 U6 W
W6 V2
208/120V-60HZ
U1
U2
W V W V W V
W5 V1
U W
W6 U1
U1 U5
W5 U2
3Phases 230V-50HZ N
TN-S U5
(12H) 240V-50HZ W2
2Phases 115V-50HZ
U6 TN-S U2 U6
W1
(4H) 120V-60HZ
W V6 V5 V2 V1 V V
V1 V5 W2 W6
3Phases 230V-50HZ N
IT
(6H) 240V-50HZ W U1 U2 U5 U6 V
V2 V6 W1 W5 2Phases + N
TN-S 240/120V-60HZ
U U1 U5 U2 U6 W (4H)
V5 W2 V1 W6
W6
V5
N
V1
W5
V6
2Phases + N
W2
W U1 U2 U5 U6 V
U5
U6
TN-S 240/120V-60HZ N W 2Phases
(12H) N TN-S 230V-50HZ
W1
U
V2
V6 W1 V2 W5
(4H)
U U1 U2 U5 U6 W
U1
U2
Installation Guide < Previous Page Index Next Page > EARTHING
Standard earthing system in HIMOINSA’s generator sets
M6 TN-S TO CHECK*
M0 TN-S TO CHECK*
* Earthing connection point changes depending on the constructive version of the control panel. For more
information get in contact with HIMOINSA’s Commercial Engineering Department.
Installation Guide < Previous Page Index Next Page > EARTHING