Earthing

General considerations

Earthing system. IEC terminology

• TT network

• TN-S network

• IT network

Standard earthing system in HIMOINSA’s generator sets

Table 1. Earth point in alternator

Table 2. Earthing system by HIMOINSA control panel type


General Considerations

Earthing

The metal parts of the installations which are The customer must connect their earthing rod to the genset’s earthing installation
via an insulated copper conductor with a minimum section of 16 mm2 or with a bare
exposed to contact with people,because of an copper conductor with a minimum section of 25 mm2.

insulation fault or other accidental causes, could The materials, dimensions and depth of the earthing rod should be chosen so as to
withstand corrosion and have appropriate mechanical strength. It should be installed
become live. To ensure people protection, vertically into the ground. The resistance of the earthing rod depends on its size, its

electrical installation and equipment, the


shape and the resistivity of the soil in which it is embedded. This resistivity usually
varies from one place to another, and varies according to the depth.
customer must earth the generator set.
To carry out the earthing, the generator sets
contain a main earthing terminal located inside the
container, and additional earthing points, usually in
the corners of the bedplate and inside the panel, if The choice and dimensioning of the conductors and
included. earthing rod will be the responsibility of the installer
performing the installation and must take into account
relative local and national regulations.

Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology

Earthing system. IEC terminology

International standard IEC 60364 distinguishes The second letter indicates the connection
three families of earthing arrangements, using the between earth or network and the electrical device
two-letter codes TN, TT, and IT: being supplied:

The first letter indicates the connection between • N: the neutral connection is supplied by the electricity
earth and the power-supply equipment: supply network, either separately to the protective earth
(PE) conductor or combined with the protective earth
• T: Direct connection of a point with earth .
(PEN) conductor.

• I: No point is connected with earth, except perhaps via a


• T: Earth connection is by a local direct connection to
high impedance.
earth, usually via a ground rod.

Three variants of TN systems are distinguished: TN-S,


TN-C y TN-C-S. The most common configurations are
shown on the following pages

Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology

TT network

In a TT earthing system, the protective earth Generator Set Distribution network

connection for the consumer is provided by a local


earth electrode, and there is another independently
installed at the generator. There is no ‘earth wire’
between the two.

Consumer

Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology

TN-S network

Separate protective earth (PE) and neutral (N) Generator Set Distribution network

conductors from transformer to consuming device,


which are not connected together at any point after
the building distribution point.

Consumer

Installation Guide < Previous Page Index Next Page > EARTHING
Earthing system. IEC terminology

IT network

In an IT network, the electrical distribution system Generator Set Distribution network

has no connection to earth at all, or it has only a


high impedance connection.

Consumer

Installation Guide < Previous Page Index Next Page > EARTHING
Standard earthing system in HIMOINSA’s generator sets

Standard earthing system in


HIMOINSA’s generator sets
Standard earthing system for Himoinsa’s It must be taken into account that exist local electrical
generator sets manufacturing, according CEI standards, which must be met when installing and earthing
60364-5-54, is a TN-S system for all voltages and gensets, always by qualified technician.

frecuencies, except three-phases voltages


In case of need variations over Himoinsa standard
without neutral and 6 wires alternator, in which manufacturing is advisable contact with Engineering
case it has been adopted an IT system. department, in order to avoid damages to genset or people.

System used will be solid grounded.


These earthing systems have been selected attending to
our worldwide clients needs, following our provider
technical recommendations and meeting relevants
It is possible another earthing system on request. european standards.

Installation Guide < Previous Page Index Next Page > EARTHING
Standard earthing system in HIMOINSA’s generator sets

Table 1. Earth point in alternator

SYSTEM DISTRIBUTION VOLTAGE EARTH POINT IN ALTERNATOR SYSTEM DISTRIBUTION VOLTAGE EARTH POINT IN ALTERNATOR
U U U
400/230V-50HZ U1 U1 U5
V5 W2 V1 W6

W6
V5
U1
230/132V-50HZ U2

V1

W5
U2 U6

V6
480/277V-60HZ U5 2Phases

W2
3Phases + N TN-S TN-S 230V-50HZ

U5

U6
U2 U6
W2 V6
440/254V-60HZ W2 V2 W6 V6 (12H) V6 W1 V2 W5
N W

W1
W5 V5 N U

V2
W1 V5
220/127V-60HZ W1 N V1
W1
W2 N V2
V1 U U1 U2 N U5 U6 W
W6 V2
208/120V-60HZ

U1

U2
W V W V W V
W5 V1

U W
W6 U1
U1 U5
W5 U2
3Phases 230V-50HZ N
TN-S U5
(12H) 240V-50HZ W2
2Phases 115V-50HZ
U6 TN-S U2 U6
W1
(4H) 120V-60HZ
W V6 V5 V2 V1 V V

V1 V5 W2 W6

3Phases 230V-50HZ N
IT
(6H) 240V-50HZ W U1 U2 U5 U6 V
V2 V6 W1 W5 2Phases + N
TN-S 240/120V-60HZ
U U1 U5 U2 U6 W (4H)

V5 W2 V1 W6

W6
V5
N

V1

W5
V6
2Phases + N

W2
W U1 U2 U5 U6 V
U5

U6
TN-S 240/120V-60HZ N W 2Phases
(12H) N TN-S 230V-50HZ

W1
U

V2
V6 W1 V2 W5
(4H)
U U1 U2 U5 U6 W
U1

U2

Gensets without panel or external panel will have a IT system.

Installation Guide < Previous Page Index Next Page > EARTHING
Standard earthing system in HIMOINSA’s generator sets

Table 2. Earthing system by HIMOINSA control panel type

CONTROL PANEL TYPE DISTRIBUTION SYSTEM EARTHING CONNECTION POINT

M6 TN-S TO CHECK*

M5 / AS5 TN-S CONTROL AND POWER PANEL

M7 / AS7 TN-S CONTROL AND POWER PANEL

SC (without panel) IT CUPPER PLATE INSIDE GENSET

External cabinet with


TN-S CONTROL AND POWER PANEL
earth-fault protection.
AC5
External cabinet without
IT CUPPER PLATE INSIDE GENSET
earth-fault protection.

M0 TN-S TO CHECK*

* Earthing connection point changes depending on the constructive version of the control panel. For more
information get in contact with HIMOINSA’s Commercial Engineering Department.