Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Introduction
1.1 Basic Ideas of Relay Protection
An electric power system should ensure the availability of electrical energy
without interruption to every load connected to the system.when the
electric power supply is extended to remote villages the power system
would consist of several thousand kilometres of distribution lines. Ihe
high voltage transmission lines carrying bulk power could extend over
several hundred kilometres. Since all these lines are generally overhead
lines and are exposed, there are many chances of their breakdown due to
storms, falling of external objects, damage to the insulators, etc. These can
result not only in mechanical damage but also in an electrical fault. One
of the sources of trouble to continuous supply is the shunt fault or short-
circuit, which produces a sudden and sometimes violent change in systenm
operation.
The nature of a fault simply implies any abnormal condition which causes
a reduction in the basic insulation strength between phase conductors, or
between phase conductors and earth, or any earthed sčreens surrounding
the conductors. Actually the reduction of the insulation is not considered
as a fault until it produces some effect on the system, that is unil it
results either in an excess current or in the reduction of the impedance
between conductors or between conductors and earth to a value below that
of the lowest load impedance normal to the circuit.
The most serious result of a major uncleared fault is fire which may not
only destroy the equipment of its origin but may spread in the system and
cause total failure. The most common type of fault which is also the
most dangerous one is the short circuit which may have any of the
following consequences:
(1) A great reduction of the line voltage over a major part of the power
system. This will lead to the breakdown of the electrical supply to the consumer and may
produce wastage in production.
(2) Damage caused to the elements of the system by the electrical arc which almost always
accompanies a short circuit.
(3) Damage to other apparatus in the system due to overheating and due to overheating and due
to abnormal mechanical forces setup.
(4) Disturbances to the stability of the electrical system and this may even lead to a complete
shutdown of the power system
(5) A marked reduction in the voltage which may sometimes be so great
that relays having pressure coils tend to fail
(6) Considerable reduction in the voltage on healthy feeders connected to
the system having fault. This may cause either an abnormally high
current being drawn by the motors or the operation of no-voltage
coils of the motors. In the latter case considerable loss of industrial
production may result as the motors will have to be restarted.
3
1.4 Fault Statistics
It is useful to have some idea of the frequency of the incidence of faults on the different items
items of equipment in a power system. This information is of help in considering the problems of
design and application of protection.
Tabel 1.1 gives an idea of how faults are distributed in the various sections of a power system.
Equipmen
O.H lines
Cables
Switchgear
Transformers
CTs and PTs
Control Equipment
Miscellaneous
CORRIGENDUM
Table 1.2 Frequency of different types of faults
occurring in overhead lines
ZONES OF PROTECTION
Note. The L-L- L fault, called the symmetrical three-phase fault, generally
occurs due to the carelessness of operating personnel. Usually the phase
lines are tied up together with a bare conductor in order to protect
lineman working on the ines against inadvertent charging of the line
Occasionally after the work is over, the lineman forgets to remove the
tie-up and when the circuit breaker is closed a threc-phase symmetrical
fault oocurs.
In our country where the neutral is not kept isolated, these eartlh
faults do produce fairly large magnitudes of fault currert. So in designing
a system of protection greater attention should be paid to the reliable
operation of relays under line-to-ground fault conditions.
Bus bar
relay zone
line relay zone
zone
Generator trans-former relay zone
1.6.1 RELIABILITY
This is the property by which only the faulty element of the system is
isolated and the remaining healthy sections are left intact. Selectivity is
absolute if the protection responds only to faults within its own zone, and
relative if it is obtained by grading the settings of the protections of
several zones all of which may respond to a given fault
Systems of protection which in principle are absolutely selective are
known as unit systems. Systems in which selectivity is relative are non-
unit systems. Examples of the former are differential protection and frame
leakage protection, and of the latter current time graded protection and
distance protection.
The shorter the time a fault is aliowed to persist the more load can be
trapsferred between given points on the power system without loss of
synchronism.Figure (1.3) shows typica1 values of power which can be transmitted as a function
of fault clearing times for various types of fault.
1.6.4 DISCRIMINATION
9
Table 1.3 Average costs in units per circuit
Indoor Outdoor
Unit or Element. A self-contained relay unit which in conjunction with one or more other relay
units performs a complex relay function, e.g. a
directional unit combined with an overcurrent unit gives a directional
overcurrent relay.
Pickup. A relay is said to pickup when it moves from the off position
10
Operating Time. The time which elapses between the instant of application
of a characteristic quantity equal to the pickup value and the instant when
the relay operates its contacts.
Resetting Time. The time which the operated relay takes to come back
to its initial position as a result of a specified sudden change of the
characteristic quantity, the time being measured from the instant at which
the change occurs.
Primary Relays. Those which are connected directly in the protected circuit
Secondary Relays. Those connected to the protected circuit through current and potential
transformers.
Backup Relay. A relay which operates usually after a slight time delay
if the norma! relay does not operate to trip its circuit breaker. A backup
relay acts as a second line of defence. (11)
Consistency: Accuracy with which the relay can repeat its electrical or
time characteristics.
Blocking. Preventing the protective relay from tripping either due to its
own characteristic or due to an additional relay
QUESTIONS
1. Explain briefly the role of protection in a power system.
2. Describe the essential features of a protective relay with reference to
reliability, selectiyity, speed of operation and discrimination.
3. What are the principal types of faults in a power system? In what
way is a fault harmful to the power system?
4. Define the terms: burden, pickup, reset, operating time.
5. Explain what is meant by primary protection and backup protection.
12
CHAPTER 2
Basic Principles and Components
of Protection
2.1 Methods of Discrimination
The main requirements and qualities of protection have been outlined in
Chapter 1. Now a brief idea of the methods of discrimination offa ult so
as to cause the appropriate and only the appropriate disconnecting device to
function will be discussed. These methods will, however, be taken up in
detail in subsequent chapters. These methods arc basically of two types:
(a) those which discriminate as to the location of fault. and (b) those which
discriminate as to the type of fault.
2.1.1 METHODS DISCRIMINATIVE TO FAULT LOCATION
The main aim is that the faulty section of the system be isolated and in the
minimum time. The various methods under this category are those in
which the behaviour of the protective apparatus is dependent upon where it
is -situated in the system relative to the point of fault occurrence
(a) Diserimination by Time. By adding time lag features to the control-
ling relays of a number of circuit breakers it is possible to trip the breaker
nearest the fault prior to thosc farther off the point of fault. This simple
scheme may be applied in a radial feeder shown in Fig. (2.1).
The breakers
FIGURE 2.1 Radial feeder.
at A, B, C and D are identical and are set to operate for a given value of
current. For a fault in any section, say CD, if the fault current exceeds
13
BASIC PRINCIPLES AND COMPONENTS OF PROTECTION
16
the set value the breakers at A, B and C will trip and the whole feeder
beyond A becomes dead
For providing time lag to the eireuit breakers at A, B, C, and D the
tripping is delayed in the following manner:
D-no added time lag
C-0.4s added time lag
B-0.8s added time lag
A-1.2s added time lag
With such a scheme obviously if the fault occurs in the section CD the
breaker at C will trip after a time of 0.4s and thus will clear the fault with
the result that the feeder up to C will remain alive. A 0.4s step time lag
is necessary to account for the time of operation of circuit breaker and its
relay operation times.
(b) Discrimination by Current Magnitude. This depends on the current
magnitudes as the magnitude of the fault current will also vary with the
location of the fault. If the relays are set to pickup at a progressively
higher current towards the source then a simple feeder system of the type
shown in Fig. (2.1) can be protected. Such a scheme is known as current
graded scheme.
(c) Discrimination by Time and Direction. In the case of a ring main which
forms a closed loop it is not possible to isolate the faulty section with the
help of time alone. Consider the ring main shown in Fig. (2.2). In one case
nondirectional relays with same current setting but different time lags are
2.0
2.0 1.7
0.1
,sf
1.5
1.3
0,5
0.5
1.0
0.9
FIGURE 2.2 Ring main feeder: (a) with nondirectional relays; (o) with
directional and nondirectional relays.
14
METHODS OF DISCRIMINATION
provided which shows that proper discrimination cannot be obtained nor can
this position be improved by varying the time lags from those shown in the
the same ring main directional feature is also
uced as shown by arrows. Now it can be seen that a fault occurring
diagram
In the second case for
introd
on an
y section will be discriminatively cleared without loss of supply.
(d) Diserimination by Distance Measurement. The methods described
above which discriminate by time and current magnitude have limitations of
being applicable to simple systems. Moreover the faults nearer to the
source which are more severe take longer time to clear in the case of time
discrimination systems.
Now if the relays are designed to measure the distance from the breaker
location to the fault and if this distance happens to be less than that to the
next breaker out from the source, the fault is within the section controlled
by the breaker concerned and this trips. If the distance is greater than
that to the next breaker out from the source, the fault is beyond the sec-
tion controlled by the breaker concerned and therefore it does not trip
All successive breakers are controlled in this way and are set to operate
only for faults in their own section
The measurement of distance is achieved in various ways by what are
known as distance relays to be discussed later
(e) Time as an Addition to Current Magnitude or Distance Discrimination
Combination of time with current magnitude discrimination or with distance
discrimination gives practical dimension to protection. It will be seen later
that combination of time and current grading gives the most practical
protection schemes and similarly the time distance discrimination forms
another practical protection scheme. These schemes will be discussed at
length in Chapter 5
(0) Current-Balan
ce Discrimination. The discriminative methods outlined
above may not be adequate for a complex system having interconnections
and alternative parallel paths, etc. This calls for a form of discrimination
which is limited in its scope to one system element which will cause isolation
of this element only in the event of fault in this element and will not respond
to any other fault external to this element, even though the fault current
passes through it. Such a protection is known as unit protection
This form of protection is based on one of the following two principles:
(a) circulating current principle; (b) opposed voltage principle or balanced
voltage principle.
The circulating current principle compares the currents at the two ends
of the protected section. This is illustrated in Fig. (2.3a), the difference of
the current magnitude at the two ends flows through the relay. For an
15
BASİC PRINCIPLES AND COMPONENTS OF PROTECTION
18
external fault the balance of currents is not disturbed and the section or
protected section the balance of currents is disturbed and the relay trips
apparatus is not isolated, whereas for a fault within the apparatus or the
the breakers at the two ends and isolates this section completely.
protecie
tbl
FIGURE 2.3 Unit protection scheme: (a) circulating current protection; (b) balanced
voltage protection.
The principle of balanced-voltage protection is shown in Fig. (2.3b)
Here the relative polarity of the CTs at the two ends is such that there
is no pilot current for the conditions of load or external fault. The CT
secondary voltages will no longer balance and current will flow in the relays
which will trip the circuit breakers at the two ends.
(g) Power-Direction Comparison Discrimination. In this case the com-
parison of the direction of fault power at the two ends of the protected
section is done by directional relays. Urder external fault conditions the
direction of the fault power is outwards at one end of the protected section.
Under internal fault conditions, fault power is fed only into the section
either at both ends or at one end, depending upon whether the source of
power supply is on both sides or only on one side of the protected section.
Figure (2.4) illustrates the principle of power directional comparison.
FIGURE 2.4
Directional comparison.
Considering one end of the line oaly and assuming that power flows into
the line at this end, one of the following three things simultaneously applies
(i) Power flows out at the otherend, which means either load conditions
orexternal fault conditions obtained; so tripping should be prevented.
(ii) Power also flows in at the other end, which means an internal
fault condition and both breakers should trip.
(ii) No power flows either in or out at the other end, meaning thereby
that there is no source on the other end and thus if the power flow
is of sufficient magnitude it is due to fault in the section and the
local breaker on this side only should trip
16
19
METHODS OF DISCRIMINATION
The scheme outlined needs considerable elaboration to give it a practical
shape. This will be discussed later in power line carrier protection.
(h) Phase Comparison Discrimination. This is another form of power
line carrier protection. In this case the phase angle of current at the two
ends of the protected section is compared, which gives an indication
whether the fault is internal or external. Information about the phase
angle of the primary current is transmitted to the other end over the
carrier link.
2.1.2 METHODS DISCRIMINATIVE TO TYPE oF FAULT
There can be cases when the fault currents may not be very high or may
differ little in magnitude from load currents with the result that current
magnitude detection fails to point out such a faul. Such a fault current
however has some peculiarity which distinguishes itself from the normal
load currents. For instance, in a three phase system the currents and
voltages can be resolved into their phase sequence components which would
ultimately give some idea about the nature of the currents or voltages
present.
(a) Zero-Phase Sequence Networks. These networks are commonly used
for the detection of earth faults. By providing a relay at such a place
where it will be energized only by zero-sequence currents an indication
is obtained of an earth fault as shown in Fig. (2.5). Such a relay will
Z ero sequence
relay
Trip circuit
FIGURE 2.5
Zero-sequence relay.
ignore load currents or phase-to-phase short circuits. Hence the setting
of such a relay will have no bearing on the load current values which is
often essential for discrimination or even for adequate protection when
earth currents are limited.
(b) Negative-Phase Sequence Networks. The presence of negative-phase
sequence current represents some form of unbalanced condition such as
17
BASIC PRINCIPLES AND COMPONENTS OF PROTECTION
20
phase-to-phase faults other than the symmetrical three-phase faults, broken
conductors, etc. A typical negative phase sequence network is shown in
Fig. (2.6).
NPS
FIGURE 2.6 Negative-phase sequence network.
2.1.3 DISCRIMINATION BY COMBINATIONS oF METHODS SENSITIVE TO
LOCATION AND TYPE OF FAULT
A combination of the methods discriminative to fault location and the
methods discriminative to type of fault is very useful in actual practice.
An example of such a combination is a protective scheme providing
protection by overcurrent and earth fault relays. This uses time current
discrimination and zero sequence device. Such a scheme is shown in
Fig. (2.7).
CTs
o/c
E/F
FIGURE 2.7
Combination of overcurrent and earth fault relays.
2.2 Derivation of a Single-Phase Quantity from Three-Phase Quantities
It will be seen later that auxiliary channels or pilot wires are used to transmit
information from one end of the line to the other end. For a normal
three-phase system three pilots would ordinarily be required which would
18
21
DERIVATION OF A SINGLE-PHASE QUANTITY
obviously be a very costly affair for longer systems, particularly transmission
circuits. It would naturally be p:eferable to have a means of deriving a
single-phase quantity which under both normal and abnormal conditions
will be representative of the three-phase conditions. Sometimes it becomes
necessary to segregate the sequence currents or voltages from corresponding
line currents or voltages in order to simplify the protection scheme by
reducing the number of relays required.
here are two commonly used methods for deriving single-phase
quantity from a three-phase system.
(a) Summation Transformers. The three line current transformers (CTs)
are connected to the primary of an auxiliary current transformer
(summation transformer) as shown in Fig. (2.8). Each line CT energizes
a different number of turns on the primary with a resulting single-phase
output from the secondary. Thus for the typical case shown in Fig. (2.8)
the output is seen to be proportional to the vector sum
(n+2)IR+(n+1)ly+nl
Summated
output
FIGURE 2.8 Summation transformer.
It is also possible to control independently the outputs for earth faults
and phase faults. The output on earth faults is usually considerably more
than that on phase faults so as to provide more sensitive ac ion on earth
faults. Consequently, the pickup setting can be expressed in termis of
combinations of n and 1 for the various faults.
Table 2.1 shows the output current for a given fault current magnitude
in each type of fault in terms of the rated current of CT.
19
BASIC PRINCIPLES AND COMPONENTS OF PROTECTION
Table 2.i Effect of summation on pickup settings
Type of faultR-E YE B-E R-Y Y-B B-R R-Y-B
Summation CT
turns
+2 n+1 1 1 2 3
14%
16.5%
20%
90%
90%
45%
52%
Pickup current
Zero output or a negligibly small output may occur under through fault
conditions when there is a phase-to-phase fault on the star side of the
delta/star transformer giving a 1:2: 1 current distribution in the protected
feeder as shown in Fig. (2.9). In general, ho wever, it is possible to choose
tappings which make such cases very unlikely
Output
FIGURE 2.9 1:2:1 Current distribution.
(b) Sequence Networks. In some cases it is desirable to make the
protection respond to a particular phase-sequence component of the three-
phase system of currents or voltages. Zero-sequence and negative-sequence
networks are frequently used in power system protection
Zero-sequence networks are extensively used for earth fault protection.
The connections of such a network are shown in Fig. (2.10). During
FIGURE 2.10 Zero-sequence network.
20
23
DERIVATION OF A SINGLE-PHASE QUANTITY
normal operation and for three-phase and phase-to-phase faults the current
passing through the relay is zero. When a single or double earth fault
occurs, the zero-sequence current flows through the relay
For unbalanced conditions or unsymmetrical faults negative-phase
sequence networks are used. One simple negative-sequence network is
shown in Fig. (2.11). The values of r and C are such as to give a phase
shift of 60. It can be seen from the vector diagrams that for the
Relay
60。
60°
(a) Positive sequence currents
(bl Negati ve sequence currents
FIGURE 2.11 Negative-phase sequence network.
positive-sequence currents the output voltage Vat Vb applied to the relay
s zero whereas for the negative-sequence currents the output voltage
Ya+Vs is of considerable magnitude to operate the relay
ever protection responding to positive-phase sequence components
alone is not used in relaying practice, because under unsymmetrical faults,
such a protection will have less sensitivity due to the fact that the positive-
phase sequence component is only a part of the fault current.
21
24
BASIC PRINCIPLES AND COMPONENTS OF PROTECTION
It is possible however to usc a combination of the positive-sequence,
networks as a general rule as
2.12). A combination of positive and negative sequence
negative-sequence and zero-sequence
networks is more common
PPS
network
Niv
Summat ed
Pz output
ne:lwork
nctwork
FIGURE 2.12 Combination of the three sequence networks.
2.3
Components of Protection
The various protective schemes to be described in the chapters to follow
would make use of a wide range of components. Some of the more
commonly used components will be described here in brief.
2.3.1 RELAYS
The main function of a protective relay is to isolate a faulty section with
the least interruption to service by controlling the circuit breaker, when
abnormal conditions develop. Thus the relays may be designed to detect
and to measure abnormal conditions and close the contacts in the tripping
circuit.
The following two categories of relays are most commonly used in
protective relaying:
ing relays: a group including practically all kinds
of relays, e.g. current, voltage, power, impedance, reactance and
frequency, whether minimum or maximum.
(b) Secondary direct-acting relays: a group of overcarrent and under-
instantaneously or with time lag.
ype which are built
voltage relays designed to operate
These are primarily relays of the electromagnetic t
into circuit breaker operating mechanisms,
22
25
COMPONENTS OF PROTECTION
2.3.2 CIRCUIT BREAKERS
Circuit breakers of various typ
and close them u
es are installed in all power circuits to open
nder normal load conditions. Circuit breakers must
d MVA breaking
correspond to nominal current and voltage rating an
capacity to the l
circuit where they inco
system one or
the protection
oad and fault power conditions at the given point of the
y are incorporated. To isolate a fault from the power
re circuit breakers are required in conjunction with
may be operated either manually or automatically.
Ion here we will assume that it is controlled
elay, so that when opening (tripping) is required
trip coil is energized,
causing the main contacts to part
directly or via an
which releases energy stored in the mechanism thus
. The relay usually closes its contacts
auxiliary relay to close the trip coil circuit through a
ker is to
ere the trip coil current exceeds the relay-contact rating,
le closing the trip coil circuit which is highly inductive the duty
attery thus energizing the trip coil. When more than one brea
be tripped or wh
an auxiliary relay of proper contact rating must be used
Wh
on the relay contacts is not so severe; but while breaking the trip co
current considera ble damage would be done to these contacts. In order
to overcome this difficulty an auxy switch operated by a mechanical
link mechanism of the circuit breaker is connected in series with the trip
coil and relay contacts. This auxiliary switch opens when the breaker
contacts open. This action, however, takes place before the contacts of
the relay open. This ensures that any inductance voltage would appear
across the auxiliary contacts only and not across the relay contacts. The
latter are thus saved from any possibility of burning
The time of operation of circuit breaker actually depends on its design
and usually lies between 0.05 and 0.25s. This must be accounted for
while calculating final fault clearance time
2.3.3 TRIPPING AND OTHER AUXILIARY SUPPLIES
It is quite evident that a source of power supply other than the supply circuit
being protected is required for the operation of the relays and the circuit
breakers. It also goes without saying that such an auxiliary supply should
be the most reliable one. Protective relay and automatic control schemes
in power system practice use two kinds of auxiliary supply: d.c. or a.c.
supply is provided from storage batteries
D.C. auxiliary power
maintained continuously charged by some type of su
The advantages of storage batteries are
independence of a.c. power circuit conditions
pply set or a charger
their high reliability and
and of the existence of faults
Usually the voltage of the auxiliary supply is maintained at 110 V. AII
24
AND COMPONENTS OF PROTECTION
possibie means are exploited in designing the
auxiliary supply circuits to
all the receivers of the
make them most reliable, such as by dividing a
these tbe most important are the protective relas
made for such supplies. Separate buses may ais
alarm or warning signals
Of
eir responsibility into different categories.
rcuits. Use of sectionalized buses is frequently
also be provided for supplying
rcuit breakers and other indicating circuits such as
respect to earth may lead to false tripping due
ypass of the current round the control devices.
pply circuits must have their insulation resistande
evel, as any breakdown in the insulation with
to formation of a path for
of this danger
Because
ery d.c. auxiliary supply installation must include a
monitoring the condition of the insulation (ins
A simple circuit providing such a test is shown in Fig
insulation is healthy the voltage of each pole relative to ea
(insulation resistance to carth)
. (2.13). When the
rth V, and
FIGURE 2.13
Insulation test of d.c. supply.
will be equal and half the voltage between both the poles. In case the
insulation of one pole drops in value with respect to earth, the voltage to
earth of this pole will also drop, but the voltage to earth of the other
pole of the circuit will increase by the same amount.
Wherever conditions permit, it is of decided economic advantage to
use a.c. instead of d.c. auxiliary supply fer circuit breaker control and for
supply for the protective
. Under fault conditions,
the current passing through the secondary of properly selected CTs, will
energizing the protective relay. А.С. auxiliary
relay scheme is mainly derived from the CTs
always be sufficient to reliably trip the associated circuit breaker
feeder overcurrent protection using a.c. auxiiary
Figure (2.14) shows o
supply from CT
During normal operation the relay contacts continuo
breaker trip coil and thus keep the breaker cos Sbut the
abnormal conditions are approached the relay operates to
This puts the trip coil into
other schemes are also possible
ly-closed contacts
breaker closed. As and when
CT circuit and the circuit-breaker trips.
Many Other schemes afe also possible.
25
27
COMPONENTS OF PROTECTION
CE
TC- trip co
CB- circuit
CT- current
t r ansiormer
FIGURE 2.14
Relay with a.c. operative power from current transformer
2.3.4 CURRENT TRANSFORMER (CT)
e primary circuit currents which are of high-magnitudes are to be
reduced to values suitable for relay operation with the help of current
transformers (CTs). Thus the CTs esseatially insulate the secondary (relay)
circuits from the primary (power) circuit
secondary which are proportional to those in the primary. The primary
winding of the CT is connected in series with the load and carries the
actual power system currents (normal or fault). The secondary is connected
to the measuring circuit or the relay, which together with the winding
impedance of the transformer and the lead resistance constitutes the
burden of the transformer
Th
s and provide currents in the
The CT is similar in operation to any other transformer so that the
primary current consists of two components, viz. the secondary current
which is transformed in the inverse ratio of the turns ratio and the exciting
current which magnetizes the core. The latter current is not transformed
and is the cause of the transformer errors. It is because of this reason that
certain values of secondary currents could never be produced whatever the
value of primary current, this happons when the core saturates and
disproportionate amount of primary current is required to magnetize the
core
The general shape of a CT magaetization curve is shown in Fig. (2.15).
The shape will change for different core materials. The characteristic is
divided into three regions defined by the ankle point and the knee point.
The boundary between the saturated and unsaturated regions is marked by
the knee point which is defined as the point at which a 10% increase in
secondary voltage produces a 50% increase in exciting current. The other
characteristic curve shown in the diagram is the phase angle of exciting
current which is not of much importance for protective CTs. It may,
however, be noted that the working range of a protective CT extends over
26
28
the full range between the ankle and the knee points and buyond
the imeasuring CT usually operates in the
HASIC PRINCIPLES A:iD COMPONEN y." OF PROTECT iori
buyond, whereas
region of the ankle point, This
10%. Inc'nninn
S0 Increment
1,00
K nou
point
0.90
0,80
rri
Ankle point
T otal exciting current
FIGURE 2, 15.
CT magnetizing characterist
is because of the radical difference in their basic functions. Measuring
CTs require comparatively high accuracy over the range of 10% to 120%
rated current, and it is an advantage if the CTs saturate for currents above
this range in order to protect the instruments. Protection CTs, on the
other hand, require linear characteristics up to the secondary voltage
corresponding to maximum fault current flowing in the connected burden.
Figure (2. 16) shows the charecteristics of two CTs both for the same rated
burden, but one for protection and the other for measurement. It is quite
Protective CT
Measuring CT
Exciting current
FIGURE 2.16. Protective and measuring CTs.
obvious that a core of larger cross section would be required for
protective CT if the material has to be the same. Grain oriented steels
having
CTs and nickel-iron alloys having low exciting ampere-turns per unit
high saturation levels are used as core materials for protective
27
COMPONENTS OF PROTECTION
29
length of the core are used for measuring CTs arn
occurs at a relatively low flux density
d the knce point
It is common practice to use IA sccondary ra
practical limit to the number of turns which can be wound on the a
primary CT which is usually about 1500 secondary turns. When n
primary currents much in excess of 1500 A are encountered then the m
bar primary CT with rated secondary current of 5A or 10A along v
auxiliary CTs of 5/1 or 10/1 A respectively, are used
rating CTs. There is a
ated
ain
ith
2.3.5 VoLTAGE TRANSFORMERS
is not possible to connect the voltage coils of the protective devics
It is therefore
directly to the system in case of high voltage systems
necessary to step down the voltage and also to insulate the protective
equipment from the primary (power) circuit. This is achieved by using a
ge transformer (VT) also known as a potential transformer (PT)
which is similar to a power transformer. The voltage transformer is rated
in terms of the maximum burden (VA output) it delivers without exo
specified limits of error, whereas the power transformer is rated by the
secondary output it delivers without exceeding a specified temperature rise.
The output of VTs is usually limited to a few hundered volt amperes and
the secondary voltage is usually 110 V between phases
Ideally a VT should preduce a secondary voltage exactly proportional
to the primary voltage and exactly in phase opposition. This cannot
obviously be achieved in practice owing to the voltage drops in the primary
and secondary coils due to the magnitude and power factor of the
secondary burden. Thus, ratio errors and phase angle errors are
introduced
The limits of ratio and phase angle errors for VTs used for protection
are much larger than those required for measurement purposes only. The
acceptable limits of error for protective VTs as specified by IS:3156
Part III)-1966 are shown in Table 2.2. A three-phase residually
connected VT is shown in Fig. (2.17), where all the three phases
FIGURE 2.17. Three-phase residual VT.
28
30
BASIC PRINCIPLES AND COMPONENTS OF P
PROTECTION
Table 2.2 Limits vo
it of voltage errors and phase displacement
Clss olage (ratio) Piase displacerent
Voltage (ratio)
error (%)
±3.0
L5.0
Phase displacement
minutes)
士 120
+ 300
3.0
of the primary windings are connected between line and earth and the
secondary windings are connected in an open delta. In this caset
residual voltage is equal to three times the zero sequence voltage
order to have a voltage in the secondary circuit there must
sequence voltages in the primary circuit. Hence such an arrangemen
used in neutral displacement schemes and for supplying the voltage circuit
dings are connected between line, and earth and the
be zero
t is
of directional earth fault relays
re two types of voltage transforming devices; the conventional
pe..voltage transformer and the capacitor voltage transformer.
or economic reasons, and the capacitor VT is used for voltages
here a
The wound type VT is conveniently used for system voltages up to or
132 KV f
above 132 KV. The capacitor VT is essen
divider with the basic circuit shown in Fig. (2.18a). Ifthe current flowing
in the output circuit (i.e., in the conncted burden) is negligibl
tially a capacitance potential
C1
V-Input
2 V Output
c2
L oad
FIGURE 2.18. Capacitor voltage divider: (a) basic circuit;
(b) compensated circuit.
But when appreciable current flows in the burden, errors, both in ratio
and phase, are introduced, because of the load current flowing through the
capacitor C1. The voltage drop on load due to reactance of the capacitors
can be compensated by inserting an inductive reactance in series with the load
as shown in Fig. (2.18b). The requirement is that a current flowing in the
burden shall meet zero impedance in the capacitor divider. In other words
the circuit must offer zero impedance to the load current with the line and
29
COMPONENTS OF PROTECTION
31
earth terminals short circuited, i c., ωL..1/(eG+wC) Value
C, are so chosen that a major part of the voltage drops across C Le
C<C, so that oLoC The vector diagram of the compens
circuit for a unity power factor (upf) load is shown in Fig. (2.19)
following three conditions are of interest:
() For constant voltage V and a constant voltage V a change
s of C, and
Ct, i.e.
burden, i.c. IB changes Ve, Vea and V
(ii) For zero burden impedance, i.e. output terminals short circuited, the
cuit has C1 in series with L and C, in parallel forms an acceptor
circuit tuned to the fundamental frequency. This results in increasing
e Ve l lea and Is to infinity. To protect from these conditions a
protective spark gap is connccted across C
(iii) For infinite burden impedance or for output terminals open circuited
Vt is zero and V-Ve
C1
FIGURE 2.19 Capacitor VT with upf burden.
2.3.6 LINEAR COUPLER
An iron-cored CT has the limitation of saturation and owing to d.c. offset
transient component present in the fault current, the stability on heavy
through faults may be difficult to obtain.
With air-cored CTs, also known as linear couplers, the problem of
n and d.c. offset transient are overcome. Two major difficulties
roblems are differential saturation and the transference
with relay transient p
of d.c. through the iron-cored CT. These are obviously solved; firstly
because iron has been removed, and secondly because this device transforms
nential waveform with a high degree of attenuation of the d.c.
the expo
offset in the output wave form.
Assuming the primary current i, to have 100% de. offset, ie.
The secondary voltage is given by Mdildt
It can thus be seen that the d.c. component voltage has been attenuated
by a ratio R/X which may be 1/10 to 1/20 depending on the system.
30
32
BASIC PRINCIPLES AND COMPONENTS OF PROTECTION
EXAMPLE 2.1
A 100/ 1 A bar primary CT supplies an overcurrent relay set at 10%
pickup and having a burden of iVA. It is required to cater
of 10 times the relay setting. Determine the knee point voltage and
cross-section of the core if the CT has 10 secondary turns. Assume the
flux density in the CT core to be I wb/m2
for a current
Solution. Secondary operating cu
rent of the relay 0,1 A
. Secondary volts 1/0.1-10 V.
For 10 times the current setting the CT secondary voltage is 100 v.
The knee point voltage must be slightly higher than 100 V
The voltage induced in the winding is given by
E-4.44xxfx N
100
4.44 x 50x10
100
or area of cross-section-4.44×50x10x1
-0.045 m2
EXAMPLE 2.2
A summation transformer used for deriving relaying quantities for a pro-
tective syste of phase
sequence RYB. Obtain an expression for the ampere-turn output of the
summation transformer in terms of the input turns ratio between primary
tappings, and the B-phase sequence currents, if system conditions are such
that IB-IBa Hence find the minimum value of n to be used with a
1:1.3:n primary-turns-ratio summation transformer, if positive outputs are
to be maintained when In/Io-4. What would be the effect on the value
of n if a ratio 1:1:n were used?
m is supplied with an unsymmetrical three-phase input
Solution. Let the input-turns-ratio of the summ ation transformer be l:m:r
as shown in Fig. (2.20). Using R-phase as the reference, according to
symmetrical component theory:
FIGURE 2.20
31
COMPONENTS OF PROTICTION
Taking B as the reference phase we can write
Ampere turns oututI(+mtm)
(n)+
Ampere turns output 1, (+2m+3n)-Ip (2m-+D)
1 : ,n :n=1 : 1 .3 : n, for zero output
0-4(3.643")-In.Χ 3.6
3.6 I 3.6
or
If
n3.6
If
l: m: n1:1:n
then
Therefore for
QUESTIONS
1. Describe briefly various methods of fault detection.
2. Explain briefly the principle of time grading in a simple radial systenm
equipped with instantaneous overcurrent and earth-fault relays, and
definite time-delay relays. Show how, by the use of directional relays
this s
assuming the latter to be supplied at one point only
ame principle may be applied to the protection of a ring system,
3. What is a unit protection? Explain the principle of current-balance
protection as applied to a simple two-ended circuit. Show how this
principle can be employed in (a) the circulating-current system; and
(b) the balanced voltage system.
32
34
4. Distinguish between time overcurrent relays, directional relays
5. Find the output of CT having a transformation ratio o
BASIC PRINCIPLES AND COMPONENTS OF PROT
ECTION
and
differential relays.
sccondary resistance of 0.1. ohm. Its secondary terminals are
connected to a relay whose burden is 4.5 VA. The resistance of the
connecting leads is 0.15 ohm
(10.75 VA)
33