Zone CFM .......................... Peak zone sensible load Calculation Months ....................................... Jan to Dec
Space CFM .................. Individual peak space loads Sizing Data ................................................... Calculated
Total coil load ....................................................... 25.2 Tons Load occurs at .................................................. Jul 1800
Total coil load ..................................................... 302.1 MBH OA DB / WB ................................................. 103.5 / 65.5 °F
Sensible coil load ................................................ 270.0 MBH Entering DB / WB ........................................... 84.2 / 63.3 °F
Coil CFM at Jul 1800 ........................................... 7760 CFM Leaving DB / WB ............................................ 50.8 / 49.0 °F
Max block CFM at Jul 1900 ................................. 8502 CFM Coil ADP .................................................................. 47.1 °F
Sum of peak zone CFM ....................................... 8730 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 0.894 Resulting RH ............................................................... 46 %
ft²/Ton ................................................................. 125.4 Design supply temp. ................................................. 56.0 °F
BTU/(hr-ft²) ........................................................... 95.7 Zone T-stat Check ............................................. 12 of 12 OK
Water flow @ 10.0 °F rise ..................................... N/A Max zone temperature deviation ................................ 0.0 °F
Max coil load ........................................................ 18.4 MBH Load occurs at ................................................. Jan 0700
Coil CFM at Jan 0700 .......................................... 4974 CFM BTU/(hr-ft²) ................................................................. 5.8
Max coil CFM ...................................................... 8502 CFM Ent. DB / Lvg DB ............................................ 47.5 / 51.0 °F
Water flow @ 20.0 °F drop ................................... N/A
Actual max CFM at Jul 1900 ................................ 8502 CFM Fan motor BHP ........................................................ 0.00 BHP
Standard CFM ..................................................... 8195 CFM Fan motor kW .......................................................... 0.00 kW
Actual max CFM/ft² ............................................... 2.69 CFM/ft² Fan static ................................................................. 0.00 in wg