Sei sulla pagina 1di 3

Vent Size for Pressure Vessels

Vent sizing of pressure vessels and process equipments based on the way of usage.
Simply the presence of a Relief valve will relief the over pressure that was developed inside and
protects the reactor, Usually the reactor will be having a pressure resistance which is known as
Design pressure, if the reactor is felt with more than the design pressure, then there may be a
chance for explosion, and i said there may be a chance of explosion because after manufacturing of
reactor there will be some recommended tests that were to be done like pressure test, spark test[if
its a GLR], etc. While performing a pressure test, the vendor will cross the limit of design pressure
and gives a specification called Test Pressure, which means the pressure upto which the test was
carried out.  

So, now i'll tell you when there is a need for Vent/Relief valve:

Vapour / Gas removal rate < = Vapour / Gas generation rate,

If the above condition is satisfied, then there requires a Relief valve / Vent for the system.

The major factors that will decide the Vent size were:

 Maximum Vapour/Gas Generation rate,


 Type of fluid inside the container, whether its a gas or liquid.

In case of Maximum generation rate, If we need to vent out Vapour / Gas that was generated, then
simply calculate the size from below equation:

V = A x S = 0.785 x D x D x S,
here, V = Volumetric flowrate in Cu.m / hr,

D is Diameter of Vent,A is Cross sectional area of the vent neck,


S is the velocity with which the vapour / gas will escape, 

If the Container / Vessel is containing any gas, then there wont be any problem because if its a
solvent then there is a chance that solvent may be transform to vapours and create some vapour
pressure, but as it is a Gas then whatever the pressure that is accumulated, that will be kept off like
that. 

One more important term, named as WCM [ Worst Credible Maloperation ], Which means the
highest pressure developed due to the maloperation responsible for the generation of vapour / Gas.
The calculation should obey the criteria, i.e., pressure that was developed during the WCM should
safely pass through the vent provided, or the Relief valve should respond to the WCM pressure with
a minimal response time 

The approach to Relief sizing depends on 2 cases:


 Fire case,
 Reaction case 

For a fire,
Vapour generation rate = Heat from fire / Latent heat of vaporization 

For a chemical reaction,


Vapour generation rate = Reaction rate x Reaction Enthalpy / Latent heat of vaporization.

So after getting the vapour generation rate, you can go with above mentioned equation, V = A x S,
if there is any problem while calculation, then better go with a direct equation which was developed
& Proposed by Leung's Long form eqn.

A = [ m x q ] / G [ { (VxT/m)+(dP/dT)}^0.5  +  {Cp x dT}^0.5  ] ^2

m - Initial mass in vessel (Kg),


q - Heat evolution rate per unit mass in vessel(Watt/Kg),
G - Vent flow capacity per unit area at set pressure(Kg/Sq.m),
V - Vessel volume(Cu.m),
T - Vessel temperature(K),
dP/dT - Rate of change of vapour pressure with temperature,
Cp - Specific heat ( J/Kg.K),
dT - difference of temperature between Maximum allowable pressure & Set pressure ( °K),

As per the Equilibrium rate model, the Value of G [ vent flow capacity] can be calculated as below,

G = (dP/dT) x SQRT(T/Cp) = hfg / [ Vfg x SQRT( Cp x T) ]

Consider a 10 KL reactor, having MOC SS316 with a design pressure of 3.2 Bar, and maximum
allowable pressure as 4.2 Bar, i.e., 30% excess to design pressure

Averag

Pressure Bar 3.2  4.16 
Bubble point temperature
°C  110  120.5  115.3 
Heat release rate ( watt/Kg)  1150  1660  1405 
Liquid density ( Kg/Cu.m)  847  835  841 
Vapor density (Kg/Cu.m)  3.75  4.62  4.19 
Latent heat (KJ/Kg)  674.9  663.0  668.95 
Liquid specific heat (KJ/Kg.K)  1.96  1.96  1.96 
dP/dT  8300  9500 
Vfg (Cu.m/Kg)  0.2655  0.2153  0.2404 

Using equation developed from Equilibrium rate model,


At 3.2 Bar pressure, G = 0.5 x (dP/dT) x SQRT(T/C) = 0.5 * 8300 * SQRT( 383/1960)

= 2385 Kg/Sq.m S.

At 4.16 Bar Pressure, G = 0.5 * 9500 * SQRT(393.15/1960) = 2128.73 Kg/Sq.m S

The average value of 2385 & 2128.73 for G gives  2256.5 Kg/Sq.m S.

Now, we need to calculate the venting area from  Leung's Long form eqn.

dP/dT = ( 4.16 - 3.2 ) x 10^5 / ( 120.5 - 110 ) = 9143 N/Sq.m K

A =  [ 1500 * 1405 ] / 2256.5 [ { 10 * 288.5 * 9143/1500 }^0.5 +{1960 * 10.5 }^0.5] ^2

    =  0.0122 Sq.m

D = SQRT(0.0122/0.785) = 0.125 m = 5" (inch)

Potrebbero piacerti anche