STRUCTURAL

ANALYSIS AND DESIGN

OF THE ADDITIONAL 3RD LEVEL FOR


TWO STOREY COMMERCIAL BUILDING

LOCATION:
OWNER:

PREPARED BY:

______________________________________________________
ENGR. JAY VINCENT A. RUBIO

PRC LICENSE NO.: 0163402


TIN NO.: 716-249-742
PTR NO.: 2181573
DATE ISSUED: 02/18/2019
PLACE ISSUED: DUMAGUETE CITY, NEG.OR.
STRUCTURAL DESIGN CRITERIA

1.0 CODES AND STANDARDS


1.1. Governing Codes
1.1.1. National Structural Code of the Philippines- NSCP 2015
1.1.2. American Concrete Institute -ACI 318-99
1.1.3. American Institute of Steel Construction -AISC 9 TH Edition

1.2. Governing Standards


1.2.1. ASTM A36 Specifications for Structural Steel
1.2.2. ASTM A616 Specifications for Deformed Bar for Concrete
‘ Reinforcement
1.2.3. ASTM C33 Specifications for Concrete Aggregates
1.2.4. ASTM C33 Specifications for Portland Cement

2.0 MATERIALS SPECIFICATIONS


2.1. Normal weight concrete Compressive strength at 28 days, fc’
2.1.1. Columns and Beams 20.7 Mpa (3000 psi)
2.1.2. Suspended slabs 20.7 Mpa (3000 psi)
2.2. Reinforcing Steel Yield Strength, fy
2.2.1. Bars 16mm diameter and larger 276 Mpa (Grade 40)
2.2.2. Bars 16mm diameter and smaller 230 Mpa (Grade 33)
2.2.3. Structural Steel 248 Mpa (36000 psi)
3.0 LOADING CRITERIA

3.1. Dead Load,DL


3.1.1. Concrete 23.5 kN/m 3
3.1.2. Steel 77 kN/m 3
3.1.3. Soil 18 kN/m 3
3.1.4. 4”thk CHB Wall 2.01 kN/m 3

3.2. Live Load,LL


3.2.1. Concrete 4.8 kN/m 3
3.3. Seismic(Earthquake),EL
Total design base shear
V= CvIW/RT
Total design base shear need not exceed the following
V= 2.5CaIW/R
Total design base shear shall not be less than
V= 0.115CaIW
V= 0.8ZNvIW/R

 Importance Factor,I= 1.0


 Z= 0.40, seismic Zone Factor
 Near Source Factor, Na= 1.0
 Near Source Factor, Nv= 1.0
 Seismic Coefficient. Ca= 0.44Na
 Seismic Coefficient. Cv= 0.64Nv
 Soil Type SD
4.1 All foundation are either spread, combined or mat footings
as shown on the foundation plan.

4.2 Footings are designed to rest on soil with an allowable


bearing capacity of 100 kPa based on 1.3 m depth. Increase of
33% is allowed for each additional 250mm of width and/or depth
to a maximum of three times the designated value.
4.3 Footings for CHB walls and other minor structures shall be
embedded atleast 600mm from the finish grade line unless
indicated otherwise.
4.4 All foundations should have a compacted gravel base course
150mm thick lean concrete unless indicated otherwise.