Definitions Of Terms:
All forces in units kN and m
All reinforcement details like area, spacing in mm
Neutral axis angle for resultant design moment is with respect to local major axis.
Ratio to account for reduction of stiffness of columns
1 βdns =
due to sustained axial loads
Moment magnification factor for frames not braced
2 δns =
against sidesway
First-order relative deflection between the top and
3 Δo =
bottom of the story due to Vu in mm
Total factored vertical load in the story corresponding
4 ∑Pu = to the lateral loading case for which ∑Pu is greatest,
kN (Clause 10.10.5)
5 δu = Design displacement in mm
Modification factor reflecting the reduced mechanical
6 λ =
properties of lightweight concrete
7 Φ = Strength reduction factor
Coefficient defining the relative contribution of
8 ac =
concrete strength to nominal wall shear strength
Cross-sectional area of a structural member measured
9 Ach = to the outside edges of transverse reinforcement in
sqmm
Gross area of concrete section bounded by web
10 Acv = thickness and length of section in the direction of
shear force considered in sqmm
Effective cross-sectional area within a joint in a plane
11 Aj = parallel to plane of reinforcement generating shear in
the joint in sqmm
Area of non-prestressed longitudinal tension
12 As =
reinforcement in sqmm
Minimum area of shear reinforcement within spacing
13 Avmin =
's' in sqmm
14 B = Width of column/ wall in mm
15 B' = width of beam along B / column width in mm
Cross-sectional dimension of member core measured
16 bc = to the outside edges of the transverse reinforcement
composing area Ash in mm
Distance from extreme compression fiber to neutral
17 c =
axis in mm
18 Cc = Clear cover of reinforcement in mm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 2 of 25
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 3 of 25
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 4 of 25
Code References:
ACI 318M-2011
Sr.No Element Clause / table
Minimum area of longitudinal reinforcement
1 : 21.6.3
for column
Maximum area of longitudinal
2 : 21.6.3
reinforcement for column
Minimum longitudinal and transverse
3 : 21.9.2.1
reinforcement for wall
4 Minimum diameter of transverse ties : 7.10.5
5 Minimum spacing of transverse ties : 7.10.5
Maximum spacing of longitudinal and
6 : 21.9.2.1
transverse reinforcement for wall
7 Applicability of boundary element : 21.9.6
Area and spacing of special confining
8 : 21.6.4
reinforcement
9 Slenderness Moments : 10.10
Shear Strength provided by concrete for
10 : 11.2
column
11 Design of shear for non-ductile wall : 11.9
12 Design of shear for ductile wall : 21.9.4
13 Minimum Flexural Strength of Columns : 21.6.2.2
14 Shear Check at Column Joint : 21.7.4.1
15 Shear Strength of Column : 21.3.3 & 21.5.4
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 5 of 25
0m to LOAD 2:
4.35 595.332 27.198 76.393 0.049 Non Sway
4.35m EZ
4.35m to LOAD 2:
3.05 289.025 8.019 53.138 0.014 Non Sway
7.4m EZ
General Data
Column No. : C1
Level : 0m To 4.35m
Design Code = ACI 318M - 2011
Grade Of Concrete = C21 N/sqmm
Grade Of Steel = Fy227 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 250 mm
Column D = 400 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 100
Critical Analysis Load Combination : 114
[13] : 1.12 (LOAD 3: DL1) +1.12 (LOAD 4: DL2) -
Load Combination =
(LOAD 1: EX) +0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = 90.82 kN
Muxt = 44.68 kNm
Muyt = -8.26 kNm
Vuxt = -1.9 kN
Vuyt = -10.27 kN
Pub = 90.82 kN
Muxb = 0 kNm
Muyb = 0 kNm
Vuxb = -1.9 kN
Vuyb = -10.27 kN
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 6 of 25
Along B
Q = 0.049
0.049< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 29.76
M1 = 0 kNm
M2 = 44.68 kNm
34 - 12 x (M1/M2) = 34
29.76 < 34, Column not slender along D
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 7 of 25
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 8 of 25
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Pu = 90.82 kN
Luy = 3950 mm
Mnty = 55.31 kNm
Mnby = 55.31 kNm
Vuy1 = 28 kN
Shear from Load combinations with
Enhanced Eq factor:
1.42 (LOAD 3: DL1) +1.42 (LOAD 4:
Load Combination = DL2) +0.5 (LOAD 5: LL1) -3 (LOAD 1:
EX) +3 (LOAD 2: EZ)
Vuy2 = 31.92 kN
Critical Analysis Load Combination : 406
[57] : 1.2 (LOAD 3: DL1) +1.2 (LOAD
Critical Load Combination = 4: DL2) +0.5 (LOAD 5: LL1) +(LOAD kN
2: EZ)
Nu = 70.21 kN
Muy = 9.52 kNm
Vuy = -2.1884 kN
Design Shear = max(Vuy, Vuy1, Vuy2)
= 28 kN
λ = 1
φ = 0.65
deff = 352 mm
ρw = 0.006
mm = 3.83 kNm
Vcy Permissible = 73.75 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 9 of 25
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 125 mm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 10 of 25
General Data
Column No. : C1
Level : 4.35m To 7.4m
Design Code = ACI 318M - 2011
Grade Of Concrete = C21 N/sqmm
Grade Of Steel = Fy227 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 250 mm
Column D = 400 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 300
Critical Analysis Load Combination : 109
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination =
(LOAD 5: LL1) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 44.46 kN
Muxt = 9.13 kNm
Muyt = 26.97 kNm
Vuxt = 13.4 kN
Vuyt = -7.49 kN
Pub = 44.46 kN
Muxb = -13.71 kNm
Muyb = -13.88 kNm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 11 of 25
Vuxb = 13.4 kN
Vuyb = -7.49 kN
Along B
Q = 0.014
0.014< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 12 of 25
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 13 of 25
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Pu = 44.46 kN
Luy = 2750 mm
Mnty = 48.29 kNm
Mnby = 48.29 kNm
Vuy1 = 35.12 kN
Shear from Load combinations with
Enhanced Eq factor:
1.42 (LOAD 3: DL1) +1.42 (LOAD 4:
Load Combination = DL2) +0.5 (LOAD 5: LL1) -3 (LOAD 1:
EX) -3 (LOAD 2: EZ)
Vuy2 = 20.7 kN
Critical Analysis Load Combination : 103
[4] : 1.42 (LOAD 3: DL1) +1.42 (LOAD
Critical Load Combination = 4: DL2) +0.5 (LOAD 5: LL1) +(LOAD kN
1: EX) +0.3 (LOAD 2: EZ)
Nu = 35.23 kN
Muy = 2.91 kNm
Vuy = -4.5069 kN
Design Shear = max(Vuy, Vuy1, Vuy2)
= 35.12 kN
λ = 1
φ = 0.65
deff = 352 mm
ρw = 0.006
mm = 0.05 kNm
Vcy Permissible = 102.44 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 14 of 25
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 125 mm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 15 of 25
General Data
Column No. : C3
Level : 0m To 4.35m
Design Code = ACI 318M - 2011
Grade Of Concrete = C21 N/sqmm
Grade Of Steel = Fy227 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 250 mm
Column D = 400 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 3950 mm
Clear Floor Height @ luy = 3950 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 102
Critical Analysis Load Combination : 113
[12] : 1.12 (LOAD 3: DL1) +1.12 (LOAD 4: DL2) +
Load Combination =
(LOAD 1: EX) -0.3 (LOAD 2: EZ)
Critical Location = Top Joint
Put = 101.68 kN
Muxt = -45.5 kNm
Muyt = 2.93 kNm
Vuxt = 0.67 kN
Vuyt = 10.46 kN
Pub = 101.68 kN
Muxb = 0 kNm
Muyb = 0 kNm
Vuxb = 0.67 kN
Vuyb = 10.46 kN
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 16 of 25
Along B
Q = 0.049
0.049< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 0.87
r = 115.47 mm
Kluy /r = 29.76
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 17 of 25
M1 = 0 kNm
M2 = -45.5 kNm
34 - 12 x (M1/M2) = 34
29.76 < 34, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.68
r = 72.17 mm
Klux /r = 37.22
M1 = 0 kNm
M2 = 2.93 kNm
34 - 12 x (M1/M2) = 34
37.22 > 34, Column slender along B
Moment Magnification:
For Non-sway frame:
Along B
βdns = 0.6
Ec = 21538.11 N/sqmm
9 = 0.521 mm^4
Ig ( x 10 )
EI ( x 10 6) = 3238287.855 N-sqmm
M2min = 2.29 kNm
Cm = 0.4
Pc = 4429.99 kN
δns = 1
Mc1 = 0 kN
Mc2 = 2.93 kN
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 18 of 25
Pu = 101.68 kN
Mux = -45.5 kNm
Muy = 2.93 kNm
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Pu = 101.68 kN
Luy = 3950 mm
Mnty = 56.88 kNm
Mnby = 56.88 kNm
Vuy1 = 28.8 kN
Shear from Load combinations with
Enhanced Eq factor:
1.42 (LOAD 3: DL1) +1.42 (LOAD 4:
Load Combination = DL2) +0.5 (LOAD 5: LL1) +3 (LOAD
1: EX) -3 (LOAD 2: EZ)
Vuy2 = 32.4 kN
Critical Analysis Load Combination : 407
[58] : 1.2 (LOAD 3: DL1) +1.2 (LOAD
Critical Load Combination = 4: DL2) +0.5 (LOAD 5: LL1) -(LOAD kN
2: EZ)
Nu = 104.27 kN
Muy = 10.77 kNm
Vuy = 2.4758 kN
Design Shear = max(Vuy, Vuy1, Vuy2)
= 28.8 kN
λ = 1
φ = 0.65
deff = 352 mm
ρw = 0.006
mm = 2.32 kNm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 19 of 25
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 20 of 25
General Data
Column No. : C3
Level : 4.35m To 7.4m
Design Code = ACI 318M - 2011
Grade Of Concrete = C21 N/sqmm
Grade Of Steel = Fy227 N/sqmm
Consider Ductile = Yes
Type of Frame = Intermediate
Column B = 250 mm
Column D = 400 mm
Clear Cover = 40 mm
Clear Floor Height @ lux = 2750 mm
Clear Floor Height @ luy = 2750 mm
No Of Floors = 1
No Of Columns In Group = 1
Load Data
Analysis Reference No. = 302
Critical Analysis Load Combination : 109
[10] : 1.42 (LOAD 3: DL1) +1.42 (LOAD 4: DL2) +0.5
Load Combination =
(LOAD 5: LL1) +0.3 (LOAD 1: EX) -(LOAD 2: EZ)
Critical Location = Top Joint
Put = 47.81 kN
Muxt = -15.74 kNm
Muyt = 25.63 kNm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 21 of 25
Vuxt = 11.73 kN
Vuyt = 10.2 kN
Pub = 47.81 kN
Muxb = 15.35 kNm
Muyb = -10.14 kNm
Vuxb = 11.73 kN
Vuyb = 10.2 kN
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 22 of 25
Along B
Q = 0.014
0.014< 0.05, Column shall be designed as non-sway frame
(Braced)
Slenderness Check
Column Is Braced Along D
Slenderness Check along D
K = 1
r = 115.47 mm
Kluy /r = 23.82
M1 = 15.35 kNm
M2 = -15.74 kNm
34 - 12 x (M1/M2) = 45.7
23.82 < 45.7, Column not slender along D
Column Is Braced Along B
Slenderness Check along B
K = 0.76
r = 72.17 mm
Klux /r = 28.96
M1 = -10.14 kNm
M2 = 25.63 kNm
34 - 12 x (M1/M2) = 38.75
28.96 < 38.75, Column not slender along B
Where
A = Moments from analysis
B = Moment due to slenderness effect
C = Final design Moment = Maximum of (Manalysis, Maximum of (Msldr or Mc))
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 23 of 25
Design Of Shear
Design for shear along D
Shear from Moment Capacity:
Pu = 47.81 kN
Luy = 2750 mm
Mnty = 48.81 kNm
Mnby = 48.81 kNm
Vuy1 = 35.5 kN
Shear from Load combinations with
Enhanced Eq factor:
1.42 (LOAD 3: DL1) +1.42 (LOAD 4:
Load Combination = DL2) +0.5 (LOAD 5: LL1) +3 (LOAD
1: EX) +3 (LOAD 2: EZ)
Vuy2 = 20.82 kN
Critical Analysis Load Combination : 119
[17] : 1.12 (LOAD 3: DL1) +1.12
Critical Load Combination = (LOAD 4: DL2) -0.3 (LOAD 1: EX) - kN
(LOAD 2: EZ)
Nu = 31.19 kN
Muy = 5.98 kNm
Vuy = 5.0547 kN
Design Shear = max(Vuy, Vuy1, Vuy2)
= 35.5 kN
λ = 1
φ = 0.65
deff = 352 mm
ρw = 0.006
mm = 3.45 kNm
Vcy Permissible = 83.15 kN
Vuy < Vcy Permissible
Link For Shear Design Along D are not required
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 24 of 25
Design Of Links
Links in the zone where special confining links are not required
Normal Links
Diameter of link = 10 mm
> Max. longitudinal bar dia / 4
= 4 mm
Criterion for spacing of normal links
Min. Longitudinal Bar dia X 16 = 256 mm
48 x diameter of links = 480 mm
Provided spacing = 125 mm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020
Column Design: Design Calculations Page 25 of 25
links:
Min. Longitudinal Bar dia x 8 = 128 mm
24 x diameter of links = 240 mm
B/2 = 125 mm
Spacing = 300 mm
Provided Spacing = 125 mm
file:///C:/Users/User/AppData/Local/Temp/tmp273.tmp 2/6/2020