1 General information 2
2 Changes in the version 2.4.0 3
3 Changes in the version 2.3.1 8
4 Changes in the version 2.3.0 9
5 Related information 14
6 Notes 16

Copyright © 2017 ComAp a.s.


Written by Michal Slavata
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: info@comap.cz, www.comap.cz New Features List
1 General information
1.1 Version information
This firmware version consists new Choke function. Also D+ function was added to AMF20, AMF25, MRS10,
MRS11, MRS1 and MRS16 controllers.

1.2 Clarification of notation


Note: This type of paragraph calls readers attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

New Features List IL-NT 2.4.0 2


2 Changes in the version 2.4.0
2.1 New features
D+ Function setpoints for AMF20, AMF25, MRS10, MRS11, MRS1 and MRS16
Added new setpoins D+ Treshold and D+ Delay

D+ Treshold
Setpoint group Engine Params Range [units] 0 .. 100 [%]
Default value 80 % Step 1%
Position Under D+ Function Related applications AMF, MRS
Description
This setpoint adjusts threshold level for D+ function.

D+ Delay
Setpoint group Engine Params Range [units] 0 .. 255 [s]
Default value 1s Step 1s
Position Under D+ Treshold Related applications AMF, MRS
Description
This setpoint adjusts delay for D+ function. This delay is used for:
alarm Wrn Charging Alternator Fail
for engine running condition - disengagement of binary output STARTER

Choke Function for AMF8, AMF9, MRS3 and MRS4 controllers


Added new setpoints ChokeStartTemp, ChokeIncrement, ChokeTempSel, ChokeVoltage, Chole Lead,
added new binary output CHOKE, added new binary input CHOKE INHIBIT

New Features List IL-NT 2.4.0 3


ChokeStartTemp
Setpoint group Basic Settings Range [units] -20,0 .. 80,0 [°C]
Default value 0,0 °C Step 0,1 °C
Position Related applications AMF, MRS
Description
This setpoint adjust the basic temperature for Choke function. When temperature will be higher than this
setpoint, Choke Time will be always 0. When temperature will be lower than this setpoint, Choke Time will
be counted by curve adjusted via setpoint ChokeIncrement.

ChokeIncrement
Setpoint group Basic Settings Range [units] 0,00 .. 20,00 [s/°C]
Default value 0,00 s/°C Step 0,01 s/°C
Position Related applications AMF, MRS
Description
This setpoint adjust the maximal time of activation of binary output Choke which depends on engine
temperature. Setpoint adjust curve which will be used for counting of actual Choke Time.

New Features List IL-NT 2.4.0 4


ChokeTempSel
Setpoint group Basic Settings Range [units] OFF/AIN2/AIN3
Default value OFF Step -
Position Related applications AMF, MRS
Description
This setpoint select source where is measurement for temperature. This temperature is used to count Choke
Time.
Note: For OFF option there is no sensor for choke and choke time will be 0.

Choke Voltage
Setpoint group Basic Settings Range [units] 0 .. 600 [V]
Default value 0V Step 1V
Position Related applications AMF, MRS
Description
This setpoint adjust threshold level for deactivation of logical binary output CHOKE. When generator voltage
is bigger than this level, then logical binary output CHOKE is deactivated.

Choke Lead
Setpoint group Basic Settings Range [units] 0 .. Prestart Time [s]
Default value 0s Step 1s
Position Related applications AMF, MRS
Description
This setpoint adjust the lead of logical binary output CHOKE. CHOKE is activated before logical binary output
STARTER.

New Features List IL-NT 2.4.0 5


Choke
Description
Logical binary output CHOKE is activated every time when logical binary output STARTER is activated. Output
is deactivated when one of these conditions is fulfilled:
Choke Time countdown
Generator voltage is bigger than Choke Voltage
Logical binary input CHOKE INHIBIT is activated
Or when there is some of these situations during starting:
Alarms of 2nd level
Emergency stop
Stop command
Cranking pause

Choke Inhibit
Description
Logical binary input CHOKE INHIBIT prevent Choke functionality when CHOKE is activated. If CHOKE INHIBIT is
activated when CHOKE LBO is active, CHOKE LBO is deactivated immediately and vice versa if LBI CHOKE
INHIBIT is deactivated and LBO CHOKE should be active then is activated.

New Features List IL-NT 2.4.0 6


2.2 Repairs
Nominal RPM in AMF8, AMF9, MRS3 and MRS4 controllers
Setpoint Nominal RPM is not connected with setpoint Nominal Frequency
Analog measurement on IGS-PTM CAN module
measured value on analog current or voltage inputs 2, 3 and 4 was 100x lower then value which was
defined in curve of analog sensor

New Features List IL-NT 2.4.0 7


3 Changes in the version 2.3.1
3.1 Repairs
Delay of D+ condition for starting
When starting level of D+ is reach, there is 1 s delay. After This delay engine is considered as started.

New Features List IL-NT 2.4.0 8


4 Changes in the version 2.3.0
4.1 New features
Choke LBO for MRS3, MRS4, AMF8, AMF9
This is a feature for small petrol gen-sets, where electronic choke control is needed. CHOKE LBO can be
activated during Prestart and Starting state and it is always deactivated at the latest at the end of
Cranking state. Choke function can be set by these setpoints:
Choke Time
Time length when CHOKE LBO is activated during Prestart and Cranking
Range: 0 - (MaxCrankTime + ChokeLead)
Defaul Value: 0
Choke Lead
Time lenght when CHOKE LBO is activated during Prestart, it can be used when choke is opening
slowly.
Range: 0 - 7 s (maximum value of Choke Lead is limited by actual Prestart Time, Choke Lead ≤
Prestart Time)
Default Value: 0

This binary output and input was added:


LBO CHOKE
Binary output connected to gen-set Choke
Can be configured as standard binary output
LBI CHOKE INHIBIT
Binary input used to deactivate LBO Choke
When LBI Choke Inhibit is activated, LBO Choke is deactivated immediately
Can be configured as standard binary input

New Features List IL-NT 2.4.0 9


Image 4.1 Start attempt with Choke

Image 4.2 Start attempt with Choke

Adjustable D+ threshold for MRS3, MRS4, AMF8, AMF9


This is a feature for small petrol gen-sets, where D+ voltage does not reach 80% of controller supply
voltage. Normally it caused Warning ChargeAlt Fail. Now the threshold and delay can be adjusted by
these setpoints:
D+ WrnThreshold
Voltage threshold in percent to evaluate Warning ChargeAlt Fail
Range: 0 - 100 %, where 100 % is supply voltage
Default Value: 80 %
D+ Delay
Time delay when D+ voltage is evaluated
Default Value: 1 s

New Features List IL-NT 2.4.0 10


During starting state: D+ voltage is evaluated as one of condition to deactivate a STARTER LBO -
when D+ voltage is reached, STARTER LBO is deactivated after D+ Delay is elapsed. Next condition
which deactivates STARTER LBO is elapsing of Cranking time or starting RPM are reached.
During Running state: D+ voltage is evaluated as condition to activate Warning ChargeAlt Fail based
on setpoints D+ WrnThreshold and D+ Delay
Modbus communication for MRS3, MRS4, AMF8, AMF9
Modbus is fully available for communication modules via setpoint group Comm Settings. It is adjusted by
these setpoints:
Controller Adress
Controller identification number. It is possible to set controller address different from the default
value (1) so that more IL controllers can be interconnected (via RS485) and accessed e.g. from
Modbus terminal.
Range: 1 - 32
COM1 Mode
Communication protocol switch for the COM1 channel.
Values:
DIRECT: LiteEdit communication protocol via direct cable.
MODEM: LiteEdit communication protocol via modem.
MODBUS: Modbus protocol. See detailed description in InteliCommunication guide.
ECU LINK: Protocol for communication with Cummins engines via Modbus.
COM2 Mode
Values:
DIRECT: LiteEdit communication protocol via direct cable.
MODBUS: Modbus protocol. See detailed description in InteliCommunication guide.
ECU LINK: Protocol for communication with Cummins engines via Modbus.
ModemIniString
If your modem needs some additional initialization AT commands (i.e. because of national
telephony network differences), it can be entered here. Otherwise leave this setpoint blank.
ModbusComSpeed
If the Modbus mode is selected on COM1 or COM2 channels, the Modbus communication speed
in bps can be adjusted here.
Values: 9600,19200, 38400, 57600

Machine state added in SNMP


Machine state is available in MIB table. It is Read only value. SNMP is supported by IB-Lite module.
Machine state values are follows:
20 Init 29 Shutdown 38 MainsRet 47 AfterCool
21 Not ready 30 Ready 39 Brks Off 48 GCB Open

New Features List IL-NT 2.4.0 11


22 Prestart 31 Cooling 40 No Timer 49 StopValve
23 Cranking 32 EmergMan 41 MCB Close 50 Start Del
24 Pause 33 ManIdle 42 ReturnDel 51 (1Ph)
25 Starting 34 MainsOper 43 Trans Del 52 (3PD)
26 Running 35 MainsFlt 44 Idle Run 53 (3PY)
27 Loaded 36 MainsFlt 45 MinStabTO 54 MRS Mode
28 Stop 37 IslOper 46 MaxStabTO
To generate MIB table go to LiteEdit 4.6 or higher and use “Controller” -> “Generate Cfg image” ->
“Generate SNMP MIB table”
Refer to IB-Lite New features list for more information about SNMP support.

Frequency selection support for AMF9 a MRS4


ECU Frequency selection support added when ECU is configured (for Volvo, Scania and Cummins
engines). These setpoints are visible when ECU is configured:
ECU FrequencySelect
Values: DEFAULT, PRIMARY, SECONDARY
Default Value: DEFAULT
ECU SpeedAdj
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. The
minimum value 0% is equal to 90% of nominal speed. Maximum value 100% is equal to 110% of
nominal speed.
Range: 0 - 100 %
Default Value: 50 %

4.2 Repairs
Missing symbols of Ukrainian language
Symbols added in Cyrilic code page
Missing values of kWh and kVArh when Chinesse language selected
Added values to:
AMF25 - Genset kWh, Genset kVARrh, Mains kWh, Mains kVArh
AMF8, 9, 20 - Genset kWh, Genset kVARrh - added new screen
MRS15, 16 - Genset kWh, Genset kVARrh
MRS3, 4, 10, 11 - Genset kWh, Genset kVARrh - added new screen
When LBO1 is configured as Not Used, it is permanently acivated
Repaired, when LBO1 isconfigured as Not Used, it is deactivated
Wrong Fls Oil Pressure evaluation
Engine is able to start even Oil pressure sensor is disconnected
When Oil Pressure analog input Direction was set to UnderLimit+Fls, sensor was disconnected and
thenFault Reset was pressed. It was possible to start engine manualy. Gen-set Red and Green LED

New Features List IL-NT 2.4.0 12


lights. It could cause Gen-set running with zero Oil Pressure
Now, after Oil Pressure sensor is disconnected, SdOilPressure alarm is evaluated and manual Gen-
set start is not allowed until Oil Pressure sensor is properly connected again. Gen-set Red LED
lights.
Undervoltage protection evaluation - MRS19
When engine was started with Generator current higher then zero, voltage autodetection was skipped
and alarm Sd Gen L1 and Sd Gen L3 appears and it terminates engine running. Alarm Sd Gen L1 and Sd
Gen L3 was evaluated incorrectly.
Now, voltage is autodetected at each starting sequence.

New Features List IL-NT 2.4.0 13


5 Related information
5.1 Available files
Firmware (*.mhx)
For: IL-NT AMF(8,9,20,25), MRS(3,4,10,11,15,16,19)
IL-NT-AMF(8,9,20,25), MRS(3,4,10,11,15,16,19)-2.4.0.mhx

Table 5.1 Available firmware

Archives (*.ail)
For: IL-NT AMF(8,9,20,25), MRS(3,4,10,11,15,16,19)
IL-NT-AMF(8,9,20,25), MRS(3,4,10,11,15,16,19)-2.4.0.ail

Table 5.2 Available archives

5.2 Overview of all available hardware


IL-NT MRS3, IL-NT MRS10, MRS11, IL-NT AMF8, IL-NT MRS19,
MRS4 MRS15, MRS16 AMF9 AMF20, AMF25
Binary Inputs 4 6 4 7
Binary Outputs 4 6 6 7
Analog Inputs 3 3 3 3
Analog Outputs 0 0 0 0
Communications USB, Ethernet, RS232, RS485, GPRS

Table 5.3 Available hardware

New Features List IL-NT 2.4.0 14


5.3 Available related documentation
Documents Description
Reference guide
IL-NT-MRS3,4-AMF8,9-2.2 Reference Guide.pdf
Link to ComAp download page
Rererence guide
IL-NT-MRS-2.2 Reference Guide
Link to ComAp download page
Rererence guide
IL-NT-AMF-2.2 Reference Guide
Link to ComAp download page
Global guide
LiteEdit 5.0.0 Global Guide
Link to ComAp download page
New Features List
LiteEdit 5.4.0 New Features
Link to ComAp download page